National Fire Protection Association Report 1 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 79-NFPA 409-2013 [ Section No. 1.1 ] 1.1 Scope. 1.1.1 This standard contains the minimum requirements for the proper construction of aircraft hangars and protection of aircraft hangars from fire. 1.1.2 This standard applies only to buildings or structures used for aircraft storage, maintenance, or related activities. Fire protection systems shall be designed to minimize fire damage to the hangar structure, and to the extent practicable, the hangar’s contents, including spare parts, maintenance equipment and aircraft. Other uses within an aircraft hangar shall be protected in accordance with other applicable NFPA Standards. Additional Proposed Changes File Name NFPA_409_1.1_Extend_scope.docx Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input 1.1.1 no change 1.1.2 The value of modern commercial and military aircraft within a hangar is often an order of magnitude higher than the hangar itself. NFPA 409 needs to provide in addition to life safety, protection for all the property within a hangar not just for the building. Aircraft are notoriously sensitive to fire, FM Global Loss Prevention Data Sheet 7-93N: “Tests by the US Federal Aviation Authority and others indicate that an aircraft fuselage skin will fail within 45 seconds from a flammable liquid fire exposure” (exposure being interpreted as engulfed in flames). On the other hand NFPA 69 (Explosion Prevention Systems) defines systems that extinguish fires within fractions of a second. So a fire protection system able to extinguish a fuel spill fire below an aircraft within, 20 to 30 seconds has to be a realistic possibility. Clearly, setting a minimum requirement of “protecting aircraft from any significant damage” is not reasonably practicable, but it would seem to be an acceptable outcome if fire damage is limited to the replacement of a few sections of fuselage skin, which would seem readily achievable using flame detection and fast acting foam delivery. Submitter Information Verification Submitter Full Name: RICHARD GILLESPIE Organization: FIRE ENGR SOLUTIONS P/L Street Address: City: State: Zip: Submittal Date: Fri Jul 12 08:55:24 EDT 2013 Committee Statement Resolution: An available protection scheme has not been developed that has been proven to extinguish a fire before the aircraft is damaged extensively. Such protection would be beyond the scope of what is considered to be a "minimum standard". 7/22/2015 2:42 PM National Fire Protection Association Report 2 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 41-NFPA 409-2013 [ Section No. 3.3.11 ] 3.3.11 Membrane Hangar . The flexible structural fabric or film that supports the imposed loads and transmits them to the supporting structure. The membrane carries only tension or shear in the plane of the membrane. Statement of Problem and Substantiation for Public Input Definition is for "membrane", not "membrane hangar". Submitter Information Verification Submitter Full Name: LIANE OZMUN Organization: FRANKFURT-SHORT-BRUZA Street Address: City: State: Zip: Submittal Date: Tue Jul 02 18:32:05 EDT 2013 Committee Statement Resolution: FR-12-NFPA 409-2013 Statement: The definition has been modified to better represent the term. 7/22/2015 2:42 PM National Fire Protection Association Report 3 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 78-NFPA 409-2013 [ New Section after 3.3.17 ] 3.3.18 Foam Concentrate. For the purpose of determining the concentrate percentage, the definition of ‘Foam Concentrate’ shall be also mean any substitutes for actual foam producing liquids, such as substituting AFFF with plain or colored water. Additional Proposed Changes File Name nfpapublicinputform_-_Kaare_Holm_NoFoam_Systems_section_3-3-18.pdf Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input NFPA 412 recently adopted the concept of ‘input based testing’ as an optional alternative to ‘output based testing’ (such as the refractometer test for determining the concentrate percentage produced by the proportioner). The proposed new definition above would effectively allow the AHJ the same privilege under this revised NFPA 409. Input based testing simply defines that you can determine the concentrate percentage from the proportioner by measuring the flowrates of both water and foam concentrate being put into the proportioner, and this concentrate proportion will by natural logic be the same as the foam/water solution coming out of the proportioner (which is what is currently being sampled and then analyzed with a refractometer to determine the concentrate percentage). As is well known and accepted, the proportioner does not need to be adjusted when changing from one type of foam concentrate to another, because it will mix any foam concentrate liquid to the same percentage. Likewise, it will mix plain or colored water to the same proportion as well. Therefore, it is possible to test the proportioner by replacing foam concentrate with plain or colored water. Testing with colored water instead of AFFF for that purpose will eliminate significant clean-up cost and associated environmental issues, and in doing so it would be more acceptable for the AHJ to test more frequently. This approach is already demonstrated by the Navy, and accepted broadly by the DoD, and new installations (foam systems in hangers) are in construction with requirements of being able to test with colored water instead of with AFFF concentrate. The basic principle being used is to simultaneously measure the water-pipe’s and the concentrate-pipe’s flow-rates with external flow meters, before they enter the proportioner, and used math to calculate the concentrate percentage. It would be in the interest of this standard to allow the AHJ to perform parts of the testing with water, while still being in full compliance with the NFPA 409. The proposed change is simply an added tool/approach, which does not take away from anyone who wishes to test as has been done in the past. The proposed change also does not modify the requirement to test with actual foam for any other purpose, as required in the standard, other than for testing the proportioner’s performance. Submitter Information Verification Submitter Full Name: KAARE HOLM Organization: NOFOAM SYSTEMS, EGE Street Address: City: State: Zip: Submittal Date: Fri Jul 12 08:22:02 EDT 2013 Committee Statement Resolution: The appropriate definition of "foam concentrate" is found in NFPA 11. 7/22/2015 2:42 PM National Fire Protection Association Report 4 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 88-NFPA 409-2013 [ New Section after 3.3.17 ] 3.3.x Foam Generators . Foam generators mix air with foam solution to deliver expanded foam to a fire or risk area. Low-expansion generators deliver expanded foam with an expansion ratios approximately 4 to 10:1. High-expansion generators deliver expanded foam with an expansion ratios approximately 500 to 1200:1. High expansion generators can be fan-driven or use air-induction to introduce air to the foam solution. Outside-air high-expansion generators use air from outside the fire compartment. Inside-air high-expansion generators use air from inside the fire compartment. Additional Proposed Changes File Name NFPA_409_Inside_or_Outside_Air_Foam_Generators.docx Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input Definition of the foam generator types is suggested as helpful. Inside air foam generators may fan driven or air inducing type. Given the normally large size and high ceilings of aircraft hangars, the use of flame detectors and the requirements of NFPA 409 and NFPA 11 for rapid fire suppression, it is most likely that there will be no significant smoke or toxic products of combustion captured by the Hi-Ex generators during a discharge in a hangar. It is not prohibited by either NFPA 409 or NFPA 11 to stop the foam discharge automatically when the fire is suppressed, in fact it is advisable to do so because when the foam concentrate runs out a continuing discharge of water will collapse the Hi-Ex blanket formed during the foam discharge. This has the added benefit of stopping the blanket building to above head height, which is likely to place evacuees in danger, not from toxic gasses in the foam but from disorientation and diminished sight and sound. Tests such as the VROM test (copy of test report attached) on the Skum HG-25 illustrate air-induction types of generator, which owe much of their fire resistance and operability to the fact they use no moving parts. Their simplicity offers economy and design flexibility not possible with fan-driven types. Note: Supporting material is available for review at NFPA Headquarters. Submitter Information Verification Submitter Full Name: RICHARD GILLESPIE Organization: FIRE ENGR SOLUTIONS P/L Street Address: City: State: Zip: Submittal Date: Fri Jul 12 09:29:18 EDT 2013 Committee Statement Resolution: The appropriate definitions for these terms are found in NFPA 11. 7/22/2015 2:42 PM National Fire Protection Association Report 5 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 80-NFPA 409-2013 [ New Section after 5.2.4 ] 5.2.5 Fixed water or foam-water systems shall be permitted to be used in lieu of the passive fire resistance separations detailed in 5.2.1, 5.2.2, 5.2.3 & 5.2.4 provided they are automatically operated, installed on both sides of the wall, and designed in accordance with 5.6, and other NFPA standards as appropriate. Additional Proposed Changes File Name NFPA_409_5.2_Internal_Separations.docx Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input NFPA 409 has long allowed active fire separation, in its requirement to protect steel columns without passive fire rated covering by spraying water on them. This proposal is an extension of that principle. It is intended that this would allow the installation of sprinklers in low rise offices, workshops, etc. adjoining hangars as a substitute for fire rated walls, doors and shutters. Submitter Information Verification Submitter Full Name: RICHARD GILLESPIE Organization: FIRE ENGR SOLUTIONS P/L Street Address: City: State: Zip: Submittal Date: Fri Jul 12 08:57:41 EDT 2013 Committee Statement Resolution: Section 5.6 applies to columns, but is not appropriate for walls. References to "other NFPA standards" is not specific enough. 7/22/2015 2:42 PM National Fire Protection Association Report 6 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 42-NFPA 409-2013 [ Section No. 5.9.1 ] 5.9.1 * Landing gear pits, ducts, and tunnels tunnels which are located below floor level shall be designed on the premise that flammable liquids and vapor will be present at all times . Materials , unless they do not connect to the hangar floor or the classified area above the floor. Materials and equipment shall be impervious to liquids and shall be fire resistant or noncombustible. Statement of Problem and Substantiation for Public Input This paragraph before modification appears to apply to open landing pits and ducts and tunnels which connect to the hangar floor or classified area. As written, it also could apply to a tunnel below the hangar floor that does not have openings into the hangar or hangar floor, but only sealed piping or conduit which enters the hangar from the tunnel. It could also apply to a duct which passes below the hangar slab, but does not communicate with the hangar floor. The modification limits the classified area to the landing gear pits, ducts and tunnels which communicate with the hangar classified areas. Submitter Information Verification Submitter Full Name: LIANE OZMUN Organization: FRANKFURT-SHORT-BRUZA Street Address: City: State: Zip: Submittal Date: Tue Jul 02 18:37:47 EDT 2013 Committee Statement Resolution: There is concern that the areas in and around a hangar will be contaminated with hydrocarbon liquids and vapors over time. These contaminates could create a classified atmosphere in tunnels that are located under the hangar, although the tunnels are not directly connected to the hangar floor. Tunnels outside the scope of 409 are not included in the requirements of 5.9.1. 7/22/2015 2:42 PM National Fire Protection Association Report 7 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 81-NFPA 409-2013 [ Section No. 5.11.2.2 ] 5.11.2.2 * Floor trench drainage systems shall be provided to restrict the spread of fuel in order to reduce the fire and explosion hazards from fuel spillage , and prevent fire spread to aircraft down-slope from a burning fuel spill . Additional Proposed Changes File Name NFPA_409_5.11.2_Hangar_Floor_Trench_Drainage.docx Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input The need for these changes is self evident. Submitter Information Verification Submitter Full Name: RICHARD GILLESPIE Organization: FIRE ENGR SOLUTIONS P/L Street Address: City: State: Zip: Submittal Date: Fri Jul 12 08:59:24 EDT 2013 Committee Statement Resolution: Provided substantiation is inadequate. 7/22/2015 2:42 PM National Fire Protection Association Report 8 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 49-NFPA 409-2013 [ Section No. 5.11.2.4 ] 5.11.2.4 * Trench drainage systems in aircraft storage or servicing areas shall be designed and constructed so that they have a capacity large enough to prevent buildup of flammable liquids and water over the drain inlet when all fire protection systems and 125 percent of the sum of all closed head automatic sprinkler systems, hose streams allowances and hand hose streams are discharging at the design rate. The discharge of low level foam systems, foam-water deluge sprinklers systems, and supplementary foam systems are excluded from the required drainage capacity. Statement of Problem and Substantiation for Public Input This section is a remnant unchanged over the years from older editions of the standard when plain water deluge systems were permitted and the concept was to flush fuel off the floor. Since foam agents blanket and secure spilled fuel, this requirement offers little benefit while imposing a high cost burden. This drainage makes little sense in high expansion foam applications when much of the liquid is bound up in bubbles. 125% is intended to provide a reasonable safety factor in removing plain water from the sprinkler system which will tend to flow beneath the foam. Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 17:04:41 EDT 2013 Committee Statement Resolution: The proposal does not address the true water flow that could be expected. 7/22/2015 2:42 PM National Fire Protection Association Report 9 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 82-NFPA 409-2013 [ Section No. 5.11.2.10 ] 5.11.2.10 Oil separators and flame traps shall be provided for the trench drainage systems serving all aircraft storage and servicing areas. These separators shall be permitted to serve each hangar trench drainage system or a group of hangar trench drainage systems or be installed as part of a general airport trench drainage system. Additional Proposed Changes File Name NFPA_409_5.11.2_Hangar_Floor_Trench_Drainage.docx Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input The need for these changes is self evident. Submitter Information Verification Submitter Full Name: RICHARD GILLESPIE Organization: FIRE ENGR SOLUTIONS P/L Street Address: City: State: Zip: Submittal Date: Fri Jul 12 09:01:04 EDT 2013 Committee Statement Resolution: "Flame trap" is not a recognized term. The substantiation was inadequate to explain the submitter's intent. 7/22/2015 2:42 PM National Fire Protection Association Report 10 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 30-NFPA 409-2013 [ Section No. 5.12.2 ] 5.12.2 In aircraft storage and servicing areas, no heating, ventilating, and air-conditioning equipment employing an open flame or glowing element shall be installed, other than as provided for in 5.12.5 . Open flame shall mean burners that utilize combustion air from within the aircraft storage and servicing area. Equipment with sealed burners and ducted combustion air shall be permitted to be installed within the aircraft the aircraft storage and servicing area. Statement of Problem and Substantiation for Public Input Use of term "open flame" needs clarification. The HVAC industry defines this as a visible flame or a flame that pulls air from within the space the the equipment is installed. Submitter Information Verification Submitter Full Name: STEPHEN TAMANKO Organization: Bascon Inc. Street Address: City: State: Zip: Submittal Date: Tue Mar 05 13:07:21 EST 2013 Committee Statement Resolution: The current wording would not necessarily prohibit the use of sealed burners and ducted combustion air that do not comply with 5.12.5. The definition of an open flame device should be interpreted in accordance with standard HVAC industry practices. 7/22/2015 2:42 PM National Fire Protection Association Report 11 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 31-NFPA 409-2013 [ Section No. 5.12.4 [Excluding any Sub-Sections] ] In aircraft storage and servicing areas, heating, ventilating, and air-conditioning systems employing recirculation of air within aircraft storage and servicing areas with open flame or glowing element shall have return air openings not less than 3 m (10 ft) above the floor and in addition must be in accordance with 5 .12.5. Supply air openings shall not be installed in the floor and shall be at least 152 mm (6 in.) from the floor measured to the bottom of the opening. Statement of Problem and Substantiation for Public Input The way this is written, no air rotation type heaters can be utilized including but not limited to hot water coil type. Submitter Information Verification Submitter Full Name: STEPHEN TAMANKO Organization: Bascon, Inc. Street Address: City: State: Zip: Submittal Date: Tue Mar 05 14:05:22 EST 2013 Committee Statement Resolution: The requirement is concerned with more than just ignition sources. One additional concern is the redistribution of flammable vapors that might be at the floor level to other areas within the hangar. 7/22/2015 2:42 PM National Fire Protection Association Report 12 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 24-NFPA 409-2013 [ Section No. 5.15.1 ] 5.15.1* Aircraft storage and servicing areas, shall be provided with grounding facilities for removal and control of static electrical accumulations on aircraft while aircraft are stored or undergoing servicing in a hangar shall be permitted in accordance with 5.15.2 and 5.15.3. Statement of Problem and Substantiation for Public Input Aircraft owners have objected to enforcement of this provision of NFPA 409 and indicate grounding of their aircraft is potentially harmful to aircraft electronics. This revision allows the designer to work with aircraft owner and appropriately protect their investment. Submitter Information Verification Submitter Full Name: Donald Cook Organization: Shelby County Department of De Street Address: City: State: Zip: Submittal Date: Thu Feb 28 15:46:30 EST 2013 Committee Statement Resolution: The provision of grounding facilities is necessary in order to provide the capability to comply with NFPA 410 or other standards for aircraft maintenance operations. Whether and how the grounding facilities are used is not within the scope of NFPA 409. 7/22/2015 2:42 PM National Fire Protection Association Report 13 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 28-NFPA 409-2013 [ Section No. 5.15.2 ] 5.15.2 Floor-grounding receptacles shall be provided permitted and where installed shall be either grounded through individual driven electrodes or electrically bonded together in a grid system and the entire system grounded to underground metal piping, such as cold water piping, or driven electrodes. Where driven electrodes are used, they shall consist of 15.9 mm ( 5?8 in.) diameter or larger metal rods driven at least 1.5 m (5 ft) into the ground. Floor-grounding receptacles shall be designed to minimize the tripping hazard. Statement of Problem and Substantiation for Public Input Aircraft owners have objected to enforcement of this provision of NFPA 409 and indicate grounding of their aircraft is potentially harmful to aircraft electronics. This revision allows the designer to work with aircraft owner and appropriately protect their investment. Submitter Information Verification Submitter Full Name: Donald Cook Organization: Shelby County Department of De Street Address: City: State: Zip: Submittal Date: Thu Feb 28 16:22:32 EST 2013 Committee Statement Resolution: The provision of grounding facilities is necessary in order to provide the capability to comply with NFPA 410 or other standards for aircraft maintenance operations. Whether and how the grounding facilities are used is not within the scope of NFPA 409. 7/22/2015 2:42 PM National Fire Protection Association Report 14 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 83-NFPA 409-2013 [ Section No. 5.17.1 ] 5.17.1 Draft curtains shall be required in Group I hangars where heat actuated fire detection devices are located below the roof . Additional Proposed Changes File Name NFPA_409_5.17_Draft_Curtains.docx Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input Draft curtains are designed to collect and concentrate hot air and fire gasses to increase the speed at which thermal devices respond. When other types of fire detection are used draft curtains do not assist fire protection, and are not economically justified. Submitter Information Verification Submitter Full Name: RICHARD GILLESPIE Organization: FIRE ENGR SOLUTIONS P/L Street Address: City: State: Zip: Submittal Date: Fri Jul 12 09:02:57 EDT 2013 Committee Statement Resolution: The requirement for draft curtains to be installed in all Group I hangars is based on testing that showed that the draft curtains substantially improved the response of the closed-head sprinkler system. 7/22/2015 2:42 PM National Fire Protection Association Report 15 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 51-NFPA 409-2013 [ New Section after 6.1.1 ] new 6.1.6 Each foam protection system shall be designed, installed, and maintained in accordance with NFPA 11, except that foam system piping shall not be required to be galvanized. Statement of Problem and Substantiation for Public Input NFPA 11 (2010 edition) 4.7.2.1 states "Galvanized pipe shall be used." While this requirement maybe useful for tanks farms it is inappropriate for foam systems inside hangars. Galvanized piping is generally incompatible with the foams. It contributes nothing to system corrosion resistance and may be harmful when the zinc coating deteriorates causing galvanic cell corrosion and potentially releasing flakes of zinc which may clog orifices. FM Global and others are eliminating requirements for galvanized piping. Related Public Comments for This Document Related Comment Relationship Public Input No. 52-NFPA 409-2013 [New Section after 7.1] Public Input No. 53-NFPA 409-2013 [Section No. 9.14.5.3] Public Input No. 54-NFPA 409-2013 [Section No. 6.2.3.3] Public Input No. 55-NFPA 409-2013 [Section No. 6.2.5.2] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 17:23:04 EDT 2013 Committee Statement Resolution: FR-13-NFPA 409-2013 Statement: NFPA 11 (2010 edition) 4.7.2.1 states "Galvanized pipe shall be used." While this requirement may be useful for tank farms, it is inappropriate for foam systems inside hangars. Galvanized piping is generally incompatible with the foams. It contributes nothing to system corrosion resistance and may be harmful when the zinc coating deteriorates causing galvanic cell corrosion and potentially releasing flakes of zinc which may clog orifices. 7/22/2015 2:42 PM National Fire Protection Association Report 16 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 47-NFPA 409-2013 [ Section No. 6.1.1 ] 6.1.1 The protection of aircraft storage and servicing areas for Group I aircraft hangars shall be in accordance with any one of the following: (1) A foam-water deluge system, as specified in 6.2.2. In addition, supplementary protection systems as specified in 6.2.3 shall be provided in hangars housing single aircraft having wing areas greater than 279 m2 (3000 ft2). (2) A combination of automatic sprinkler protection in accordance with 6.2.4 and an automatic low-level low-expansion foam system in accordance with 6.2.5. (3) A combination of automatic sprinkler protection in accordance with 6.2.4 and an automatic low-level high-expansion foam system in accordance with 6.2.5. (4) A combination of automatic sprinkler protection in accordance with 6.2.4 and a fuel containment floor system in accordance with 6.2.X Statement of Problem and Substantiation for Public Input The Fuel Containment Floor System can be an alternative to the current accepted foam based fire suppression systems, that for certain hangars can be a better suited solution in terms of fire protection. Submitter Information Verification Submitter Full Name: TRISTAN MACKINTOSH Organization: Fireless Flooring Street Address: City: State: Zip: Submittal Date: Fri Jul 05 11:33:36 EDT 2013 Committee Statement Resolution: The fuel containment floor system technology has not been fully tested. 7/22/2015 2:42 PM National Fire Protection Association Report 17 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 56-NFPA 409-2013 [ Section No. 6.2.2.3 ] 6.2.2.3 In aircraft storage and servicing areas, the protection area as projected on the floor shall be limited to 12 m 2 (130 ft 2 ). The maximum distance between sprinklers either on branch lines or between branch lines shall be 3.7 m (12 ft). In buildings with storage bays 7.6 m (25 ft) wide, a distance of 3.8 m (12 ft 6 in.) shall be permitted. Statement of Problem and Substantiation for Public Input Allow NFPA 13 to set parameters for spacing along and between branchlines. Note this section is also referenced by also 7.2.3 and 9.14.2(3)(c). Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 17:41:23 EDT 2013 Committee Statement Resolution: The existing requirements were justified during the previous revision cycle (see Proposal 18 and Comment 5). There is inadequate justification to revise this section as suggested at this time. 7/22/2015 2:42 PM National Fire Protection Association Report 18 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 54-NFPA 409-2013 [ Section No. 6.2.3.3 ] 6.2.3.3 Each supplementary protection system shall be designed, installed, and maintained in accordance with NFPA 11. Statement of Problem and Substantiation for Public Input Delete as redundant with proposed new 6.1.6 to apply to all foam systems: "Each foam protection system shall be designed, installed, and maintained in accordance with NFPA 11, except that foam system piping shall not be required to be galvanized." See PI 51. Related Public Comments for This Document Related Comment Relationship Public Input No. 51-NFPA 409-2013 [New Section after 6.1.1] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 17:32:14 EDT 2013 Committee Statement Resolution: FR-14-NFPA 409-2013 Statement: Delete as redundant with new 6.1.6 (FR 13) to apply to all foam systems. 7/22/2015 2:42 PM National Fire Protection Association Report 19 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 84-NFPA 409-2013 [ Sections 6.2.3.5.1, 6.2.3.5.2, 6.2.3.5.3, 6.2.3.5.4, 6.2.3.... ] Sections 6.2.3.5.1, 6.2.3.5.2, 6.2.3.5.3, 6.2.3.5.4, 6.2.3.5.5 6.2.3.5.1 Supplementary high expansion foam systems shall utilize surfactants as the foaming ingredient and shall be designed for local application. comply with 6.2. 3 5 .5 .2 * These systems shall be designed to discharge at a rate to cover the protected area to a depth of at least 0.9 m (3 ft) within 1 minute. 6.2.3.5.3 Discharge rates shall take into consideration the sprinkler breakdown factor required in 6.12.8.2.2(2) of NFPA 11. except that they shall be designed for local or portable application including all parts of the hangar floor beneath an aircraft’s wings when parked in the hangar. This shall allow additional foam as necessary to maintain the application density over all alternative wing locations. 6.2.3.5. 4 The foam generators shall be located at the ceiling or on exterior walls in such a way that only air from outside the aircraft storage and servicing area can be used for foam generation. Roof vents shall be located to avoid recirculation of combustion products into the air inlets of the foam generators. 6.2.3.5.5 * Generators shall be powered by reliable water-driven or electric motors. Electric power reliability for generators shall be in accordance with electric fire pump requirements of NFPA 20 2 Supplementary high expansion foam system generators may be fixed or portable as necessary to facilitate aircraft movement and types, and shall be supported by work procedures to ensure they are used when aircraft with wing areas above 279 m 2 are parked in the hangar . Additional Proposed Changes File Name NFPA_409_6.2.3.5_6.2.5.5_Rationalisation.docx Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input 6.2.3.5 and 6.2.5.5 largely repeat each other and this proposed arrangement reduces this duplication 6.2.3.5.2 Guidance of high-expansion foam local delivery. 6.2.5.5 The term low level is not defined and following the inference that outside-air high-expansion generators should be mounted in hangar walls, not practicable for Group I hangars which have with only two or three exterior walls. Due to the slow horizontal spread of Hi-Ex the use of wall mounted generators should be discouraged. 6.2.5.5.1 changed to be used defining all types of Hi-Ex generation. 6.2.5.5.2 changed to be consistent with the requirement to follow NFPA 11 calculation methodology. 6.2.5.5.3 Expanded to allow zoning of large systems 6.2.5.5.4 Changed to better describe the requirements of general area coverage and supplementary systems 6.2.5.5.5 & 6 Changed to allow inside-air generators 6.2.5.5.6 Minimum quality statement for inside-air generators Inside-air generators offer several advantages over fan driven and outside-air types, the main advantages being :• They have no moving parts thus require less maintenance 7/22/2015 2:42 PM National Fire Protection Association Report 20 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... • They are light weight reducing hangar roof loads • They are better able to withstand fire conditions before use. • They cost less than fan driven generators and deliver a more fluid foam blanket which improves the horizontal spread velocity, offering quicker fire suppression. • They offer significant economies in water and foam consumption and discharges into the environment Submitter Information Verification Submitter Full Name: RICHARD GILLESPIE Organization: FIRE ENGR SOLUTIONS P/L Street Address: City: State: Zip: Submittal Date: Fri Jul 12 09:04:57 EDT 2013 Committee Statement Resolution: The proposed text would radically change the intent of the low-level foam system without adequate justification. Adequate technical data has not been provided to support the use of inside air. The foam application rate does not need to match NFPA 11. Low-level foam systems (6.2.5.5) do not have the same performance criteria as supplementary foam systems (6.2.3.5), as these protection options are used in different protection schemes. The committee has formed a task group to study the issue of zoning of the low-level foam systems. Portable foam generators would not meet the minimum reliability and suppression time that is required for aircraft hangars. Inadequate substantiation was provided to remove the requirement to use surfactants. 7/22/2015 2:42 PM National Fire Protection Association Report 21 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 74-NFPA 409-2013 [ Section No. 6.2.3.5.3 ] 6.2.3.5.3 Discharge rates shall take into consideration the sprinkler breakdown factor required in 6.12.8.2. 3. 2 (2) of NFPA 11 using the total actual discharge from the number of sprinklers expected to operate in L/min (gpm) . Additional Proposed Changes File Name nfpa409_PI_Kasiski_6-2-3-5-3.pdf Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input The revised wording provides clarity on how to properly design a high expansion foam system compensating for breakdown of the foam blanket by using the actual discharge from the sprinkler system. If the design discharge from a sprinkler is used the total rate of discharge from the generator may be incorrect and impact the performance of providing adequate fire protection. Submitter Information Verification Submitter Full Name: Robert Kasiski Organization: FM Global Street Address: City: State: Zip: Submittal Date: Thu Jul 11 13:28:18 EDT 2013 Committee Statement Resolution: There are sufficient safety factors in the existing design criteria to address this concern. 7/22/2015 2:42 PM National Fire Protection Association Report 22 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 89-NFPA 409-2013 [ Sections 6.2.3.5.4, 6.2.3.5.5 ] Sections 6.2.3.5.4, 6.2.3.5.5 6.2.3.5.4 The Outside-air foam generators shall be located at the ceiling or on exterior walls in such a way that only air from outside the aircraft storage and servicing area can be used for foam generation. Roof vents shall be located to avoid recirculation of combustion products into the air inlets of the foam generators. 6.2.3.5.5 * Generators Outside-air generators shall be powered by reliable water-driven or electric motors. Electric power reliability for generators shall be in accordance with electric fire pump requirements of NFPA 20. 6.2.3.5.6 Inside-air generators shall be listed and shall be oriented and located in accordance with the manufacturer's approvals in respect to air inlet clearance and direction of discharge. Additional Proposed Changes File Name NFPA_409_Inside_or_Outside_Air_Foam_Generators.docx Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input Definition of the foam generator types is suggested as helpful. Inside air foam generators may fan driven or air inducing type. Given the normally large size and high ceilings of aircraft hangars, the use of flame detectors and the requirements of NFPA 409 and NFPA 11 for rapid fire suppression, it is most likely that there will be no significant smoke or toxic products of combustion captured by the Hi-Ex generators during a discharge in a hangar. It is not prohibited by either NFPA 409 or NFPA 11 to stop the foam discharge automatically when the fire is suppressed, in fact it is advisable to do so because when the foam concentrate runs out a continuing discharge of water will collapse the Hi-Ex blanket formed during the foam discharge. This has the added benefit of stopping the blanket building to above head height, which is likely to place evacuees in danger, not from toxic gasses in the foam but from disorientation and diminished sight and sound. Tests such as the VROM test (copy of test report attached) on the Skum HG-25 illustrate air-induction types of generator, which owe much of their fire resistance and operability to the fact they use no moving parts. Their simplicity offers economy and design flexibility not possible with fan-driven types. Note: Supporting material is available for review at NFPA Headquarters. Submitter Information Verification Submitter Full Name: RICHARD GILLESPIE Organization: FIRE ENGR SOLUTIONS P/L Street Address: City: State: Zip: Submittal Date: Fri Jul 12 09:31:26 EDT 2013 Committee Statement Resolution: Adequate technical data has not been provided to support the use of inside air. 7/22/2015 2:42 PM National Fire Protection Association Report 23 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 4-NFPA 409-2012 [ Section No. 6.2.3.5.5 ] 6.2.3.5.5 * Foam Generators shall be powered by reliable water-driven or electric motors. Electric power reliability for generators foam generators shall be in accordance with electric fire pump requirements of NFPA 20. Statement of Problem and Substantiation for Public Input Clarifies that the section is specifically addressing foam generators. Submitter Information Verification Submitter Full Name: John Chartier Organization: Northeastern Regional Fire Cod Street Address: City: State: Zip: Submittal Date: Thu Aug 16 11:27:16 EDT 2012 Committee Statement Resolution: FR-17-NFPA 409-2013 Statement: Clarifies that the section is specifically addressing foam generators. 7/22/2015 2:42 PM National Fire Protection Association Report 24 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 35-NFPA 409-2013 [ Section No. 6.2.4.5 ] 6.2.4.5 The design Regardless of the ceiling slope, the design density of water from sprinkler systems shall be a minimum of 6.9 L/min/m 2 (0.17 gpm/ft 2 ) over any 1394 m 2 (15,000 ft 2 ) area, including the hydraulically most demanding area as defined in NFPA 13. Statement of Problem and Substantiation for Public Input There is a great deal of confusion regarding the rules of NFPA 13 and the 30% increase to the design area for buildings with a ceiling/roof slope of more than 2 in 12. As far as NFPA 13 is concerned, this 30% increase only applies to light, ordinary and extra hazard situations (it is in Chapter 11, which only applies to those hazard classifications). But many people try to apply it to other occupancies. Other occupancies need to clarify whether their density/area criteria applies to sloped roof/ceilings. It is our understanding that the criteria in NFPA 409 was developed to be used regardless of the shape or slope of the roof/ceiling. The hanger rules have been sufficiently used to protect barrel shaped roofs that have a slope much greater than 2 in 12. The safety factors involved in the criteria in NFPA 409 allow the discharge criteria in this document to adequately protect sloped roof/ceilings without the 30% increase in the design area. NFPA 409 needs to definitively state that the 30% increase does not apply. We have chosen to do this by inserting the phase, "regardless of the ceiling slope", which should clarify the situation sufficiently. Submitter Information Verification Submitter Full Name: Kenneth Isman Organization: National Fire Sprinkler Association Affilliation: NFSA E&S Committee Street Address: City: State: Zip: Submittal Date: Sat Jun 29 13:11:06 EDT 2013 Committee Statement Resolution: FR-15-NFPA 409-2013 Statement: There is a great deal of confusion regarding the rules of NFPA 13 and the 30% increase to the design area for buildings with a ceiling/roof slope of more than 2 in 12. As far as NFPA 13 is concerned, this 30% increase only applies to light, ordinary and extra hazard situations (it is in Chapter 11, which only applies to those hazard classifications). But many people try to apply it to other occupancies. The safety factors involved in the criteria in NFPA 409 allow the discharge criteria in this document to adequately protect sloped roof/ceilings without the 30% increase in the design area. The committee also clarified that the increase for preaction systems also does not apply to NFPA 409. 7/22/2015 2:42 PM National Fire Protection Association Report 25 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 55-NFPA 409-2013 [ Section No. 6.2.5.2 ] 6.2.5.2 Each low-level foam protection system shall be designed, installed, and maintained in accordance with NFPA 11. Statement of Problem and Substantiation for Public Input Delete as redundant with proposed new 6.1.6 to apply to all foam systems: "Each foam protection system shall be designed, installed, and maintained in accordance with NFPA 11, except that foam system piping shall not be required to be galvanized." See PI 51. Related Public Comments for This Document Related Comment Relationship Public Input No. 51-NFPA 409-2013 [New Section after 6.1.1] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 17:38:54 EDT 2013 Committee Statement Resolution: FR-39-NFPA 409-2013 Statement: Delete as redundant with new 6.1.6 (FR 13) to apply to all foam systems. 7/22/2015 2:42 PM National Fire Protection Association Report 26 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 85-NFPA 409-2013 [ Section No. 6.2.5.5 ] 6.2.5.5 Low-Level High-Expansion Foam Systems. 6.2.5.5.1 Low High - level high- expansion foam systems shall be designed and installed in accordance with requirements for local application systems of NFPA 11 6 . 12.4. 6.2.5.5.2 The minimum application rate shall be a minimum of 0.9 m 3 /min/m 2 (3 ft 3 /min/ft 2 ) determined for a flammable liquids hazard using the calculation method of NFPA 11, Section 6.12 . 6.2.5.5.3 The discharge rate of the system shall be based on the application rate multiplied by the entire aircraft storage and servicing zone floor area. The application total discharge rate shall include the sprinkler breakdown factor specified in 6.12.8.2.2(2) of NFPA 11. rate, unless there are no sprinklers or low expansion deluge nozzles above. Zones shall be the larger of 2500 m 2 (27,000 ft 2 ), or the area assigned to a single aircraft. The design shall allow for the worst case number of wall openings to have foam spilling out to form a wedge outside. Openings shall include hangar doors, workshop hatches, boundaries between zones, etc. unless there is a wall or barrier able to contain the foam. The foam angle of repose used for these calculations shall be determined by testing and confirmed during commissioning. 6.2.5.5.4 The high-expansion foam generators shall be arranged to achieve initial foam coverage in the expected aircraft parking potential fuel spill area. 6.2.5.5.5 Foam Outside-air foam generators shall be supplied with air from outside the aircraft storage and servicing area. Roof vents shall be located to avoid recirculation of combustion products into the air inlets of the foam generators. 6.2.5.5.6 * Foam Outside-air generators shall be powered by reliable water-driven or electric motors. Electric power reliability for foam generators shall be consistent in accordance with electric fire pump requirements specified in Chapters 6 and 7 of NFPA 20. 6.2.5.5.7 Inside-air generators shall be listed and shall be oriented and located in accordance with the manufacturer’s approvals in respect to air inlet clearance and direction of discharge. Additional Proposed Changes File Name NFPA_409_6.2.3.5_6.2.5.5_Rationalisation.docx Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input 6.2.3.5 and 6.2.5.5 largely repeat each other and this proposed arrangement reduces this duplication 6.2.3.5.2 Guidance of high-expansion foam local delivery. 6.2.5.5 The term low level is not defined and following the inference that outside-air high-expansion generators should be mounted in hangar walls, not practicable for Group I hangars which have with only two or three exterior walls. Due to the slow horizontal spread of Hi-Ex the use of wall mounted generators should be discouraged. 6.2.5.5.1 changed to be used defining all types of Hi-Ex generation. 6.2.5.5.2 changed to be consistent with the requirement to follow NFPA 11 calculation methodology. 6.2.5.5.3 Expanded to allow zoning of large systems 6.2.5.5.4 Changed to better describe the requirements of general area coverage and supplementary systems 6.2.5.5.5 & 6 Changed to allow inside-air generators 6.2.5.5.6 Minimum quality statement for inside-air generators Inside-air generators offer several advantages over fan driven and outside-air types, the main advantages being :• They have no moving parts thus require less maintenance 7/22/2015 2:42 PM National Fire Protection Association Report 27 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... • They are light weight reducing hangar roof loads • They are better able to withstand fire conditions before use. • They cost less than fan driven generators and deliver a more fluid foam blanket which improves the horizontal spread velocity, offering quicker fire suppression. • They offer significant economies in water and foam consumption and discharges into the environment Submitter Information Verification Submitter Full Name: RICHARD GILLESPIE Organization: FIRE ENGR SOLUTIONS P/L Street Address: City: State: Zip: Submittal Date: Fri Jul 12 09:07:13 EDT 2013 Committee Statement Resolution: The proposed text would radically change the intent of the low-level foam system without adequate justification. Adequate technical data has not been provided to support the use of inside air. The foam application rate does not need to match NFPA 11. Low-level foam systems (6.2.5.5) do not have the same performance criteria as supplementary foam systems (6.2.3.5), as these protection options are used in different protection schemes. The committee has formed a task group to study the issue of zoning of the low-level foam systems. Portable foam generators would not meet the minimum reliability and suppression time that is required for aircraft hangars. Inadequate substantiation was provided to remove the requirement to use surfactants. 7/22/2015 2:42 PM National Fire Protection Association Report 28 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 75-NFPA 409-2013 [ Section No. 6.2.5.5.3 ] 6.2.5.5.3 The discharge rate of the system shall be based on the application rate multiplied by the entire aircraft storage and servicing floor area. The application total discharge rate shall include the sprinkler breakdown factor specified in 6.12.8.2. 3. 2 (2) of NFPA 11 using the total actual discharge from the number of sprinklers expected to operate in L/min (gpm) . Additional Proposed Changes File Name nfpa409_PI_Kasiski_6-2-5-5-3.pdf Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input The revised wording provides clartiy on how to properly design a high expansion foam system compensating for breakdown of the foam blanket by using the actual discharge from the sprinkler system. If the design discharge from a sprinkler is used the total rate of discharge from the generator may be incorrect and impact the performance of providing adequate fire protection. Submitter Information Verification Submitter Full Name: Robert Kasiski Organization: FM Global Street Address: City: State: Zip: Submittal Date: Thu Jul 11 13:31:14 EDT 2013 Committee Statement Resolution: There are sufficient safety factors in the existing design criteria to address this concern. 7/22/2015 2:42 PM National Fire Protection Association Report 29 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 60-NFPA 409-2013 [ Section No. 6.2.5.5.5 ] 6.2.5.5.5 Foam generators shall be supplied with air from outside the or inside the aircraft storage and servicing area. Roof vents shall be located to avoid recirculation of combustion products into the air inlets of the foam generators. area in accordance with the provisions of 6.9 of NFPA 11. Statement of Problem and Substantiation for Public Input In past NFPA 409 TC meetings inside air test data was presented by Ansul which demonstrated compliance with NFPA 11 6.9.1 and 6.9.2 for high expansion foam produced with inside air. At the time the TC rejected the proposal to allow inside air with some members citing life safety concerns. However there is no compelling reason to believe that life safety is more at risk in an aircraft hangar than in a flammable liquids warehouse with aisles of rack storage. Therefore it is recommended that the TC accept this proposal which will allow HEF systems to be implemented more reliably by eliminating roof penetrations and dampers. Related Public Comments for This Document Related Comment Relationship Public Input No. 61-NFPA 409-2013 [Section No. 7.5.5] Public Input No. 62-NFPA 409-2013 [Section No. 9.14.7.5.5] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 17:59:25 EDT 2013 Committee Statement Resolution: Adequate technical data has not been provided to support the use of inside air. 7/22/2015 2:42 PM National Fire Protection Association Report 30 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 90-NFPA 409-2013 [ Sections 6.2.5.5.5, 6.2.5.5.6 ] Sections 6.2.5.5.5, 6.2.5.5.6 6.2.5.5.5 Foam Outside-air foam generators shall be supplied with air from outside the aircraft storage and servicing area. Roof vents shall be located to avoid recirculation of combustion products into the air inlets of the foam generators. 6.2.5.5.6 * Foam Outside-air generators shall be powered by reliable water-driven or electric motors. Electric power reliability for foam generators shall be consistent with electric fire pump requirements specified in Chapters 6 and 7 of NFPA 20. 6.2.5.5.7 Inside-air generators shall be listed and shall be oriented and located in accordance with the manufacturer’s approvals in respect to air inlet clearance and direction of discharge, Additional Proposed Changes File Name NFPA_409_Inside_or_Outside_Air_Foam_Generators.docx Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input Definition of the foam generator types is suggested as helpful. Inside air foam generators may fan driven or air inducing type. Given the normally large size and high ceilings of aircraft hangars, the use of flame detectors and the requirements of NFPA 409 and NFPA 11 for rapid fire suppression, it is most likely that there will be no significant smoke or toxic products of combustion captured by the Hi-Ex generators during a discharge in a hangar. It is not prohibited by either NFPA 409 or NFPA 11 to stop the foam discharge automatically when the fire is suppressed, in fact it is advisable to do so because when the foam concentrate runs out a continuing discharge of water will collapse the Hi-Ex blanket formed during the foam discharge. This has the added benefit of stopping the blanket building to above head height, which is likely to place evacuees in danger, not from toxic gasses in the foam but from disorientation and diminished sight and sound. Tests such as the VROM test (copy of test report attached) on the Skum HG-25 illustrate air-induction types of generator, which owe much of their fire resistance and operability to the fact they use no moving parts. Their simplicity offers economy and design flexibility not possible with fan-driven types. Note: Supporting material is available for review at NFPA Headquarters. Submitter Information Verification Submitter Full Name: RICHARD GILLESPIE Organization: FIRE ENGR SOLUTIONS P/L Street Address: City: State: Zip: Submittal Date: Fri Jul 12 09:36:12 EDT 2013 Committee Statement Resolution: Adequate technical data has not been provided to support the use of inside air. 7/22/2015 2:42 PM National Fire Protection Association Report 31 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 86-NFPA 409-2013 [ Section No. 6.2.6 ] 6.2.6 * Foam Concentrate Supply. The friction losses in piping carrying foam concentrate shall be calculated using the Darcy formula, also known as the Fanning formula. 6.2.6.1 * The quantities of low-expansion foam concentrate , either protein foam, fluoroprotein, or AFFF, shall be large enough for a 10-minute foam discharge based on the supply calculation in 6.2.2.4 and NFPA 16 . 6.2.6.2 * The quantity of high-expansion foam concentrate shall be large enough for a 12 15 -minute discharge at the water flow rate based on the supply calculation method required in 6.2.2.4 . of NFPA 11. 6.2.6.3 A reserve supply of foam concentrate of compatible type for the system shall be directly connected to the system and immediately available. The reserve supply shall be in the same quantity as the main supply. To prevent accidental depletion of this reserve supply, it shall be available to the system only by intentional manual operation. 6.2.6.4 Control valves, foam concentrate liquid storage tanks, concentrate pumps, controllers, and bypass balancing equipment shall be located outside the aircraft storage and service area. 6.2.6.5 Where possible all foam systems within a hangar should use the same foam type, in terms of foam concentrate compatibility and expansion ratio. Differing types shall only be permitted where the combination is endorsed by the foam manufacturer(s). 6.2.6.6 To prevent unnecessary sprinkler breakdown, low-expansion foam shall not be applied above high-expansion foam unless the low-expansion foam is released under control of heat detectors and the high-expansion foam by flame detectors. Additional Proposed Changes File Name NFPA_409_6.2.6_Foam_Concentrate_Supply.docx Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input 6.2.6.1 Protein foam is no longer manufactured, and Lo-Ex foam types do not include FFFP, this level of detail does not seem necessary. 6.2.6.2 NFPA 409 requires compliance with NFPA 11, which requires 2x 15 minute supplies. The calculation method in 6.2.2.4 is only part of the necessary calculation, and NFPA 11 offers a better calculation method. 6.2.6.5 Since the formulation of high-expansion foam concentrate is significantly different to all other types of foam, it is unlikely that any manufacturer would endorse Lo-Ex and Hi-Ex in combination. 6.2.6.6 It is necessary for Group I hangars (6.1.1 (1)) for aircraft with wing areas over 279 m2 to allow AFFF deluge with Hi-Ex supplementary protection. Given that flame detectors are used to initiate the supplementary Hi-Ex protection, if the heat detectors at roof level operate it can be assumed the Hi-Ex system has failed, one or more aircraft within the hangar will be severely damaged, and the high level system will provide protection to the hangar roof structure. Note: Supporting material is available for review at NFPA Headquarters. Submitter Information Verification Submitter Full Name: RICHARD GILLESPIE Organization: FIRE ENGR SOLUTIONS P/L Street Address: 7/22/2015 2:42 PM National Fire Protection Association Report 32 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... City: State: Zip: Submittal Date: Fri Jul 12 09:11:32 EDT 2013 Committee Statement Resolution: Fluoroprotein is still available. There is inadequate substantiation to increase the supply duration. See FR 55 (6.2.6.3) regarding changes to the requirements for a reserve foam supply. The standard does not necessitate the use of low-expansion foam below high-expansion foam in a single hangar. 7/22/2015 2:42 PM National Fire Protection Association Report 33 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 45-NFPA 409-2013 [ New Section after 6.2.7.10 ] 6.2.X Fuel Containment Floor System. 6.2.X.1 Hangars protected in accordance with 6.1.1(4) shall be protected with a fuel containment floor system. 6.2.X.2 The fuel containment floor system shall be designed to achieve (1) containment of aviation fuel spilled out of aircrafts within the storage and service area and prevent the fuel from being (re)ignited. (2) Suppression of burning aviation fuel spilled out of aircrafts within the storage and service area. 6.2.X.3 System floor size 6.2.X.3.1 In aircraft storage and servicing areas where the aircraft parking area is fixed, a fuel containment floor system shall be installed directly underneath the aircraft’s fuel tanks in accordance with 6.2.X.3.2 6.2.X.3.2 The fuel containment floor system shall cover the floor from the perimeter of the aircraft’s fuel tanks and all area within. 6.2.X.3.2.1 The fuel containment floor system shall consist of a single continuous floor per each aircraft. 6.2.X.3.2 In aircraft storage and servicing areas where the aircraft parking area is flexible, a fuel containment floor system shall cover the entire area where an aircraft can potential be parked in accordance with 6.2.X.3.2 6.2.X.3.3 The edge of the fuel containment floor system should be a minimum of 6m. (18 ft.) in horizontal distance from the perimeter of the fuel tanks. 6.2.X.4 Activated water sprinklers as per 6.2.4 shall not affect the performance of the fuel containment floor system. The drainage capacity of the system shall include the maximum amount of water deployed by the overhead sprinkler system. 6.2.X.5 Fuel removal 6.2.X.5.1 The system shall have an integrated flush capability to flush out contained fuel. The flush system shall be discharged into the trench drain system in accordance with 5.11.2 6.2.X.5.2 In case of existing aircraft storage and service areas where (1) the trench drain layout is not practically located in relation to the fuel containment floor system, (2) or the concrete floor slab does not have sufficient pitch, a suction system may be installed to remove liquids from the system into the nearest trench drain or directly to a safe outside location in accordance with 5.11.2.3. Statement of Problem and Substantiation for Public Input The Fuel Containment Floor System can be an alternative to the current accepted foam based fire suppression systems, that for certain hangars can be a better suited solution in terms of fire protection. Submitter Information Verification Submitter Full Name: TRISTAN MACKINTOSH Organization: Fireless Flooring Street Address: City: State: Zip: Submittal Date: Fri Jul 05 11:23:31 EDT 2013 7/22/2015 2:42 PM National Fire Protection Association Report 34 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Committee Statement Resolution: The fuel containment floor system technology has not been fully tested. 7/22/2015 2:42 PM National Fire Protection Association Report 35 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 29-NFPA 409-2013 [ Section No. 6.2.7.10 ] 6.2.7.10 Controllers for foam concentrate pumps shall be as follows: (1) For electric-drive foam concentrate pumps greater than 22.4kW (30 horsepower) , a listed electric foam pump controller shall be used. (2) For electric-drive foam concentrate pumps not exceeding 22.4kW (30 horsepower), a listed electric foam pump controller or limited-service foam pump controller shall be used. (2) For diesel engine–driven foam concentrate pumps, a listed fire pump controller shall be used. Additional Proposed Changes File Name 6.2.7.10_1_.pdf Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input Foam pumps feed full service controllers and should be no less than full service controllers. Listed full service controllers are now available in horsepowers down to 1.0 Hp. Also, Limited Service Controllers are no longer Listed (Approved) by Factory Mutual. Note: At one time, full service controllers were not available below 30 Hp. Note: Similar proposals have been submitted to NFPA-11 and NFPA-16. Submitter Information Verification Submitter Full Name: James Nasby Organization: Columbia Engineering Street Address: City: State: Zip: Submittal Date: Fri Mar 01 07:48:06 EST 2013 Committee Statement Resolution: FR-16-NFPA 409-2013 Statement: To allow limited service foam pump controllers is inconsistent with the reliability and redundancy requirements throughout this standard. 7/22/2015 2:42 PM National Fire Protection Association Report 36 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 57-NFPA 409-2013 [ Section No. 6.2.7.10 ] 6.2.7.10 Controllers for foam concentrate pumps shall be as follows: (1) For electric-drive foam concentrate pumps greater than 22.4kW (30 horsepower), a listed full service electric foam pump controller shall be used. (2) For electric-drive foam concentrate pumps not exceeding 22.4kW (30 horsepower), a listed electric foam pump controller or limited-service foam pump controller shall be used. (3) For diesel engine–driven foam concentrate pumps, a listed fire pump controller shall be used. Statement of Problem and Substantiation for Public Input Limited service fire pump controllers have been recommended for deletion twice by the NFPA 20 TC. Since full service controllers are available for all pump motor sizes at only a small additional cost, this should be the minimum requirement. To allow limited service foam pump controllers is inconsistent with the reliability and redundancy requirements throughout this standard. Also the language in 6.2.7.10 should be identical to 7.3.3.9 and 9.14.9.3. Related Public Comments for This Document Related Comment Relationship Public Input No. 58-NFPA 409-2013 [Section No. 7.3.3.9] Public Input No. 59-NFPA 409-2013 [Section No. 9.14.9.3] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 17:45:11 EDT 2013 Committee Statement Resolution: FR-16-NFPA 409-2013 Statement: To allow limited service foam pump controllers is inconsistent with the reliability and redundancy requirements throughout this standard. 7/22/2015 2:42 PM National Fire Protection Association Report 37 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 67-NFPA 409-2013 [ New Section after 6.2.8.1 ] proposed new 6.2.8.1.4 Listed detection systems (such as optical flame detection) shall be acceptable in lieu of heat detection if both approved by the Authority Having Jurisdiction and installed in accordance with NFPA 72. Statement of Problem and Substantiation for Public Input The purpose of this change is to make it clear than an owner and AHJ may agree to adopt an alternate detection system without requiring two detection systems. Related Public Comments for This Document Related Comment Relationship Public Input No. 68-NFPA 409-2013 [New Section after 7.7] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 18:33:45 EDT 2013 Committee Statement Resolution: FR-18-NFPA 409-2013 Statement: The purpose of this change is to make it clear than an owner and AHJ may agree to adopt an alternate detection system without requiring two detection systems. 7/22/2015 2:42 PM National Fire Protection Association Report 38 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 65-NFPA 409-2013 [ New Section after 6.2.8.4 ] proposed new 6.2.8.4.1 Where wet-pipe sprinkler systems are provided, detection of sprinkler water flow shall be acceptable as the means of heat detection. Statement of Problem and Substantiation for Public Input This is a clarification of the intent of the standard. Related Public Comments for This Document Related Comment Relationship Public Input No. 66-NFPA 409-2013 [New Section after 7.7.1] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 18:25:02 EDT 2013 Committee Statement Resolution: The proposed text would place requirements regarding the actuation of the low-level foam system within the section that addresses the actuation of preaction sprinkler systems. 7/22/2015 2:42 PM National Fire Protection Association Report 39 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 73-NFPA 409-2013 [ Section No. 6.2.8.5.1 ] 6.2.8.5.1 * Actuation of any closed-head sprinkler system shall simultaneously operate the low-level foam protection system (s) associated with it's area of coverage . Statement of Problem and Substantiation for Public Input In Group I hangars low-level foam systems may need to be divided into multiple systems or zones. The standard is very clear that the capability to discharge all zones of a low-level foam system must be provided. For foam-water deluge sprinklers the standard implies that the systems are to be operated on a system by system basis in response to fire alarm initiating devices. Similarly for low-level foam, the standard needs to clarify if the systems or zones must all be discharged simultaneously, or if the response can be zoned in some manner. The recommendation is to allow a zoned response of the low-level systems. Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Mon Jul 08 23:17:33 EDT 2013 Committee Statement Resolution: The committee has formed a task group to study the issue of zoning of the low-level foam systems. 7/22/2015 2:42 PM National Fire Protection Association Report 40 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 40-NFPA 409-2013 [ Section No. 6.2.9.3.1.1 ] 6.2.9.3.1.1 Where aircraft storage and servicing areas house only unfueled aircraft, as defined in 3.3.15 , hand hose systems shall be provided in accordance with 6.2.9.4 of this standard. Statement of Problem and Substantiation for Public Input Hand hose systems for hangars housing unfueled aircraft are addressed in Chapter 12, Unfueled Aircraft Hangars. Paragraphs 12.5.10 and 12.5.6.1 indicate inside hand hose systems are not required. This change relocates unfueled aircraft hangar criteria to the chapter covering the subject, and eliminates conflicting criteria. Submitter Information Verification Submitter Full Name: LIANE OZMUN Organization: FRANKFURT-SHORT-BRUZA Street Address: City: State: Zip: Submittal Date: Tue Jul 02 13:20:53 EDT 2013 Committee Statement Resolution: FR-19-NFPA 409-2013 Statement: Hand hose systems for hangars housing unfueled aircraft are addressed in Chapter 12, Unfueled Aircraft Hangars. Paragraphs 12.5.10 and 12.5.6.1 indicate inside hand hose systems are not required. This change relocates unfueled aircraft hangar criteria to the chapter covering the subject, and eliminates conflicting criteria. 7/22/2015 2:42 PM National Fire Protection Association Report 41 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 63-NFPA 409-2013 [ Section No. 6.2.10.8.2 ] 6.2.10.8.2 The total pumping capacity shall be such that the maximum demand is met with the largest fire pump out of service. be provided using fire pumps of equal capacity. No fewer than two fire pumps shall be provided. Statement of Problem and Substantiation for Public Input The "largest fire pump out of service" requirement is a level of redundancy not found in any other NFPA occupancy standard. NFPA 20 takes considerable care in ensuring fire pump reliability. This proposal relaxes the requirement for water supply redundancy in a manner analogous to the divided water supply requirement of.6.2.10.7 and does not allow the hangar to be protected by only a single fire pump. Related Public Comments for This Document Related Comment Relationship Public Input No. 64-NFPA 409-2013 [Section No. 9.14.13.2] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 18:17:04 EDT 2013 Committee Statement Resolution: FR-41-NFPA 409-2013 Statement: The "largest fire pump out of service" requirement is a level of redundancy not found in any other NFPA occupancy standard. NFPA 20 takes considerable care in ensuring fire pump reliability. This revision relaxes the requirement for water supply redundancy, but does not allow the hangar to be protected by only a single fire pump. See also CI 40, which proposes an alternative revision for this section. 7/22/2015 2:42 PM National Fire Protection Association Report 42 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 1-NFPA 409-2012 [ Section No. 6.2.10.9 ] 6.2.10.9* Flushing Underground Pipe. Underground mains and each lead-in connection shall be flushed as specified in NFPA 15 24 . Statement of Problem and Substantiation for Public Input The addition of NFPA 24 into this section makes the document more consistent with the flushing guidelines established in the reference for Private Underground Fire Service Mains and is consistent with section 9.14.13.7. Submitter Information Verification Submitter Full Name: Doug Hohbein Organization: Northcentral Fire Code Develop Street Address: City: State: Zip: Submittal Date: Thu Aug 16 09:52:47 EDT 2012 Committee Statement Resolution: FR-20-NFPA 409-2013 Statement: The addition of NFPA 24 into this section makes the document more consistent with the flushing guidelines established in the reference for Private Underground Fire Service Mains and is consistent with section 9.14.13.7. 7/22/2015 2:42 PM National Fire Protection Association Report 43 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 3-NFPA 409-2012 [ Section No. 6.2.10.9 ] 6.2.10.9* Flushing Underground Pipe. Underground mains and each lead-in connection shall be flushed as specified in NFPA 15 25 . Statement of Problem and Substantiation for Public Input NFPA 25 addresses testing, inspection, and maintenance of water based systems. Submitter Information Verification Submitter Full Name: John Chartier Organization: Northeastern Regional Fire Cod Street Address: City: State: Zip: Submittal Date: Thu Aug 16 11:25:42 EDT 2012 Committee Statement Resolution: FR-20-NFPA 409-2013 Statement: The addition of NFPA 24 into this section makes the document more consistent with the flushing guidelines established in the reference for Private Underground Fire Service Mains and is consistent with section 9.14.13.7. 7/22/2015 2:42 PM National Fire Protection Association Report 44 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 52-NFPA 409-2013 [ New Section after 7.1 ] new 7.1.5 Each foam protection system shall be designed, installed, and maintained in accordance with NFPA 11, except that foam system piping shall not be required to be galvanized. Statement of Problem and Substantiation for Public Input See proposed new 6.1.6 which is PI 51. Related Public Comments for This Document Related Comment Relationship Public Input No. 51-NFPA 409-2013 [New Section after 6.1.1] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 17:26:28 EDT 2013 Committee Statement Resolution: FR-42-NFPA 409-2013 Statement: NFPA 11 (2010 edition) 4.7.2.1 states "Galvanized pipe shall be used." While this requirement may be useful for tank farms, it is inappropriate for foam systems inside hangars. Galvanized piping is generally incompatible with the foams. It contributes nothing to system corrosion resistance and may be harmful when the zinc coating deteriorates causing galvanic cell corrosion and potentially releasing flakes of zinc which may clog orifices. 7/22/2015 2:42 PM National Fire Protection Association Report 45 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 70-NFPA 409-2013 [ Sections 7.1, 7.2, 7.3, 7.4 ] 7.1 Sections 7.1, 7.2, 7.3, 7.4 7.1 General. 7.1.1 The protection of aircraft storage and servicing areas of Group II aircraft hangars shall be in accordance with any one of the following: (1) The provisions of Chapter 6 , unless foam-water deluge systems utilizing air-aspirating discharge devices are installed for the protection of Group II aircraft hangars, in which case the discharge rate specified in 6.2.2.12 of this standard is permitted to be reduced to a minimum of 6.5 L/min/m 2 (0.16 gpm/ft 2 ) of floor area (2) A combination of automatic sprinkler protection in accordance with Section 7.2 and an automatic, low-level, low-expansion foam system in accordance with Sections 7.3 and 7.4 (3) A combination of automatic sprinkler protection in accordance with Section 7.2 and an automatic, high-expansion foam system in accordance with Sections 7.3 and 7.5 (4) A closed-head foam-water sprinkler system in accordance with Section 7.6 7.1.2 Group II aircraft hangar storage and service areas housing unfueled aircraft shall be provided with automatic sprinkler protection as specified in Chapter 12 . 7.1.3 Automatic closed-head sprinkler protection shall be provided inside separate shop, office, and storage areas located inside aircraft maintenance and servicing areas. The design shall be in accordance with hazard classifications specified in NFPA 13. 7.1.4 In addition to the provision for sprinkler and foam extinguishing systems as required by this chapter, protection as required by 6.2.9 and Sections 6.3 and 6.4 also shall be provided. 7.2 Closed-Head Water Sprinkler System for Aircraft Storage and Servicing Areas. 7.2.1 * Sprinkler systems shall be either wet pipe or preaction, designed and installed in accordance with the applicable sections of NFPA 13 and the provisions of this chapter. 7.2.2 Sprinkler piping shall be hydraulically sized in accordance with NFPA 13. 7.2.3 Sprinkler spacing shall be as specified in 6.2.2.3 . 7.2.4 Where open hangar doors result in interference with the distribution of water from the hangar sprinkler systems, additional sprinklers shall be provided to ensure required floor coverage. 7.2.5 The design density of water from sprinkler systems shall be a minimum of 6.9 L/min/m 2 (0.17 gpm/ft 2 ) over any 464.5 m 2 (5000 ft 2 ) area, including the hydraulically most demanding area as defined in NFPA 13. 7.2.6 Sprinklers shall be nominal K-80 (K-5.6) or K-115 (K-8.0) sprinklers. 7.2.7 Sprinklers shall have a temperature rating of 162°C to 190°C (325°F to 375°F). 7.2.8 Sprinkler systems shall be flushed and tested in accordance with NFPA 13. 7/22/2015 2:42 PM National Fire Protection Association Report 46 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 7.3 * Foam Concentrate — General. The friction losses in piping carrying foam concentrate shall be calculated using the Darcy formula, also known as the Fanning formula. 7.3.1 The foam concentrate supplied with the system shall be listed for use with the distribution equipment. 7.3.2 There shall be a reserve of foam concentrate of a compatible type directly connected to the system. The reserve supply shall be in the same quantity as the main supply. To prevent accidental depletion of this reserve supply, it shall be available to the system only by intentional manual operation. 7.3.3 Foam Concentrate Pumps. 7.3.3.1 Foam concentrate pump installations shall comply with the applicable provisions of NFPA 20, except as modified by this standard. 7.3.3.2 Where foam concentrate is introduced into the water stream by pumping, the total foam concentrate pumping capacity shall be such that the maximum flows and pressures are met with the largest foam concentrate pump out of service. The reserve pump(s) shall be arranged to operate only upon failure of the primary pump(s). 7.3.3.3 Piping shall be arranged so that maximum foam concentrate demand is supplied by any foam concentrate pump from either primary or reserve foam concentrate tanks. 7.3.3.4 Foam concentrate pumps shall be provided with means of pressure relief from the pump discharge to prevent excessive pressure and temperature. Discharge from the relief valve shall be piped back to the foam concentrate storage tank. Connection to the suction piping shall not be permitted. 7.3.3.5 The pressure-regulating valve shall not be used as the pressure relief valve. Foam concentrate pumps shall be started automatically by either a pressure drop in the foam concentrate piping system or a signal from the detection system control panel. 7.3.3.6 A pressure maintenance pump shall be provided to maintain pressure in the foam concentrate piping system where foam concentrate lines to the protective system injection points are run underground or where they run aboveground for more than 15 m (50 ft). 7.3.3.7 Once started, foam concentrate pumps shall be arranged to run continuously until stopped manually. There shall be an audible “pump running” alarm in a constantly attended location. 7.3.3.8 Power supply for the drivers of foam concentrate pumps shall be installed in accordance with NFPA 20 and NFPA 70 . Power supplies shall be arranged such that disconnecting power to the protected facility during a fire shall not disconnect the power supply to the foam concentrate pump feeder circuit. 7.3.3.9 Controllers for foam concentrate pumps shall be as follows: (1) For electric-drive foam concentrate pumps greater than 22.4 kW (30 horsepower), a listed fire pump controller shall be used. (2) For electric-drive foam concentrate pumps greater than 11 kW (15 horsepower) but not exceeding 22.4 kW (30 horsepower), a listed fire pump controller or listed limited service controller shall be used. (3) For electric foam concentrate pumps less than 11 kW (15 horsepower), a listed limited service controller shall be used. (4) For diesel engine–drive foam concentrate pumps, a listed fire pump controller shall be used. 7.3.4 The control valves, foam–liquid concentrate storage, injection system, and foam concentrate pump shall be located outside aircraft storage and servicing areas. 7.3.5 7/22/2015 2:42 PM National Fire Protection Association Report 47 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Plans and specifications for closed-head foam-water sprinkler systems shall provide the information required by 6.2.1 of this standard and NFPA 16. Plans and specifications for other foam extinguishing systems shall provide the information required by 6.2.1 . 7.3.6 Acceptance Tests. 7.3.6.1 Acceptance tests for closed-head foam-water sprinkler systems shall be performed in accordance with NFPA 16. 7.3.6.2 Acceptance tests for foam extinguishing systems shall be performed in accordance with 6.2.11.1 , 6.2.11.2 , 6.2.11.6 , and 6.2.11.8 . 7.3.6.2.1 The systems shall be subjected to flow tests, with foam flowing from the maximum number of foam distributors expected to operate, in order to ensure that the hangar is protected in conformance with the design specifications and to determine if the flow pressures, agent discharge capacity, foam coverage, and percentage of concentration are satisfactory. 7.3.6.2.1.1 A flow test shall be performed with only the foam system operating. 7.3.6.2.1.2 A flow test shall be performed with the foam system operating at the design pressure with the sprinkler system and hose demand. 7.3.6.3 * The timing of foam system discharge shall be measured beginning at the time of system actuation. 7.3.7 The installing company shall furnish a written statement to the effect that the work has been completed in accordance with approved plans and specifications and tested in accordance with the provisions of 7.3.6 . 7.4 * Low-Expansion Foam System. 7/22/2015 2:42 PM National Fire Protection Association Report 48 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 7.4.1 Foam systems shall be of the fixed type and shall be designed and installed in accordance with the requirements for fixed-type systems in NFPA 11. 7.4.2 The minimum application rate of foam solution shall be 6.5 L/min/m 2 (0.16 gpm/ft 2 ) where protein-based or fluoroprotein-based concentrate is used. Where AFFF concentrate is used, the minimum application rate of foam solution shall be 4.1 L/min/m 2 (0.10 gpm/ft 2 ). 7.4.3 * The discharge rate of the system shall be based on the rate of application multiplied by the entire aircraft storage and servicing floor area. 7.4.4 The foam system shall use low-level monitor-type discharge nozzles, with individual manual shutoff valves for each nozzle. The discharge nozzles shall be arranged to achieve initial foam coverage in the expected aircraft parking area. 7.4.5 * The quantity of foam concentrate shall be calculated for a 10-minute discharge at the water flow rate based on the supply calculation method. 7.4.6 The low-level foam system shall be designed to achieve distribution of foam over the entire aircraft storage and service area. The design objective shall be to achieve coverage of the entire aircraft storage and servicing area to within 1.5 m (5 ft) of the perimeter walls and doors within 3 minutes of system actuation. We propose that subparts (1), (2), (3), and (4) of 7.1.1 be removed and replaced with the following amendment: (1) Group II hangars used for storage of aircraft and routine maintenance only shall have an automatic sprinkler protection system in accordance with Section 7.2, but the hangar shall be exempt from foam requirements per 412.4.6 of the International Building Code. (2) Hazardous operations and equipment (doping, hot work, fuel transfer, fuel tank repair/maintenance, and spray finishing) per International Building Code 412.4.6.1 and 412.4.6.3 is prohibited in Group II hangars without a foam fire suppression system in accordance with sections 7.3, 7.4, 7.5, and 7.6. Additional Proposed Changes File Name Description NFPA_Letter_2_.docx NFPA Ch. 7 proposed changes Approved Statement of Problem and Substantiation for Public Input Group II Hangars would no longer be required to install foam fire suppression systems. See letter attached. Submitter Information Verification Submitter Full Name: Will Hickman Organization: City of Fort Worth Affilliation: Fort Worth Spinks Airport Street Address: City: State: Zip: Submittal Date: Mon Jul 08 15:04:04 EDT 2013 Committee Statement 7/22/2015 2:42 PM National Fire Protection Association Report 49 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Resolution: No new information has been provided to change the protection criteria for Group II hangars. 7/22/2015 2:42 PM National Fire Protection Association Report 50 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 46-NFPA 409-2013 [ Section No. 7.1.1 ] 7.1.1 The protection of aircraft storage and servicing areas of Group II aircraft hangars shall be in accordance with any one of the following: (1) The provisions of Chapter 6 , unless foam-water deluge systems utilizing air-aspirating discharge devices are installed for the protection of Group II aircraft hangars, in which case the discharge rate specified in 6.2.2.12 of this standard is permitted to be reduced to a minimum of 6.5 L/min/m2 (0.16 gpm/ft2) of floor area (2) A combination of automatic sprinkler protection in accordance with Section 7.2 and an automatic, low-level, low-expansion foam system in accordance with Sections 7.3 and 7.4 (3) A combination of automatic sprinkler protection in accordance with Section 7.2 and an automatic, high-expansion foam system in accordance with Sections 7.3 and 7.5 (4) A closed-head foam-water sprinkler system in accordance with Section 7.6 (5) A combination of automatic sprinkler protection in accordance with 7.2 and a fuel containment floor system in accordance with 7.X Statement of Problem and Substantiation for Public Input The Fuel Containment Floor System can be an alternative to the current accepted foam based fire suppression systems, that for certain hangars can be a better suited solution in terms of fire protection. Submitter Information Verification Submitter Full Name: TRISTAN MACKINTOSH Organization: Fireless Flooring Street Address: City: State: Zip: Submittal Date: Fri Jul 05 11:32:36 EDT 2013 Committee Statement Resolution: The fuel containment floor system technology has not been fully tested. 7/22/2015 2:42 PM National Fire Protection Association Report 51 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 36-NFPA 409-2013 [ Section No. 7.2.5 ] 7.2.5 The Regardless of the ceiling slope, the design density of water from sprinkler systems shall be a minimum of 6.9 L/min/m 2 (0.17 gpm/ft 2 ) over any 464.5 m 2 (5000 ft 2 ) area, including the hydraulically most demanding area as defined in NFPA 13. Statement of Problem and Substantiation for Public Input There is a great deal of confusion regarding the rules of NFPA 13 and the 30% increase to the design area for buildings with a ceiling/roof slope of more than 2 in 12. As far as NFPA 13 is concerned, this 30% increase only applies to light, ordinary and extra hazard situations (it is in Chapter 11, which only applies to those hazard classifications). But many people try to apply it to other occupancies. Other occupancies need to clarify whether their density/area criteria applies to sloped roof/ceilings. It is our understanding that the criteria in NFPA 409 was developed to be used regardless of the shape or slope of the roof/ceiling. The hanger rules have been sufficiently used to protect barrel shaped roofs that have a slope much greater than 2 in 12. The safety factors involved in the criteria in NFPA 409 allow the discharge criteria in this document to adequately protect sloped roof/ceilings without the 30% increase in the design area. NFPA 409 needs to definitively state that the 30% increase does not apply. We have chosen to do this by inserting the phase, "regardless of the ceiling slope", which should clarify the situation sufficiently. Submitter Information Verification Submitter Full Name: Kenneth Isman Organization: National Fire Sprinkler Association Affilliation: NFSA E&S Committee Street Address: City: State: Zip: Submittal Date: Sat Jun 29 13:24:36 EDT 2013 Committee Statement Resolution: FR-46-NFPA 409-2013 Statement: There is a great deal of confusion regarding the rules of NFPA 13 and the 30% increase to the design area for buildings with a ceiling/roof slope of more than 2 in 12. As far as NFPA 13 is concerned, this 30% increase only applies to light, ordinary and extra hazard situations (it is in Chapter 11, which only applies to those hazard classifications). But many people try to apply it to other occupancies. The safety factors involved in the criteria in NFPA 409 allow the discharge criteria in this document to adequately protect sloped roof/ceilings without the 30% increase in the design area. The committee also clarified that the increase for preaction systems also does not apply to NFPA 409. 7/22/2015 2:42 PM National Fire Protection Association Report 52 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 23-NFPA 409-2013 [ Section No. 7.3.3.9 ] 7.3.3.9 Controllers for foam concentrate pumps shall be as follows: (1) For electric-drive foam concentrate pumps greater than 22.4 kW (30 horsepower), a listed fire pump controller shall be used. (2) For electric-drive foam concentrate pumps greater than 11 kW (15 horsepower) but not exceeding 22.4 kW (30 horsepower), a listed fire pump controller or listed limited service controller shall be used. (3) For electric foam concentrate pumps less than 11 kW (15 horsepower), a listed limited service controller shall be used. For diesel engine–drive foam concentrate pumps, a listed fire pump controller shall be used. (1) Controllers for foam concentrate pumps shall comply with the requirements of section 6.2.7.9. Additional Proposed Changes File Name Description Approved 7.3.3.9.pdf Cover Sheet Statement of Problem and Substantiation for Public Input Foam pumps feed full service controllers and should be no less than full service controllers. Listed full service controllers are now available in horsepowers down to 1.0 Hp. Note: At one time, full service controllers were not available below 30 Hp. Note: Similar proposals have been submitted to NFPA-11 and NFPA-16. Submitter Information Verification Submitter Full Name: James Nasby Organization: Columbia Engineering Street Address: City: State: Zip: Submittal Date: Tue Feb 26 09:05:04 EST 2013 Committee Statement Resolution: FR-50-NFPA 409-2013 Statement: To allow limited service foam pump controllers is inconsistent with the reliability and redundancy requirements throughout this standard. 7/22/2015 2:42 PM National Fire Protection Association Report 53 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 58-NFPA 409-2013 [ Section No. 7.3.3.9 ] 7.3.3.9 Controllers for foam concentrate pumps shall be as follows: (1) For electric-drive foam concentrate pumps greater than 22.4 kW (30 horsepower), a listed full service fire pump controller shall be used. (2) For electric-drive foam concentrate pumps greater than 11 kW (15 horsepower) but not exceeding 22.4 kW (30 horsepower), a listed fire pump controller or listed limited service controller shall be used. (3) For electric foam concentrate pumps less than 11 kW (15 horsepower), a listed limited service controller shall be used. (4) For diesel engine–drive foam concentrate pumps, a listed fire pump controller shall be used. Statement of Problem and Substantiation for Public Input See proposed change to 6.2.7.10 which is PI 57. Related Public Comments for This Document Related Comment Relationship Public Input No. 57-NFPA 409-2013 [Section No. 6.2.7.10] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 17:48:44 EDT 2013 Committee Statement Resolution: FR-50-NFPA 409-2013 Statement: To allow limited service foam pump controllers is inconsistent with the reliability and redundancy requirements throughout this standard. 7/22/2015 2:42 PM National Fire Protection Association Report 54 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 72-NFPA 409-2013 [ Section No. 7.4.4 ] 7.4.4 The foam system shall use low-level discharge nozzles Where monitor -type discharge nozzles are used , they shall be provided with individual manual shutoff valves for each nozzle. The discharge nozzles shall be arranged to achieve initial foam coverage in the expected aircraft parking area. Statement of Problem and Substantiation for Public Input This comment is to make 7.4.4 read the same as 6.2.5.4.3. There is no reason to restrict low-level low expansion foam systems in Group II hangars to be only monitor nozzles, while allowing other foam delivery systems such as grate nozzles in Group I hangars. Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Mon Jul 08 22:42:14 EDT 2013 Committee Statement Resolution: FR-21-NFPA 409-2013 Statement: The revision harmonizes 7.4.4 for Group II hangars with 6.2.5.4.3 for Group I hangars. 7/22/2015 2:42 PM National Fire Protection Association Report 55 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 76-NFPA 409-2013 [ Section No. 7.5.4 ] 7.5.4 The discharge rate of the system shall be based on the application rate multiplied by the entire aircraft storage and servicing floor area. The application total discharge rate shall include the sprinkler breakdown factor specified in in 6.12.8. 2.3. 5. 2 (b) of NFPA 11 using the total actual discharge from the number of sprinklers expected to operate in L/min (gpm) . Additional Proposed Changes File Name Description Approved nfpa409_PI_Kasiski_7-5-4.pdf Cover Sheet Statement of Problem and Substantiation for Public Input The revised wording provides clartiy on how to properly design a high expansion foam system compensating for breakdown of the foam blanket by using the actual discharge from the sprinkler system. If the design discharge from a sprinkler is used the total rate of discharge from the generator may be incorrect and impact the performance of providing adequate fire protection. Submitter Information Verification Submitter Full Name: Robert Kasiski Organization: FM Global Street Address: City: State: Zip: Submittal Date: Thu Jul 11 13:34:07 EDT 2013 Committee Statement Resolution: There are sufficient safety factors in the existing design criteria to address this concern. 7/22/2015 2:42 PM National Fire Protection Association Report 56 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 61-NFPA 409-2013 [ Section No. 7.5.5 ] 7.5.5 Foam generators shall be supplied with air from outside the or inside the aircraft storage and servicing area. Roof vents shall be located to avoid recirculation of combustion products into the air inlets of the foam generators. area in accordance with the provisions of 6.9 of NFPA 11. Statement of Problem and Substantiation for Public Input See proposed revision to 6.2.5.5.5 which is PI 60. Related Public Comments for This Document Related Comment Relationship Public Input No. 60-NFPA 409-2013 [Section No. 6.2.5.5.5] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 18:10:00 EDT 2013 Committee Statement Resolution: Adequate technical data has not been provided to support the use of inside air. 7/22/2015 2:42 PM National Fire Protection Association Report 57 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 37-NFPA 409-2013 [ Section No. 7.6.2 ] 7.6.2 The Regardless of the celing slope, the minimum discharge density shall be 6.5 L/min/m 2 (0.16 gpm/ft 2 ) of foam solution over the entire storage and service area. Statement of Problem and Substantiation for Public Input There is a great deal of confusion regarding the rules of NFPA 13 and the 30% increase to the design area for buildings with a ceiling/roof slope of more than 2 in 12. As far as NFPA 13 is concerned, this 30% increase only applies to light, ordinary and extra hazard situations (it is in Chapter 11, which only applies to those hazard classifications). But many people try to apply it to other occupancies. Other occupancies need to clarify whether their density/area criteria applies to sloped roof/ceilings. It is our understanding that the criteria in NFPA 409 was developed to be used regardless of the shape or slope of the roof/ceiling. The hanger rules have been sufficiently used to protect barrel shaped roofs that have a slope much greater than 2 in 12. The safety factors involved in the criteria in NFPA 409 allow the discharge criteria in this document to adequately protect sloped roof/ceilings without the 30% increase in the design area. NFPA 409 needs to definitively state that the 30% increase does not apply. We have chosen to do this by inserting the phase, "regardless of the ceiling slope", which should clarify the situation sufficiently. Submitter Information Verification Submitter Full Name: Kenneth Isman Organization: National Fire Sprinkler Association Affilliation: NFSA E&S Committee Street Address: City: State: Zip: Submittal Date: Sat Jun 29 13:26:48 EDT 2013 Committee Statement Resolution: FR-47-NFPA 409-2013 Statement: There is a great deal of confusion regarding the rules of NFPA 13 and the 30% increase to the design area for buildings with a ceiling/roof slope of more than 2 in 12. As far as NFPA 13 is concerned, this 30% increase only applies to light, ordinary and extra hazard situations (it is in Chapter 11, which only applies to those hazard classifications). But many people try to apply it to other occupancies. The safety factors involved in the criteria in NFPA 409 allow the discharge criteria in this document to adequately protect sloped roof/ceilings without the 30% increase in the design area. The committee also clarified that the increase for preaction systems also does not apply to NFPA 409. 7/22/2015 2:42 PM National Fire Protection Association Report 58 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 48-NFPA 409-2013 [ New Section after 7.6.7.1 ] 7.X Fuel Containment Floor System. 7.X.1 Hangars protected in accordance with 7.1 (5) shall be protected with a fuel containment floor system. 7.X.2 The fuel containment floor system shall be designed to achieve (1) containment of aviation fuel spilled out of aircrafts within the storage and service area and prevent the fuel from being (re)ignited. (2) Suppression of burning aviation fuel spilled out of aircrafts within the storage and service area. 7.X.3 System floor size 7.X.3.1 In aircraft storage and servicing areas where the aircraft parking area is fixed, a fuel containment floor system shall be installed directly underneath the aircraft’s fuel tanks in accordance with 7.X.3.2 7.X.3.2 The fuel containment floor system shall cover the floor from the perimeter of the aircraft’s fuel tanks and all area within. 7.X.3.2.1 The fuel containment floor system shall consist of a single continuous floor per each aircraft. 7.X.3.2 In aircraft storage and servicing areas where the aircraft parking area is flexible, a fuel containment floor system shall cover the entire area where an aircraft can potential be parked in accordance with 7.X.3.2 7.X.3.3 The edge of the fuel containment floor system should be a minimum of 6m. (18 ft.) in horizontal distance from the perimeter of the fuel tanks. 7.X.4 Activated water sprinklers as per 7.2 shall not affect the performance of the fuel containment floor system. The drainage capacity of the system shall include the maximum amount of water deployed by the overhead sprinkler system. 7.X.5 Fuel removal 7.X.5.1 The system shall have an integrated flush capability to flush out contained fuel. The flush system shall be discharged into the trench drain system in accordance with 5.11.2 7.X.5.2 In case of existing aircraft storage and service areas where (1) the trench drain layout is not practically located in relation to the fuel containment floor system, (2) or the concrete floor slab does not have sufficient pitch, a suction system may be installed to remove liquids from the system into the nearest trench drain or directly to a safe outside location in accordance with 5.11.2.3. Statement of Problem and Substantiation for Public Input The Fuel Containment Floor System can be an alternative to the current accepted foam based fire suppression systems, that for certain hangars can be a better suited solution in terms of fire protection. Submitter Information Verification Submitter Full Name: TRISTAN MACKINTOSH Organization: Fireless Flooring Street Address: City: State: Zip: Submittal Date: Fri Jul 05 11:34:47 EDT 2013 7/22/2015 2:42 PM National Fire Protection Association Report 59 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Committee Statement Resolution: The fuel containment floor system technology has not been fully tested. 7/22/2015 2:42 PM National Fire Protection Association Report 60 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 68-NFPA 409-2013 [ New Section after 7.7 ] proposed new 7.7.5 Listed detection systems (such as optical flame detection) shall be acceptable in lieu of heat detection if both approved by the Authority Having Jurisdiction and installed in accordance with NFPA 72. Statement of Problem and Substantiation for Public Input See proposed new 6.2.8.1.4 which is PI 67. The purpose of this change is to make it clear than an owner and AHJ may agree to adopt an alternate detection system without requiring two detection systems. Related Public Comments for This Document Related Comment Relationship Public Input No. 67-NFPA 409-2013 [New Section after 6.2.8.1] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 18:36:09 EDT 2013 Committee Statement Resolution: FR-52-NFPA 409-2013 Statement: The purpose of this change is to make it clear than an owner and AHJ may agree to adopt an alternate detection system without requiring two detection systems. 7/22/2015 2:42 PM National Fire Protection Association Report 61 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 87-NFPA 409-2013 [ Section No. 7.7 ] 7.7 Detection and Actuation Systems. 7.7.1 Detectors for actuating high- or low-expansion foam systems and for actuating preaction sprinkler systems shall be rate-of-rise, fixed-temperature, or rate-compensation type. deluge and sprinkler systems at ceiling or roof height, shall be heat detectors or flame detectors. Detectors and systems for initiating discharge of expanded foam onto a fuel spill or fire shall be flame detectors configured to actuate foam discharge in less than 10 seconds. Flame detectors shall be arranged optimize detection of fires at floor level below aircraft fuel tanks at planned aircraft parking areas. The first detector to operate shall signal alarm, but two detectors shall operate before initiating a foam discharge. Flame detectors shall be aligned to, and provided in sufficient quantity to ensure proper coverage in the event of any single detector being out of service. In multiple zone systems sharing a common water or foam supplies, the first zone to actuate shall prevent later zones from operating to avoid unnecessary depletion of foam concentrate supplies. Manual controls shall be configured to override this selection if necessary. 7.7.2 These detectors shall be installed in accordance with NFPA 72 . 7.7.3 Detection systems shall be provided with supervision as required by NFPA 72 . 7.7.4 Manual actuation stations shall be located so that each system can be individually operated from both inside and outside the aircraft storage and servicing area. The manual stations shall be installed so that they are unobstructed, readily accessible, and located in the normal paths of exit from the area. Additional Proposed Changes File Name NFPA_409_7.7_Flame_Detectors.docx Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input In high roof buildings like hangars, thermal detection responds fast enough to protect the building structure but too slowly to deliver effective fire protection to high value property within the hangar at low level such as spare parts and aircraft. To meet the fuel spill foam suppression criteria of NFPA 11 fire suppression is required in 2.5 minutes, 30 seconds to start the foam delivery and 2 minutes to generate a foam blanket of adequate depth to submerge the risk. Flame detectors can be, and are often allowed to start hangar foam systems using the provisions of NFPA 409 1.3 & 1.4, however many AHJs are reluctant to deviate from the letter of NFPA codes, and in the past some have simply refused to allow such deviation. Although it is expected that each zone would have 4 flame detectors, where there are two parking areas sharing a hangar doorway, with no convenient flame detector mounting available air-side between the two parking areas it is possible to meet these requirements with 3 flame detectors per parking area. Note: Supporting material is available for review at NFPA Headquarters. Submitter Information Verification Submitter Full Name: RICHARD GILLESPIE Organization: FIRE ENGR SOLUTIONS P/L Street Address: City: State: 7/22/2015 2:42 PM National Fire Protection Association Report 62 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Zip: Submittal Date: Fri Jul 12 09:25:35 EDT 2013 Committee Statement Resolution: This proposal exceeds the level of safety prescribed by this minimum standard. See FR 52 (7.7.5). 7/22/2015 2:42 PM National Fire Protection Association Report 63 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 66-NFPA 409-2013 [ New Section after 7.7.1 ] proposed new 7.7.1.1 Where wet-pipe sprinkler systems are provided, detection of sprinkler water flow shall be acceptable as the means of heat detection. Statement of Problem and Substantiation for Public Input See proposed new section 6.2.8.4.1 which is PI 65. This is a clarification of the intent of the standard. Related Public Comments for This Document Related Comment Relationship Public Input No. 65-NFPA 409-2013 [New Section after 6.2.8.4] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 18:29:01 EDT 2013 Committee Statement Resolution: FR-23-NFPA 409-2013 Statement: The section was revised to harmonize with the requirements in Chapter 6 for Group I hangars. 7/22/2015 2:42 PM National Fire Protection Association Report 64 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 25-NFPA 409-2013 [ Section No. 8.7.1 ] 8.7.1* Grounding facilities shall be provided for removal and control of static electrical accumulations on aircraft while aircraft are stored or are undergoing servicing in a hangar shall be permitted . Statement of Problem and Substantiation for Public Input Aircraft owners have objected to enforcement of this provision of NFPA 409 and indicate grounding of their aircraft is potentially harmful to aircraft electronics. This revision allows the designer to work with aircraft owner and appropriately protect their investment. Submitter Information Verification Submitter Full Name: Donald Cook Organization: Shelby County Department of De Street Address: City: State: Zip: Submittal Date: Thu Feb 28 15:57:56 EST 2013 Committee Statement Resolution: The provision of grounding facilities is necessary in order to provide the capability to comply with NFPA 410 or other standards for aircraft maintenance operations. Whether and how the grounding facilities are used is not within the scope of NFPA 409. 7/22/2015 2:42 PM National Fire Protection Association Report 65 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 27-NFPA 409-2013 [ Section No. 8.7.2 ] 8.7.2 Floor-grounding receptacles shall be provided permitted and where installed shall be either grounded through individual driven electrodes or electrically bonded together in a grid system and the entire system grounded to underground metal piping or driven electrodes. Where driven electrodes are used, they shall consist of 15.9 mm ( 5?8 in.) diameter or larger metal rods driven at least 1.5 m (5 ft) into the ground. Floorgrounding receptacles shall be designed to minimize the tripping hazard. Statement of Problem and Substantiation for Public Input Aircraft owners have objected to enforcement of this provision of NFPA 409 and indicate grounding of their aircraft is potentially harmful to aircraft electronics. This revision allows the designer to work with aircraft owner and appropriately protect their investment. Submitter Information Verification Submitter Full Name: Donald Cook Organization: Shelby County Department of De Street Address: City: State: Zip: Submittal Date: Thu Feb 28 16:12:45 EST 2013 Committee Statement Resolution: The provision of grounding facilities is necessary in order to provide the capability to comply with NFPA 410 or other standards for aircraft maintenance operations. Whether and how the grounding facilities are used is not within the scope of NFPA 409. 7/22/2015 2:42 PM National Fire Protection Association Report 66 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 26-NFPA 409-2013 [ Sections 9.12.1, 9.12.2 ] Sections 9.12.1, 9.12.2 9.12.1 Membrane-covered rigid-steel-frame-structure hangars housing other than unfilled aircraft shall be provided with grounding Grounding facilities for the removal and control of static electrical accumulations on aircraft while aircraft are stored or undergoing servicing in a hangar. membrane-covered rigid-steelframe-structure hangars housing other than unfilled aircraft shall be permitted. 9.12.2 Floor-grounding receptacles shall be provided. The permitted. Where installed, the receptacles shall be either grounded through individual driven electrodes or electrically bonded together in a grid system and the entire system grounded to underground metal piping, such as cold water piping, or driven electrodes. Where driven electrodes are used, they shall consist of 15.9 mm ( 5?8 in.) diameter or larger metal rods driven at least 1.5 m (5 ft) into the ground. Floor-grounding receptacles shall be designed to minimize the tripping hazard. Statement of Problem and Substantiation for Public Input Aircraft owners have objected to enforcement of this provision of NFPA 409 and indicate grounding of their aircraft is potentially harmful to aircraft electronics. This revision allows the designer to work with aircraft owner and appropriately protect their investment. Submitter Information Verification Submitter Full Name: Donald Cook Organization: Shelby County Department of De Street Address: City: State: Zip: Submittal Date: Thu Feb 28 16:05:13 EST 2013 Committee Statement Resolution: The provision of grounding facilities is necessary in order to provide the capability to comply with NFPA 410 or other standards for aircraft maintenance operations. Whether and how the grounding facilities are used is not within the scope of NFPA 409. 7/22/2015 2:42 PM National Fire Protection Association Report 67 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 53-NFPA 409-2013 [ Section No. 9.14.5.3 ] 9.14.5.3 Each protection system shall be designed, installed, and maintained in accordance with NFPA 11 , except that foam system piping shall not be required to be galvanized . Statement of Problem and Substantiation for Public Input See proposed new 6.1.6 which is PI 51. Related Public Comments for This Document Related Comment Relationship Public Input No. 51-NFPA 409-2013 [New Section after 6.1.1] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 17:29:33 EDT 2013 Committee Statement Resolution: FR-45-NFPA 409-2013 Statement: NFPA 11 (2010 edition) 4.7.2.1 states "Galvanized pipe shall be used." While this requirement may be useful for tank farms, it is inappropriate for foam systems inside hangars. Galvanized piping is generally incompatible with the foams. It contributes nothing to system corrosion resistance and may be harmful when the zinc coating deteriorates causing galvanic cell corrosion and potentially releasing flakes of zinc which may clog orifices. 7/22/2015 2:42 PM National Fire Protection Association Report 68 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 77-NFPA 409-2013 [ Section No. 9.14.7.5.3 ] 9.14.7.5.3 The discharge rate of the system shall be based on the application rate multiplied by the entire aircraft storage and servicing floor area. The application total discharge rate shall include the sprinkler breakdown factor specified in 6.12.8.2. 3. 2 of NFPA 11 using the total actual discharge from the number of sprinklers expected to operate in L/min (gpm) . Additional Proposed Changes File Name nfpa409_PI_Kasiski_9-14-7-5-3.pdf Description Approved Cover Sheet Statement of Problem and Substantiation for Public Input The revised wording provides clartiy on how to properly design a high expansion foam system compensating for breakdown of the foam blanket by using the actual discharge from the sprinkler system. If the design discharge from a sprinkler is used the total rate of discharge from the generator may be incorrect and impact the performance of providing adequate fire protection. Submitter Information Verification Submitter Full Name: Robert Kasiski Organization: FM Global Street Address: City: State: Zip: Submittal Date: Thu Jul 11 13:35:44 EDT 2013 Committee Statement Resolution: There are sufficient safety factors in the existing design criteria to address this concern. 7/22/2015 2:42 PM National Fire Protection Association Report 69 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 62-NFPA 409-2013 [ Section No. 9.14.7.5.5 ] 9.14.7.5.5 Foam generators shall be supplied with air from outside outside or inside the aircraft storage and servicing area. Roof vents shall be located to avoid recirculation of combustion products into the air inlets of the foam generators. area in accordance with the provisions of 6.9 of NFPA 11. Statement of Problem and Substantiation for Public Input See proposed revision to 6.2.5.5.5 which is PI 60. Related Public Comments for This Document Related Comment Relationship Public Input No. 60-NFPA 409-2013 [Section No. 6.2.5.5.5] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 18:12:35 EDT 2013 Committee Statement Resolution: Adequate technical data has not been provided to support the use of inside air. 7/22/2015 2:42 PM National Fire Protection Association Report 70 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 59-NFPA 409-2013 [ Section No. 9.14.9.3 ] 9.14.9.3 Controllers for foam concentrate pumps shall be as follows: (1) For electric-drive foam concentrate pumps greater than 22.4kW (30 horsepower), a listed full service fire pump controller shall be used. (2) (3) For electric-drive foam concentrate pumps greater than 11kW (15 horsepower) but not exceeding 22.4kW (30 horsepower), a listed fire pump controller or listed limited-service controller shall be used. (4) For electric-drive foam concentrate pumps less than 11kW (15 horsepower), a listed limited-service controller shall be used. (5) For diesel engine–drive foam concentrate pumps, a listed fire pump controller shall be used. Statement of Problem and Substantiation for Public Input See proposed change to 6.2.7.10 which is PI 57. Related Public Comments for This Document Related Comment Relationship Public Input No. 57-NFPA 409-2013 [Section No. 6.2.7.10] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 17:52:50 EDT 2013 Committee Statement Resolution: FR-51-NFPA 409-2013 Statement: To allow limited service foam pump controllers is inconsistent with the reliability and redundancy requirements throughout this standard. 7/22/2015 2:42 PM National Fire Protection Association Report 71 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 64-NFPA 409-2013 [ Section No. 9.14.13.2 ] 9.14.13.2 The total pumping capacity shall be such that maximum demand shall be met with the largest fire pump out of service. provided using fire pumps of equal capacity. No fewer than two fire pumps shall be provided. Statement of Problem and Substantiation for Public Input See proposed change to 6.2.10.8.2 which is PI 63. Related Public Comments for This Document Related Comment Relationship Public Input No. 63-NFPA 409-2013 [Section No. 6.2.10.8.2] Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 18:21:28 EDT 2013 Committee Statement Resolution: FR-54-NFPA 409-2013 Statement: The "largest fire pump out of service" requirement is a level of redundancy not found in any other NFPA occupancy standard. NFPA 20 takes considerable care in ensuring fire pump reliability. This revision relaxes the requirement for water supply redundancy, but does not allow the hangar to be protected by only a single fire pump. See also CI 53, which proposes an alternative revision for this section. 7/22/2015 2:42 PM National Fire Protection Association Report 72 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 39-NFPA 409-2013 [ Section No. 10.2.1 ] 10.2.1 The Regardless of the ceiling slope, the protection of aircraft paint hangars shall be in accordance with either Chapter 6 or Chapter 7 of this standard, whichever is applicable. Statement of Problem and Substantiation for Public Input There is a great deal of confusion regarding the rules of NFPA 13 and the 30% increase to the design area for buildings with a ceiling/roof slope of more than 2 in 12. As far as NFPA 13 is concerned, this 30% increase only applies to light, ordinary and extra hazard situations (it is in Chapter 11, which only applies to those hazard classifications). But many people try to apply it to other occupancies. Other occupancies need to clarify whether their density/area criteria applies to sloped roof/ceilings. It is our understanding that the criteria in NFPA 409 was developed to be used regardless of the shape or slope of the roof/ceiling. The hanger rules have been sufficiently used to protect barrel shaped roofs that have a slope much greater than 2 in 12. The safety factors involved in the criteria in NFPA 409 allow the discharge criteria in this document to adequately protect sloped roof/ceilings without the 30% increase in the design area. NFPA 409 needs to definitively state that the 30% increase does not apply. We have chosen to do this by inserting the phase, "regardless of the ceiling slope", which should clarify the situation sufficiently. Submitter Information Verification Submitter Full Name: Kenneth Isman Organization: National Fire Sprinkler Association Affilliation: NFSA E&S Committee Street Address: City: State: Zip: Submittal Date: Sat Jun 29 13:32:15 EDT 2013 Committee Statement Resolution: FR-48-NFPA 409-2013 Statement: There is a great deal of confusion regarding the rules of NFPA 13 and the 30% increase to the design area for buildings with a ceiling/roof slope of more than 2 in 12. As far as NFPA 13 is concerned, this 30% increase only applies to light, ordinary and extra hazard situations (it is in Chapter 11, which only applies to those hazard classifications). But many people try to apply it to other occupancies. The safety factors involved in the criteria in NFPA 409 allow the discharge criteria in this document to adequately protect sloped roof/ceilings without the 30% increase in the design area. The committee also clarified that the increase for preaction systems also does not apply to NFPA 409. 7/22/2015 2:42 PM National Fire Protection Association Report 73 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 69-NFPA 409-2013 [ Chapter 11 [Title Only] ] Final Acceptance Testing and Periodic Inspection and Testing Proposal is that a new Chapter be created to put all testing requirements for final acceptance and ongoing maintenance in one place. Centralizing these requirements will give us an opportunity to eliminate common sources of confusion and make the standard easier to use. Recommend that a Task Group be formed to accomplish this. Statement of Problem and Substantiation for Public Input Centralizing all testing requirements will eliminate common sources of confusion and make the standard easier to use. Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 18:56:24 EDT 2013 Committee Statement Resolution: CI-60-NFPA 409-2013 Statement: This Committee Input proposes to significantly revise Chapter 11. The committee has formed a task group to better define the inspection and maintenance requirements of fire protection systems in hangars, since many of these systems are not within the scope of NFPA 25. This proposal is provided as a baseline to seek public comment on the subject. The section references in the revised table are based on the following documents: NFPA 25, 2011 Edition; NFPA 11, 2010 Edition; NFPA 72, 2010 Edition; NFPA 80, 2010 Edition; NFPA 90A, 2009 Edition; NFPA 1962, 2008 Edition; NFPA 33, 2007 Edition; Air Force Instruction AFI 32-1065, Grounding Systems, October 1998. 7/22/2015 2:42 PM National Fire Protection Association Report 74 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 38-NFPA 409-2013 [ Section No. 12.5.6 [Excluding any Sub-Sections] ] The Regardless of the ceiling slope, the design density from sprinkler systems shall be a minimum of 6.9 L/min/m2 (0.17 gpm/ft2) over any 464.5 m2 (5000 ft2) area, including the hydraulically most demanding area as defined in NFPA 13. Statement of Problem and Substantiation for Public Input There is a great deal of confusion regarding the rules of NFPA 13 and the 30% increase to the design area for buildings with a ceiling/roof slope of more than 2 in 12. As far as NFPA 13 is concerned, this 30% increase only applies to light, ordinary and extra hazard situations (it is in Chapter 11, which only applies to those hazard classifications). But many people try to apply it to other occupancies. Other occupancies need to clarify whether their density/area criteria applies to sloped roof/ceilings. It is our understanding that the criteria in NFPA 409 was developed to be used regardless of the shape or slope of the roof/ceiling. The hanger rules have been sufficiently used to protect barrel shaped roofs that have a slope much greater than 2 in 12. The safety factors involved in the criteria in NFPA 409 allow the discharge criteria in this document to adequately protect sloped roof/ceilings without the 30% increase in the design area. NFPA 409 needs to definitively state that the 30% increase does not apply. We have chosen to do this by inserting the phase, "regardless of the ceiling slope", which should clarify the situation sufficiently. Submitter Information Verification Submitter Full Name: Kenneth Isman Organization: National Fire Sprinkler Association Affilliation: NFSA E&S Committee Street Address: City: State: Zip: Submittal Date: Sat Jun 29 13:29:08 EDT 2013 Committee Statement Resolution: FR-49-NFPA 409-2013 Statement: There is a great deal of confusion regarding the rules of NFPA 13 and the 30% increase to the design area for buildings with a ceiling/roof slope of more than 2 in 12. As far as NFPA 13 is concerned, this 30% increase only applies to light, ordinary and extra hazard situations (it is in Chapter 11, which only applies to those hazard classifications). But many people try to apply it to other occupancies. The safety factors involved in the criteria in NFPA 409 allow the discharge criteria in this document to adequately protect sloped roof/ceilings without the 30% increase in the design area. The committee also clarified that the increase for preaction systems also does not apply to NFPA 409. 7/22/2015 2:42 PM National Fire Protection Association Report 75 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 2-NFPA 409-2012 [ Section No. A.3.3.2 ] 7/22/2015 2:42 PM National Fire Protection Association Report 76 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... A.3.3.2 Aircraft Hangar. 7/22/2015 2:42 PM National Fire Protection Association Report 77 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... For overall height of various transport-type aircraft, see Table A.3.3.2. Offices and similar administrative areas are not considered part of the hangar when properly separated per 5.2.3, 8.2.3 and 9.2.3. Table A.3.3.2 Gross Wing Area and Overall Height for Selected Aircraft Gross Wing Area Aircraft Airbus A-380* m2 830.0 ft 2 Overall Height m ft–in. 8920 24.1 † 79–0 Antonov An-124* 628.0 † 6760 21.0 † 69–2 Lockheed L-500-Galaxy* 576.0 † 6200 19.8 † 65–1 Boeing 747* 541.1 † 5825 19.4 † 63–8 Airbus A-340-500, -600* 437.0 † 4703 16.7 † 54–11 Boeing 777* 427.8 † 4605 18.5 † 60–9 Ilyushin II-96* 391.6 † 4215 DC-10-20, 30* 367.7 † 3958 17.7 † 58–1 Airbus A-340-200, -300, A-330-200, -300* 361.6 † 3892 16.7 † 54–11 DC-10-10* 358.7 † 3861 17.7 † 58–1 Concorde* 358.2 † 3856 12.2 † 40–0 Boeing MD-11* 339.9 † 3648 17.6 † 57–9 Boeing MD-17* 353.0 † 3800 16.8 † 55–1 L-1011* 321.1 † 3456 16.9 † 55–4 Ilyushin II-76* 300.0 † 3229 14.8 † 48–5 Boeing 767* 283.4 † 3050 15.8 † 52–0 Ilyushun IL-62* 281.5 † 3030 12.3 † 40–6 DC-10 MD-10 272.4 2932 DC-8-63, -73 271.9 2927 DC-8-62, -72 271.8 2926 DC-8-61, 71 267.8 2883 Airbus A-300 260.0 † 2799 16.5 † 54–3 Airbus A-310 218.9 † 2357 15.8 † 51–10 Tupolev TU-154 201.5 † 2169 11.4 † 37–4 Boeing 757 185.2 † 1994 13.5 † 44–6 Tupolev TU-204 182.4 † 1963 13.9 † 45–7 Boeing 727-200 157.9 † 1700 10.4 † 34–0 Lockheed L-100J Hercules 162.1 † 1745 11.6 † 38–3 Yakovlev Yak-42 150.0 † 1614 9.3 † 32–3 Boeing 737-600, -700, -800, -900 125.0 † 1345 12.5 † 43–3 Airbus A-318, A-319, A-320, A-321 122.6 † 1319 11.8 † 38–8 Boeing MD 80 112.3 † 1209 9.0 † 29–7 9.3 † 30–7 7.9 † 25–10 MD 90 Gulfstream V 105.6 † 1137 7/22/2015 2:42 PM National Fire Protection Association Report 78 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Gross Wing Area m2 Aircraft ft 2 Overall Height m ft–in. Boeing 737-300, -400, -500 105.4 † 1135 11.1 † 36–6 Tupolev TU-334, TU-354 100.0 † 1076 9.4 † 30–9 BAC 1-11-500 95.8 † 1031 7.5 † 24–6 NAMC YS-11 94.8 † 1020 8.9 † 29–5 Fokker 100, 70 93.5 † 1006 8.5 † 27–10 BAC 1-11-300, -400 93.2 1003 7.5 † 24–6 Boeing 717 93.0 † 1001 8.8 † 29–1 DC-9-30 93.0 † 1001 8.4 † 27–6 Boeing 737-200 91.0 † 980 11.3 † 37–0 Gulfstream IV 88.3 † 950 7.4 † 24–5 DC 9-10 86.8 † 934 8.4 † 27–6 BAe 146, RJX-70, -85, -100 77.3 † 832 8.6 † 28–3 Fokker 50, 60 70.0 † 753 2.7 † 27–3 Canadair RJ-700 68.6 † 738 7.6 † 24–10 Dash 8 Q400 63.0 † 679 7.5 † 24–7 ATR 72 61.0 † 656 7.6 † 25–1 Airtech CN-235 59.1 † 636 8.2 † 26–10 Saab 2000 55.7 † 600 7.7 † 25–4 Canadair RJ-100, -200 54.5 † 587 6.2 † 20–5 ATR 42 42.5 † 586 7.6 † 24–10 Dash 8 Q100, Q200 54.3 † 585 7.5 † 24–7 Embraer ERJ-135, -145 51.1 † 550 6.9 † 22–1 Cessna 750 48.9 † 527 5.8 † 18–11 Cessna 680 47.9 † 516 5.5 † 19–2 Saab 340 41.8 † 450 6.9 † 22–1 Embraer EMB-120 39.4 † 424 6.3 † 20–10 Bell Boeing V-22 39.5 † 382 6.6 † 21–9 Britten-Norman BN2 30.2 † 325 4.2 † 13–8 Cessna 650 28.9 † 312 5.1 † 16–9 Beech 1900 28.8 † 310 4.7 † 15–6 Beech King Air C90 27.3 † 294 4.3 † 14–3 *Aircraft with wing area in excess of 279 m2 (3000 ft2). †Data from Jane’s All the World's Aircraft. Statement of Problem and Substantiation for Public Input Offices separated from aircraft storage and servicing areas should not be held to the strict standard of a hangar 7/22/2015 2:42 PM National Fire Protection Association Report 79 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... when fire rated construction is provided. This will allow a two-story office area adjacent to but separated from the hangar. Section 8.1.2 would seem to prohibit this arrangement. Submitter Information Verification Submitter Full Name: Doug Hohbein Organization: Northcentral Fire Code Develop Street Address: City: State: Zip: Submittal Date: Thu Aug 16 09:53:57 EDT 2012 Committee Statement Resolution: CI-61-NFPA 409-2013 Statement: This Committee Input proposes to significantly revise the requirements of Chapter 8. There is sufficient confusion and uncertainty in the application of the standard to Group III hangars that this proposal is presented for public review. The concepts of hangar clusters and row hangars tend to cause confusion. In order to simplify this chapter, the committee is considering whether aircraft storage and servicing areas that are adequately separated by internal or external partitions should be considered independently of other nearby spaces and in accordance with the locally adopted building code. See also CI 62 (3.3.9). 7/22/2015 2:42 PM National Fire Protection Association Report 80 of 80 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... Public Input No. 50-NFPA 409-2013 [ Section No. A.5.11.2.4 ] A.5.11.2.4 In general, this means that the design has to be adequate to ensure that the liquid level at the center of the drain is below the top surface of the drain trench drain inlet grating for grated round, rectangular, and long trench-type inlets or below the floor surface in the case of a slit trench . Statement of Problem and Substantiation for Public Input Appendix material was not updated when trench drains were required. This is an editorial correction. Submitter Information Verification Submitter Full Name: Michael Aaron Organization: The RJA Group, Inc. Street Address: City: State: Zip: Submittal Date: Sun Jul 07 17:16:19 EDT 2013 Committee Statement Resolution: FR-25-NFPA 409-2013 Statement: The clarification provided by the annex material is no longer needed. 7/22/2015 2:42 PM
© Copyright 2026 Paperzz