MULTIPLES OF CURRENT SENSOR TAP (X) .4 .6 .8 .1 1 .1 .2 .4 .6 .8 .2 .4 .6 .8 1 .1 1 .2 .4 .6 .8 1 1000 900 800 700 1000 900 800 700 600 600 500 500 400 400 300 300 200 200 100 90 80 70 50 Ground Fault Pickup Points AKR-75 100 90 80 70 60 Ground Fault Pickup Points AK-100 AKR-100 50 30 20 20 .2X 10 9 8 7 .25X .22X .25X .3X 6 .27X .35X 5 4 .3X .37X .35X .4X 4 .6X .5X 5 .2X .25X .3X .4X 6 .22X .22X .3X 10 9 8 7 .18X 30 .2X 40 .2X 40 .25X TIME IN SECONDS 60 GES-6035B Ground Fault Pickup Points AK-75 Ground Fault Pickup Points AKT-50 AKRT-50 3 3 2 2 1 .9 .8 .7 .6 .9 .8 .7 .6 .5 .5 .4 1 .4 Maximum .3 .3 .2 Intermediate .2 Ground Fault Delay Bands Minimum .1 .09 .08 .07 .06 .1 .09 .08 .07 .06 .05 .05 .04 .04 .03 .03 .02 .02 .01 .01 .1 .2 .4 .6 .8 .1 1 .1 .2 .4 .6 .8 .2 .4 .6 .8 1 .1 1 .2 .4 .6 MULTIPLES OF CURRENT SENSOR TAP (X) GE Consumer & Industrial Electrical Distribution Current Sensor Taps (Amperes) AKT/AKRT-50 800, 1200, 1600, 2000 AK-75 1200, 1600, 2000, 3000 AKR-75 1200, 1600, 2000, 3200 AK/AKR-100 1600, 2000, 3000, 4000 Low-Voltage Power Circuit Breakers Type AK/AKR SSTâ„¢ Solid-state Overcurrent Trip Device Ground Trip Time-current Curves Curves apply at 50/60 Hertz. From -20ºC to 70ºC Programmer Ambient. GES-6035B Programmer Set Points Ground Fault Pickup: AK/AKRT-50 AKR-75 AKRT-75 AK/AKR-100 .2x, .25x, .3x, .4x, .5x, & 6x .2x, .22x, .25x, .3x, .35x, & 4x .2x, .22x, .25x, .3x, .35x, & .37x .18x, .2x, .22x, .25x, .27x, & .3x Where X = Sensor tap setting Ground Fault Delay Bands: Maximum, Intermediate & Minimum 10.84 1M TIME IN SECONDS .2 .8 1 GES-6035B .1