TMR-FF 03-24-04 Air Flow Factors Models: TMR and TMR-AA Air Flow Measurements: 1. Place the velometer probe in four equally spaced positions around the inner cone as shown. 2. Record and average these four velocity readings. 3. Calculate the flow rate using the following equation. Flow Rate: CFM = Factor x Average Velocity (FPM) Note: Select and use the applicable factor from the following table. E Alnor 6070, 6000, 2220, or 2220-A TMR, TMR-AA Air Flow Factors Nominal Round Duct Size (inches) 6 8 10 12 14 16 18 20 24 30 36 ® Cones Down Dimension E Balancing (inches) Factor 1 3/4 0.117 2 1/8 0.201 2 7/8 0.318 3 1/8 0.467 3 3/8 0.626 4 0.813 4 3/4 1.010 5 7/8 1.260 7 3/4 1.840 8 1/8 2.900 10 1/8 3.180 Cones Up Dimension E (inches) 1 1/8 1 1/2 2 1/8 2 3/8 2 5/8 3 1/4 3 7/8 4 7/8 6 5/8 6 5/8 8 3/8 Balancing Factor 0.152 0.266 0.420 0.616 0.832 1.060 1.350 1.680 2.410 3.830 4.150 Note: Refer to the Air Balancing Application Guide for more information about balancing air systems. 605 Shiloh Road • Plano, Texas 75074• 972-212-4800 All rights reserved. No part of this work may be reproduced or transmitted in any form or any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies