PLEA2009 - 26th Conference on Passive and Low Energy Architecture, Quebec City, Canada, 22-24 June 2009 Displacement Ventilation and Passive Cooling Strategies PAUL CAREW1, BERNARD BEKKER1 1 PJCarew Consulting, Cape Town, South Africa ABSTRACT: The publication of the ASHRAE “System Performance Evaluation and Design Guidelines for Displacement Ventilation” [0] has contributed to the wider acceptance of displacement ventilation (DV) as a ventilation strategy, by offering clear guidelines from an established organisation. A significant advantage of DVis that it lowers the supply air quantities required for cooling compared to conventional mixing ventilation (MV) at the same supply air temperature.This opens up opportunities for the use of passive (non refrigeration-cycle based) cooling sources, which typically are limited in supply air temperature and based on 100% fresh air supply when compared to conventional refrigeration-cycle based sources. This paper quantifies the impacts of using DVin comparison to MV on the peak capacity, size and humidity levels associated with the following passive cooling sources: evaporative cooling, two stage evaporative cooling, thermal stores and air to ground heat exchangers. Ageneric office building in Johannesburg, South Africa, is used as a model. The paper illustratesthe extent to which the use of DVexpands the ability of passive cooling strategies to serve spaces previously considered as having too high a heat load (when calculated using MV system guidelines). The paper however also recognises that passivecooling strategies are unlikely to be widely implemented until design guidelines exist from organizations similar to ASHRAE. Keywords: passive design strategies, displacement ventilation INTRODUCTION Based on the authors’ experiences as consultants in the built environment, conventional Heating Ventilation and Air Conditioning (HVAC) engineers keep to using clear guidelines and calculations methods provided by established organisations. It is unlikely that unconventional strategies and systems will be incorporated in a project in the absence of such guidelines or methods, unless it is a showcase project with sufficient resources to adequately investigate alternatives. Displacement ventilation (DV) can be seen as an example of this. While popular in Scandinavia [0], the American Society for Heating, Refrigeration and Airconditioning Engineers (ASHRAE) only recently released “System Performance Evaluation and Design Guidelines for Displacement Ventilation” [0], which provides generic DV sizing and design guidelines. This publication differs from existing supplier-specific DV design guidelines in that itprovides a simple ten-step guide to design the DV system [0]. While the authors have not found literature that documents the worldwide growth in the number of installed DV systems, since the ASHRAE publication was released they have found HVAC engineers in general to be more receptive to the use of DV for conventional projects. The aim of this paper is to illustrate the impacts of using DV in comparison tomixing ventilation (MV) on the peak capacity, size and humidity levels associated with various passive cooling strategies, informed by the ASHRAE DV guidelines. The intention is NOT to provide clear design guidelines for these passive strategies, but merely to demonstrate the implications of these strategies through quantitative analysis. Through this analysis it is demonstrated that a number of passive cooling strategies, considered impractical for MV applications, can potentially be of benefit in building designs utilising DV.The comparison also highlights the risk of over-design when conventional MV guidelines are used to design cooling sources for DV applications. DISPLACEMENT VS. MIXED VENTILATION DV introduces air at low level and low velocity, and at high supply air temperature (Ts),typically around 18°C,when compared to conventional air conditioning systems which use MV. The air that is slightly cooler than the intended room temperature runs along the floor until it reaches a heat load (Fig. 1). The heat load induces a plume of warmer air that rises due to lower density. This induces stratification in room temperature with the occupied area of the room within comfort conditions and the space near the ceiling at higher temperature conditions. The air near the ceiling is continually exhausted to prevent a build up of warm air into the occupied zone. PLEA2009 - 26th 2 Conference onn Passive and Low w Energy Architecture, Quebec City, Canada, 22-24 Juune 2009 HOTTER ED UNOCCUPIE ZONE OCCUPIED D ZONE t occupants, low level ligghts and as the loads from the ment (kW), Ql as the load froom the overheaad lights equipm (kW) and a Qex as the envelope loadss with aoe, al, aex as the fractioons of the reespective loadds that occur in the occupiied zone(0.2955, 0.132 and 0.185 in [1]). The resultinng supply air flow f rate is calcculated as Vh = Qdis ΔThf ρC p …(3) withΔT Thf as the tempperature differeence between head h and feet annd set at 2°C. Figure 1: Dispplacement ventillation with indiccative temperatuure gradient relatiive to height When usiing MV the co ool air - typicaally around 12 to 14°C - is inttroduced at hiigher velocitiees and at a higgh level, inducinng room air to mix with it as shown in Fig. 2. There shouldd be a relatively y consistent temperature in thhe room. Exhaust air teemperatureW When using DV D the exhausst air temperaature (Te) is inn general highher than when using MV. Inn the case of MV M the Te shhould be close to the desiggn room tem mperature, whhile the ASHR RAE DV guidelines supply thhe following equations to calcculate Te for DV V systems: Te = Ts + Qt ρC pV where WELL-MIXE ED AIR Ts = Th − ΔThf − … (4) θ f Qt ρC p V … (5) from θf = 1 Vρ C p A Figure 2: Mixing M ventilatio on with indicaative temperatuure difference relaative to height sh hown as constannt Supply air flow ratee calculationssA fundamenttal difference inn the calculatio on of the suppply air flow raate between DV V and MV beco omes apparent in the ASHRA AE DV guidelinees. Assuming no n latent coolinng, with MV thhe rate is calculated according g to the entire room r load withh Qt V= ρC p (Th − Ts ) …(1) 3 where V is the supply airr rate (m /s), Qt is total rooom d (kgdryaiir/m3), Cp is thhe load (kW), ρ is the air density specific heaat capacity off air (kJ/kgdryaair), Th is rooom design tempeerature (°C) an nd Ts is supplyy air temperatuure (°C.) Howeverr with DV the flow rate is i based on thhe portion of the t total room m load that iss present in thhe occupied zonne using the folllowing breakddown [0]: Qdis = aoe Qoe + al Ql + aex Qex ( 1 αr + 1 α cf … (6) ) +1 whereT Tf is the flooor temperatuure (°C), Th is the temperrature at the heead or room deesign temperatuure (°C), θf is thhe dimensionlless temperatuure, αr is the radiative r heat transfer coefficient of the floorr (W/°C m2) annd αcfthe convecctive heat trannsfer coefficiennt of the flooor (W/°C m2), booth put forwardd as 5 by ASHRAE [0]. BACK KGROUND TO O MODEL For thee purpose of thhis paper a genneric 100m2 oppen plan office space in Johannnesburg, Souuth Africa, is used u as a model onto which different venntilation and passive coolingg strategies cann be applied. The T peak coolinng loads within this office spaace areshown inn Table 1. Table 1:Peak 1 cooling loads of the 100m2 space (7W/m2 for 2 people, 13W/m for equipment and 10 W/m W 2 for lightingg) Occuupants and equippment Qoe 2 kW k Overrhead lighting Ql 1 kW k Exteernal loads Qex 4 kW k Totaal loads Qt (ffor MV) 7 kW k Loadds with occupiedd zone Qdiss (for DV) 1.4462kW …(2) withQdis as the t load betweeen the head and a the feet off a sedentary occcupant being served s by the DV system, Qoe Thrree ventilationn systems will now be consiidered: a DV syystem, as weell as two MV M systems, one o that PLEA2009 - 26th 2 Conference onn Passive and Low w Energy Architecture, Quebec City, Canada, 22-24 Juune 2009 supplies air at the same high temperatture as the DV D system (MV Vht) and the otther at a mucch lower suppply temperature (MVlt). Using Eq. 1 to 3, thee required suppply air flow rate into the room m for each of thhese systems caan now be calcuulated, as show wn in Table 2. Table 2: Resulting air flow fro om MV (low andd high Ts) and DV D systems with % relative to lo ow (and high teemperature mixinng ventilation (M MVlt and MVht) Mode Ts (°C) Th/Te (°C) V (m3/s) % ofMV Vlt % ofMV Vht MV Vlt 14 26 0.59 9 100% 37% % MVht 22 26 1.61 273% 100% DV 22 26/31 0.74 125% 46% From Tabble 2 it is clearr that the air flow rate requireed for DVislesss than half th hat required for MVht, eveen though both ventilation sy ystems have the same suppply temperature. The airflow rates for DV V and MVlt are a similar, but MV M lttypically require a mucch larger coolinng source than DV D in order to obtain the low w Ts. u the Evvaporative coooling Evaporaative cooling uses changee of phase of o the water contained in an air stream m/volume to cool down the aiir. Energy from m the air and noon-evaporatingg water is usedd to supply thhe latent energyy required. This results in a teemperature droop in the air andd residual watter, and an inccrease in absolute and relative humidity of the t air. The minimum temperature achievable through evaporrative coolingg is expresseed by the wet w bulb temperrature (Twb) off the air. In reallity the air cann only be cooledd a part of the way between the dry bulb (Tdb) and wet bulb b temperatture and thiss is known as the evaporrative cooling efficiency e (hevaap), assumed ass 80%. Ts = Tdb − η evap (Tdb d − Twb ) Figuree 4 provides thhe probability of Ts throughhout the year baased on eq. 7 and a on annual climatic c data [44]. % The compparison in Tab ble 2 highlightss the efficienciies introduced by b using DV in nstead of MV.The rest of thhis paper will explore e how th hese efficienciies impact on a selection off passive coo oling strategies.A number of passive desiggn strategies arre potentially applicable a in thhe Johannesburgg climate baseed on Fig. 3, which w indicatess a wide diurnaal temperaturee range and low wet buulb temperature for much of th he year.This ciity was therefoore chosen as thee context for th he simulations presented in thhis paper. Typical office hourss were assumedd. dry bulb temp …(7) 2-stage e evaporative cooling single stag ge evaporativ ve cooling Ts Figure 4: Cumulative distributed freqquency of Ts forr 2-stage evaporaative cooling (1 ( st line) and evaporative e coooling (2nd line)[0,0] Altthough evaporrative cooling might be clim matically suitablle, the comfoort expectationns and room loading represeent the actual limitations l to thhis strategy. As A shown in Fig. 5, evaporativee cooling resullts in an increase in the absoluute and relativve humidity of the space, which impactts on comfort. w bulb temp wet Figure 3:Dry and wet bulb temperatures for f Johannesburrg. [0,0] IMPACT OF O DISPLACEMENT VENTILATIO V ON ON PASSIV VE COOLING G STRATEGIES The applicaability of passsive cooling strategies is a function of climate, c comfo ort expectationns related to thhe activity in thhe space, interrnal loading of o the space annd equipment/deesign implicattions – often relating r back to cost. What thhis paper puts forward is thaat the method of introducing the t cooling into o the space also impacts on thhe suitability. The T impact is quite specific to each passivve cooling strattegies, and will w now be explored e for thhe following sttrategies: evap porative coolinng – single annd two stage, thermal storag ge based on night time air a temperaturess and air to ground heat exchaangers. Figure 5:Psychrometrric chartsshowinng(left) the evaaporative coolingg process with 1 as the outdoorr, 2 the supplyaand 3 the room air a conditions with w increasing absolute a humidity during the dayy, and (right) thhe 2-stage evapporative coolingg process indicatiing the sensibble(1a to 1b) as well as adiabatic a componnent (1b to 2) The increase in humidity in thhe space overr time is relative to the amoount of vapourr being addedd to the space. The amount of o vapour enterring a space is directly relatedd to the supply air flow. Therrefore the loweer the air flow, the t lower the abbsolute amounnt of vapour inttroduced PLEA2009 - 26th 2 Conference onn Passive and Low w Energy Architecture, Quebec City, Canada, 22-24 Juune 2009 into the spaace, slowing th he build up of vapour of thhe space duringg the day. Fig g. 8 indicatess a significanttly lower inflow w of humidity fo or DV compareed to MV. Figure 6: Fann driven evaporative cooling This meaans that the comfort c and cooling c capaciity (and therefoore also cost)) requirementss of a speciffic project mighht be met thrrough the use of evaporativve cooling utilissing DV, wherre it might havve failed utilisinng MV. In other words, using g evaporative cooling c with DV D rather than with w MV mean ns that a higheer room load caan be met (moree cooling for th he same humiddity increase), or alternatively a lower increaase in humidityy can be realiseed for the same room load. Two-stagge evaporative cooolingTwo-stagge evaporative cooling add ds a sensibble pre-coolinng component to t the cooling process, p whichh lowers the wet w bulb temperrature before applying dirrect evaporativve cooling, as shhown in Figs. 5 and 7: T1bdb = T1addb − η sens (T1addb − T1awb ) …(8) from which TS = T1bdb − η evap (T1bdb − T1bwb ) …(9) wherehsensis taken t to be 90% % and hevap 80% % [0] This sennsible pre-coo oling componeent is typicallly provided byy water that is i cooled thouugh evaporativve cooling, usinng residual waater from the evaporative e paart. Other strateggies can also bee used for sensible pre-coolinng, e.g. passing air through an n air-to-groundd heat exchangger before applying an evaporaative cooling coomponent. The resullt impacts in two t ways; air is i delivered att a lower temperrature to the sp pace and/or theere is an increaase in duration in i the year thaat evaporative cooling can be b used (Fig. 4) based on a maaximum Ts of 22 2 °C. This influuences the sizee of the room load that can be b served by thiis strategy and d the comfort conditions c of thhe occupants ass less humidity is being addedd to the space as indicated in Fig. F 9. Figure 7: Diagram indicating i 2-staage evaporativee cooling ment equipm Figure 8: Air flow ratees(V) and humiddity inflow (g) ovver a day for singgle(Evap) and 2-stage (2S) evvaporative cooliing for a space with w a peak totaal cooling load of 70W/m2 indiccated the differennce between DV V and MV. Diu urnal range and thermaal store Night time ventilaation and exposed thermal mass m is a relativvely well knownn passive coolinng strategy. It uses u low nightt time air temperratures to flushh the structure of the buildingg of heat built up u during the previous p day. The T same princciple can be useed in the introdduction of a reemote thermal store in the forrm of a packedd bed, as show wn in Fig 9. This bed is cooledd down at nightt by flushing with w outside air through mechaanical ventilatioon. During the day outside aiir is then introduuced through this bed,whichh cools the aiir before introduuction into thhe space. Thee packed bed can be construucted by incorpporating a variiety of thermall storage materials, including ceramic ballss and tiles, roocks and possibly phase changge materials. The climatic lim mitation of thee packed bed thermal store strategy is thhe number off days that thhe night temperrature drops to a usable tempperature. Basedd on a Ts of 22°C, C and a miniimum temperature differencee of 3°C betweeen the store material and the supply air, the PLEA2009 - 26th 2 Conference onn Passive and Low w Energy Architecture, Quebec City, Canada, 22-24 Juune 2009 duration thatt the strategy iss applicable is indicated in Fig F 10. It is cleear that the ambient a tempeerature betweeen 24h00 and 05h00 0 is lowerr than 19°C foor 98.5% of thhe year. Figure 9: Packed bed thermall store Figure 10: DVIEW D indicatees duration thaat the night tim me cooling strateggy is applicable in Johannesburgg. bed for DV can be rooughly estimatted at 27m3, coompared to a beed of 58m3 for MV M ht. Usiing DV ratheer than MV therefore t signnificantly reducees the required size of the paccked bed therm mal store, impactting on both material m costs and more impportantly the spaace that the sttore takes up. This last impaact is, in the auuthors’ experiennce, the comm mon factor thaat makes the strrategy unfeasibble, due to thee high cost off making the spaace available. An additionall benefit derivved from the low wer air flow raate is the reducction in fan poower and therefoore energy consumption. Airr to ground heat h exchangeersAir to grouund heat exchanngers consist of o two distincttly different strategies. The firrst one, seasonnal ground souurce cooling (F Fig. 12), utilisess thedifferencee between thee ambient tem mperature and thhe ground tem mperature at deepths typicallyy greater than 3m.Fig. 14indiccates how the amplitude of seasonal variation in the soil temperature decreases, d and shifts in phase, as the depth increases.The second strateggy, daily thermaal storage (Figg. 13), uses thee lower night time air temperrature in a way w similar too the thermal storage strateggy described in the previoous section, with w the storagee medium beiing the groundd immediatelyy around the pipping. Compared to seasonal ground g source cooling, the pipping for daily thermal t storagee can be locateed nearer to the surface, and the piping runns are typicallly closer togetheer. The feasiibility of the sttrategy is furthher influenced by b the cost and size of packeed bed, which is a function of the storage capacity off the thermall material, thhe efficiency of o the heat transfer t betweeen the storagge medium and the air, and thee air flow rate through the beed. Hollmuller et e al. [0] notees that ideallyy a packed beed should causee a 180° phasee shift in the daily temperatuure profile, as shhown in Fig 11 1. For such a 180° 1 phase shift, they suggestt a packed beed volume of roughly1m3 for f every 100m3/h air flow raate. They furthher note that thhe amplitude change (transm mission) of thhe phase-shifteed output is rellated to the th hermal storage material that is used: Figure 12: Seasonal grround source coooling Figure 11: Thhe input and outp tput temperaturees of a packed bed b thermal store over time, illustrating the effecct of a 180 degrree shift in phase. Based on [0]. Figure 13: Daily grounnd source coolingg. for a cost-efffective materiaal like gravel the t transmissioon of the input amplitude a is arround 50%. Ussing the volum meairflow relatiionship, the sizze of a 180° phhase shift packeed The climatic appplicability of thhe daily groundd source coolingg strategy is similar to tthat describedd in the PLEA2009 - 26th 2 Conference onn Passive and Low w Energy Architecture, Quebec City, Canada, 22-24 Juune 2009 previous seection on thermal stores. The climattic applicability of the season nal ground soource cooling is demonstratedd in Figs. 14 an nd 15.The perccentage of office hours that this t strategy is applicable in i Johannesbuurg depends on a variety of factors, incluuding the deptth, a the air floow diameter andd length of thee exchanger, and rate. Fig. 15 illustrates how w the percentaage applicabiliity of this strategy can be up u to 100% at a a Ts of 22°C, C depending on o the length of o the exchangger, in this caase shown for ann air velocity of 5m/s and a deepth of 3m. Evaaporative coolling – significcantly less hum midity is being introduced i intoo the space duee to the lower air a flow. 2-sstage evaporaative cooling–– intrinsically 2-stage evaporrative coolingg introduces less humiditty than convenntional evaporrative coolingg due to the sensible coolingg component. This advantagge is further am mplified by DV V in the lower supply s air flow w required com mpared to MV making m the strattegy applicablee to more projects due to com mfort levels. Theermal storagee – the storage volume is reduced, r with thhe main impacct being the reeduction in thee cost of providding the space for f the store. Airr to ground heeat exchangerss – the pipe length l is reduceed dramaticallyy. Figure 14: Annual A air tem mperature and expected grounnd temperature at a 3m, based on [0] [ Figure 15: Peercentage of offfice hours (6h too 18h) that Tout of the exchangerr is below maxim mum Ts of the loaad, for air velocity of 5 m/s, pipe diameter of 0.38 8m, and depth off 3m. Based on [0] [ Using thee methodology y described by Mihalakakou et al. [0] to esttimate the leng gth of exchanger required for f the simulateed Johannesb burg office, with w the sam me assumptions as in Fig. 15,, results in thee following: DV D mpared to MV Vht requires rouughly 80m off pipes, com requiring rouughly 170m. The abovve estimation illustrates thatt, as DV loweers the volume air a flow rate reequired, it signiificantly reducces the pipe lenngths required d and thereforre increases thhe technical annd financial feeasibility of thhe strategy. An A additional beenefit is a relatiive reduction in i fan power annd therefore eneergy consumptiion. CONCLUSIIONS DV significaantly lowers th he required suppply air flow to serve a room m heat load, when w compareed to MV at thhe same Ts. Thhis reduction im mpacts the feaasibility of usinng passive cooliing strategies in n projects in a various ways: The publication of the ASH HRAE Guideliines has assisteed in determinning with connfidence the fllow rate requireed for DV:siignificantly loower than previously estimaated using MV V calculations.. However, thhe sizing and caalculations of the t various passsive coolingsttrategies (with exception e of evaporative e annd 2 stage evaaporative coolingg) still dependds on non-stanndardised methhods that would typically noot be consideered by convventional HVAC C engineers. Establishing E g guidelines for passive coolingg, which are enndorsed by orgganisations thatt HVAC engineeers refer to inn confidencee.g. ASHRAE E, would assist greatly with gaining g furtherr penetration of these strateggies beyond envvironmentally extreme projeccts. ERENCES REFE 1. Chen, Q. and Glicksman, L. (20003) System Perfformance Evaluattion and Deesign Guidelinnes for Dispplacement Ventilaation. ASHRAE 2. Svvensson, A.G.L L. (1989). Nordic N experiennces of displacement ventilatioon systems. ASH HRAE Trans. 95((2). 3. Grapph produced usinng DView Versioon 1.09 developped by the Nationaal Renewable Energy Labboratory and Mistaya Engineering Inc. using IWEC weather file 4. Inteernational Weatther for Energyy Calculations (IWEC) weatherr data file from sourced http://w www.eere.energyy.gov/buildings/eenergyplus/cfm//weather_ data3.cfm, last visited on 22nd May 20008 5. IWA AC Two stage evvaporative cooliing units producct manual from PROTEK P CC, Box B 1943, Halfw way House 16885, South Africa 6. Holllmuller et al.(2006) - A new ventilation andd thermal storagee technique forrpassive coolingg of buildings: thermal phase-sshifting, PLEA, Geneva, G 6-8 Sepptember 2006 7. Kusuuda, I. and Acheenbach, P. (19655), Earth temperature and thermall diffusivity at seelected stations in i USA, Nationaal Bureau of Stanndards, Building Research Div., Washington W D.C C. 8. Mihalakakou, G. et al, Parametric prediction of thhe buried pipes cooling c potentiall for passive coooling applicatioons, Solar Energyy
© Copyright 2026 Paperzz