FARLINE Total system for perimeter wall installation with integrated

HWEa
® FARLINE
Total system for perimeter wall installation with integrated electrical trunking
FARLINE
• FARLINE HWBa offers the same total solution as HWAa
with cooling, heating and ventilation but is equipped
with the Stifab Farex integrate distribution system for
electrical, data, alarm and telecommunications cables.
• Using FARLINE you maintain full flexibility with regard
to interior wall positioning.
HWEa
• The FARLINE system has a large capacity despite its
compact size.
FUNCTIONS
– Ventilation
– Cooling
– Heating
– Integrated room temperature control
– Integrated electrical trunking
– Integrated socket panel for connectors
– Casings
– Approved to supply several fire compartments
APPLICATIONS
New building, extension and refurbishment of:
– Offices
– Conference rooms
– Hotels
KEY FIGURES
Cooling effect:
1279 W (L= 1600 mm, ∆t mk = 10°C,
q = 45 l/s).
l
Heating effect:
1958 W (L= 1600 mm, ∆tmk= 30°C).
Air flow:
10 to 45 l/s.
Pressure array:
150 - 300 Pa.
Lengths:
800, 1000, 1300 and 1600 mm.
Height:
500, 550, 650 and 700 mm.
Ducting dimensions: Ø160, Ø200 mm.
Control:
Integrated system control equipment for
sequential control per room.
The product is patent pending
We reserve the right to change the technical specification.
Stifab Farex Indoor climate systems 2000 - 2002
www.stifarex.se
153
HWEa
ADVANTAGES OF FARLINE HWBa
• In addition to the fact that Stifab Farex perimeter system
FARLINE HWBa, as FARLINE HWAa, is a total solution for
cooling, heating, ventilation and control, FARLINE HWBa
also offers an integrated electrical trunking solution.
• It can be supplied in a screened design with aluminium
ducting which is connected to a cable shelf, folding cover
and front casing panel for earthing.
Function
+
-
• Vertical connection of plugs allows more options for
furnishing along the perimeter wall without connectors
and sockets being concealed. Excess cables can be collected
inside the folding cover.
• As with the Stifab Farex perimeter wall system FARLINE
HWAa all components are prefabricated and matched for
installation by a contractor – giving short attendance times
and a minimum of coordination with other contractors.
Cooling
FARLINE HWE
FARLINE HWE is a perimeter wall unit with the functions
cooling, heating, ventilation and electrical trunking.
Installation
Neutral
Heating
Air terminal with folding cover
Installation:
The units are suspended on an assembly rail and the
prefabricated pipe and electrical trunking are positioned
once the units are fixed to the wall.
Hinge at the back
Connection:
Connection pipes, pipe stops and ducting covers are fitted at
the start and end of a unit branch.
Control equipment:
The connection cable is connected to snap-in terminals on
the unit’s connection card and is routed on to the adjacent
unit. The transformer is suspended on a wall rail and is
connected to the connection card, number as required.
Casing:
Perimeter casing and supply air grille are fitted in position
after which the room regulator is connected to the snap-in
terminals on the unit’s connection card.
Socket panel with strain relief
Cable channel
Electrical
trunking
System solution with casing Topline YMC and
folding cover (see separate section YMC).
RANGE AVAILABLE ON ORDER
Perimeter unit with cooling, heating and ventilation. Factory
fitted valves, actuator, connection card and cable shelf with
socket panel and support for electrical trunking.
Length:
800, 1000, 1300 and 1600 mm.
Height:
650 mm with duct size Ø160 mm and
700 mm with duct size Ø200 mm.
Ducting dimensions:Ø160 mm or Ø200 mm.
Pressure range:
1 = Up to 150 Pa
2 = 160 - 300 Pa
Air flow for respective pressure ranges, see separate brochure
HWD.
154
FARLINE HWE
Stifab Farex Indoor climate systems 2000 - 2002
www.stifarex.se
ACCESSORIES HWE
The accessories listed below are unique to FARLINE HWBa.
Accessories
Connection set HWET AR
Contains end cover, connection pipes, terminating pipes
with venting nipples pipe brackets and cable entries.
Coupling pipe set HWET SP
Coupling pipe set for joining heating, cooling and supply air
between units. Electrical trunking is available in either ABS
plastic or aluminium.
Wall block HWET VF
Sound dampening prefabricated wall block for fixed or interior walls.
Loose end section HWET LG
End sections in either right or left-hand designs with the same
dimensions as the FARLINE end sections.
HWDT AR
HWET SP
HWET VF
Insert unit HWET IP
Loose cable shelf with socket panel and two loose end
sections for freestanding installation between two units.
Units are available in lengths 800, 1000, 1300 and 1600 mm
and have the same outside dimensions as FARLINE HWE.
HWDT AR
HWDT MS
Electrical trunking HWET EK
1 x pipe Ø40 mm in ABS-plastic or aluminium.
Casing TOPLINE YMCa
A presentation of the casing and folding cover can be found
in the brochure TOPLINE YMC.
TECHNICAL SPECIFICATION
Cooling effect & pressure drop data
The air’s cooling effect & sound data.
Heating effect water & pressure drop data.
For technical data refer to the section in the brochure HWD:
Control: See separate section in the brochure water based
climate systems.
Insert unit HWET IP
HWEa
Stifab Farex Indoor climate systems 2000 - 2002
www.stifarex.se
155
HWEa
DIMENSIONS
Length HWE
Nominal measurements
HWE:
220
800, 1000, 1300 and 1600 mm
Length HWE:
Nominal - 10 mm.
Outlet sleeve internally:
Nominal - 235 mm.
180
140
60
Ø8
123
172
Ø40
Outlet sleeve
135
700
90
25
74
348
Ø25
500
Ø8
260
(View: end)
HWE duct dimension 200 mm
Length
58
(View:
front)
Socket panel, L
220
180
140
60
Ø8
123
172
Ø40
650
74
25
348
Ø25
240
95
30
215
450
Ø8
Ø160
90
220
(View: end)
HWE duct dimension 160 mm
156
Stifab Farex Indoor climate systems 2000 - 2002
www.stifarex.se
290
265
119
120
110
Ø200
60
180
270
30
SPECIFICATION
Perimeter unit system type FARLINE HWBa for cooling, heating
and ventilation and electrical trunking. The system shall comprise Stifab Farex room control equipment and essential accessories for connection of pipes and the air supply. Each unit shall
be supplied with a preset prescribed air flow.
The Stifab Farex delivery shall include all material for each unit
branch shown on the drawings for the physical limit of contract.
Wall penetration shall be carried out using Stifab Farex wall
block VF-1, Stifab Farex wall penetration VF-2 built on site or any
other method as set out on the drawing. Carried out by VE or
another contactor.
Stifab Farex casing Topline YMCa as set out in the drawing shall
be carried out by VE or another contractor.
Limits of contract
Stifab Farex’s limits of contract are the connection points for
water (according to the figure under Project planning –
Contractor – Physical limits of contract on page 141). At these
connection points RE connects to plain pipe ends, fills the
system, vents and carries out a pressure test.
VE connects to the duct connections with dimensions as set
out on the basic size drawing under the section
“Dimensions”.
EE provides an earthed 230 V socket for each transformer and
a fitted connection box for each thermostat.
EE supplies and installs requisite sockets for electricity, data,
telecom and route cables.
BE makes the cut outs in interior walls and soundproofs as
per the drawings.
Specification
Product
FARLINE
HWE aaa - bbb - bbb - c - ddd - ee
Length:
800, 1000, 1300
and 1600 mm
HWET SP - a - bbbb - cccc
Type:
1= Electrical trunking of ABS-plastic.
2= Electrical trunking of aluminium
Ducting dimensions:
160, 200 mm or
1620 (adapter Ø200 to Ø160 mm)
Length:
According to the specification
within the range 300 ≤ L ≤ 5000 mm.
Control cables order separately according to the specification
in brochure RWB. If these are to be included state the cable
type and length.
Loose ends
HWDT LG -
a - bbb-bbb
Design:
V= left
H= right
Ducting dimension and height (mm):
Ø160 - 650 or
Ø200 - 700
HWET VF - a - bbb-bbb - ddd
Wall penetration
Design:
1= wall block
2= wall penetration built
on site EI60
Ducting dimension and height (mm):
Ø160 - 650 or
Ø200 - 700
Thickness:
100, 150 mm.
(VF-2 only t=150 mm)
Height and ducting
dimension (mm):
650 - 160, 500 -160,
550 - 200 or 700 - 200
Insert set
HWET IP - aaa
- bbb
Ducting dimensions:
160, 200 mm.
Pressure range:
Length:
1 = Nozzles for pressure up to 150 Pa
800, 1000 1300 and 1600 mm.
Electrical trunking
Drive pressure:
State the required pressure 150 – 300 Pa
HWEa
2 = Nozzles for pressure up to
160 – 300 Pa
Air flow rate:
State the required air flow
rate as set out in tables 1-4
Jointing pipe set
HWET EK - a - bbbb
Type:
1= ABS-plastic
2= Aluminium
Length:
According to the specification
within the range 300 ≤ L ≤ 5000 mm.
Stifab Farex Indoor climate systems 2000 - 2002
www.stifarex.se
157
HWEa
158
Stifab Farex Indoor climate systems 2000 - 2002
www.stifarex.se