2804 kB - Stavoklima

Nucleo 3000
Design Air Curtain
The superb design and technical considerations make the Nucleo range of units a
must for any entrance area. Its slim design
and use of materials such as stainless steel
or painted any RAL colour, ensures this
type of unit is a leader in its class. Being
competitive on cost and with various options for installation suspension systems,
what more could a Designer ask for.
The Nucleo units are very popular with
our customers when a luxurious and
modern approach is needed to couple
up with a high technological design.
The Nucleo unit can only be mounted in
the horizontal position above a door
opening but can facilitate different types
of door openings and widths.
405
x
1000 / 1500 / 2000 / 2470
715
26
Air curtains | www.stavoklima.eu
Nucleo 3000
Design Air Curtain
Technical data and recommended mounting height for different types of units.
Nucleo 3000
.. X
Nucleo 3000
.. 0
Nucleo 3000
.. 1
2,4 m
2,8 m
3,2 m
1
5,7 m/s
1
6,8 m/s
1,5
6,5 m/s
1,5
4,3 m/s
1,5
5,1 m/s
2
5,1 m/s
2
3,4 m/s
2
4,0 m/s
2,5
4,2 m/s
2,5
2,8 m/s
2,5
3,3 m/s
3
3,6 m/s
3m
2,3 m/s
3m
2,8 m/s
3,5 m
3,1 m/s
Finished Floor Level
Technical data
Nucleo
3000
10X W(E)
Nucleo
3000
100 W(E)
Nucleo
3000
101 W(E)
Nucleo
3000
15X W(E)
Nucleo
3000
150 W(E)
Nucleo
3000
151 W(E)
Nucleo
3000
20X W(E)
Nucleo
3000
200 W(E)
Nucleo
3000
201 W(E)
Nucleo
3000
25X W(E)
Nucleo
3000
250 W(E)
Nucleo
3000
251 W(E)
Airflow Water coil
[m3/h]
1800
2400
2900
2750
3500
4290
4080
4500
5740
5100
5500
7000
Airflow Electric coil
[m3/h]
1800
2400
2900
2750
3500
4500
4080
4500
6000
5100
5500
7000
heating capacity [kW]
17,9
21,3
23,8
30,1
35,1
39,7
44,5
47,3
55,1
56
58,7
68,3
water 80/60°C / ti=18°C water pressure drop [kPa]
Water coil
5,9
8,1
9,9
12,2
16,1
20,1
13,1
14,8
19,5
9,7
10,6
11,9
Water Flow [m3/h]
0,8
1
1,1
1,3
1,5
1,7
1,9
2,1
2,4
2,4
2,6
3
[DN]
20
20
20
20
20
20
20
20
20
20
20
20
Water Connection size
Electric coil **
Max. heating capacity
[kW]
10
12,5
12,5
15,0
15,0
17,5
17,5
17,5
25
17,5
25
27,5
mains voltage
[V]
400
400
400
400
400
400
400
400
400
400
400
400
Fan electrical data
power [W]
510
770
720
770
1020
1080
1280
1280
1440
1530
1530
1800
current [A]
2,3
3,4
4,2
3,4
4,5
6,3
5,6
5,6
8,4
5,6
6,8
10,5
voltage [V]
230
230
230
230
230
230
230
230
230
230
230
230
IP22
Control type
Ditronic (Plus)
Protection class
Sound level*
Weight
IP22
IP22
IP22
IP22
IP22
IP22
IP22
IP22
IP22
IP22
IP22
dB (A)
58
58
60
60
59
62
60
60
63
61
61
64
[kg]
68
69
69
86
86
88
124
126
128
152
152
158
* Acoustic pressure Lp(A) measurement taken at a distance of 3m from the unit source. ** Electric heating elements can be supplied in different ratings if required.
Suspension ”A1”
Suspension ”A2”
Suspension ”B”
Suspension ”C”
125
220
400
15/M
10
max
.1"
410
405
457/
457
707/
957/
X (m
1192
in.2
457/
707/
1000
/150
0/20
5
/123
5
Z1 -
/119
2
m)
1192
457
/957
/119
Z1 Z1 -
2
0/15
380
00/2
000
/247
0
1000
/150
500
/750
/100
0/12
35
380
Z8
410
70
140
600
00/2
470
500/
750/
5
/123
Z7
X+X
Z1 -
'+40
5
Z8
Z1 -
/150
X+40
1000
X
X
1000
0/20
Z7
Z8
/707
100
X'
200
Z1 -
/957
00m
957/
X+40
500/
750/
470
1000
00/2
/707
Suspension ”D”
160
4x
120
1000
0/20
00/2
470
/150
500/
5
750/
1000
/123
5
380
0/20
00/2
470
500/
Z8
X
X+40
750/
5
1000
/123
5
X+4
05
Accessories:
Electric (see page 50)
Mechanical (see page 52)

Ditronic - LCD display controller

DKM - mechanical door contact

Econ - controller

2 or 3 way valves - thermostatic or electrothermic valves (see pages 58)

DKMG - magnetic door contact

Suspension - under ceiling and wall mounted

Room sensor

Flexible Connection hoses

TP - room thermostat

Spare filters - EU2
Air curtains | www.stavoklima.eu
27