The Grundfos CM BYE-PAC range of packaged booster sets
with skid mounted cold water storage tank are designed for
pumping clean water. Typical applications include:
CM BYE-PAC with 50 gallon tank
• Boosting to pressurised hot and cold water systems in
domestic and commercial premises.
• Irrigation systems.
• Water transfer applications.
The CM BYE-PAC sets incorporate the Grundfos CM stainless
steel horizontal multistage end suction pumps. CM pumps
provide a compact, cost effective and reliable solution for
pressure boosting and transfer applications.
The CM BYE-PAC sets are available for single phase 240V and
three phase 415V operation with a 50 gallon or 100 gallon WRAS
approved storage tank with Type AB Air Gap. The weir is sized in
accordance with the Water Regulations.
The CM BYE-PAC is ready for installation to the system, requiring
only a mains water and electricity supply. All necessary isolating
and non return valves are included.
The pump is on/off controlled by the PM2 pump controller which
features dry running protection.
OPERATION
The Grundfos PM2 pressure manager is a compact pump
on/off controller, incorporating a pressure and flow sensor, and
non-return valve. The flow sensor prevents on/off cycling of the
pump while there is a flow demand, which helps prevent water
hammer. A pressure vessel is incorporated to make up for
small leaks on the system. The cut-in pressure setting is
selectable in 0.5 bar steps from 1.5 bar to 5 bar. The pump is
stopped when the pressure rises by 0.5 bar above the cut-in
pressure, and the flow demand has stopped.
The PM2 incorporates protection against dry running and
excessive starts. The red alarm indicator illuminates if the
pump has stopped due to a fault condition. The PM2 can be
set to be manually or automatically reset.
PERFORMANCE RANGE
FEATURES
• Compact pump unit with water storage tank
• Stainless steel pump
• Integral controls
•
•
•
•
Motor protection
Dry run protection
Low noise
WRAS Approved pumps
PUMP PERFORMANCE
CM
Range
Flow
(l/s)
-3
CM Models
-4
-5
CM 3
0.9
2.0 / 2.8
2.7 / 3.6
3.4 / 4.5
4.0 / 5.5
CM 5
1.4
2.1 / 2.8
3.0 / 3.7
3.8 / 4.6
4.5 / 5.5
-6
The table gives the pump duty pressure in Bar at the best
efficiency point, and closed valve pressure at zero flow. For
example a CM 3-5 gives 3.4 bar at 0.9 l/s and has a closed
valve pressure of 4.5 bar. For specific pump performance
details please refer to WebCaps at www.grundfos.co.uk.
CM BYE-PAC SIZING
CM
50 Gallon
100 Gallon
BYE-PAC
Bathrooms
Occupants
Bathrooms
Occupants
CM 3
1 to 2
up to 4
1 to 2
up to 7
CM 5
2 to 4
up to 4
3 to 4
up to 7
CM BYE-PAC PRODUCT CODES
BYE-PAC
PUMPED LIQUIDS
Potable water, rain water or other clean, thin, non-aggressive
liquids not containing solid particles or fibres.
BE >THINK > INNOVATE
240V 1ph 50Hz
415V 3ph 50Hz
Model
50 Gallon
100 Gallon
50 Gallon
100 Gallon
CM 3-3
97762774
97762778
97806427
97806441
CM 3-4
97762775
97762779
97806428
97806443
CM 3-5
97762776
97762780
97806429
97806444
CM 3-6
97762777
97762781
97806430
97806445
CM 5-3
97762782
97762786
97806446
97806450
CM 5-4
97762783
97762787
97806447
97806451
CM 5-5
97762784
97762788
97806448
97806452
CM 5-6
97762785
97762789
97806449
97806453
CM BYE-PAC BOOSTERS
INSTALLATION
TECHNICAL DATA: CM PUMPS
1. The CM BYE-PAC should be sited in a dry, well ventilated
but frost-free position where it will not be subjected to
extremes of temperature.
2. The unit should be installed on a solid surface to adequately
support its weight, and to help reduce noise/vibration.
3. The environment should be non-aggressive and the
atmosphere non-explosive.
4. Attention should be given to the possibility of water leakage
from the unit during commissioning or service activities, in
order to prevent possible damage to the surrounding area.
5. In accordance with the Water Regulations a minimum of 1m
of 15mm pipe should be used to connect the mains water
supply pipe to the BYE-PAC.
6. A pressure reducing valve can be included after the outlet to
regulate the discharge pressure, as the pump pressure can
rise up to the pumps closed valve pressure.
Mains voltage:
Anti vibration feet are available as an accessory if required,
see Accessories below.
ELECTRICAL DATA CM
It is not recommended to fit the CM in a loft or attic space.
PM2 CONTROLLER
The switch settings within the PM2 controller are factory set;
there is no need to change the settings. The standard factory
positions are show below. Switch positions 1, 2 & 3 determine
the cut-in pressure setting.
CUT-IN PRESSURE SETTINGS
CM BYE-PAC
Model
Cut-in
Pressure
CM BYE-PAC
Model
Cut-in
Pressure
CM 3-3
1.5 bar
CM 5-3
2.0 bar
CM 3-4
2.5 bar
CM 5-4
CM 3-5
3.0 bar
CM 5-5
CM 3-6
3.5 bar
CM 5-6
DIMENSIONS (mm)
CM BYE-PAC WITH 50 GALLON TANK
1 x 220-240V, 50 Hz
3 x 380-415V 50 Hz
Voltage tolerances:
-10%/+10%
Casing pressure:
10 bar max
Liquid temperature:
0°C to +40°C
Ambient air temperature: 0°C to +40°C
Sound pressure level:
54 dB(A) max
TECHNICAL DATA: PM2
Mains voltage:
Voltage tolerances:
Enclosure class:
Contact rating:
Pressure rating:
Liquid temperature:
1 x 220-240 V, 50 Hz
-10%/+10%
IP65
10 Amps
10 bar max
40°C max
240V 1ph 50Hz
Pump
Model
Full Load
Current (A)
Starting
Current (A)
Motor Input
Power (W)
CM 3-3
2.8
14.8
500
CM 3-4
2.8
14.8
500
CM 3-5
2.8
14.8
500
CM 3-6
4.0
15.6
670
CM 5-3
2.8
14.8
500
CM 5-4
4.0
15.6
670
CM 5-5
5.0
21.5
900
CM 5-6
8.0
27.2
1300
ELECTRICAL DATA CM
415V 3ph 50Hz
2.5 bar
Pump
Model
Full Load
Current (A)
Starting
Current (A)
Motor Input
Power (W)
3.5 bar
CM 3-3
1.2
5.9
460
4.0 bar
CM 3-4
1.2
5.9
460
CM 3-5
1.2
5.9
460
CM 3-6
1.8
10.4
650
CM 5-3
1.8
10.4
650
CM 5-4
2.2
12.7
850
CM 5-5
3.0
17.4
1200
CM 5-6
3.0
17.4
1200
CHI BYE-PAC REPLACEMENT
CM BYE-PAC WITH 100 GALLON TANK
CHI BYE-PAC
Model
CM BYE-PAC
Replacement
CHI BYE-PAC
Model
CM BYE-PAC
Replacement
CHI 2-30
CM 3-3
CHI 4-30
CM 5-3
CHI 2-40
CM 3-4
CHI 4-40
CM 5-4
CHI 2-50
CM 3-5
CHI 4-50
CM 5-5
CHI 2-60
CM 3-6
CHI 4-60
CM 5-5
Minimal maintenance of the CM BYE-PAC is required.
Periodically the pre-charge pressure of the 8 litre tank should
be checked.
ACCESSORIES
Anti vibration feet, 6 off required:
GBAV0100
Outlet connection BYE-PAC with CM3 & CM5: 1” BSPF
GB/BYE-PACMBOOSTER/DBS/0711: Rev 2.31
BE >THINK > INNOVATE