GENERAL STRUCTURAL NOTES DESIGN CRITERIA: INTERNATIONAL BUILDING CODE - 2012 CONCRETE - ACI 318 AND ACI 301 WELDING - AWS D1.1 STRUCTURAL STEEL - AISC "MANUAL OF STEEL CONSTRUCTION" FOURTEENTH EDITION DESIGN LOADS: WIND DESIGN: 110 MPH EXPOSURE C SDC: D ROOF SNOW LOAD: 20 PSF ROOF DEADLOAD: 15 PSF FLOOR LOAD: 100 PSF SOIL BEARING CAPACITY: 2000 PSF (NOTE: HDJ DESIGN GROUP TO VERIFY SOIL FILL AND COMPACTION PROCESS PER REPORT #3950-00 - MARCH 25TH, 2015) GENERAL PROJECT NOTES: 1) THESE PLANS AND ALL WORK SHALL COMPLY WITH THE IBC 2012 EDITION AND AS REQUIRED BY GOVERNING ENTITIES. ANY ELECTRICAL WORK TO COMPLY WITH NEC REQUIREMENTS. 2) DRAWINGS SHALL NOT BE SCALED, WRITTEN DIMENSIONS SHALL GOVERN. ALL TRADES SHALL VERIFY ALL CONDITIONS AT THE JOB SITE AND NOTIFY THE DESIGNER OF CONFLICTS OR DISCREPANCIES BEFORE PROCEEDING ALL BOUNDARY AND SETBACK INFORMATION SHOWN ON THESE DRAWINGS WAS COMPILED OF ASSESSOR'S OFFICE DATA AND GENERAL FIELD MEASUREMENTS TO EXISTING FENCES AND STREET IMPROVEMENTS. HOWEVER THIS IS NOT A SURVEY OF THE PROPERTY. IT IS THE RESPONSIBILITY OF THE PROPERTY OWNER TO VERIFY PROPERTY LINE LOCATIONS. SUB-CONTRACTORS SHALL PROTECT THE WORK AND ALL ADJACENT PROPERTY FROM LOSS AND DAMAGE RESULTING FROM OPERATIONS. 3) MECHANICAL EQUIPMENT SHALL OBSERVE MINIMUM SETBACKS. NO PART OF RETAINING WALLS AND FOOTINGS SHALL ENCROACH INTO ADJACENT PROPERTIES OR EASEMENTS. 4) FOOTINGS SHALL EXTEND A MINIMUM OF 24 INCHES BELOW LOWEST ADJACENT FINISH GRADE (WITHIN 2 FEET HORIZONTAL OF FOOTINGS) STEEL MATERIAL NOTES: WIDE FLANGE BEAMS AND COLUMNS: WELD TO BEAMS AND COLUMNS: HSS TUBE STEEL: BASE PLATE: ANCHOR RODS: BOLTS: NUTS: WASHERS: STEEL PLATE: ASTM A992 E70 ELECTRODE ASTM A500 GRADE C ASTM A36 ASTM F-1554 GRADE 55 ASTM A325 TYPE N ASTM A563 ASTM F436 ASTM A36 STEEL REINFORCING AS FOLLOWS: #3 THROUGH #5 BARS = GRADE 40 MINIMUM #6 AND ABOVE = GRADE 60 MINIMUM T E R E N C E L. THORNHILL ARCHITECT 9221 SANDIFUR PARKWAY SUITE "A" PASCO, WA 99301 FASTENERS IN TREATED WOOD - FASTENERS IN PRESERVATIVE TREATED WOOD AND FIRE-RETARDANT WOOD SHALL BE HOT DIPPED ZINC COATED GALVANIZED STEEL, STAINLESS STEEL, SILICON BRONZE OR COPPER. COATING WEIGHTS FOR ZINCCOATED STEEL SHALL BE IN ACCORDANCE WITH ASTM B-695 CLASS 55 MINIMUM. FASTENERS OTHER THAN NAILS, WOOD SCREWS AND LAG SCREWS MAY BE MECHANICALLY DEPOSITED IN ZINC IN ACCORDANCE WITH ASTM B-695, CLASS 55 509-547-8854 FAX 509-547-8912 [email protected] HOLDOWN BOLTS: HDU2 (3,075 lbs) - SSTB16 (3,780 lbs) 5/8" DIA. AND 12-5/8" EMBED LENGTH HDU4 (4,565 lbs) - SSTB20 (4,785 lbs) 5/8" DIA. AND 16-5/8" EMBED LENGTH HDU5 (5,645 lbs) - SSTB28 (11,060 lbs) 7/8" DIA. AND 24-7/8" EMBED LENGTH HDU8 (7,870 lbs) - SSTB28 (11,060 lbs) 7/8" DIA. AND 24-7/8" EMBED LENGTH HDU14 (14,375 lbs) - SSTB34 (14,445 lbs) 7/8" DIA. AND 28-7/8" EMBED LENGTH A Professional Service Corporation REFER TO SIMPSON'S LATEST CATALOG FOR ADDITIONAL DETAILS HARDY FRAME ANCHORAGE NOMENCLATURE (REFER TO HARDY FRAME SHEET HFXI FDN.) 1 1/8" - HS - 20 - 30 5) IF DURING EXCAVATION SOILS ARE DISCOVERED TO BE SUSPECT, EXPANSIVE OR OTHER GEOLOGIC INSTABILITY CONTRACTOR SHALL NOTIFY STRUCTURAL ENGINEER AND GEOTECH ENGINEER. CONTRACTOR TO VERIFY RECOMMENDATIONS OF THE GEOTECH REPORT HAVE BEEN INCORPORATED AND APPROVED BY STRUCTURAL ENGINEER AND GEOTECH ENGINEER. Ca 1, Ca 2 - (EDGE AND END DISTANCE Le - ROD EMBEDMENT LENGTH (BEYOND 10" MIN) ROD GRADE (HIGH STRENGTH) ROD DIAMETER CONCRETE AND FOUNDATION NOTES: 2549 W 33RD PL. KENNEWICK, WA, 99337 509.308.8015 866.421.7049 FAX SILL BOLTS: 1) ALL FOUNDATIONS AND SLABS TO BEAR ON NATIVE SOILS OR COMPACTED BACKFILL IN ACCORDANCE WITH STRATA REPORT 2) ALL FILL OR BACKFILL SHALL BE COMPACTED TO 95% OF MAXIMUM DENSITY IN ACCORDANCE WITH ASTM D1557 PER STRATA REPORT 3) CONCRETE SHALL CONFORM TO ACI 318-08, ACI 301-10 AND IBC 2012 AND BE A MINIMUM OF 4 INCHES THICK. 4) ALL STRUCTURAL CONCRETE SHALL HAVE A NORMAL COMPRESSIVE STRENGTH OF 3,000 PSI AT 28 DAYS. MAXIMUM SIZE OF AGGREGATE TO BE 3/4 INCH. SLUMP SHALL BE BETWEEN 2 AND 4 INCHES. CEMENT SHALL BE PORTLAND CEMENT TYPE 1 OR 2. ENTRAINED AIR SHALL BE BETWEEN 4 AND 6 PERCENT FOR CONCRETE. 5) PROVIDE 5000 PSI MINIMUM NON-SHRINK AND NON-METALLIC GROUT FOR COLUMN BASE PLATES. 6) CONTROL JOINTS SHALL BE TRUE STRAIGHT LINES, 1/4" WIDE BY 3/4" DEEP AND CUT WITHIN 24 HOURS AFTER FOUR. FILL CONTROL JOINTS WITH SEALANT. 1) PROVIDE 5/8" ANCHOR BOLTS AT 48" O.C. MAX. OR AS SHOWN ON PLANS AND SHEAR WALL SCHEDULE. SEE DETAILS. These drawings are intended for use 2) EMBED BOLTS 7 INCHES MINIMUM INTO CONCRETE OR MASONRY 3) PROVIDE A MINIMUM OF 2 BOLTS PER SECTION OF SILL OR WOOD PLATES. LOCATE BOLTS MINIMUM 4 INCHES TO 12 INCHES MAX FROM ENDS OF SILL PLATE. INSTALL BOLTS WITH PROPERLY SIZED NUTS AND WASHERS. solely with respect to this project and are the property of TERENCE L. THORNHILL Architect Inc. P.S. which reserves all common law 4) WASHERS SHALL BE MINIMUM 3 INCH SQUARE BY 0.229 INCHES THICK AT EACH BOLT LOCATION UNLESS NOTED OTHERWISE. statutory, copyright and other rights. HILTI FASTENER ICC-ES #ESR-2379 SHANK DIA = 0.145" MINIMUM PENETRATION INTO CONCRETE = 1" MAXIMUM PENETRATION INTO CONCRETE = 1 3/8" SPACING = 16" O.C. MAX SHEAR = 130 lbs MINIMUM DRAWN BY: DG CHECKED BY: - 7) ALL EXPOSED CONCRETE EDGES SHALL BE CHAMFERED 3/4 INCH UNLESS NOTED OTHERWISE. PHASE: SPECIAL INSPECTION: 8) ALL SERVICE PIPING, POTABLE WATER GAS, ETC. PENETRATING FOUNDATION WALL SHALL HAVE PIPE SLEEVES. SLEEVES SHALL BE IN ACCORDANCE WITH ASTM A52 STD WT PIPE AND WILL HAVE 1 INCH MINIMUM CLEARANCE FROM THE OUTSIDE FACE OF THE SERVICE LINE TO THE INSIDE FACE OF THE PIPE SLEEVE. SEAL GAP WITH BACKER ROD AND CONTINUOUS BEAD OF SEALANT ALL AROUND. 9) HOLD ALL EXPANSION JOINT MATERIAL AND INSULATION 1/2 INCH BELOW TOP OF SLAB AND SEAL TOP WITH INDUSTRIAL POLYURETHANE CAULK. CD SPECIAL INSPECTIONS SHALL BE PAID BY ARCHITECT. SPECIAL INSPECTIONS ARE REQUIRED PER INTERNATIONAL BUILDING CODE, CHAPTER 17, IN ADDITION TO THE REQUIREMENTS OF THE SPECIFICATIONS. SPECIAL INSPECTOR SHALL INSPECT THE FOLLOWING CONSTRUCTION: REVISION NO: MARK DATE DESCRIPTION - BOLTS INSTALLED IN CONCRETE - REINFORCING STEEL - STRUCTURAL WELDING - HIGH-STRENGTH BOLTING 18) ALL INTERIOR STUD WALLS (OTHER THAN SHEAR WALLS) TO HAVE HILTI SHOT-PINS @ 32" O.C. USE HILTI X-CF 72-P8-S23 (ICC-ES #ESR-2379) OR EQUAL AT BOTTOM OF PLATES TO SLAB. SEE FOUNDATION PLAN FOR SHEARWALL BOLTING. 19) ALL HOLDOWN ANCHORS TO BE 'SIMPSON' BRAND UNLESS NOTED OTHERWISE. 20) HD BOLTS AT EXTERIOR WALLS TO BE SSTB16 (UNLESS NOTED OTHERWISE) W/ 12 5/8" MINIMUM EMBEDMENT AND 3" CLEAR TO SOIL. (TYP. AT HD2A, PHD2, HD5A, AND PHD5). USE 5/8" THREADED RODS BETWEEN FLOORS UNLESS NOTED OTHERWISE. 21) EXPOSED WOOD TO WEATHER OR WEATHER SPLASH SHALL BE 1" MINIMUM ABOVE CONCRETE SLAB OR 6" MINIMUM ABOVE GRADE. 22) NO WORK OF ANY KIND SHALL BE PERFORMED PRIOR TO CONCRETE REACHING 70% OF DESIGNED COMPRESSIVE STRENGTH. MINIMUM WAITING PERIOD AFTER POURING CONCRETE SLABS ON GRADE TO START OF CONSTRUCTION SHALL BE: A) 24 HOURS - WALK ON SLAB B) 5 DAYS - BEGIN WALL FRAMING C) 7 DAYS - ROOF AND FLOOR FRAMING D) 14 DAYS - ROOF LOADING T S TA G I S T ER E D SI G ONA L EN ER 43454 RE E ES N 17) SLAB AND FOOTINGS TO BE ONE POUR METHOD (MONOLITHIC POUR TYP.) EXCEPT AT STEEL COLUMNS AND AS NOTED OTHERWISE. F TO 16) HORIZONTAL DISTANCE FROM BOTTOM LEADING EDGE OF FOOTING TO DAYLIGHT SHALL BE 7' - 0" MINIMUM. IN EL 15) PROVIDE EXPANSION JOINTS IN ALL SLABS AS NOTED ON DRAWINGS (16' - 0" OC. MAX). O E G 14) UFER GROUND BAR - PROVIDE #4 BAR MIN. 20 FEET CONTINUOUS, LOCATED AT BOTTOM OF FOOTING (MIN. 3 INCHES ABOVE GRADE) AND PROTRUDING 12 INCHES ABOVE SLAB OR STEM WALL FOR ELECTRICAL GROUND. LOCATION SHALL BE VERIFIED BY ELECTRICAL CONTRACTOR IF APPLICABLE. O PR 13) MINIMUM CONCRETE WIDTH SHALL BE 8 INCHES FOR RECEIVING MPA'S AND HPAHD22'S. VERIFY LOCATIONS OF HOLDOWNS AND ANCHOR BOLTS WITH FRAMING PLAN TO ASSURE PROPER AND ACCURATE INSTALLATION. B TO R E R F WA SH A N G 12) ALL HOLDOWNS, ANCHOR BOLTS, POSTS, ETC. SHALL BE SECURELY TIED IN PLACE SPECIAL INSPECTOR TO SUBMIT INSPECTION REPORTS AND A FINAL SIGNED REPORT PRIOR TO INSPECTION AND POURING CONCRETE. ALL HOLDOWNS AND POST ANCHORS ARE FOR THE ABOVE MENTIONED ITEMS TO ENGINEER OF RECORD. TO BE INSTALLED ACCORDING TO SIMPSON STRONG TIE SPECIFICATIONS AND REQUIREMENTS OF I.C.B.O REPORT NUMBER 1211 AND 4448. RIG O 10) REINFORCING STEEL SHALL CONFORM TO THE REQUIREMENTS OF ASTM A615, GRADE 60, EXCEPT #3 TIES MAY BE GRADE 40. CONCRETE COVER FOR REINFORCEMENT SHALL BE PER PARAGRAPH 7.7.1 OF ACI 318. REINFORCEMENT SHALL BE CONTINUOUS BENT AROUND CORNERS, OR CORNER BARS OF THE SAME SIZE MAY BE INSTALLED WITH A MINIMUM LEG INSPECTOR SHALL VERIFY COMPLIANCE WITH THE APPROVED PLANS, CITY CODES LENGTH THAT CONFORMS WITH ACI 318, CLASS B SPLICES. AND ORDINANCES. INSPECTOR HAS THE DISCRETION TO REQUIRE THE REMOVAL OF FINISH WORK TO VISUALLY INSPECT THE WORK. THE GENERAL CONTRACTOR SHALL 11) VERIFY LOCATIONS OF ALL ITEMS TO BE - IN, UNDER, THROUGH OR EMBEDDED IN BE RESPONSIBLE TO REPLACE FINISHES AT NO COST TO THE OWNER OR INSPECTING CONCRETE PRIOR TO POURING CONCRETE. AGENCY. IN PORT OF KENNEWICK COLUMBIA DR. WINE VILLAGE Kennewick, WA STRUCTRUAL NOTES 0201 213-030 12/14/2015 14' - 6" 18' - 8" 9' - 4" " 4' '-6 8' - 0" 0" 12' - 0" 5' - 0" 37' - 8" 39' - 4" 9' - 4" C9 3' - 0" C9 C9 8' - 4" C9 5' - 0" 2' - 0" 8' - 4" 8' - 4" C9 C9 8' - 4" C9 C9 UP C9 UP PARTIAL HEIGHT EM WALL ( NO CORE INSULATION) PARTIAL HEIGHT EM WALL ( NO CORE INSULATION) 8' - 6" 8' - 6" 8' - 6" C6 8' - 1 1/2" TYP. 8' - 8" 4" CONCRETE SLAB W/ #4 @12" O.C. EACH WAY 6' - 8" 6' - 0" C6 C4 C4 C4 C4 6' - 0" CJ C8 8' - 1 1/2" 8' - 6" 8' - 6" 8' - 6" C7 C7 14' - 0" C7 PAVING PER SITE PLAN 8' - 1 1/2" 2' - 3 1/2" TYP. NOTCH BANDING TO ACCOMMODATE COLUMN (TYP.) C1 14' - 0" C1 C8 CJ C1 2549 W 33RD PL. KENNEWICK, WA, 99337 509.308.8015 866.421.7049 FAX C4 CJ COLUMN FOOTING (TYP.) 2' - 3 1/2" 4" CONCRETE SLAB W/ #4 @ 12" O.C. EACH WAY O/ 2" RIGID (R-10) O/ COMPACTED FILL C1 C8 C7 TYPICAL EM WALL - FULL HEIGHT 14' - 0" C4 TYPICAL EM WALL - FULL HEIGHT C7 C7 4" CONCRETE SLAB W/ #4 @ 12" O.C. EACH WAY O/ 2" RIGID (R-10) O/ COMPACTED FILL C8 84' - 0" C4 14' - 0" C1 7 0251 TYP. CJ These drawings are intended for use solely with respect to this project and BOLLARD (TYP.) SLOPE SLOPE 1/8" : 12" 1/8" : 12" C8 are the property of C7 C7 CJ TRENCH DRAIN WITH TRAP CJ 14' - 0" 0251 C8 1/8" : 12" 1/8" : 12" TERENCE L. THORNHILL Architect Inc. P.S. which reserves all common law statutory, copyright and other rights. CJ DRAWN BY: 5 C7 TYP SLOPE C8 COLUMN FOOTING (TYP.) 5 SLOPE 14' - 0" C1 CJ 7 0251 C7 DG 0251 TYP 14' - 0" C1 A Professional Service Corporation C4 CJ 14' - 0" 9' - 10" C1 G CJ CJ CONCRETE COLUMN (TYP.) C4 509-547-8854 FAX 509-547-8912 [email protected] FLAT SLAB FLAT SLAB C4 9221 SANDIFUR PARKWAY SUITE "A" PASCO, WA 99301 C9 2' - 3 1/2" EM WALL PER PLAN (TYP.) TRENCH DRAIN WITH TRAP C7 C7 CHECKED BY: - C8 14' - 0" CJ PHASE: F CD REVISION NO: 14' - 0" 188' - 4" CJ 26' - 0" MARK DATE DESCRIPTION C3 C3 C5 D C4 B TO R E R F WA SH A N O IN TO EL G E G N THICKENED SLAB UNDER BEARING WALL 19' - 6" CJ FD 14' - 0" C3 S TA C3 31' - 6" C5 TYP RIG O 12 0251 12' - 0" E T 70' - 0" 22' - 4" C9 3 0251 H 2' - 0" C4 TYP. 5' - 10" C4 14' - 0" 10' - 5" C4 3 0251 8' - 2" 2' - 0" 7' - 6" 12' - 0" 4" CONCRETE SLAB W/ #4 @12" O.C. EACH WAY C9 C4 9' - 0" 4 RISERS J 14' - 0" 22' - 4" C9 C9 T E R E N C E L. THORNHILL ARCHITECT 5 RISERS 70' - 0" 2 0" C9 23' - 0" 46' - 4" 8' - 8" 8' - C9 6" 6' - 4" 37' - 8" 7' - 6" 5 7' - 3' - 0" 5 7' - 6" 58' - 8" 21' - 10" " '-0 4 14' - 10" 46' - 4" 10' - 0" 3 189' - 0" 5' - 4" 2 3' - 0" 1 6' - 0" 6x 6x 1/ 4 F C2 C2 C2 C2 28' - 0" C4 H SS C TYPICAL EM WALL - FULL HEIGHT CJ 70' - 0" 7 0251 TYP. 4" CONCRETE SLAB W/ #4 @12" O.C. EACH WAY O/ 2" RIGID (R-10) O/ COMPACTED FILL PAVING PER SITE PLAN COLUMN FOOTING SCHEDULE 46' - 4" CJ SLOPE SLOPE 1/8" : 12" 1/8" : 12" PARTIAL HEIGHT EM WALL (WITH CORE INSULATION PER STANDARD DETAIL) 5 0251 CJ 14' - 0" TRENCH DRAIN WITH TRAP TYP CJ 0252 TYP. 14' - 0" 46' - 4" FOOTING TYPE C1 HSS 6x6x1/4" 1 45" 45" 12" (4) #4 @ 16" O.C. EACH WAY C2 HSS 6x6x1/4" 1 36" 36" 12" (4) #4 - EACH WAY C3 HSS 6x6x1/4" 2 60" 36" 12" (5) #4 - EACH WAY C4 HSS 6x6x1/4" 2 48" 24" 12" (4) #4 - EACH WAY C5 HSS 6x6x1/4" 3 33" 33" 12" (4) #5 - EACH WAY C6 HSS 6x6x1/4" 3 24" 24" 12" (4) #5 - EACH WAY C7 HSS 6x6x1/4" 1 24" 24" 24" (2) #4 - EACH WAY C8 HSS 6x6x1/4" 2 24" 12" 18" (2) #4 - EACH WAY C9 HSS 6x6x1/4" EM WALL 24" CONTINUOUS 18" SEE DETAIL 10/0251 NOTE: 27' - 4" 30' - 0" 1' - 4" 14' - 0" 14' - 0" 14' - 0" 84' - 0" 14' - 0" 14' - 0" 4' - 2" 14' - 0" 3 0251 3 0251 TYP. 7 0251 TYP. 3 12' - 0" PARTIAL HEIGHT EM WALL ( NO CORE INSULATION) X COLUMN (A) B A WIDTH (X) LENGTH (Y) SEE SHEET 0252 FOR COLUMN FOOTING DETAILS DEPTH (Z) REINFORCING ES 43454 RE G I S T ER E D SI G ONA L EN E O PR FLAT SLAB ER CJ IN PORT OF KENNEWICK COLUMBIA DR. WINE VILLAGE Kennewick, WA FOUNDATION PLAN 0210 213-030 1 FOUNDATION PLAN 3/32" = 1'-0" 12/14/2015 1 2 8' - 6" 8' - 6" 8' - 6" 8' - 1 1/2" 2' - 3 1/2" 2' - 3 1/2" 10' - 5" T E R E N C E L. THORNHILL ARCHITECT G 14' - 2" HSS 6x12x1/4 PERIMETER BEAM 9221 SANDIFUR PARKWAY SUITE "A" PASCO, WA 99301 2 11' - 8 1/2" OPEN TO BELOW HSS 6x12x1/2 SUPPORT BEAM (TYP.) 3 1/2" 19' - 0 1/2" 509-547-8854 FAX 509-547-8912 [email protected] 2' - 10" A Professional Service Corporation 3' - 9" PLATE EMBED LOCATION BEARING WALL 14' - 0" CJ CJ 10' - 1" 2549 W 33RD PL. KENNEWICK, WA, 99337 509.308.8015 866.421.7049 FAX CJ CJ CJ CJ CJ 2" CONCRETE OVER 3" METAL DECK (5" TOTAL) W/ #3 @ 18" O.C. 6 These drawings are intended for use 0252 solely with respect to this project and are the property of PLATE EMBED LOCATION TERENCE L. THORNHILL Architect Inc. P.S. which reserves all common law NOTE: LOFT - LIGHT STORAGE = 150 PSF LIVE LOAD CAPACITY PAN DECK: N FORMLOK - 16 GAGE FRAMING PLAN - LOFT - 1/3 1 1/4" = 1'-0" DRAWN BY: DG 43' - 0" 42' - 6" HSS 6x2x1/4 @ 4' - 4" O.C. statutory, copyright and other rights. CHECKED BY: - PHASE: CD 1 REVISION NO: 2 MARK PLATE EMBED LOCATION DATE DESCRIPTION NOTE: LOFT - LIGHT STORAGE = 150 PSF LIVE LOAD CAPACITY PAN DECK: N FORMLOK - 16 GAGE D PLATE EMBED LOCATION 6" 2" CONCRETE OVER 3" METAL DECK (5" TOTAL) W/ #3 @ 18" O.C. BEARING WALL 3 UP HSS 6x12x1/2 SUPPORT BEAM (TYP.) FRAMING PLAN - AWNING 1/4" = 1'-0" F T ES G I S T ER E D SI G ONA L EN ER 43454 RE E CJ CJ F N O PR CJ CJ TO S TA RIG O IN EL CJ O E G CJ B G HSS 6x12x1/4 PERIMETER BEAM TO R E R F WA SH A N IN PORT OF KENNEWICK COLUMBIA DR. WINE VILLAGE Kennewick, WA MEZANING AND AWNING FRAMING PLANS 0220 213-030 2 FRAMING PLAN - LOFT - 2 1/4" = 1'-0" 12/14/2015 1 2 3 5 HSS 6x6x1/4 PURLIN (TYP.) SEE BUILDING SECTION FOR PURLIN SPACING HSS 6x6x1/4 PURLIN (TYP.) SEE BUILDING SECTION FOR PURLIN SPACING G T E R E N C E L. THORNHILL ARCHITECT 9221 SANDIFUR PARKWAY SUITE "A" PASCO, WA 99301 13' - 6" 13' - 6" 6" CONCRETE END TRUSS (TYP.) 6" CONCRETE END TRUSS (TYP.) 4 14' - 0" CONCRETE ARCH TRUSS (TYP.) CONCRETE ARCH TRUSS (TYP.) 14' - 0" 509-547-8854 FAX 509-547-8912 [email protected] A Professional Service Corporation WALL BELOW (TYP.) 14' - 0" 14' - 0" WALL BELOW (TYP.) PURLINS AT PEAK DO NOT CONTINUE THROUGH CUPOLA SEE SECTION 14' - 0" 14' - 0" CONCRETE ARCH TRUSS W/ CUPOLA (TYP. OF 3) 2549 W 33RD PL. KENNEWICK, WA, 99337 509.308.8015 866.421.7049 FAX These drawings are intended for use 6" HSS 6x6x1/4 PURLIN (TYP.) SEE BUILDING SECTION FOR PURLIN SPACING are the property of 14' - 0" 13' - 6" solely with respect to this project and TERENCE L. THORNHILL Architect Inc. P.S. which reserves all common law statutory, copyright and other rights. 3" F DG 13' - 6" 12' - 9" DRAWN BY: CHECKED BY: CONCRETE ARCH MINI TRUSS (TYP. OF 3) 6" - E PHASE: 12' - 9" CD REVISION NO: 3" CONCRETE END TRUSS (TYP.) 13' - 6" 6" D MARK DATE DESCRIPTION HSS 6x6x1/4 PURLIN (TYP.) SEE BUILDING SECTION FOR PURLIN SPACING O IN S TA 14' - 0" G I S T ER E D SI G ONA L EN E 43454 RE ER N ES TO O PR F EL E T B G RIG O CONCRETE ARCH TRUSS (TYP.) TO R E R F WA SH A N G 14' - 0" C IN 14' - 0" PORT OF KENNEWICK COLUMBIA DR. WINE VILLAGE 13' - 6" Kennewick, WA 6" A 1 FRAMING PLAN - ROOF 3/32" = 1'-0" ROOF FRAMING PLANS 0230 213-030 12/14/2015 GRID GRID GRID GRID 556" 30" 278" 556" CL 278" 30" 24" 6" NOTE: SEE DETAIL FOR PLATE EMBEDS NOTE: SEE DETAIL FOR PLATE EMBEDS 24" 30" 278" 24" 30" 6" HSS CUPOLA SEE DETAIL 2" 7' - HSS 6x6x1/8 Top Plate 36' - 8" C L 6" 12 24" 8" 9" " 15 COLLAR TIE (TYP.) 30° 36 0" SEE DETAIL FOR DOUBLE RADIUS RAFTER TAIL (TYP.) 60" S-ROOF TRUSS - ARCH (FOR REFERENCE ONLY) 1/8" = 1'-0" 2 GRID 25" C L Top of B.B. 20' - 0" 38" 32" COLLAR TIE (TYP.) 29" 217" 217" SEE DETAIL FOR DOUBLE RADIUS RAFTER TAIL (TYP.) S-ROOF TRUSS - ARCH W/ CUPOLA (FOR REFERENCE ONLY) 1/8" = 1'-0" 3 29" 32" 509-547-8854 FAX 509-547-8912 [email protected] A Professional Service Corporation COLLAR TIE (TYP.) S-ROOF TRUSS - ARCH MINI (FOR REFERENCE ONLY) 1/8" = 1'-0" THREADED NELSON STUD (CUT TO LENGTH) GRID 556" 2549 W 33RD PL. KENNEWICK, WA, 99337 509.308.8015 866.421.7049 FAX ROOF TYPE PER PLAN CL 278" 0" 9221 SANDIFUR PARKWAY SUITE "A" PASCO, WA 99301 60" 60" 30° 36 0" 0" 36 253" 7' - 20' - 0" 6" 253" 192" 25" 72" 10" 10" 6" 38" C L Top of B.B. 228" 108" 4" 10" 10" 108" 192" 38" 0" 2 0702 300" 30° PURLIN " 15 60° 60" 1 60° 60° T E R E N C E L. THORNHILL ARCHITECT 6" 30° 25" C L 8' - 300" SEE DETAIL FOR DOUBLE RADIUS RAFTER TAIL (TYP.) 253" 36 0" 1 0702 6" 253" 0" 7 20' - 0" 300" 6" 25" Top of B.B. NOTE: PURLINS SHOWN FOR STRUCTURAL POINT LOADS. SEE DETAIL FOR ADDITIONAL INFORMATION 8' - 12" 6" 6" 20" NOTE: SEE DETAIL FOR PLATE EMBEDS NOTE: SEE COPULA DETAIL FOR ATTACHMENT 9" 60° 278" 24" 66" 12" 9" " 15 9" 7 60° 38" CL 278" 12 1 0702 GRID 556" CL 278" GRID GRID 278" CL These drawings are intended for use solely with respect to this project and CL NOTE: SEE DETAIL FOR PLATE EMBEDS are the property of TERENCE L. THORNHILL Architect Inc. P.S. which reserves all common law 12" 0" 8' - statutory, copyright and other rights. CL BOND BEAM DRAWN BY: 6 DG 0250 12 8' - 7 1 0702 EM WALL INFILL 60° 60° 12 EXTEND WALL REINFORCING INTO BOND BEAM 253" 253" 25" - HSS 6x2x1/8 BLOCKING WELD TO EMBED PLATE 0" 3" CL 3" 6' - REVISION NO: 6x12x1/4 EMBED PLATE CENTER UNDER PURLINS (PURLIN LOCATION PER ARCH DETAILS) 1/2"x6" NELSON STUD (MIN 4 PER PURLIN BLOCKING) CONCRETE ARCH TRUSS MARK DATE DESCRIPTION CONCRETE TRUSS CL 1/2" SLIP BOLTS @ 48" O.C. CAST INTO ARCH AT PARTITION WALL ONLY. (MIN 3" EMBED) 8" NOTE: END TRUSS TO BE INCORPORATED INTO END WALL CONSTRUCTION. FORM RAFTER TAILS AS PART OF WALL BOND BEAM SEE DETAIL FOR DOUBLE RADIUS RAFTER TAIL (TYP.) 0" CD HSS 6x2x1/8 PURLIN BLOCKING 3" HSS 6x6x1/4 PURLIN WELD TO EMBED PLATE 38" PHASE: HSS 6x6x1/4 PURLIN 2" 25" 6" 6" WALL BOND BEAM 8' - CHECKED BY: 1/8" CL 7 Top of B.B. 20' - 0" 38" 0" HSS PURLIN EMBED PLATE 2" NELSON STUD (TYP.) CONCRETE TRUSS O IN E S TA HSS 6x6x1/8 ES 43454 RE G I S T ER E D SI G ONA L EN ER N F TO O PR ROOF PER PLANS E B TO R E R F WA SH A N EL S-ROOF TRUSS TO PURLIN 6 1 1/2" = 1'-0" G S-ROOF TRUSS - ARCH PURLIN LOCATION 5 1/4" = 1'-0" G S-ROOF TRUSS - END 4 1/8" = 1'-0" T PLAN RIG O ALIGN PURLIN AT END OF TRUSS TAIL IN HSS 6x6x3/16 PORT OF KENNEWICK COLUMBIA DR. WINE VILLAGE HSS 6x6x1/8 6-Top Plate HSS 6x6x1/8 36' - 8" 1/8" SEE RAKE DETAIL FOR FASCIA CONSTRUCTION Kennewick, WA HSS 6"x6"x1/8" HSS 6x6x1/4 PURLIN HSS 6x2x1/8 BLOCKING 1/8 2' - 0" ROOF AND WALL NOT SHOWN FOR CLARITY 6x1/4" PLATE CONCRETE ARCH 2' - 7" CONCRETE ARCH TRUSS DRAWINGS PROVIDED FOR REFERENCE ONLY. SEE STRUCTURAL DRAWINGS BY OTHERS FOR REINFORCING DETAILS AND ADDITIONAL INFORMATION. HSS 6"x6"x1/4" PURLIN 1/8 HSS 6"x2"x1/8" BLOCKING 8 0250 CONCRETE TRUSS 7 S-CUPOLA 1" = 1'-0" NOTE: 8 S-CUPOLA ATTACHMENT DETAIL 3" = 1'-0" ARCH TRUSS DETIALS 0250 213-030 12/14/2015 2' - 0" 1' - 8" 1' - 8" 4" CONCRETE - SEE TYPICAL EM WALL DETAIL 2 1/2" 4" 2 1/2" 7" TIE #2 (2) #4 CONTINUOUS CENTERED IN BEAM (EQUALLY SPACED) #4 GFRP (5) #4 CONTINUOUS @ BOTTOM OF BEAM (EQUALLY SPACED) VERTICAL WALL REINFORCING PER DETAIL GFRP TIE #3 @ 12" O.C. EM FORM NOTE: ALL TIES ARE GLASS FIBER REINFORCED POLYMER (GFRP) EM FOAM INFILL GFRP TIE #1 @ 48" O.C. 2' - 8" HORIZONTAL WALL REINFORCING PER DETAIL 3' - 0" 20 #4 GFRP 2" EM FORM BRACE CONCRETE BOND BEAM 2 1/2" 2' - 6" GFRP TIE #3 @ 12" O.C. EM FORM JOINT #5 GFRP 18 9221 SANDIFUR PARKWAY SUITE "A" PASCO, WA 99301 1" (8) #6 VERTICAL REINFORCING T E R E N C E L. THORNHILL ARCHITECT 11 /2" GFRP SPAR REINFORCING ASSEMBLY GFRP SPAR TIE #1 @ 48" O.C. 9" 20' - 0" 1' - 0" 4-Top Of B.B. 9" GFRP LOOP TIE #4 @ 12" O.C. SEE EM WALL CAP DETAIL FOR ADDITIONAL WALL REINFORCING (NOT SHOWN FOR CLARITY) 1/ 2" 1' - 8" 4" 2 1/2" (3) #4 CONTINUOUS @ TOP OF BEAM 1 2' - 1" 10" #3 HORIZONTAL HOOP CAGE @ 6" O.C. 5' - 6" 17 24"x24" CONCRETE CORNER COLUMN SEE TYPICAL EM WALL REINFORCING DETAIL FOR WALL REINFORCING 16 TIE #1 GFRP SPAR REINFORCING ASSEMBLY TIE #3 509-547-8854 FAX 509-547-8912 [email protected] 1' - 10" 16" ICF SYSTEM GFRP TIE #2 @ 12" O.C. 1" 8 1/2" 4" CAST IN PLACE CONCRETE 2' - 0" 1/2" SHOTCRETE FINISH 14 A Professional Service Corporation 2' - 6" 15 FOAM INFILL 2" 13 4' - 0" 12 4" 1' - 4" TIE #4 4" SEE EM WALL TYPICAL REINFORCING FOR ADDITIONAL WALL REINFORCING (NOT SHOWN FOR CLARITY) 2' - 6" 1 1/2" COVER MINIMUM S-EM WALL CAP 2 1" = 1'-0" 11 S-EM WALL CORNER PLAN DETAIL 3 1" = 1'-0" 2549 W 33RD PL. KENNEWICK, WA, 99337 509.308.8015 866.421.7049 FAX S-EM WALL GFRP REINFORCING TIES 4 1" = 1'-0" 2' - 0" 10 GFRP TIE #2 @ 12" O.C. 9 4" CONCRETE - SEE TYPICAL EM WALL DETAIL EM FORM JOINT 8 5' - 6" EM FORM BRACE 7 EM FORM are the property of TERENCE L. THORNHILL Architect Inc. P.S. #5 BAR FENESTRATION REINFORCEMENT (1) BAR IN EACH MEMBRANE ALL EDGES OF FENESTRATION 6 VERTICAL WALL REINFORCING PER DETAIL EM FOAM INFILL solely with respect to this project and which reserves all common law HORIZONTAL WALL REINFORCING PER DETAIL EM FORM 5 These drawings are intended for use P. TY " 36 P. TY 2" 4" CONCRETE #3 BAR DIAGONAL REINFORCEMENT (1) BAR IN EACH MEMBRANE (TYP BOTH SIDES) statutory, copyright and other rights. DRAWN BY: DG EM FOAM INFILL EM FORM JOINT #4 @ 12" O.C. VERT - CONTINUOUS FROM FOUNDATION TO TOP OF WALL - 2" SPACING FOR NONCONTACT LAP SPLICE ALLOWED 3 SPAR REINFORCING ASSEMBLY #4 VERT. CONTINUOUS FOUNDATION TO TOP OF WALL (8) #6 VERTICAL REINFORCING 1 1/2" COVER MINIMUM 6" 2' - 6" GFRP SPAR TIE #1 @ 48" O.C. CHECKED BY: OPENING - PHASE: CD 2 REVISION NO: #4 @ 12" O.C. HORIZ. - CONTINUOUS FULL LENGTH OF WALL - 2" SPACING FOR NON-CONTACT LAP SPLICE ALLOWED 1 #3 HORIZONTAL HOOP CAGE @ 6" O.C. MARK 1' - 6" 0' - 0" 1' - 0" 2-Finish Floor 18"x24" CONCRETE COLUMN DATE DESCRIPTION (2) EM REINFORCING TIE #3 GFRP TIE #3 @ 12" O.C. SEE EM WALL FOOTING DETAIL FOR ADDITIONAL WALL REINFORCING (NOT SHOWN FOR CLARITY) 4" 7 S-EM WALL COLUMN PLAN DETAIL 1" = 1'-0" 8 S-CONCRETE OPENING REINFORCING DETAIL 1" = 1'-0" B TO R E R F WA SH A N O IN TO EL G E T S-EM WALL TYPICAL REINFORCING 1" = 1'-0" S TA 6 1' - 4" G S-EM WALL SPAR REINFORCING LOCATIONS 1/2" = 1'-0" 4" RIG O 5 1 1/2" COVER MINIMUM N 4" 1' - 4" EM FORM JOINT 4" EM FORM BRACE (TYP.) 45 DEG. CHAMFER EM WALL PER PLAN SEE TYPICAL EM WALL REINFORCING DETAIL FOR WALL REINFORCING CONCRETE BAND GFRP TIE #3 4" CONCRETE FLOOR SLAB - SEE PLAN 4" PVC 2x12 12"x24"x4" #4 TIE @ 48" O.C. GFRP TIE #3 @ 12" O.C. 2' - 0" 2' - 6" LINE OF WALL SPAR ASSEMBLY, GFRP TIE #3 AND VERTICAL #4 BAR 9 S-EM WALL REINFORCING SPACING DETAIL 3" = 1'-0" 2' - 0" 10 S-EM WALL FOOTING 1" = 1'-0" SI G ONA L EN IN PORT OF KENNEWICK COLUMBIA DR. WINE VILLAGE EM WALL CONCRETE GRADE BEAM FOOTING 11 S-EM WALL OPENING PLAN DETAIL 1" = 1'-0" Kennewick, WA 0251 (3) #5 BARS AT BOTTOM OF GRADE BEAM SECTION G I S T ER E D STRUCTURAL DETAILS EQ (2) #5 BARS AT TOP OF GRADE BEAM 1' - 6" #4 REBAR VERTICAL CONTINUOUS FROM FOUNDATION TO TOP OF WALL ELEVATION FILL 1/2" GAP WITH SEALANT AND BACKER ROD 1 1/2" PVC TRUE 4x4 BUCK W/ 3/8" DIA LAG @ 18" O.C. STAGGERED 1/2" 6" 1' - 0" QUADLOCK REBAR CHAIR 43454 RE EQ 2-FINISH FLOOR 0' - 0" 4" 2' - 0" #4 REBAR HORIZONTAL CONTINUOUS LENGTH OF WALL ES 1' - 0" #4 BAR CONTINUOUS FROM FOOTING TO TOP OF WALL (TYP.) #5 FENESTRATION REINFORCEMENT 1' - 6" GFRP WALL SPAR TIE #1 @ 48" O.C. F E 2" O PR 3/4" MIN. COVERAGE FROM HORIZONTAL BAR TO ICF FORM ER 4" 12 S-EM WALL - BREEZWAY COLUM 1" = 1'-0" 213-030 12/14/2015 CONCRETE WALL CAP 10" #4 @ 18" O.C. (HOOK) WALL TYPE PER PLAN PROVIDE EXPANSION GAP AT EDGE OF BEAM (1/2" MIN - 3/4" MAX) #4 @ 12" O.C. 4-Top of Wall (3) #4 CONTINUOUS (EQUALLY SPACED) 8' - 0" (2) #4 CONTINUOUS @ EACH FACE - HORZ X 8" CONCRETE WALL (BAG AND SACK FINISH) 2 1/2" HSS 12x6x1/4 PERIMETER BEAM 2" CONCRETE OVER 3" METAL DECK (5" TOTAL) HSS 12x6x1/4 PERIMETER BEAM 3-2nd Floor 10' - 6" 4" 6" L 5x3x1/4 4" WALL TYPE PER PLAN 5" 2' - 1" GFRP TIE #3 @ 12" O.C. 3-LOFT 10' - 6" 5" HSS 12x6x1/2 BEAM SLOPE FINISH GRADE 1% MINIMUM AWAY FROM WALL (TYP.) ASPHALT PAVING OVER COMPACTED BASE PER CIVIL GFRP SPAR TIE #1 @ 48" O.C. HSS 6x6x1/2 BEAM (2) #4 CONTINUOUS @ EACH FACE - HORZ 1/2" SHOTCRETE FINISH X (3) #4 CONTINUOUS - HORZ 4" CAST IN PLACE CONCRETE HSS 6x6x1/4 COLUMN HSS 6x6x1/4 COLUMN 509-547-8854 FAX 509-547-8912 [email protected] A Professional Service Corporation 8" X 9221 SANDIFUR PARKWAY SUITE "A" PASCO, WA 99301 #3 @ 18" O.C. (HOOK) - VERT 2' - 0" MIN. SEE TYPICAL EM WALL REINFORCING DETAIL FOR WALL REINFORCING T E R E N C E L. THORNHILL ARCHITECT 16" ICF SYSTEM FOAM INFILL 8" 4" S-EM WALL AT LOFT 1 1" = 1'-0" S-EM WALL AT LOFT - PERPENDICULAR 2 1" = 1'-0" 1' - 4" 4" 8" 8" COMPACTED BASE BACKFILL PER GEOTECH ENGINEER 2' - 0" S-EM WALL CAP @ GARDEN WALL 3 1" = 1'-0" 2549 W 33RD PL. KENNEWICK, WA, 99337 509.308.8015 866.421.7049 FAX S-TRASH ENCLOSURE - WALL DETAIL 4 1" = 1'-0" HSS 12x6x3/16 CORTEN STANDING SEAM METAL ROOF 1/4" KNIFE PLATE 1 1/2" B-22 GAGE METAL DECKING DRIP FLASHING 2' - 10" 6" 2" 3" 3/8" 1/4" KNIFE PLATE 1/4" CAP TERENCE L. THORNHILL Architect Inc. P.S. which reserves all common law HSS BEAM PER STRUCTURAL HSS 4x4x1/4" statutory, copyright and other rights. 3" BRACKET DETAIL 2" 1 1/ 3" BRACKET SEE DETAIL 1 1/2" METAL DECKING HSS 6x2x1/4" @ 4' - 4" O.C. 2" 2 1/ 2" 1 1/ CORTEN STANDING SEAM METAL ROOF 1/8 are the property of 2" 1/8" HSS 6x2x1/8" solely with respect to this project and 1/4" DOUBLE PLATE T.O. BEAM 14'-0" These drawings are intended for use 3/4" BOLT 3"x10"x3/8" EMBED PLATE W/ (2) 1/2" DIA. x 3" NELSON STUDS TYP. OF 4 - SEE LOCATIONS ON FRAMING PLAN DRAWN BY: DG NOTE: 1) WELDS = 1/4" FILLET ALL AROUND 2) GRIND ALL EDGES SMOOTH HSS 4x4x1/4" HSS 6x6x1/4" 1/8 CHECKED BY: 1/2" @ 16" O.C. - HSS12x6x3/16" T.O. BEAM 14'-10" HSS6x6x1/4" 3" 3" 3" 1/8" CONCRETE SLAB 6" MARK 2" 1 1/ 3" 3" 4" REVISION NO: 1/4" KNIFE PLATE 2" 2 1/ 3" 6" PAVING PER CIVIL CD DEFLECTION TRACK 2" 1 1/ 3" SEE STRUCTURAL FOR FOOTING DETAILS HSS 6x2x1/4" @ 4' - 4" O.C. PHASE: BRACKET SEE DETAIL DATE DESCRIPTION WALL TYPE PER PLANS HSS 4x4x1/4" HSS12x6x3/16" 1/2" GAP HSS6x6x1/8" 8 EQ EQ EQ REINFORCING [B] O.C. EACH WAY (3" MINIMUM CLEAR ABOVE BOTTOM) [A] BASE PLATE PLAN A 5/16 3 1/2" 5/16 1" NON-SHRINK GROUT 1' - 0" CONCRETE SLAB PER PLAN 5/8" ANCHOR BOLT (7" MIN. EMBED) [Z] 10 S-COLUMN FOOTING - TYPE 2 1/2" = 1'-0" 1" NON-SHRINK GROUT 5/8" ANCHOR BOLT (7" MIN. EMBED) [Z] 1' - 0" 1' - 0" [Z] S-COLUMN FOOTING - TYPE 1 1/2" = 1'-0" FILL WITH NON-SHRINK GROUT REINFORCING [B] PER SCHEDULE WALL FOOTING PER DETAIL SECTION A-A 5/8" ANCHOR BOLT EPOXIED INTO FOOTING A REINFORCING [B] PER SCHEDULE REINFORCING PER SCHEDULE 10" COMPACTED FILL PER GEOTECH WALL FOOTING PER DETAIL SECTION A-A 11 S-COLUMN FOOTING - TYPE 3 1/2" = 1'-0" F ES 43454 RE G I S T ER E D SI G ONA L EN IN PORT OF KENNEWICK COLUMBIA DR. WINE VILLAGE Kennewick, WA BASE PLATE [A] CONCRETE SLAB PER PLAN 5/8" ANCHOR BOLT (7" MIN. EMBED) 9 PLAN FILL WITH NON-SHRINK GROUT CONCRETE SLAB PER PLAN COMPACTED FILL PER GEOTECH CL WALL FOOTING PER DETAIL A 1" NON-SHRINK GROUT SECTION A-A 5/8" ANCHOR BOLT EPOXIED INTO FOOTING BASE PLATE [A] FILL WITH NON-SHRINK GROUT 5/16 1' - 2" WALL FOOTING PER DETAIL 3/4" BASE PLATE 2" TYP. [X] 3 1/2" 5/8" ANCHOR BOLT EPOXIED INTO FOOTING PLAN CL [X] EQ 1' - 2" REINFORCING [B] PER SCHEDULE EXTEND REINFORCING INTO WALL FOOTING MINIMUM 18" 3/4" BASE PLATE 2" TYP. 10" 2" TYP. EQ [X] CL 3 1/2" REINFORCING [B] PER SCHEDULE EXTEND REINFORCING INTO WALL FOOTING MINIMUM 18" 3/4" BASE PLATE 2" TYP. 2) COLUMN FOOTING TO BE POURED MONOLITHIC WITH WALL FOOTING ER 2) COLUMN FOOTING TO BE POURED MONOLITHIC WITH WALL FOOTING 1) SEE FOUNDATION PLAN FOR FOOTING SCHEDULE CL E [Y] A [Y] 10" EQ 1) SEE FOUNDATION PLAN FOR FOOTING SCHEDULE N [Y] CL IN TO A NOTE: O PR NOTE: SEE FOUNDATION PLAN FOR FOOTING SCHEDULE CL O E EL A B TO R E R F WA SH A N G NOTE: S-PARTITION WALL TO BEAM 3" = 1'-0" T S-CROSS BRACING DETAIL 1" = 1'-0" 7 S TA S-AWNING AT WALL 1" = 1'-0" 6 G S-AWNING AT POST 1" = 1'-0" 10" 5 CROSS BRACE DETAIL RIG O ELEVATION COMPACTED FILL PER GEOTECH STRUCTURAL DETAILS 0252 213-030 12/14/2015
© Copyright 2026 Paperzz