CONSTRUCTION
Luminaire housing, reflectors and end caps are die formed
code gauge cold rolled steel. High transmission extruded
acrylic lenses feature custom formulation for high efficacy
without pixelation.
FEATURES
• Twin lens configuration
• High efficiency acrylic lenses feature custom formulation for high
performance without pixelation
• Appropriate for offices, schools, medical, and public spaces
• High performance reflector with matte white paint standard
• 60,000 hour LEDs at L80 (up to 86,000 projected life) for reduced
maintenance*
• Four LED color choices and 82 or greater CRI
• Eight lumen packages
• Multiple driver options to satisfy different applications
• LED modules and electrical accessible from below
• Optional architecturally styled integration of daylight and
occupancy sensor(s)
• QR code traceability
• Integral battery pack optional on most models
• Compatible with Dual-Lite inverters
• Recessed, surface or cable mount
• Five year warranty (Terms and Conditions apply)
• DesignLights Consortium® (DLC) qualified; see www.designlights.org
CERTIFICATION
All luminaires are built to UL1598 and 2108 standards,
and bear appropriate CSA labels. Damp location is
standard. Emergency-equipped fixtures labeled UL
924 and Dry Location unless specified. Adheres to LM79,
LM80, and TM21 industry standards. DesignLights
Consortium® (DLC) qualified. Please refer to the DLC
website for specific product qualifications at www.
designlights.org.
SHIELDING
Removable lenses and center channel for easy access to LED
module and electrical components.
FINISH
All reflective surfaces are finished after fabrication with
unique formula high reflectivity matte white paint for soft,
uniform illumination.
IC RATING
IC label is standard for recessed products.
WARRANTY
Five year warranty (Terms and Conditions apply).
INSTALLATION
An access plate is furnished with each luminaire for fast wiring
access without the necessity to open the fixture or wireway.
CEILING COMPATIBILITY
Luminaire fits recessed exposed Grid ceilings (G); four integral
NEC compliant T-bar clips are standard. Can be placed in
Slot Grid (SG) style ceiling with regress 9.5mm above ceiling
plane. A Flange Kit (FK) accessory is available for recessed
hard ceiling applications. Surface Mount (SM) option allows
placement below ceiling plane. Cable Mount (CM) option
allows suspension below ceiling plane.
* Lifetime hours based on TM21-11 calculations
ORDERING INFORMATION
TCAT
612
EXAMPLE TCAT612-35MLG-ESDU
–
MODEL
–
COLOR
TEMPERATURE
TCAT LED Twin
Contemporary
Architectural
Troffer
30
35
40
50
SIZE
3000K
3500K
4000K
5000K
–
CEILING TYPE
VOLTAGE
G Grid Lay-in1
SM Surface Mount
CM Cable Suspended
Mount2
U 120V-277V
347 347V
LUMEN OUTPUT
612 600mm x 1200mm
XW Extra Low Watt
VW Very Low Watt
MW Medium Low Watt
LW Low Watt
ML Medium Lumen
HL High Lumen
VL Very High Lumen
XL Extra High Lumen
See Product Availability Table below.
DRIVER
E
ESD
ED
ED1
LUTH
Fixed Output
Step Dimming3
0-10V Dimming
0-10V 1% Dimming
Hi-lume 1% EcoSystem
LED driver with Soft-on,
Fade-to-Black dimming
technology3,4
LUT5 5-Series EcoSystem LED
driver3,4
DRIVER AVAILABILITY TABLE
E
ED
ED1
ESD
LUT5
LUTH
XW
X
X
X
VW
X
X
X
MW
X
X
X
X
X
X
X
Page 1/3 Rev. 02/27/17
LW
X
X
X
X
X
X
ML
X
X
X
X
X
X
HL
X
X
X
X
X
X
VL
X
X
X
X
XL
X
X
X
X
For drywall, order G with Flange Kit Accessory.
Order hanger accessories separately
Not available in 347V
4
For compatability with Dual-Lite LiteGear® inverters, contact Hubbell
Lighting Representative
5
Only available with 0-10V Dimming (ED) Driver Option.
6
Not available with ESD, LUTH or LUT5.
7
VIVE is a trademark of Lutron Electronics Co., Inc.
For questions about configuration options, contact Hubbell Representative.
1
2
OPTIONS
ELL14
C388
C488
C588
GLR
EOR
INT
CP
NYC
ODP
LV
Emergency Battery Pack Installed, 1400 Lumens3,4
3-Wire Flex
4-Wire Flex
5-Wire Flex
Fast Blow Fuse
End of Row (SM and CM only. Provides end wiring
access for continuous row mounting.)
Intermediate (SM and CM only. Provides ends with
wiring access for continuous row mounting.)
Chicago Plenum
NYC Compliant
Occupancy and Daylight Sensors, Philips3,5
Lutron Vive Enabled, 0-10V6,7
ACCESSORIES
(ORDER SEPARATELY)
FK612 600mm x 1200mmSingle Flange Kit
(Shipped separately)
CM48Y2SC3F-KIT 1200mm Cable Mount Kit for 600mm
wide Cable Mount fixtures, 3 Wire
3
© 2017 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice.
701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com
LED / TCAT612
TCAT612
600mm × 1200mm LED Twin Contemporary Architectural Troffer
Product Availability
Lumen Package
Lumens
Input Watts
LPW
TCAT612-30XWG
2493
19
131.2
TCAT612-35XWG
2568
19
135.2
TCAT612-40XWG
2608
19
137.3
TCAT612-50XWG
2667
19
140.4
TCAT612-30VWG
3157
25
126.3
TCAT612-35VWG
3251
25
130.0
TCAT612-40VWG
3302
25
132.1
TCAT612-50VWG
3595
25
143.8
TCAT612-30MWG
3558
28
127.1
130.9
TCAT612-35MWG
3665
28
TCAT612-40MWG
3722
28
132.9
TCAT612-50MWG
4053
28
144.8
TCAT612-30LWG
4152
34
122.1
125.8
TCAT612-35LWG
4276
34
TCAT612-40LWG
4343
34
127.7
TCAT612-50LWG
4729
34
139.1
TCAT612-30MLG
4713
39
120.8
TCAT612-35MLG
4855
39
124.5
TCAT612-40MLG
4930
39
126.4
TCAT612-50MLG
5368
39
137.6
TCAT612-30HLG
5368
45
119.3
TCAT612-35HLG
5530
45
122.9
TCAT612-40HLG
5615
45
124.8
TCAT612-50HLG
6115
45
135.9
TCAT612-30VLG
6883
55
125.1
TCAT612-35VLG
7090
55
128.9
TCAT612-40VLG
7200
55
130.9
TCAT612-50VLG
7840
55
142.5
TCAT612-30XLG
8321
69
120.6
124.2
TCAT612-35XLG
8571
69
TCAT612-40XLG
8704
69
126.1
TCAT612-50XLG
8932
69
129.4
Page 2/3 Rev. 02/27/17
© 2017 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice.
701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com
LED / TCAT612
TCAT612
600mm × 1200mm LED Twin Contemporary Architectural Troffer
PHOTOMETRIC DATA
LUMINAIRE DATA
Luminaire
Ballast
Ballast Factor
Lamp
Fixture Lumens
Watts
Mounting
Shielding Angle
Spacing Criterion
Luminous Opening in Feet
Test #16567 Test Date 8/13/2016
ZONAL LUMEN SUMMARY
TCAT612-35LWx-EDU
TCAT LED Troffer, Recessed
Architectural
2x4 LED with Acrylic Refractor
XI040C110V054BST1
1.00
LED
4276
33.50
Recessed
0º = 90 90º = 90
0º = 1.19 90º = 1.26
Length: 3.92
Width: 1.92
Height: 0.00
Zone
INDOOR CANDELA PLOT
90
Lumens % Lamp % Fixt.
0-30
1236
28.9
28.9
0-40
2007
46.9
46.9
0-60
3453
80.7
80.7
0-90
4276
100.0
100.0
0-180
4276
100.0
100.0
75
800
ENERGY DATA
60
Total Luminaire Efficiency
100.0%
Total Lumens per Watt
IESNA RP-1-2004 Compliance
Comparative Yearly Lighting Energy Cost per
1000 Lumens
128
Non-Compliant
$1.90 based on
3000 hrs. and
$0.08 per KWH
1600
0
15
30
45
Horiz 0-180
0.0
45.0
90.0
Test #16570 Test Date 8/13/2016
LUMINAIRE DATA
Luminaire
Ballast
Ballast Factor
Lamp
Fixture Lumens
Watts
Mounting
Shielding Angle
Spacing Criterion
Luminous Opening in Feet
ZONAL LUMEN SUMMARY
TCAT612-35MLx-EDU
TCAT LED Troffer, Recessed
Architectural
2x4 LED with Acrylic Refractor.
XI040C110V054BST1
1.00
LED
4855
38.90
Recessed
0º = 90 90º = 90
0º = 1.19 90º = 1.26
Length: 3.92
Width: 1.92
Height: 0.00
Zone
INDOOR CANDELA PLOT
90
Lumens % Lamp % Fixt.
0-30
1404
28.9
28.9
0-40
2280
47.0
47.0
0-60
3920
80.7
80.7
0-90
4855
100.0
100.0
0-180
4855
100.0
100.0
75
950
ENERGY DATA
60
Total Luminaire Efficiency
100.0%
Total Lumens per Watt
IESNA RP-1-2004 Compliance
Comparative Yearly Lighting Energy Cost per
1000 Lumens
125
Non-Compliant
$1.94 based on
3000 hrs. and
$0.08 per KWH
1900
0
15
30
45
Horiz 0-180
0.0
45.0
90.0
Test #16576 Test Date 8/13/2016
LUMINAIRE DATA
Luminaire
Ballast
Ballast Factor
Lamp
Fixture Lumens
Watts
Mounting
Shielding Angle
Spacing Criterion
Luminous Opening in Feet
ZONAL LUMEN SUMMARY
TCAT612-35HLx-EDU
TCAT LED Troffer, Recessed
Architectural
2x4 LED with Acrylic Refractor
XI054C150V054BST1
1.00
LED
5530
44.60
Recessed
0º = 90 90º = 90
0º = 1.19 90º = 1.26
Length: 3.92
Width: 1.92
Height: 0.00
Zone
0-30
INDOOR CANDELA PLOT
Lumens % Lamp % Fixt.
1597
28.9
28.9
0-40
2593
46.9
46.9
0-60
4462
80.7
80.7
0-90
5530
100.0
100.0
0-180
5530
100.0
100.0
90
75
1100
ENERGY DATA
60
Total Luminaire Efficiency
100.0%
Total Lumens per Watt
IESNA RP-1-2004 Compliance
Comparative Yearly Lighting Energy Cost per
1000 Lumens
124
Non-Compliant
$1.95 based on
3000 hrs. and
$0.08 per KWH
2200
0
15
30
45
Horiz 0-180
0.0
Page 3/3 Rev. 02/27/17
© 2017 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice.
701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com
45.0
90.0
LED / TCAT612
TCAT612
600mm × 1200mm LED Twin Contemporary Architectural Troffer
23 3/4"
DIMENSIONAL DATA — GRID
Back of Housing, Grid
Recessed Section, Grid
23
3/4"
594mm
47 3/4"
1194mm
4"
102mm
594mm
23 3/4"
STANDARD METRIC - 23 25/64" x 47"
23 3/4"
4"
CEILING COMPATIBILITY
STANDARD METRIC - 23 25/64" x 47"
Type G
FKCR
FK24 Flange Kit
Side
End
Side
For lay-in installation in exposed
grid ceilings. Maximum tee
widths of 25mm and maximum
tee heights of 51mm allowed.
End
For hard ceiling applications,
order FK612 flange kit.
Flange kit wires directly into
concealed ceiling opening for
a clean, finished appearance.
For flanged fixtures in row configurations, the FKCR adapter bracket kit is required in addition to the FK612 kit. Order one less FKCR than the total number
of fixtures in row. (Example: Row of two, order (2) FK612 & (1) FKCR)
Row cut out dimensions using FK612s & FKCR adapters:
Width 619mm, Length [1219mm × (# in row)] + 9.5mm.
Example: (1219mm x 2) + 9.5mm = 2448mm
Flange kit cut out dimension for single unit only: 619mm × 1229mm
DIMENSIONAL DATA — SURFACE MOUNT OR CABLE MOUNT
Surface Section (SM)
51mm
1016mm
44 29/32"
2"
44 29/32"
2"
B
A
B
A
B
B
A
A
B
B
A
216
215.9
mm
38mm
A
8 1/2"
8 1/2"
A
B
A
B
A
A
B
B
A
A
12 1/2"
B
B
89
mm
318mm
12 1/2"
Surface Mount:
Order SM ceiling type. Mounting
collar required for surface mounting. (4) Mounting
knock-outs, 9.5mm,
provided in center channel as
indicated at left, marked A.
3 1/2"
1245mm
49"
3 1/2"
25"
49"
Back of Housing, Surface Mount (SM) and Cable Mount (CM)
635mm
25"
4 5/8"
Cable Mount:
Order CM ceiling type.
Use CM48Y2SC3F-KIT 1219mm Cable Mount Kit for
610mm wide CM trim fixtures. Mounting holes are
provided in diagonal straps shown at left, marked B.
117mm
4 5/8"
For Cable Mount a 51mm x 76mm access plate with (4) 22mm KOs provided in place of Mounting Collar shown.
NOTE: All dimensions are in millimeters; dimensions and specifications are subject to change without notice. Please consult factory or check sample for verification.
*
Page 4/3 Rev. 02/27/17
© 2017 Columbia Lighting, a division of Hubbell Lighting, Inc. Specifications subject to change without notice.
701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.columbialighting.com
LED / TCAT612