1756-IF16, TC-IAH161 (Differential Current w/2 wire transmittters)

1756-IF16, TC-IAH161 (Differential Current w/2 wire transmittters)
1492-AIFM16-F-3
+V
0F
+V
1F
+V +V +V +V +V +V +V
2F 3F 4F 5F 6F 7F 8F
+V
0
1
2
3
4
5
+V +V +V +V +V +V +V
9F 10F 11F 12F 13F 14F 15F
DIFFERENTIAL CURRENT INPUTS
6
7
8
9 10 11 12 13
14
15 RTN
SHIELD
À Cables are available in 0.5m, 1.0m, 2.5m and 5.0m
standard lengths (005=0.5m, 010=1.0m, 025=2.5m,
050=5.0m). Custom length cables are also available.
Á Shield terminals on AIFM are connected to pre-wired
cable shield through D-shell housing.
2-Wire Transmitter
1492-AIFM16-F-3
+V
+V
OF
Power Supply
Transmitter
Notes:
This diagram illustrates using two wire current
transmitters (with a common power supply) with the
1756-IF16 running in differential mode and using
1492-AIFM16-F-3 interface module. The power
supply is connected to the V+ and RTN terminal of
the IFM. Each transmitter receives power from the
+VxF fused output terminal of the IFM and the
current input feeds into the corresponding IN-x
terminal.
Only the EVEN numbered(IN-0,IN-2, etc) terminals
are used. All ODD numbered terminals must be
jumpered to the RTN terminal on the IFM module.
1492-ACABLEÀUD
1492-HWACABÀUD
IN
0
IN
1
+V
2F
IN
2
IN
3
SHIELD Á
Á
RTN
IN-0
IN-1
SHIELD Á
Transmitter
TC-IAH161
1756-IF16
IRTN-0