OPzV 2-800 2V800Ah

OPzV 2-800
2V800Ah
OPzV Series SLA Battery
Range Summary
By combining the newly developed tubular positive plates with fumed
gelled electrolyte, BSB created the innovative OPzV range of batteries.
The range offers 20 years design life and very high deep cycling
capabilities. This range is recommended for telecom outdoor
applications, renewable energy systems and other harsh environment
applications.
Application
·
Medical Equipment
·
UPS
·
Railroad Utility
·
Photovoltaic System
·
Alternative Energy System
·
Telecommunications
·
Cable Television
·
Electric Utility
·
Control Equipment
·
Security System
General Features
·
Sealed and maintenance free operation.
·
Non-Spillable construction design.
·
ABS containers and covers(UL94 V0, optional).
·
Safety valve installation for explosion proof.
·
High quality and high reliability.
·
Super long service life.
·
Lowest self discharge characteristic.
·
Super reliability.
7mm (0.28inch)
20mm (0.79inch)
M8mm (0.31inch)
Construction
Safety valve
Terminal
Separator
Electrolyte
......
......
......
......
EPDR
Copper
Polymer
Thixotropic Gel
191mm(7.52inch)
Terminal Dimensions
681mm(26.8inch)
Lead dioxide
Lead
ABS
ABS
Epoxy Resin
646mm(25.4inch)
Positive ......
Negative ......
Container ......
......
Cover
Sealant ......
210mm(8.27inch)
Battery Model
OPzV 2-800
Designed Floating Life
Capacity(20oC)
20 Years
20HR(43.0A,1.80V)
10HR(80.0A,1.75V)
1HR(448A,1.75V)
705Ah
448Ah
800Ah
860Ah
Dimensions
5HR(141A,1.75V)
Length
Width
Height
Total Height
191mm(7.52inch)
210mm(8.27inch)
646mm(25.4inch)
681mm(26.8inch)
Approx. Weight
58.5Kg (129 lbs)
Internal Resistance
Full charged at 20oC: 0.0004 Ohm
Self Discharge
2% of capacity declined per month at (20oC)
Capacity Affected
by Temp.(10HR)
Charge Voltage(20oC)
40oC
109%
20oC
0oC
100%
85%
Cycle use
2.35V-2.40V(-5mV/ oC), max. Current: 160A
Page 1 of 2
-15oC
65%
Float use
2.25-2.29V(-3mV/ oC)
OPzV 2-800
2V800Ah
Charge
Voltage
(CA) (V/Cell)
(%)
120
2.35
100
80
0.20
Discharge Characteristic (20oC)
Charge Characteristic
o
Constant Charge At 0.2CA-2.35V (20 C)
Charge
Capacity
Charge
Voltage
2.17
100%Discharge
60
0.15
40
0.10
20
0.05
2.00
50%Discharge
1.83
Charge Current
0
0
0
2
4
6
8
10
Discharge Voltage (V/Cell)
Current
Charge
Charge
Capacity
OPzV Series SLA Battery
2.17
2.00
1.83
0.05CA
0.25CA 0.1CA
1.67
1.60
0
12
2
6
30
60
3
10
Hour
20
Self Discharge Characteristics
2.25
110
105
2.17
100
95
90
Capacity (%)
Battery Voltage (V/Cell)
12
Min
Relationship of OCV and state of charge
2.00
0.6CA
1.33
Time(hour)
2.08
1CA
85
80
75
70
65
60
55
50
1.92
45
1.83
0
10
20
30
40
50
60
70
80
90
100
40 0
o
3
20oC
30oC
40 C
6
9
12
15
18
21
24
27
30
Storage time:months
Remained Capacity(%)
Constant current discharge ratings-amperes at 20oC
F.V/Time
1.70V
1.75V
1.80V
1.83V
1.87V
1.90V
15min
848
752
656
592
480
416
30min
688
624
560
504
440
392
1h
468
448
416
384
344
312
2h
286
278
266
256
236
220
3h
212
208
200
195
183
172
5h
142
141
139
136
130
124
8h
98.0
97.6
96.0
94.0
89.6
86.0
10h
82.0
81.0
80.0
78.0
74.5
71.5
20h
44.3
43.7
43.0
42.1
40.2
38.6
3h
427
417
402
396
389
353
5h
293
289
284
269
260
256
8h
195
191
189
179
174
167
10h
158
156
154
151
146
138
20h
86.5
86.0
85.0
84.0
81.0
78.5
Constant power discharge ratings-watts at 20oC
F.V/Time
1.70V
1.75V
1.80V
1.83V
1.87V
1.90V
15min
1462
1346
1192
1096
1038
890
30min
1190
1142
1074
919
870
799
1h
849
810
779
718
699
635
2h
542
528
514
490
480
472