13.8 IF1091

X20 module • Communication in the X20 IF module • IF1091
13.8 IF1091
13.8.1 General information
The IF1091 interface module is used for application-specific expansion of the X20 CPUs. It is
equipped with an X2X Link master interface.
•
X2X Link connection
13.8.2 Order data
Model number
Short description
Figure
X20IF1091
X20 interface module, 1 X2X Link master interface,
electrically isolated. Order 1x TB704 terminal block
separately.
Interface module
Required accessories
0TB704.9
Accessory terminal block, 4-pin, screw clamp, 1.5 mm²
0TB704.91
Accessory terminal block, 4-pin, cage clamp, 2.5 mm²
Table 243: IF1091 - Order data
424
X20 System User's Manual V 2.10
X20 module • Communication in the X20 IF module • IF1091
13.8.3 Technical data
Product ID
IF1091
Short description
Communication module
1x X2X Link master
Interfaces
Interface IF1
Type
Design
X2X Link master
4-pin multipoint connector
General information
Status indicators
Module status, data transfer
Diagnostics
Module status
Data transfer
Yes, with status LED
Yes, with status LED
Electrical isolation
PLC - IF1
Yes
Power consumption
0.97 W
Certification
CE, C-UL-US, GOST-R
Operating conditions
Operating temperature
Horizontal installation
Vertical installation
0°C to +55°C
0°C to +50°C
Relative humidity
5 to 95%, non-condensing
Horizontal or vertical
Installation at altitudes above sea level
0 - 2000 m
>2000 m
Chapter 4
X20 module
Mounting orientation
No derating
Reduction of ambient temperature by 0.5°C per 100 m
Protection type
IP20
Storage and transport conditions
Temperature
-25°C to +70°C
Relative humidity
5 to 95%, non-condensing
Mechanical characteristics
Slot
In X20 CPU
Comment
Order 1x TB704 terminal block separately
Table 244: IF1091 - Technical data
X20 System User's Manual V 2.10
425
X20 module • Communication in the X20 IF module • IF1091
13.8.4 Additional technical data
Product ID
IF1091
IF1 interface, X2X Link master
Number of stations
Max. 253
Distance between two stations
Max. 100 m
Network topology
Line
Internal bus supply
No
Bus termination resistor
Internal
General information
B&R ID code
$1F24
Table 245: IF1091 - Additional technical data
13.8.5 Status LEDs
LED
Color
Status
Description
STATUS
Green
On
Interface module is active
Red
On
CPU starting up
X2X
Yellow
On
The module sends data via the X2X Link interface
Table 246: IF1091 - Status indicators
426
X20 System User's Manual V 2.10
X20 module • Communication in the X20 IF module • IF1091
13.8.6 Operating and connection elements
LED status indicators
IF1 - X2X Link
Figure 180: IF1091 - Operating and connection elements
13.8.7 X2X Link interface (IF1)
Interface
1
- X2X Link
1
X2X
2
X2X
3
X2X\
4
SHLD
Chapter 4
X20 module
Application interface
X2X Link
Pin assignments
Terminal
Shield
4
4-pin multipoint connector
Table 247: IF1091 - X2X Link interface (IF1)
13.8.8 Firmware
The IF1091 module comes with preinstalled firmware. The firmware is also part of the B&R
Automation Runtime operating system for the PLC. If the two versions are different, the
Automation Runtime firmware is loaded to the module.
The latest IF1091 firmware is available automatically by updating your B&R Automation
Runtime.
X20 System User's Manual V 2.10
427