B420 Ethernet Communication Module

Intrusion Alarm Systems | B420 Ethernet Communication Module
B420 Ethernet Communication Module
www.boschsecurity.com
The Conettix B420 Ethernet Communication Module is
a communication device that manages secure, two-way
IP communications over Ethernet networks for
compatible control panels.
Typical applications include:
• Reporting and path supervision to a Conettix
Communications Receiver/Gateway.
• Remote administration and control with Remote
Programming Software.
• Connecting to building automation and integration
applications.
u
Full 2-way IP alarm/event reporting with support for
panel programming and control
u
10/100Base-T Ethernet with DHCP or static IP
support
u
128-bit AES Encrypted Line Security (NIST-FIPS
197)
u
Plug and Play installation on most DHCP networks
and available UPnP router configuration
u
Advanced configuration available by browser, either
remotely, or by Auto-IP direct connection
System overview
The system overview diagram shows several available
configuration options of a Conettix IP system. Items 1
through 3 are installed at the protected premises,
while the remaining system components can be
connected locally or remotely.
1
2
The B420 is built for a wide variety of secure
commercial and industrial applications. Flexible endto-end path supervision, 128 bit AES encryption and
anti-substitution features make B420 desirable for
high security and fire monitoring applications. It is
capable as a stand-alone path or it can be used in
conjunction with another communication technology.
For Fire Monitoring applications, the B420 meets
UL864 and NFPA72 standards for Single
Communication Technology with approved Bosch
control panels.
4
13
3
12
5
8
10
6
9
11
7
2 | B420 Ethernet Communication Module
1.
Compatible Bosch Control Panel
LED
Function
2.
Data Bus Connection between the control panel and the B420
RX:
3.
B420 Ethernet Communication Module
Indicates when an inbound packet is received on the
bus.
4.
Ethernet Network Connection between B420 and the Ethernet
network
TX:
Indicates when an outbound packet is transmitted on
the bus.
5.
Ethernet network, Local Area Network (LAN), Metropolitan Area
Network (MAN), Wide Area Network (WAN), or Internet
Heart
[icon]:
Indicates the system health of the B420 and its
connection to the panel.
6.
Ethernet Network Connection to the D6100i Communications
Receiver
7.
Conettix D6100i Communications Receiver/Gateway
8.
Ethernet Network Connection to the D6680/ITS-D6682 (ITSD6682 shown) Ethernet Network Adapter
9.
Conettix D6680/ITS-D6682 (ITSD6682 shown) Ethernet
Network Adapter
10.
Connection from ITS-D6682 to the COM4 Port on the D6600
Communications Receiver/Gateway
11.
Conettix D6600 Communications Receiver/Gateway
12.
Ethernet network connection between the host computer
Ethernet network interface card (NIC) and the Ethernet network
13.
Host PC running RPS, Automation, or the D6200 Programming
Administrative Software
Certifications and approvals
US
UL 365-Police Station
Connected Burglar Alarm
Units and Systems
GV4 Series, GV3 Series
UL 864-Control Units and
Accessories for Fire Alarm
Systems (including NFPA 72)
GV4 Series, GV3 Series, FPD-7024
UL 1610-Central Station
Burglar Alarm Units
GV4 Series, GV3 Series
FCC Part 15 Class A
GV4 Series, GV3 Series, FPD-7024
CSFM-California Office of
The State Fire Marshal
GV4 Series, GV3 Series, FPD-7024
GV4 Series, GV3 Series, FPD-7024
Functions
NIST FIPS-197 AES
Certification (IP
Communications)
Conettix IP Communication
The B420 uses Conettix IP protocol which supports:
Region
Certification
USA
CSFM
•
•
•
•
•
Full event code reporting and administration
Flexible supervision intervals
Resistance to Denial of Service attacks
128-bit AES encryption
Anti-replay and anti-substitution
Rotary Switch Addressing
Use the rotary address switch to easily assign a bus
address or setup for web configuration.
Installation/configuration notes
Compatibility Information
Control Panels
LEDs
Three LEDs provide status and troubleshooting
information about the Interface Module and its
connection.
GV4 Series
GV3 Series
IP Network Support
Supports DHCP, UPnP, and Auto IP addressing by
default, but can also be configured for Static IP
networks.
Easy Configuration
For most DHCP network installations, the default
settings of the B420 allow installation with no PC
required. Universal Plug & Play (UPnP) supports
automatic UDP port mapping for remotely
programming a B420 behind a firewall, as well as http
port mapping for web configurations. For customized
settings, the B420 supports a full web configuration
menu remotely, or by a direct Ethernet connection.
The GV4 Series Control Panels can configure the B420
through the keypad, or through RPS.
7300-1615:0241 for use with D6600
receiver
GV2 Series (version 7.06 or higher)
D9412 (version 7.0 or higher)
D7412 (version 7.0 or higher)
D7212 (version 7.0 or higher)
DS7400XiV4 (version 4.10 or higher)
DS7220 (version 2.10 or higher)
DS7240 (version 2.10 or higher)
FPD-7024 (version 2.10 or higher)
Applications
RPS/RPS Lite:
Supported on all compatible control panels.
PC9000:
Supported on D9412, D7412, D7212, G
Series, GV2 Series and GV3 Series (version
8.05 only).
IS2000:
Supported on all G and GV Series control panels.
3 | B420 Ethernet Communication Module
Mounting Considerations
Mount the B420 inside the control panel enclosure
using the standard three-hole pattern.
Wiring Considerations
The B420 connects to a control panel using a data bus
connection and to an Ethernet network using a
standard Category 5 or above Ethernet cable with an
RJ45 plug.
Parts included
Quantit
y
Component
1
B420 Ethernet Communication Module
1
Hardware pack
1
Interconnect cable wiring
1
Quick Start Guide (hardcopy)
1
Literature (mini-CD)
Technical specifications
Environmental Considerations
Relative Humidity
Up to 93% non-condensing
Temperature Operating
0° to +49°C (+32° to +120°F)
Properties
Board Dimensions:
2.49 in x 3.9 in x 0.6 in
(63.3 mm x 101 mm x 15 mm)
Power Requirements
Current:
10Base-T Ethernet: 90 mA maximum
100Base-T Ethernet: 100 mA maximum
Voltage:
12 VDC nominal
Connectors
Control panel:
Option, SDI or SDI2 bus terminals- interconnect
LAN/WAN:
RJ-45 modular port (Ethernet)
Cabeling
Ethernet Cable:
Category 5 or better unshielded twisted pair
Ethernet Cable
Length:
328 ft (100 m) max length
Wiring
Data Bus Wire
Gauge:
18 AWG or 22 AWG
Data Bus Wire
Length:
500 ft (152 m) using 22 AWG wire
Browser Support
Internet Explorer 6+, Mozilla Firefox 3+
Ordering information
B420 Ethernet Communication Module
Creates two-way communications over Ethernet
networks for compatible control panels.
Order number B420
4 | B420 Ethernet Communication Module
Represented by:
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
[email protected]
www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5617 BA Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
[email protected]
www.boschsecurity.com
© Bosch Security Systems 2013 | Data subject to change without notice
2536990859 | en, V6, 01. Oct 2013
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security
Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
[email protected]
www.boschsecurity.asia
China:
America Latina:
Bosch (Shanghai) Security Systems Ltd. Robert Bosch Ltda Security Systems Division
201 Building, No. 333 Fuquan Road
Via Anhanguera, Km 98
North IBP
CEP 13065-900
Changning District, Shanghai
Campinas, Sao Paulo, Brazil
200335 China
Phone: +55 19 2103 2860
Phone +86 21 22181111
Fax: +55 19 2103 2862
Fax: +86 21 22182398
[email protected]
www.boschsecurity.com.cn
www.boschsecurity.com