Canberra Building Inspections Fast and Professional 2015 25/10 Federal Highway Watson – ACT Inspection address: 25/10 Federal Highway, Watson, ACT Page 1 Canberra Building Inspections Fast and Professional 2015 Canberra Building Inspections Fast and Professional ABN: 32524279672 Email: Inspector: Inspection Date: [email protected] Nick Broadhurst 0452233863 18 August 2015 Client: Inspection Address: Suburb: Sue O’Connell 25/10 Federal Highway Watson The following inspection report is designed as a statement of the condition of said property at the time of the inspection. The inspector is not obligated or qualified to give legal advice to any client as a part of this inspection. It will be the client's obligation to discuss these issues with the agent directly to determine any remedies or expectations that may form part of the offer and acceptance. Depending on the clauses included in the "offer and acceptance" the vendor may not be obligated to make good some or all of the issues discovered in this report. This is not a termite/ pest inspection report. It is the buyer's responsibility to carefully read the offer and acceptance and accurately follow the requirements of the contract within the designated required time frames where significant defects are to be reported to the vendor. A PrePurchase Building report is compliant with Australian Standards 4943.1- 2007 Abbreviations LV RHS LHS WC HWU low voltage right hand side left hand side water closet (toilet) hot water unit Access restrictions Did any of the below listed items limit access to the property? Y Furniture in the home. Y Insufficient manholes to roof space. Y Type of insulation: Bats Blown in Foam Sisilation/Anticon Safe access to top of roof limited by excess height? Y Insufficient access to subfloor areas- Timber floors only? Y Locked doors to store rooms/ sheds? Y Inspection address: 25/10 Federal Highway, Watson, ACT N N/A N N/A N N/A Non Standard N N/A N N/A N N/A Page 2 Canberra Building Inspections Fast and Professional 2015 BUILDING INSPECTION POINT SUMMARY BUILDING REPORT: Building Report: Compliance Report Pest Inspection Report: Energy Efficiency Rating: Any significant defects? Any unapproved structures? Any subterranean termites found? No No No 3.5 Star INSPECTOR DETAILS Inspection Date: Name of attending inspector Name of Client: Address of Property Inspected: Block No: 19 Section No: 61 18/08/2015 Nick Broadhurst Sue Oconnell 15 Years HOME DESCRIPTION: Year built: 2000 Style: Two Storey Townhouse Description: The property is a two story townhouse with an adjoining wall to the next townhouse. It has one garage. The townhouses are generally well built and are good condition for their age. They exhibit little wearing or cracking. Overall these townhouses seem to require less maintenance than others. This inspector has seen other units inside and they are also in good condition. Also notice the attention to details externally. It is good quality with no maintenance issues at this stage. There are no external structural cracks, and inside there is no evidence of any structural movement. (Sizes are scaled and include all external wall areas.) Block size Allotment size(approximately) House size (sizes scaled as guides) Garage and workshop: Alfresco TOTAL: 9741 M2 286.3 M2 139.6 M2 19 M2 15.1 173.6 M2 HOME DETAILS: Window frames: Aluminium in timber reveals. They are good quality and work well. Insulation: Walls: No Ceiling: The top floor has 130 mm lose fiber, and over the ground living area there is 85 mm of lose fiber insulation with sarking over that under the flat roof section. Garage: There is room for one car with an electric roller door. Inspection address: 25/10 Federal Highway, Watson, ACT Page 3 Canberra Building Inspections Fast and Professional 2015 Significant Defects Summary Action may be enforceable under a significant defect clause on the following items: COMMENTS: No significant defects were found in this inspection No significant defects were found in the structure End of Significant Defect Report Summary Inspection address: 25/10 Federal Highway, Watson, ACT Page 4 Canberra Building Inspections Fast and Professional 2015 Maintenance Report Summary The following items are not enforceable unless specified: The below items are not significant but observed during the inspection 1. It is advisable to paint the existing rear and side timber paling fence so that it can survive much longer into the future without being replaced. While the fence serves now as a fence, it will need a small amount of maintenance to help preserve it well. End of Maintenance Report Summary Inspection address: 25/10 Federal Highway, Watson, ACT Page 5 Canberra Building Inspections Fast and Professional 2015 Faulty Fixtures & Fittings Summary Faulty Fixtures and Fittings (enforceable under most fixtures and fittings warranty clauses.) Any missing light globes that are identified in item 53 on the checklist should be rechecked at the final inspection to ensure that no significant electrical fault is present here. 1. No action required. End of Fixtures and Fittings Summary Inspection address: 25/10 Federal Highway, Watson, ACT Page 6 Canberra Building Inspections Fast and Professional 2015 Structural Checklist Any item marked with an R will have a corresponding note in the relevant summary section of this report. R Refer to Summary notes OK No significant issue N/A Not Applicable 1. 2. 3. 4. 5. Overall roof cover condition acceptable. Visible cracks to roof tiles exceeding tolerance. (tiled roof only) Visible cracking to flexipointing exceeding tolerance. (tiled roof only) Sags or bows in any plane of roof causing structural concern. Excessive rusting of flashings causing significant leaks. 6. Gutters generally functional. Excessive rust or leaks? 7. Significant water backflow leaks evident in eaves. OK OK OK OK OK OK OK Meter Box 8. Access to live mains adequately covered. 9. Any isolated or danger tagged circuits. 10. Any Horizontal cracking which exceeds normal settlement cracks. OK OK OK External Walls & Perimeter 11. Any Vertical cracking which exceeds normal settlement cracks. 12. Visual evidence of rising damp in the bottom 400mm of the walls. 13. Asbestos may be present but not necessarily limited to the following areas: OK OK OK ___________________________________ ___________________________________ 14. Any significantly loose brickwork or soft mortar. 15. Steps to outside of home in good condition and safe. 16. All visible waste pipes connected to drains. 17. Garage ceiling lining in good condition OK OK OK OK Footings / Foundation 18. Cracks visible in concrete footings. OK 19. Sides of footings fully covered beneath soil level. OK Pergolas 20. Any timbers rotten or damaged beyond safe tolerances. N/A 21. Fixing of posts to ground creating a termite barrier. N/A Inspection address: 25/10 Federal Highway, Watson, ACT Page 7 Canberra Building Inspections Fast and Professional 2015 22. Retaining wall construction acceptable. N/A 23. Significant horizontal or vertical cracks in retaining walls. N/A 24. Loose Brickwork present in retaining walls. N/A 25. Soft mortar or limestone resulting from insufficient tanking. N/A 26. Rotten stumps, beams or sleepers in retaining walls. N/A Interior Ceilings 27. Popped screws or degraded straps causing sagging. OK 28. Sagging to ceilings causing structural concern. OK 29. Cracks along ceiling joins beyond acceptable tolerances. OK 30. Cornice cracking exceeding normal settlement expectations. OK 31. Evidence of significant water leaks in ceilings. OK 32. Severe mould or water damage to wet areas. OK 33. Hard wired or equivalent smoke detectors. OK Internal Walls 34. Any cracking which exceeds normal settlement cracks. OK 35. Moisture reading behind shower recess walls. OK 36. Any evidence of significant moisture barrier issues in the plaster. OK Internal Floors 37. Cracks to ground slabs exceeding normal limitations. OK 38. Condition of timber floor boards (if applicable) OK 39. Sufficient access panels available to sub floors (if applicable) OK Roof Space 40. Any significant gaps between structural members due to sagging. OK 41. Unsound modifications done to roof/load bearing walls removed. OK 42. Lateral shift in hangers or strutting beams. OK 43. Sagging to any major roof beams, struts or purlins. OK 44. Inspection address: 25/10 Federal Highway, Watson, ACT Page 8 Canberra Building Inspections Fast and Professional 2015 Balconies & Stairs 45. Balustrading present to balconies and stairs (if applicable) OK 46. Balustrading in good condition and undamaged. (if applicable) OK Additional Pre Purchase Items Electrical Note; This PrePurchase inspection is not a substitute for a safety inspection by a licensed electrician. Items identified by your inspector are advisory only, a technical assessment by a licensed electrician may uncover additional issues that cannot be reasonably identified by a registered building inspector. External 47. Unsafe exposed wiring to external walls below 2.4m. OK 48. Orange conduit used above ground unpainted exposed to UV light. OK 49. External wall lights correctly functioning and properly installed. OK Some sensor lights can only be switched on at night time due to built in light sensors in this event the sensor light may not be properly tested during the inspection. 50. Garage sectional door opening and closing properly. OK Flat batteries to remotes may limit testing of this item. Internal 51. Light switches in good condition and functioning throughout. OK 52. Light globes missing or blown during inspection. OK The following rooms contained missing or blown light globes, therefore, these lights were not properly tested during the inspection. None ______________________________ ______________________________ 53. GPOs in good condition and correctly fixed to walls. OK 54. Wet area exhaust fans working properly. OK 55. Exposed wiring below 2.4m inside the home. OK 56. Ceiling fans functioning correctly. OK 57. Loose wiring present in the roof space causing safety concern. OK 58. Single insulated lengths of wiring present in the roof space causing a OK Inspection address: 25/10 Federal Highway, Watson, ACT Page 9 Canberra Building Inspections Fast and Professional 2015 safety hazard. 59.Heat shields present over low voltage down lights. (if applicable) OK 60. Any obvious evidence of electrical extensions by uncertified individuals which may require safety testing by an electrician? Plumbing 61. Gas connected and available to site. OK 62. Taps functioning correctly and easy to turn. OK 63. Shower roses in good condition and functioning. OK 64. Toilet flushing correctly, cisterns refilling without running continuously. OK 65. Leaks present to wastes beneath sinks/ basins/ troughs. OK 66. Significant blockages to basin/ sink wastes. OK Appliances 67. Oven functioning. OK Oven will be turned on and considered to be functioning if heat is being produced. Older gas ovens can be difficult to light, in this instance the oven may not be properly tested and a notation will indicate this in the summary of this report. 68. Hotplate functioning. OK All burners will be tested and will be considered functional if heat is being produced. 69. Air conditioner functioning. OK The air conditioner will be tested for basic function only. A detailed inspection of the functions is not included as a part of a PrePurchase inspection. If required this must be carried out by an air conditioner technician. Air conditioning may not be tested if remotes are not present or batteries are flat during the inspection. 70. HWU working and in good condition. Check base of unit for corrosion. OK 71. Kitchen range hood functioning. OK Water Bodies 72. Fencing to water bodies compliant with safety recommendations. N/A 73. Self closing gates and doors to water body access points. N/A 74. Safe header course around swimming pool. N/A 75. Unsafe wiring present to pool pump area. N/A 76. Orange conduit unpainted above ground in pool pump area. N/A 77. Inspection address: 25/10 Federal Highway, Watson, ACT Page 10 Canberra Building Inspections Fast and Professional 2015 Boundaries 78. Any part of the structure extending over boundary fences. OK 79. Any additions or other structures that may require evidence of council OK approval. __________________________________ __________________________________ 80. General condition of fencing within 30m of the home. OK Fencing will be considered adequate if it is performing its intended function. End of Checklist PHOTOS AND NOTES: END OF REPORT Inspection address: 25/10 Federal Highway, Watson, ACT Page 11 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 12 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 13 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 14 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 15 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 16 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 17 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 18 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 19 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 20 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 21 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 22 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 23 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 24 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 25 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 26 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 27 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 28 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 29 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 30 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 31 Canberra Building Inspections Fast and Professional 2015 COMPLIANCE CERTIFICATE SUMMARY This is the pre-purchase compliance report with regard to approval of any alterations to the property as requested. The compliance documentation was provided by ACTPLA. The documentation provided is attached to this report. Client: Inspection Address: Suburb: Sue O’Connell 25/10 Federal Highway Watson Canberra Building Inspections Fast and Professional Email: Inspector: Inspection Date: ABN: 32524279672 [email protected] Nick Broadhurst 0452233863 18 August 2015 The plans and certificates included are all for existing and additional work done after the original dwelling was built. On the day of this inspection, the works appeared to substantially conform to these approved plans. The following documents are in the accompanying conveyancing file from ACTPLA: Residential conveyance enquiry Building file index Survey Plan / Certificate Draining Plan Certificates as listed below Plans as listed below. Building Works Certificate New Town House U 25 Cert of Occupancy Permit Approved Plans Date 994259/A 994259/A 21/6/99 994259/A 18/1/00 994259N1C2 Inspection address: 25/10 Federal Highway, Watson, ACT Page 32 Canberra Building Inspections Fast and Professional 2015 Civil Law (Sale of Residential Property) Regulations 2004 a) Within 7 days after this report being prepared, the following information will be given to the ACT government for inclusion in a publically available register: the fact that the report has been prepared, the street address of the property, the inspection date stated in the report, the name of the person preparing the report and the company name and contact details. b) The person who prepared this report, or any other entity, may give a copy of this report, on payment of a reasonable charge, to a person who has entered into a contract to buy the property. c) No reliance may be placed on the report for any contract entered into more than 180 days after the date of this inspection. d) In accordance with the above Act this report excludes reporting on minor defects and / or maintenance items. If any of these items are included in the report they are for information purposes only. End of Compliance Report Inspection address: 25/10 Federal Highway, Watson, ACT Page 33 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 34 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 35 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 36 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 37 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 38 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 39 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 40 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 41 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 42 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 43 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 44 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 45 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 46 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 47 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 48 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 49 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 50 Canberra Building Inspections Fast and Professional 2015 Inspection address: 25/10 Federal Highway, Watson, ACT Page 51
© Copyright 2026 Paperzz