Temperature Transmitter Model HPT - Electro

Temperature Transmitter
Model HPT
The Conax Model HPT is a low cost, 2-wire, non-isolated
temperature transmitter for RTD sensors, and is designed
to fit in our popular T11 model terminal head.
The HPT housing has a removable base allowing
access to the electronics for the purpose of temperature
range changes, which are easily accomplished with
plug-in resistors.
Specifications
Output SPAN
4-20mA, limiting @ <28mA
Input
RTD - 100Ω, 2 or 3 wire connection
Input Span
RTD: 20°C min., 500°C max.
Burnout Detection
Upscale, Standard
Supply Voltage
8-38 VDC polarity protected
Maximum Load
Rmax = (V supply - 8V)÷ 20 mA
Ambient Temp.
-20°C to +70°C
Humidity
0-95% RH, non-condensing
Linearity
RTD: Better than ±.05% of SPAN referred to sensor temperature
Stability (for both ZERO and SPAN)
RTD (100°C SPAN): .03% of SPAN/°C
All specifications are subject to change without notice.
Dimensions & Electrical Connections
Dimensions are in inches (mm)
1.30
(33)
(RTD)
.300 (7.6)
.165 (4.2)
1.73
(44)
1.10
(28)
.71
Ordering Information
Model: HPT – RTD– (32-500) – F
Measurement Range
Units (°F or °C)
With Weatherproof, Cast Aluminum Head: Add Prefix: – T11
Example of complete Assembly with Sensor: RTD43W3-SS25-T11HPT -(32-500 F) -12.00”
Represented By:
For more information call
Conax Buffalo Technologies
at: 1-800-223-2389
™
2300 Walden Avenue
Buffalo, New York 14225
FAX: 716-684-7433 • Phone: 716-684-4500
Toll free in the USA at 1-800-223-2389
www.conaxbuffalo.com • e-mail: [email protected]
European Office
PO Box 91
BOGNOR REGIS PO22 7JB, England
FAX: +44 (0) 1243 587799 • Phone: +44 (0) 1243 587878
e-mail: [email protected]
Temperature Transmitter
HART® Smart Isolated 2-Wire Transmitter –
Signal Transmission the Smart Way
Model HST
The Conax Model HST HART® Smart Isolated 2-Wire Transmitter
features universal input capability in 3 variations to accept most
of today’s process parameters: Thermocouples, RTDs, DcmV,
Potentiometers, Resistance Sensors, DcmA, DCV, AC Amps,
Frequency and Pulse.
Model HST is fully software driven and all input parameters are
programmable. An external hand-held programmer, an integral
transmitter mounted programmer, or HART protocol hand-held
enables on site calibration, and indication of process parameters.
Other features of the Model HST include high precision
linearization for thermocouple and RTD sensor inputs, inverse
output capability, variable input signal damping, sensor
breakdown indication, full display scaling capability, auto-zero
input, and more.
Heavy duty metal case construction and carefully designed input
and output circuitry ensures a high degree of protection from
adverse environmental conditions to maximize RFI/EMI immunity.
Optional features include LCD display with integral
programmer, hand-held programmer, and explosion-proof
enclosure:
CL I, GRPS B, C, D
CL II, GRPS E, F, & G
CL III Type 4X
General Specifications
Inputs
TC - Types E, J, K, T, R, S, N, B, C.
RTD - 2, 3, and 4-wire Pt-100, (DIN & NIST curves) Pt-200,
Ni-100, Cu-10 and other RTDs.
DC mV ±120.00mV input SPAN.
Potentiometers - 100Ω to 20KΩ.
Resistance - 2, 3, and 4-wire 0 to 600Ω.
Optional: DCmA, DCV.
Optional: AC-Volts, AC-Amps, Frequency/Pulse.
Minimum Range
None. Limited only by signal quality.
Digital Resolution
>17 bits
Outputs
4-20mA isolated analog current loop, or Digital communication,
HART® protocol.
Supply
12-45 VDC (@ no load). Reverse polarity protected.
Display (optional)
8x1 Character LCD indicator for programming and
display of input and output parameters and status.
General Specifications continue on inside cover.
HART® Smart Communications Protocol Specification is a trademark of Rosemount, Inc.
General Specifications, cont…
Operating Conditions
-20°C to +70°C. 0-95% RH, non-condensing
Storage Temperature
-55°C to +125°C
Turn-On Time
Within 4 seconds to rated response
Response Time
0.5 seconds to 99% of reading (2 updates per second).
Damping Factor
Programmable 0.0 to 32.0 seconds
Long Term Stability
Better than ±0.1% of SPAN for 6 months
Isolation
800 VDC or peak AC
RFI/EMI Immunity
Tested per SAMA PMC 33.1C from 20 to 1000 MHz and for field
strength up to 30 V/m.
C.M.R.R.
>120db DC to 60 Hz
Enclosure
Extruded, anodized aluminum
Dimensions
3.00” x 2.44” x 2.46”
3.00” x 2.44” x 3.00” (with programmer/display)
(Hockey-puck housing. Suitable for mounting inside
3.5” diameter explosion-proof enclosures.
All specifications are subject to change without notice.
Performance Specifications
Analog Output Resolution
0.025% of SPAN (±4µA)
Analog Output (D/A) Linearity
±0.025% of SPAN
Digital Sensor Linearization
<±0.02°C for Pt-100 RTD
<±0.1°C for thermocouples
Cold Junction Compensation
Automatically corrected to within <±0.3°C for all T/C types
Temperature Stability
Zero: <±0.003%/°C of SPAN
Span: <±0.005%/°C of SPAN
Supply Voltage Effect:
<±0.001% per volt
Calibration
Automatic. Unit includes all of the calibration parameters. It
performs periodic “ZERO”, “SPAN”, self-test, and auto
calibration. No field calibration is required.
Physical Dimensions & Electrical Connections
Dimensions are in inches (mm)
IHST
OPTIONAL MAGNETIC
SWITCHES FOR
PROGRAMING THRU XP
ENCLOSURE’S WINDOW.
THERMOCOUPLE
POTENTIOMETER
DC MV
Optional Programmer
with Display
4-WIRE RTD
3-WIRE RTD
2-WIRE RTD
(62)
2.44
HST
PROGRAMMING
PORT
LOOP WIRING
(76.2)
3.00
Input-Wiring Diagram
OPTIONAL PROGRAMMER WITH DISPLAY
(76.2)
3.00
(62.5)
2.46
(49)
1.93
35mm DIN RAIL
2.75” SNAP TRACK
DIN RAIL ADAPTER
Transmitter Mounting
Arrangement
Physical Dimensions & Electrical Connections
Dimensions are in inches (mm)
HART
PROGRAMMER
(REMOTE)
POWER SUPPLY
(123)
4.84
BELL 202
MODEM
(70)
2.75
PLC / PC
x (29mm)
1.14 Thick
Hand Held Programmer
Sample Loop showing the HST with
both Analog and Digital Devices.
Ordering Information
Model:
HST - 01 - H - K
01-T/C, RTD, mV, POT, RES
02-DCmV, DCmA, DC Volt
03- AC Volt/AMP/FREQ/Pulse
A - Standard 4-20mA Output
H - HART® + Analog Output
Integral Display Option
K - Integral Programmer/Display
R - Programmer + Reed Contacts
Represented By:
For more information call
Conax Buffalo Technologies
at: 1-800-223-2389
™
2300 Walden Avenue
Buffalo, New York 14225
FAX: 716-684-7433 • Phone: 716-684-4500
Toll free in the USA at 1-800-223-2389
www.conaxbuffalo.com • e-mail: [email protected]
European Office
PO Box 91
BOGNOR REGIS PO22 7JB, England
FAX: +44 (0) 1243 587799 • Phone: +44 (0) 1243 587878
e-mail: [email protected]
Temperature Transmitters
Model DRT2-T/C &
DRT4-T/C
The Conax Model DRT2-T/C and DRT4-T/C are compact,
DIN rail mounted transmitters for any thermocouple type.
The units provide an output which is linear with respect to
the thermocouple sensor’s mV input.
The units are powered by standard industrial loop
powered supply and provide a 4-20mA current loop
output on a 2-wire transmitter system (DRT2-T/C) or
any standard current or voltage output on a 4-wire
system (DRT4-T/C).
Specifications
Input
Any Thermocouple type
Input Span
5mV Min.
(20mV for rated accuracy)
Output (DRT2-T/C) 2-Wire
(DRT4-T/C) 4-Wire
Current loop 4-20mA
0...1...4...20mA
0...1...2...5...10V
Linearity
0.02% of SPAN
(Ref. to mV input)
Burnout Detection
Upscale, Standard
Reference Junction
1.0°C max. error over 0-50°C of operating ambient temp.
Stability (20mV input)
Zero: 1mV/°C or 0.01% of SPAN/°C
Power Supply Range
24 VDC ±20%, polarity protected
Adjustments
±25% on both ZERO and SPAN
Operating Temperature
-20°C to 70°C (0°F to 160°F)
Mounting
DIN rail 35 mm
All specifications are subject to change without notice.
Dimensions & Electrical Connections
Dimensions are in inches (mm)
Loop powered
Current
Monitor
+
DIN Rail (35 mm)
1
2
1
2
–
Power
Output
Signal
+ – + –
3
4
1
2
3
4
3
4
1
2
3
4
DRT4-T/C
TC-K
(800-1200)C
(4-20) mA
5
2.56
(65)
2.12
(54)
6
7
8
Thermocouple Input
DRT2-T/C
2.34
(60)
DRT2-T/C
TC-J
(0-350)F
(0-10) V
5
6
7
8
0.94
(24)
DRT4-T/C
Ordering Information
Model: DRT2 – K– (32-500) – F – (4-20)mA
2 = Loop Powered
4 = Four Wire
Thermocouple Type
Measurement Range
Units (°F or °C)
Output Range
DRT2-T/C: 4-20mA
DRT4-T/C: V or mA
Output Units
Represented By:
For more information call
Conax Buffalo Technologies
at: 1-800-223-2389
™
2300 Walden Avenue
Buffalo, New York 14225
FAX: 716-684-7433 • Phone: 716-684-4500
Toll free in the USA at 1-800-223-2389
www.conaxbuffalo.com • e-mail: [email protected]
European Office
PO Box 91
BOGNOR REGIS PO22 7JB, England
FAX: +44 (0) 1243 587799 • Phone: +44 (0) 1243 587878
e-mail: [email protected]
Temperature Transmitters
Model DRT2-RTD &
DRT4-RTD
The Conax Model DRT2-RTD and DRT4-RTD are
compact, DIN rail mounted transmitters for 2, 3, and
4 wire RTD sensors. The output is linear with respect
to the sensor's temperature. The 4-wire input circuitry
provides near perfect compensation for the effect of
long leadwire resistance.
The units are powered by standard industrial loop
power supply and provide a 4-20mA output on a 2-wire
transmitter system (DRT2-RTD) or any standard current
or voltage output on a 4-wire system (DRT4-RTD).
Specifications
Input
Pt-100, 2, 3, or 4-wire RTD.
Other Pt, Ni, NiFe, Cu RTDs, available
Input Temp Range
-200°C (-328°F) to +850°C (1562°F)
Input Span
20°C Min. to 800°C Max.
Output (DRT2-RTD) 2-Wire
(DRT4-RTD) 4-Wire
Current loop 4-20mA
0...1...4...10...20mA
0...1...2...6...10V
Linearity
Better than 0.1%, referred to the sensor's actual temperature
Lead Wire Error (4-Wire)
(3-Wire)
Negligible, for 4-Wire sensors
Better than 100:1 compensation
Temperature Stability
<±0.01% of range/°F (100°C SPAN)
Power Supply Range
24 VDC ±20%, polarity protected
Adjustments
±25% on both ZERO and SPAN
Operating Temperature
-20°C to 70°C (0°F to 160°F)
Mounting
DIN rail 35 mm
All specifications are subject to change without notice.
Dimensions & Electrical Connections
Dimensions are in inches (mm)
Loop powered
Current
Monitor
+
DIN Rail (35 mm)
1
2
1
2
–
Power
Output
Signal
+ – + –
3
4
1
2
3
4
3
4
1
2
3
4
DRT4-RTD
Pt-100
(0-100)C
(0-10) V
(4-20) mA
5
2.56
(65)
2.12
(54)
6
7
8
RTD Input
DRT2-RTD
2.34
(60)
DRT2-RTD
Pt-100
(0-350)F
5
6
7
8
0.94
(24)
DRT4-RTD
Ordering Information
Model: DRT2 – RTD – 3 – (32-500) – F – (4-20)mA
2 = Loop Powered
4 = Four Wire
No. of Wires of RTD
Measurement Range
Units (°F or °C)
Output Range
DRT2-RTD: 4-20mA
DRT4-RTD: V or mA
Output Units
Represented By:
For more information call
Conax Buffalo Technologies
at: 1-800-223-2389
™
2300 Walden Avenue
Buffalo, New York 14225
FAX: 716-684-7433 • Phone: 716-684-4500
Toll free in the USA at 1-800-223-2389
www.conaxbuffalo.com • e-mail: [email protected]
European Office
PO Box 91
BOGNOR REGIS PO22 7JB, England
FAX: +44 (0) 1243 587799 • Phone: +44 (0) 1243 587878
e-mail: [email protected]
TM
Temperature Transmitter
PC Programmable
DIN Rail Transmitter
Model PDT-400
The Conax Model PDT-400 is a slim DIN rail
mount programmable 2-wire transmitter, featuring
a state-of-the-art microprocessor-based design
that enables full configuration with user friendly
configuration software.
Standard Features
• Full featured and highly accurate
• No power supply needed to program
• User-friendly software provides
complete programmability of sensor
type and input range
• Linearized 4-20mA current loop output
for sensor input
• 2000 Volts I/O isolation
• RFI/EMI protected,
marked
• Custom linearization in minutes
• Dual sensor input capability
All specifications are subject to change without notice.
1-800-223-2389
www.conaxbuffalo.com
Configuration
GENERAL SPECIFICATIONS
All input types and range parameters are easily
configurable with user-friendly technology. No power
supply is required for programming. The PA-400
programming adapter and the graphic user interface
software operate under Windows® operating
systems through the PC’s RS232 serial port.
Minimum Range
2 mV. Limited mostly by input
signal quality.
Output
4-20mA isolated loop
powered.
Supply Voltage
9-40 VDC (@ no load).
Reverse polarity protected.
Specifications
Maximum Load
Rmax = ( Vsupply - 9V) ÷
20mA.
INPUT CONFIGURATIONS
Thermocouples
Most standard types and all
special types using customer
defined tables and
polynomials.
RTD
2, 3, and 4 wire, Pt-100,
Ni-110 and other RTDs.
Includes Callandar-VanDusen adaptation and custom
sensors linearization with user
defined tables and
polynomials.
Operating Temperature
-40˚ to +85˚C (-40˚F to
185˚F).
Storage Temperature
-55˚C to +125˚C (-67˚F to
257˚F)
Humidity
0-95% RH, non condensing.
Response Time
0.3 seconds, to 90% of input.
(>3 updates per second).
Damping Factors
Programmable 0.0 to 64.0
seconds, to 0 - 120% of input
range, using software
interface.
Better than ± 0.1% of span
for 12 months.
Stability
PERFORMANCE SPECIFICATIONS
Output Resolution
0.015% of span (2.5µA).
I/O Isolation
2000 VDC or peak AC.
Output (D/A) Linearity
Better than 0.02% of
output span.
RFI Protection
Sensor Linearization
Better than 0.1˚C for RTDs.
Better than 0.2˚C for T/Cs.
<1% effect of span at
20-1000 MHz and at field
strength of 20V/m.
marked.
Cold Junction
Compensation
Automatic to within ±0.7˚C
for all T/C.
Temperature Stability
0.015%/˚C combined ZERO
and SPAN.
Supply Voltage Effect
<±0.003% per Volt.
Calibration
Automatic. Unit includes all
of the calibration parameters.
It performs periodic “zero”,
“span”, self-test, and auto
calibration.
Input Linearity
Better than 0.01% of span
(mV input).
Accuracy
RTD 0.1˚C typical
T/C 0.3˚C typical
Ordering Information
Model: TRANSMITTER, PDT-400
Programming Adapter (RS232)
Model: PA-400
Windows® is a registered trademark of Microsoft Corporation.
Represented By:
For more information call Conax Buffalo
Technologies at: 1-800-223-2389
™
2300 Walden Avenue European Office
Buffalo, New York 14225 PO Box 91
FAX: 716-684-7433 • Phone: 716-684-4500 BOGNOR REGIS PO22 7JB, England
Toll free in the USA at 1-800-223-2389 FAX: +44 1243 773050 • Phone: +44 1243 784060
e-mail: [email protected] e-mail: [email protected]
w w w. c o n a x b u f falo.com • www. p a r t s d r aw e r. c o m
ISO certification refers to Buffalo location.
©2002 Conax Buffalo Technologies
Bulletin 6022
6/02 5M
W A L L M O U N T T E M P E R AT U R E S E N S O R
Room Ambient Temperature Monitoring
Wall mount temperature sensors provide
highly accurate measurement of room air
temperature in industrial workspaces and
commercial, industrial or apartment
buildings. The RTD sensor is housed in an
attractive enclosure that offers very stable
readings. These units submit input to
readouts and HVAC controls, and when
combined with a data logging device, can
provide a history for validation of room
ambient temperatures. Wall mount
temperature sensors are ideal for clean
rooms, close tolerance machining centers, calibration/metrology
laboratories and medical laboratories. The assembly field-mounts onto a
standard single-gang electrical conduit box.
Model WM1 sensor is a high accuracy, encapsulated, platinum,
100Ω @ 0˚ C, ±0.3˚ C, 0.00385 Ω/Ω/˚C coefficient RTD. Increased
sensor accuracy of ±0.1˚ C is also offered.
Progressive Description Example:
Model WM2 sensor with Model HPT
fixed range transmitter offers a 4-20mA
output with an accuracy of 0.1% of
SPAN typical, supply voltage 8-38 VDC,
polarity protected. Typical room ambient
temperature range is preset at 40˚ F to
90˚ F (4.4˚ C to 32.2˚ C).
Model WM3 sensor with Model PTH-400
programmable transmitter features a
state-of-the-art microprocessor design
that enables full configuration with a
Windows®-based PC and user-friendly
software. This model offers a 4-20mA current loop output with an
accuracy of 0.1˚ C typical. Typical room ambient temperature range is
preset at 40˚ F to 90˚ F (4.4˚ C to 32.2˚ C). Programmable features allow
the operator to change upon demand the upper and lower room
temperature points (zero/span).
WM3-43W3 (0/100F)
/
Model
RTD Probe
WM1
Probe only with
terminal strip
43 - 100Ω RTD at 0˚ C
WM2
With HPT fixed range
transmitter
WM3
With PTH-400
programmable
transmitter
86 - 200Ω RTD at 0˚ C
(Available on WM1
and WM3)
215 - 500Ω RTD at
0˚ C (Available on
WM1 only)
Sensor
Accuracy
W - Class B
(±0.3˚ C @ 0˚ C)
Transmitter
Range
Configuration
3 - 3-wire
Required for
types WM2
and WM3 only
V - 1/3 Class B
(±0.1˚ C @ 0˚ C.
Available for RTD
Probe 43 only)
Note:Minimum
span of HPT is
36˚ F (20˚ C)
Unit
˚F
˚C
(Required for types
WM2 and WM3)
430 - 1000Ω RTD
at 0˚ C (Available on
WM1 only)
™
For more information call: 1 - 8 0 0 - 2 2 3 - 2 3 8 9 • e-mail: c o n a x b u f @ c o n a x b u f fa l o . c o m • visit our website: w w w. c o n a x b u f fa l o . c o m
R E L AT E D P R O D U C T S A VA I L A B L E F R O M C O N A X B U F FA L O T E C H N O L O G I E S
Conax Buffalo is leading the way in the
Pressure and Vacuum Sealing Assemblies
development of engineered solutions
Conax manufactures a complete line of pressure/vacuum
compression sealing glands for wires and probes. A wide range
of standard products and virtually unlimited customized designs
are available, all featuring the Conax-developed "soft sealant"
technology. This technology offers unequalled adaptability to meet
the application needs of any industry. Request Catalog 5001A.
for today’s challenging applications in
temperature sensing and pressure/
vacuum sealing. Our technical design
and development staff has set
engineering standards in these areas
Temperature Transmitters
for more than 40 years. Today we
Conax Buffalo offers a variety of types of temperature transmitters
including fixed range, isolated or non-isolated transmitters in hockey
puck or DIN-rail styles; and programmable models in hockey puck,
DIN-rail or Hart Smart protocol models. Request Bulletin #C505-19.
manufacture more than 100,000
standard assemblies in our state-ofthe-art production facilities. In most
cases, our wide variety of off-theshelf designs can be combined to
meet the needs of your application.
For those truly unique requirements,
our engineers are ready to put their
years of experience to work to
design the perfect solution for your
application. Many of our custom
designs have now become industry
standards. For further information on
any of our industrial products or to
Temperature Sensor Assemblies
Conax temperature sensor assemblies feature a wide
variety of termination heads, sheath materials,
mounting styles, and accessories to meet the requirements of industrial
thermocouple and RTD temperature sensing applications. Every Conax sensor
delivers rugged, reliable service and precision performance. Request Bulletin #6002.
High Temperature
Thermocouple Assemblies
Conax Buffalo High Temperature Thermocouple Assemblies
are specially designed for durability and reliability in high
temperature applications to 4200º F (2315º C). Such applications generally
involve oxidizing, reducing, inert gas or contamination atmospheres that
challenge the life of the thermocouple. Request Bulletin #6008.
request the literature listed below, call
Thermowells
800-223-2389, visit the Literature
Proper selection of thermowells for the
protection of your sensor assemblies in harsh
environments can be a challenge in itself. Conax’s
detailed thermowell catalog will guide you through
the appropriate sizing and selection of our extensive
range of thermowells. Request Catalog W-898-D.
Selector section of our website at
www.conaxbuffalo.com, or e-mail
us at [email protected].
Call Conax Buffalo today at 1-800-223-2389!
™
2300 Walden Avenue
Buffalo, New York 14225
FAX: 716-684-7433 • Phone: 716-684-4500
1-800-223-2389
e-mail:[email protected]
European Office
PO Box 91
BOGNOR REGIS PO22 7JB, England
FAX: +44 1243 773050 • Phone: +44 1243 784060
e-mail:[email protected]
w w w. c o n a x b u f falo.com • www. p a r t s d r aw e r. c o m
Conax Buffalo Technologies is a registered trademark of Conax Buffalo Technologies.
Windows is a registered trademark of Microsoft Corporation.• ISO certification refers to Buffalo location.
©2002 Conax Buffalo Technologies
Bulletin 6020
6/02 5M