GC63 Battery Type Digital Differential Pressure Gauge

Cat.No. B04-07-Q
GC63
Battery Type
Digital Differential
Pressure Gauge
Gas measurement
interface with
silicon diaphragm
Outline
Battery-operated digital differential pressure gauge
suited for HVAC and semiconductor manufacturing
field monitoring. Easy to install without wiring or
detect the filter crogging with comparator output
using optional external power source.
Features
•17mm large LCD (3 1/2 digit)
•Analog bar graph display to know a
measurement situation
•Comparator output with external power cable
(Option)
•Filter, Peak & bottom holding and Zero
adjustment function
Function
Features of sensor
Silicon capacitance (SC) Sensor
Because of its simple construction
designed with moving parts fewer
than ever, combined with a fine,
micro silicone diaphragm, the sensor
is very resistant to vibrations and
shocks.
Actual size
•Easy to know the measurement situation by analog
bar graph display.
•When using the external power source,
comparator one-output is available. (Option)
SC Sensor
Sensor chip
Comparator action indication
Analog bar graph
Digital display
Voltage of battery
monitor
Pressure to be measured
Silicone diaphragm
SET Pilot light
Unit display
Upper electrode
Plate glass
MODE
MODE key
MODE key
to select an operation
mode and switch
between submodes.
Lower electrode
Pressure to be measured
▼
DOWN key
DOWN key
to set values and select items.
It displays bottom hold value
in the measurement mode.
▲
UP key
UP key
to set values and select items.
It displays peak hold value
inthe measurement mode.
GC63
Digital Differential Pressure Gauge
Specifications 1
Item
Description
Fluid
Dry air, nitrogen gas (Not contain moisture and/or powder)
Operating condition
Normal conditions (No flammable liquids or explosive gaseous atmospheres)
Mounting
Surface mounting
Process connection
G1/8
Gas contact materials
Silicon, aluminum, silicone, glass and ABS
Differential pressure range
0 to 50Pa → 0 to 5kPa, ±50Pa → ±500Pa
Please refer to the range table
Maximum allowable pressure
50kPa
Accuracy
Differential pressure display accuracy:
± (1.0%F.S.+1digit) at 23℃ (Differential pressure range: 1kPa and over),
± (2.0%F.S.+1digit) at 23℃ (Differential pressure range 500Pa and under)
Square root operation accuracy
(GC63-□□2)
±0.5%F.S. (Within 5 to 100%F.S.)
Square root display
(GC63-□□2)
0 to 1999 (Decimal point and the maximum display value change are available)
Display system
3 1/2 digit, 17mm LCD
LCD Analog bar graph (21 Segment)
Display update
1s
Units of display
Differential pressure display (GC63-□□1)Pa, kPa
Square root display (GC63-□□2) (LCD Pressure unit display turns off)
Battery
Alkaline Dry cell (LR6) ×2
Battery life span
Continuous operation Approx. 2 years
Power supply brownout monitor
When external power and
output cable attached
(Option)
External power source 24V DC 5mA Maximum
One-comparator output N channel opening drain (30V DC 80mA Maximum)
Response: Within 2s
Operation mode: Window comparator
Dead band: 1%F.S. fixed
Operation display: H, L display
Function
Filter
1s, 2s, 4s (Moving average)
Error indication
Over pressure, Out of pressure range for zero adjustment
Hold
Display of peak and bottom values
Others
Zero adjustment, key locking
Alarm display
Power supply brownout monitor
Operating temperature
0 to 40℃ (No freezing)
Operating humidity
35 to 85%RH (No dew condensation)
Storage temperature
-10 to 50℃ (No freezing)
Allowable leak rate
1.7×10−4Pa・m3/s *1
Case construction
Indoor use (IP40 IEC Standard)*2
Case materials
ABS
Weight
Approx. 130g (Include battery)
Accessory
Hexagon socket head plug, Size AA alkaline battery
Inscribed unit (×10, ×100, ×1000, m/s, m3/min, m3/h) …At GC63-□□2
*1 This product can not be used for applications that need to be precisely measured amount of leakage, such as leak test.
*2 When front case is closed.
GC63
GC63
Digital Differential Pressure Gauge
Specifications 2
Differential pressure range, Display figures, Accuracy and temperature coefficient:
0
0
0
0
0
0
0
to
to
to
to
to
to
to
50Pa
100Pa
200Pa
500Pa
1kPa
2kPa
5kPa
Accuracy
LCD Display digit
Pa (kPa)
Differential pressure range
50.0
100
200
500
1.00
2.00
5.00
±50Pa
±100Pa
±200Pa
±500Pa
Display accuracy
Temperature coefficient
± (2.0%F.S.+1digit)
at 23℃
±0.2%F.S./℃
(Zero/Span)
± (1.0%F.S.+1digit)
at 23℃
±0.1%F.S./℃
(Zero/Span)
※Minus mark (-) is displayed when the pressure sensed at high pressure port (H) is lower than the pressure sensed at low pressure port (L).
※When with square root display, ± Indication range is not available.
Dimensions 1
Unit: mm
30
□ 72
28.5
4.4
(Mounting hole)
22.5
NAGANO KEIKI
H
L
SET
9
4.4
(Mounting hole)
27
H
L
14
kPa
ADJ.
Low pressure port
(Pressure connection) G1/8
High pressure port
(Pressure connection) G1/8
Power/output cable hole
H
Power/Output cable hole
4
20
High pressure port
(Pressure connection) G1/8
10
L
Change of batteries
(Alkaline battery (LR6)×2)
4
18.5
20
20
Low pressure port
(Pressure connection) G1/8
Clump for surface mounting
70
50
2-4.4
6
15
44
70
(100)
45
(135)
15
1.6
4.4
50
Article
Mounting clamp (Standard)
4.4
(94)
Material
QTY.
Remarks
SPCC
1
M4 sems screw
*Assembly of GC63 to a mounting clamp uses a M4 sems screw.
Please give the tightening torque of the M4 sems screw to me as 2N/m and under.
3-A
(Hole)
1.6
6.4
74.5
)
(R
2-
70
50
15
20
4.4
L type clump
*For the panel type, pressure connecting ports are provided
on the back side (One each of L and H) and on the lower side
(One each of L and H), you can select one of the back side
and the lower side. The unused L and H connecting ports
should be closed with the provided hexagon head socket head
plugs.
Please give the tightening torque of the G1/8 screw to me as
1N/m and under.
GC63
Digital Differential Pressure Gauge
Unit: mm
Dimensions 2
Process Connection
GC63-□2□
GC63-□3□
φ5 Barb (Straight)
GC63-□4□
φ7 Barb (Straight)
GC63-□5□
GC63-□6□
Joint for φ6 metal pipe
φ7 Barb (Rotary)
Rc1/8 Conversion joint
φ7
φ5
(21.5)
G1/8
13X15 Hex.
O-ring
O-ring
1
φ8
2000
Model number configuration
16
φ8 With 2m tube
1
2000
φ6
φ5
φ7
13×15 Hex.
φ8 With 2m tube
1
G1/8
23.2
φ6 With 2m tube
Rc1/8
G1/8
O-ring
O-ring
φ8
φ4
φ5
O-ring
φ6
13×15 Hex.
(46)
G1/8
17×19.6 Hex.
17
G1/8
14X16.2 Hex.
13
2000
For ordering, please specify the model number, each specs and the differential pressure range.
Model
G C 6 3
Digital Differential Pressure Gauge
①
②
③
④
Model number
⑤
⑥
⑦
Selective spec.
①
Mounting
②
Process
connection *1
1
Surface mounting
2
With clump for surface mounting
3
With L type clump for mounting
⑨
⑩
G1/8 (Standard)
2
φ5 Barb (Straight)
With 2m vinyl tube
3
φ7 Barb (Straight)
With 2m vinyl tube
4
φ7 Barb (Rotary)
With 2m vinyl tube
5
Joint for φ6 metal pipe
6
Rc 1/8 Conversion joint
1
Differential pressure display
2
Square root display (± Indication range is not available.)
④
Differential
pressure range *2
⑤
Display accuracy
④
⑤
④Differential pressure range
M
9
0 to 50Pa
N
9
0 to 100Pa
P
9
0 to 200Pa
Q
9
0 to 500Pa
R
7
0 to 1kPa
S
7
0 to 2kPa
T
7
0 to 5kPa
B
9
±50Pa
C
9
±100Pa
D
9
±200Pa
E
9
±500Pa
⑧
Cable for power
source / signaling
*1: 2m vinyl tube is attached for above 2 to 4.
⑮
Documents
*2: Minus mark (-) is displayed when the pressure sensed
at high pressure port (H) is lower than the pressure sensed
at low pressure port (L).
※Specify "X" if there is no specification item.
■Caution of operation
Sensing part is applicable to dry air, water mist air or nitrogen gas.
Please do not use corrosive gas, inflammable gas and liquid.
⑪
⑫
⑬
⑭
⑮
Additional spec. (Option)
1
③
Display
Please specify the
differential pressure range
and units separately besides
selection of range code.
⑧
⑤Display accuracy
± (2.0%F.S.+1digit) at 23℃
± (1.0%F.S.+1digit) at 23℃
Except by
GC63-□□2
± (2.0%F.S.+1digit) at 23℃
0
Nil
D
Cable for power source / signaling: With 2 m
0
1
Nil
Required
(Please specify the desired documents separately.)
Submission drawings, instruction manual,
inspection procedure,test report (1 pc 1 copy),
inspection / traceability certificate,
standard inspection report,
attended inspection