MS4800-SB1 Quick Fix Blanking Safety Light Curtains Operation

.....
MS4800S-SB1
Quick Fixed Blanking Models
Addendum to MS4800 Instruction Manual
OMRON Scientific Technologies Inc.
© STI 1208 PN 99804−0030 Rev.A
Cat. No. F288I-E-01
.....
Introduction
The purpose of this addendum is to outline the functionality of a new Quick Blanking feature on the
MS4800S. This version will be referred to as the MS4800S-SB1, it offers customers a quick and easy
method of remotely programming fixed blanking. This feature allows for quick set-up in metal
stamping bending applications.
Difference between MS4800S and MS4800S-SB1
• Individual Beam Indicators (IBIs) behavior within the fixed blanked areas has been modified. The
blanked area will now illuminate when the fixed blanked object is in place.
• Program Dip Switch in the receiver does not function on the MS4800S-SB1.
Programming
Warning! Use of Fixed Blanking and Floating Blanking will make the MS4800 system less
sensitive to objects in the detection zone. Improper use of these features can result in severe injury to
personnel. Fixed Blanking and Floating Blanking may require a hard barrier guard. Fixed
Blanking and Floating Blanking may require an increase in the safety distance.
Fixed Blanking Programming Steps:
• Activate Fixed Blanking
Step
Description
LED Indicator Behavior
1
Enable Fixed Blanking via dip switches.
Yellow indicator flashing.
2
Power cycle (or insert key and turn key-switch #2 to the
Amber LED on.
START/RESET position and then release the key-switch (on-off)
• Program Fixed Blanking
Step
Description
LED Indicator Behavior
1
Insert the object in the detection zone.
Red LED on and corresponding IBIs are on.
2
Insert key into key-switch #1 and turn the key to the PROGRAM
- ENABLE (on) position, and hold through Step 5.
Red LED on and corresponding IBIs are on.
3
Turn key-switch #2 to the PROGRAM position and then release
the key-switch (on-off) to enter the programming mode.
Red and Amber LED’s flashing at a 3Hz rate,
corresponding IBIs are flashing at a 3Hz rate.
4
User has 10 minute to position the object, if necessary, and
complete the next step.
No change.
5
Turn key-switch #2 to the PROGRAM position and then release
the key-switch (on-off) to complete the programming process
and enter the interlock mode.
Yellow LED on; Red and Amber LEDs continue flashing at
a 3Hz rate, corresponding IBIs remain on.
6
Set key-switch #1 to the PROGRAM - DISABLE (off) position
and then remove key.
Yellow LED on; Red and Amber LEDs continue flashing at
a 3Hz rate, corresponding IBIs remain on.
7
Power cycle (or turn key-switch #2 to the START/RESET
position and then release the key-switch (on-off).
Amber LED on, green LED on, corresponding IBIs remain
on.
OMRON Scientific Technologies Inc.
1
© OMRON STI 0715 PN99804-0010 Rev. R
System State
OSSD Outputs
Reset
Stop Mode
Run Mode
Program
Mode
Interlock
Mode
Run Mode
ON
ON
OFF
Actuated
Released
Released
Enabled
Programming
Sequence
Program
Disabled
Disabled
Actuated
Actuated
Released
Released
t1
t2
t2
7LPHEHWZHHQ3URJUDPPLQJ W
W!VHF
9DOLG$FWLYDWLRQ7LPH W
PVWVHF
3URJUDPPLQJ7LPHRXW W
PVWPLQ
5HVWDUW7LPLQJ W
PVW
Released
t2
t2
t4
t4
Figure 1 Remote Programming Timing Diagram
OMRON Scientific Technologies Inc.
2
© OMRON STI 0715 PN99804-0010 Rev. R
.....
Connections
There are two connection options for using this feature:
1. User supplied key switch
The user selects the switch type and mounting location. Consumer must use key switch under supervisor
control. See drawing below.
Power Supply
Earth
Ground +24VDC
0 VDC
MS4800-SB1 Receiver
SUPPRESSOR
Green
Earth
6
Black
ED 1
OSSD 1
SUPPRESSOR
6
OSSD 2 White
ED 2
4
Red
2
1
EDM
ED 1 ED 2
3
To Machine Control Contacts
Pink Auxiliary
Output
Brown
ED 2
ED 1
+24VDC
EDM (External Device Monitoring) must be
used when force-guided control relays are
used as the Final Switching Devices.
Connect the red wire though NC contacts to
0 VDC
1
#1
Start
2
#2
SW1
5
8
SW2
3
MS4800 Transmitter
MTS
White
MTS/Test
7
4
5
Black
MTS
Return
Brown
Blue
Green
For the purpose of bench testing prior to installation,
the user may select EDM OFF(default factory setting).
In this case the EDM line, terminal 5 (red wire) must
be connected to the 0 VDC line.
Aux. Output PNP 100 mA. max. @ 24VDC,
connect to PLC (default)
User -supplied fuse
Start connections are shown with NO switch
(pulled to 0 VDC). Use a remote key-switch (onoff-on-off) to enable programming.
+24VDC
6
The EDM coils must be suppressed with the
components provided in the documentation Kit.
0 VDC
7
MTS requires a NC contact. If MTS is not used,
verify that the function is disabled.
8
Earth
SW1: program disable = Open
program enable = closed
SW2: contact #1 open
Run
contact #2 open
contact #1 closed
Start/Reset
contact #2 open
contact #1 open
Program
contact #2 closed
}
}
}
Figure 2 User Supplied Key Switch Option
OMRON Scientific Technologies Inc.
3
© OMRON STI 0715 PN99804-0010 Rev. R
2. RM-2AC-IP-SB1
This module provides power to the MS4800 system and converts the PNP safety solid-state outputs into
electromechanical relay outputs. It also includes a key switch for programming and reset. See drawing
below.
Brown
}
}
}
}
}
0 VDC
+24VDC
White
Blue
MTS/TEST
Black
CTL 1
CTL 2
CTL RET
Green
COM -
AUX 2
Green
Yellow
Red
AUX 1
NOTE:
1 = MTS requires a NC switch. If not used,
install a jumper wire between CTL RET
and MTS on TB3.
Program
2 SW1: contact #1 open
contact #2 closed disable
contact #1 closed
Program
contact #2 open
enable
SW2: contact #1 open
Run
contact #2 open
contact #1 closed
Start/Reset
contact #2 open
contact #1 open
Program
contact #2 closed
MS4800 Transmitter
EDM
START/
PROGRAM
COM +
White
Pink
OSSD 2
Black
OSSD 1
0 VDC
+24VDC
Blue
Brown
MS4800-SB1 Receiver
Earth
EDM on the MS4800 must be active.
CTL RET
MTS/TEST
CTL 2
EDM
0 VDC
+24VDC
TB2
START/
PROGRAM
CTL 1
SW2
AUX
PNP
NPN
SW1
EDM
SW3
F3SJ
NO YES
INT
EXT
!
RUN
TB3
#1
.N
#1
S TA R T
PRO G RA M
.
.C
.O
#2
K4
1
2
SW2
MTS
.N
N
K3
AC DC POWER MODULE
.O
The programing and reset
switch is located on the lid of
the RM-2AC-IP-SB1.
SWITCH #2
5
TB
!
K2
TB4
ON
The Program OFF-ON switch
is located on the lid of the
RM2-AC-IP-SB1.
O.S.S.D.
F1
(L) Line (N) Neut
PRO G
O FF
N.C.
N.O.1
N.O.2
K1
TB1
Protective
Earth
.
6
TB
.
C
AUX1
#2
SW1
AUX2
N
SWITCH #1
To PLC Control
Fuse
ED2
Line Voltage
100 - 240 VAC
SUPPRESSOR
ED1
To Machine Control
ED1 ED2
SUPPRESSOR
Control Voltage
Figure 3 RM-2AC-IP-SB1 Option
OMRON Scientific Technologies Inc.
4
© OMRON STI 0715 PN99804-0010 Rev. R
.....
Alternate Switch Configurations
Program & Start/Reset Switch Requirements
1. Start and Programming functions must be implemented using separate switches.
2. Implementation of the Start & Programming Switches must ensure that short between +24VDC and
0VDC are avoided.
3. Program Input requires a Normally Open Key-switch connected to +24VDC.
4. Start Input requires a Normally Open Key-switch or Push-button switch connected to ground, 0VDC.
581
352*5$0
',6$%/(
352*5$0
(1$%/(
6:,7&+
1& 12 &
1& 12 & 1&
12
.H\VZLWFK6SHFLILFDWLRQV
3RVLWLRQGHJUHH
:D\UHWXQ!FHQWHUVZLWFK
6ZLWFKVKRZQLQGHIDXOWFHQWHU
SRVLWLRQ
67$575(6(7
6:,7&+
29'&
67$57B,1387
9'&
.H\VZLWFK6SHFLILFDWLRQV
3RVLWLRQGHJUHH
:D\UHWXQ!FHQWHUVZLWFK
6ZLWFKVKRZQLQGHIDXOWFHQWHUSRVLWLRQ
1RWHSRVLWLRQVZLWFKXVHGWRSUHYHQW
VLJQDOVKRUWV
Figure 4 Two Key-Switch Configuration
352*5$0
',6$%/(
6:,7&+
29'&
(1$%/(
1&
12
&
67$575(6(7 6:,7&+
6:386+%87721'367
12
1&
67$57B,1387
.H\VZLWFK6SHFLILFDWLRQV
3RVLWLRQGHJUHH
.H\UHWDLQHGLQOHIWSRVLWLRQRQO\
6ZLWFKVKRZQLQGHIDXOWOHIWSRVLWLRQ
9'&
3XVK%XWWRQ6ZLWFK6SHFLILFDWLRQV
3RVLWLRQ121&'367
6ZLWFKVKRZQLQGHIDXOWQFSRVLWLRQ
1RWH6ZLWFKXVHGVKRXOGSUHYHQWVLJQDOVKRUWV
Figure 5 One Key-switch, One Push-button Configuration
OMRON Scientific Technologies Inc.
5
© OMRON STI 0715 PN99804-0010 Rev. R
352*5$0
',6$%/(
(1$%/(
&
1&
6:,7&+
67$575(6(7
12
1&
12
&
29'&
6:,7&+
6:386+%87721'367
67$57B,1387
9'&
.H\VZLWFK6SHFLILFDWLRQV
3RVLWLRQGHJUHH
.H\UHWDLQHGLQOHIWSRVLWLRQRQO\
6ZLWFKVKRZQLQGHIDXOWOHIWSRVLWLRQ
3XVK%XWWRQ6ZLWFK6SHFLILFDWLRQV
3RVLWLRQ121&'367
6ZLWFKVKRZQLQGHIDXOW1&SRVLWLRQ
1RWH6ZLWFKXVHGVKRXOGSUHYHQWVLJQDOVKRUWV
Figure 6 One Key-switch, One Push-button Configuration
MS4800S-SB1 Remote Programming Sequence using one key-switch as shown in Figure 5 and 6.
• Activate Fixed Blanking
Step
Description
LED Indicator Behavior
1
Enable Fixed Blanking via dip switches
Yellow indicator flashing
2
Power cycle (or press and release the Start/Reset button
(on-off)
Amber LED on.
• Program Fixed Blanking
Step
Description
LED Indicator Behavior
1
Enable Fixed Blanking via dip switches
Yellow indicator flashing
2
Power cycle (or press and release the Start/Reset button
(on-off)
Amber LED on.
3
Insert object in detection zone
Red & Amber LEDs on, corresponding IBIs are on.
4
Insert key into key-switch #1 and turn to the ProgramEnable position and then release the key-switch (on-off) to
enter the programming mode.
Red & Amber LED’s flashing at 3Hz rage,
corresponding IBIs are flashing at 3Hz rate.
5
User has 10 minutes to position the object, if necessary, and
complete the next step.
No change.
6
Insert key into key-switch #1 and turn to the ProgramEnable position and then release the key-switch (on-off) to
complete the programming process and enter the interlock
mode.
Yellow LED on; Red and Amber LEDs continue
flashing at a 3Hz rate, corresponding IBIs remain on.
7
Set key-switch#1 to the Program-Disable (off) position and
then remove the key.
Yellow LED on; Red and Amber LEDs continue
flashing at a 3Hz rate, corresponding IBIs remain on.
8
Power cycle (or press and release Start/Reset button (onoff)
Amber LED on, green LED on, corresponding IBIs
remain on.
OMRON Scientific Technologies Inc.
6
© OMRON STI 0715 PN99804-0010 Rev. R
OMRON AUTOMATION AND SAFETY • THE AMERICAS HEADQUARTERS • Chicago, IL USA • 847.843.7900 • 800.556.6766 • www.omron247.com
OMRON CANADA, INC. • HEAD OFFICE
Toronto, ON, Canada • 416.286.6465 • 866.986.6766 • www.omron247.com
OMRON ARGENTINA • SALES OFFICE
Cono Sur • 54.11.4783.5300
OMRON ELECTRONICS DE MEXICO • HEAD OFFICE
México DF • 52.55.59.01.43.00 • 01-800-226-6766 • [email protected]
OMRON CHILE • SALES OFFICE
Santiago • 56.9.9917.3920
OMRON ELECTRONICS DE MEXICO • SALES OFFICE
Apodaca, N.L. • 52.81.11.56.99.20 • 01-800-226-6766 • [email protected]
OTHER OMRON LATIN AMERICA SALES
54.11.4783.5300
OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICE
São Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br
OMRON EUROPE B.V. • Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. • +31 (0) 23 568 13 00 • www.industrial.omron.eu
Authorized Distributor:
Automation Control Systems
• Machine Automation Controllers (MAC) • Programmable Controllers (PLC)
• Operator interfaces (HMI) • Distributed I/O • Software
Drives & Motion Controls
• Servo & AC Drives • Motion Controllers & Encoders
Temperature & Process Controllers
• Single and Multi-loop Controllers
Sensors & Vision
• Proximity Sensors • Photoelectric Sensors • Fiber-Optic Sensors
• Amplified Photomicrosensors • Measurement Sensors
• Ultrasonic Sensors • Vision Sensors
Industrial Components
• RFID/Code Readers • Relays • Pushbuttons & Indicators
• Limit and Basic Switches • Timers • Counters • Metering Devices
• Power Supplies
Safety
• Laser Scanners • Safety Mats • Edges and Bumpers • Programmable Safety
Controllers • Light Curtains • Safety Relays • Safety Interlock Switches
F288I-E-01
12/08
Note: Specifications are subject to change.
Printed on recycled paper.
© 2016 Omron Electronics LLC
Printed in U.S.A.