EMLock
R
Exit Check
R
SELECTRIC
R
TM
Spacesaver
HiTower
R
Sure Exit
R
TM
EntryCheck
RISER DIAGRAM
TO 120VAC POWER SOURCE
602RF POWER
SUPPLY
TO FIRE ALARM – CLOSED
CONTACT CONNECTION
5 COND
3 COND
3 COND
3 COND
3 COND
1512 / 1572 MAGNETIC LOCK
POWER TRANSFER LOOPS
(SUPPLIED WITH PSB560)
4 COND
BREAK
GLASS
491 BREAK
GLASS
SWITCH
3
1
2
4
5
7
8
9
*
0
#
6
925
KEYPAD
PSB560 REX EXIT BARS
NOTES: (1) ALL LOW VOLTAGE SIGNAL WIRING SHALL BE 20-GAUGE MINIMUM. THE MINIMUM INDUCTIVE LOAD (LOCK) POWER WIRE GAUGE SHALL BE DETERMINED PER THE SDC WIRE
GAUGE CHART. ALL WIRING (SINGLE OR MULTI-CONDUCTOR) SHALL BE COLOR CODED WITHOUT SPLICES. A MINIMUM OF TWO SPARE CONDUCTORS IS RECOMMENDED. (2) SPECIFY
VOLTAGE WHEN ORDERING PRODUCTS. VOLTAGE IS NOT SPECIFIED ON THIS WIRE DIAGRAM, BE SURE ALL PRODUCTS ARE VOLTAGE COMPATIBLE. (3) ALL WIRING MUST CONFORM TO
NATIONAL, STATE AND LOCAL CODES. (4) ALWAYS CONSULT WITH THE AUTHORITY HAVING JURISDICTION (AHJ) BEFORE INSTALLATION. (5) WHERE REQUIRED BY CODE, CONNECT
FAILSAFE SYSTEMS TO THE LOCAL FIRE LIFE SAFETY SYSTEM FOR EMERGENCY RELEASE.
Components
Qty
1
1
1
1
2
Description
Double Magnetic Lock
Power Supply
Break Glass Switch
Exterior Digital Keypad
Request to Exit (REX) Push Bar
Part Number
1512 EMLock
602RF
491
925
PSB560
Manufacturer
SDC
SDC
SDC
SDC
SDC
Method of Operation
Access/Egress: Entering a valid digital code releases the locking device momentarily for access. Pressing either exit bar releases the locking
device momentarily for egress. Entry and exit momentary unlock time is determined by digital keypad & PSB560 programming. Emergency
Release: All locks will release automatically (see note 5) upon activation of the fire life safety system OR if the 491 Break Glass Switch is activated.
© 2004 Security Door Controls Printed in U.S.A
PROJECT NAME:
DWG. NO.: 1-RS-Library-0013-R2
CONTACT:
LOCATION:
DISTRIBUTOR:
SO. NO.:
DATE: 10-2004
DWN BY: MD
SECURITY DOOR CONTROLS
3580 Willow Lane
Westlake Village CA 91361-4921
Tel. 805-494-0622 FAX: 805-494-8861
EMLock
R
Exit Check
SELECTRIC
R
R
TM
Spacesaver
HiTower
R
Sure Exit
TM
R
EntryCheck
POINT TO POINT WIRING DIAGRAM
TO 120VAC PRIMARY
VOLTAGE CONNECTION
WHT
SPDT
DRY CONTACT
NC
ORG
G W B
NO
C
REFER TO POWER
SUPPLY
INSTRUCTIONS FOR
12 OR 24V VOLTAGE
SELECTION
PROCEDURE
YEL
SN
BLK
491
BREAK
GLASS
SWITCH
RED
BREAK
GLASS
602 SERIES
POWER SUPPLY
+
-
C
+
-
925
KEYPAD
12VDC OR 24VDC
OUTPUT
925 ENTRY CHECK
J3
NO
COMMON
NC
J4
1
2
3
4
5
6
7
8
9
*
0
#
OUTPUT #3
1+
POWER
23 DISABLE/INHIBIT
4 COMMON
5 REQUEST TO ENTER
6 EARTH GROUND
LEFT DOOR
OUTPUT #4
NO
COMMON
NC
COMMON GROUND
RED
BLK
GRN
BLU
-
1
2
3
4
5
6
7
8
9
(REMOVE FACTORY
JUMPER ONLY
IF FIRE ALARM IS USED)
RIGHT DOOR
POWER +
POWER COM
NC
BRN
NO
WHT
COM
ORG
YEL
NC
NO
DPS
POWER +
POWER COM
BLU
NC
BRN
NO
WHT
COM
ORG
YEL
NC
NO
BAS PLUG IN
BAS PLUG IN
POWER TRANSFER LOOPS
(PROVIDED WITH REX BAR)
RED
BLK
GRN
CLOSED FIRE ALARM
CONTACT
J-BOX
BAS
PSB560 REX BARS
STANDBY BATTERY
CONNECTION
{
{
NO
COM
BAS
NC
NO
DPS
COM
NC
POWER
+
-
{
{
NO
COM
NC
POWER
J1
NO
COM
NC
+
-
J1
1512 / 1572 DOUBLE MAGNETIC LOCK
© 2004 Security Door Controls Printed in U.S.A
PAGE 1 OF 1
PROJECT NAME:
LOCATION.:
DIST.:
CONTACT:
DWG. NO.: 1-PP-Library-0013-R2
DATE: 03 / 2005
DRAWN BY: MD
SECURITY DOOR CONTROLS