Envelope Assessment Jaffrey Grade School Prepared for Design Day Mechanicals May 2015 Table of Contents Introduction 2 Historic Energy Usage 3-4 Envelope Analysis Summary 5-6 Summary of Recommendations 7 Construction Eras and Orientations 8 Floor Plan Schematics 9-10 Roof and Attic Performance Assessments 11-18 Wall Types 19-25 Doors and Air Leakage 26-27 Window Types 28-30 Blower Door Testing 31 Heating Systems 32-33 Introduction This envelope assessment report has four goals: 1. To describe the Jaffrey Elementary School’s (JGS) thermal envelope in term of each component’s existing effective performance and specific weaknesses. 2. To identify cost effective envelope improvement strategies which can reduce the total heating load in a meaningful way. 3. To present this and other pertinent information in a way that facilitates energy modeling by another team member. 4. To create a document which may be helpful to school personnel in gaining a better understanding of heat loss and the importance of an effective thermal envelope. The original JGS building was built in 1938. There have been at three major additions to the school. It is presumed that a gym and cafeteria was added at some point after 1938, followed by a classroom building designed in 1986 and a smaller classroom wing designed in 2003. Part of the bus port was enclosed for offices in 2004 and many windows were replaced at that time. This Envelope Assessment has attempted to describe existing components of the thermal envelope in terms of their effective performance in conserving heat generated by the existing oil fired boiler. This is considered the “demand side” of the building energy equation: the more effective the thermal envelope in conserving heat, the less energy (heating fuel) needed for supply. The primary goal of the assessment was to identify opportunities for cost effective improvements to the thermal envelope. The goal of this report is to present a summary of the existing conditions and a breakdown of the building’s thermal envelope for the rest of the energy audit team as well as the School’s facility managers and decision makers. Therefore, it has been written and organized with that goal in mind. The most cost effective time to make an energy efficient building is during the initial design and construction phase. It is hoped that this document will serve all parties, for the purposes of completing this energy audit, but also during the planning and implementation of future construction and capital improvements. 2 Historic Energy Usage Energy Heating Oil Propane - Cooking Electricity Totals EUI KBtu/ft2 Unit 17,100 468 221,280 Site Btu's 2,368,350,000 42,728,400 755,007,360 3,166,085,760 57,830 54.75 Floor Area KBtu/ft2 Source Btu's 2,723,602,500 49,137,660 1,920,710,400 4,693,450,560 81.16 KBtu/ft2 Cost $54,891 $922 $38,572 $94,385 $1.63 $ per ft2 The usage chart above represents the average heating oil and propane use based on calendar years 2013 and 2014. It also represents the annual average electric usage, based on 24 months, from July 2013 through June, 2014. The monthly data can be found on the next page. Electric and propane costs are based on actual costs, and fuel costs are based on the SAU’s contract prices with Rymes Oil through June 2015: $3.21 per gallon of oil. The cost of heating fuels has historically been very volatile, and increasingly so in this century. NHOEP’s “Current Heating Fuel Values” as of January 15, 2015 is $2.85 for oil and $3.19 for propane, and predicting future costs is always a gamble. For estimating predicted savings from improvements—this report uses the current contracted prices, but please note that too, involves the same gambling. Therefore, converting energy sources to their Btu content is the more reliable way to determine a building’s Energy Utilization Index (EUI). And it allows for a ‘snap shot’ comparison between a building’s overall energy usage and efficiency and other buildings of similar sizes and functional uses. There are NH school buildings with EUI’s ranging from 119 KBtu’s per square foot down to newly constructed, very high performing 29KBtu’s per square foot. At 54.75 KBtu per ft2 floor area, JGS is somewhere in between. This assessment addresses the specific opportunities available to the School to lower that EUI. From both a cost, and source energy use, perspective, heating fuel represents 58% of total energy delivered. This assessment focuses on the demand side aspect for heating costs in terms of heat lost to the outside through foundation, walls, windows, doors, and the ceiling or roof. The supply side—that is the heating and ventilation equipment and distribution, accounts for anywhere from 25—45% of the heating costs. So improvements to the envelope and mechanical systems should be analyzed as one whole building system. 3 Heating Oil Delivery Date 11/19/12 12/12/12 01/04/13 02/01/13 02/21/13 03/20/13 04/24/13 05/29/13 11/13/13 12/05/13 12/19/13 01/10/14 01/24/14 01/31/14 02/11/14 02/21/14 03/06/14 03/14/14 03/26/14 04/04/14 04/24/14 05/22/14 10/20/14 11/11/14 11/25/14 12/10/14 12/31/14 01/08/15 01/16/15 Gallons Totals 2013 Heating Oil and 2014 2010 1500 2000 2000 2000 1000.1 1000.1 1920.1 1,500.5 1,500.2 1,000.0 3,041.3 14,962.3 1,200.1 3,041.3 1,209.3 1,161.0 1,610.0 765.0 1,000.0 836.1 1,000.0 1,000.0 1,200.0 1,200.0 1,200.0 1,315.6 1,500.0 19,238.4 600.0 1,100.0 Propane—Cooking Gallons $ Cost LP 129 $211 Delivery 10/4/2012 1/3/2013 4/4/2013 7/3/2013 8/22/2013 11/21/2013 2/20/2014 5/15/2014 11/21/2014 101 115 111 22 152 $174 $206 $182 $45 $327 501 135 142 160 $934 $415 $259 $245 436 $920 Electric Period Ending July August September October November 2011-2012 kWh 10,480 13,920 18,960 19,600 20,080 Cost $2,191.54 $2,839.15 $3,417.80 $3,539.94 $3,613.60 2012-2013 kWh 9,760 15,280 20,080 24,960 18,160 Cost $1,754.24 $2,752.59 $3,289.72 $3,825.22 $3,092.03 December January February March April May June 18,400 17,600 18,720 21,120 19,360 20,160 16,080 $3,360.85 $3,231.32 $3,353.79 $3,646.99 $3,495.46 $3,593.20 $2,917.05 20,000 20,720 21,840 22,000 18,560 22,000 14,720 $3,325.05 $3,412.13 $3,580.80 $3,539.13 $3,274.55 $3,519.95 $2,576.35 214,480 $39,201 228,080 $37,942 Fuel usage was updated in January 2015, but electric use data ended in spring 2014, so the 24 months above represents the fiscal years 2011-2013. The EUI on the previous page was based on two year averages for oil, propane, and electric. 4 Envelope Analysis Summary Fundamental thermodynamics informs us that heat moves in three ways: conduction, convection, and radiation. These three transfer mechanisms typically occur at the same time, though one usually dominates in a given situation. A building’s thermal envelope consists of control layers to slow conduction, limit convection, and manage radiative transfer—while at the same time managing water and vapor. Simplistically, insulation slows conductive losses, air barriers slows or stops convective losses, and opaque surfaces eliminate radiative losses (and gains). Since heat moves to cold and warm air rises, conductive losses can occur in any direction, while convective losses are often a matter of air infiltration at lower levels and exfiltrating nearer the top of a building. A continuous air barrier (stopping air leakage) not only saves heating and cooling energy, but is also a very important method of vapor control. It is also important to understand that the effectiveness of insulating materials is largely dependent on its being in contact with an air barrier—most especially at the ceiling plane. The R-values listed by the manufacturer were calculated in a laboratory under optimal installation conditions. Unfortunately, this has not been understood over decades of installations, so ‘field’ performance is often 25-75% less effective than the manufacturer’s ratings. The rate of conductive heat loss depends on three factors: The conductivity of the materials in an assembly, the surface area of the material or assembly, and the temperature difference between inside and outside. Therefore, assessing the thermal performance of a building’s envelope includes, among other things, measuring the surface area of all surfaces, assessing the conductivity of each surface or assembly. The chart below offers a summary snapshot of RMS surfaces areas, categorized by construction era. A spreadsheet with room by room details accompanies this report as a pdf. Building Era Exterior Wall Surface Area Ft2 Area Ft2 Glazing Area Ft2 Ceiling SA Ft2 Door Volume SA Ft2 Ft3 UA Btu's UA Ratio 1938 9,765 4,639 1,533 4,876 32 117,104 3,488 26% Gym 8,907 4,330 624 4,552 137 133,953 3,613 27% 1986 17,213 6,658 1,027 9,191 108 297,039 5,238 39% 5,833 4,104 228 2,906 20 65,046 1,210 9% 3,413 21,525 297 613,142 2003 TOTALS 41,717 19,731 13,549 100% Conductivity is described as a material or assembly’s “u” value, which happens to be the inverse of the more familiar “R” value. The UA of a building is calculated by multiplying an assembly’s u-value by the surface area of that assembly. Breaking JGS down into the three construction era’s, or four ‘buildings’, we can see that the 1986 building represents both the largest floor area and the largest heating demand at 39%. Another interesting thing to note is that the original classroom and gym are similar in both exterior surface area and heating demand or load. 5 The chart to the right summarizes the building’s heat loss Component UA ratios based on envelope component. Estimated air leakage Air Leakage 5,107 in winter months accounts for almost 38% of the building’s Windows 2,131 heat loss. Walls are responsible for an estimated 18%, folRoof/Attic 1,918 lowed by windows at 16% and the ceiling plane at 14%. Walls 2,485 The foundation and slab less at 12%, and the doors just Floor/Slab 1,631 over 2%. These calculations are, again, largely based on 278 Doors estimated thermal conductivity performance and surface 13,549 TOTAL UA area. Even more complicating is the fact that the windows, doors, ceilings, all share responsibility for convective losses represented as “air leakage”. Ratio 37.7% 15.7% 14.2% 18.3% 12.0% 2.1% 100% This is especially relevant because even though there may be a lot of insulating material above a ceiling, thereby suggesting low conductivity, if warm air is allowed to rise through the insulation—then the performance of the entire ceiling is compromised. This dynamic is stated several times in this report because common practice throughout the industry has been to keep adding more and more low density, loose fill, insulation over time—but with minimal, or less than optimal, improvement because establishing the more costly air barrier is ignored. At JGS, this is especially the case in the attic of the 1938 and 1956 buildings, as indicated in the infra red images on page 12. Warm air rising through a ceiling plane plays a role in the creation of icicles and ice dams—and the $5,000 cost each time ice has to be removed from eaves. It should also be noted that heating or ventilation equipment and duct work in an attic, above the ‘thermal barrier’ also contributes to heating distribution losses and attic warming—therefore also contributing to icicles and ice dams. These and other dynamics create a more complicated story than can be expressed in a simple chart as above, however “snap shots” can be helpful in creating realistic expectations around costly improvement strategies. For greater detail and a room by room envelope “UA analysis”, please refer to the spreadsheet accompanying this report. Based on an estimated UA of about 13,549, or building’s total conductance, and the relatively constant thermostat settings of close to 70 degrees throughout the school 24 hours a day, seven days a week, it can be estimated that the building’s envelope load—that is, the amount of heating btu’s required to maintain an indoor temperature of 70 degrees in the winter—is about 1,561,000,000 Btu’s or 1,561MMBtu’s. Since the school uses an average of 2,394 MMBtu’s worth of heating oil each winter, it can be further estimated that the heating and ventilation equipment may be responsible for up to 40% of the school’s fuel use. Reducing energy costs requires reducing the building’s heating load through improvements to the envelope and/or reducing the “supply losses” by improving the efficiency Building UA 13,549 of the heating and ventilation equipment and distribution sysTotal PHL 975,564 Btu/hr tems. Envelope load Boiler at .75 AFUE Ventilation losses Actual Usage This report explores the demand side part of that equation, in full acknowledgement that there are great opportunities on the supply side as well. The third component of the full audit is a comprehensive energy model which considers all factors for a Difference cost—benefit financial analysis of all improvements. Model Error 6 1,561 1,951 2,244 2,394 MMBtu MMBtu MMBtu MMBtu (150) MMBtu -6.27% Summary of Recommendations The following recommendations are based on the assessment of the existing envelope and opportunities for envelope improvements which is believed to have a significant impact on comfort, heating energy demand, and issues of air quality, maintenance and durability. . The are listed in order of impact more than installed costs. The financial analysis will be based on energy modeling performed by another member of this team. 1. Replace the three sets of double doors which serve as entrances to the gym with insulated steel doors which close and air seal completely. (If approved by the fire marshall, an alternate approach might be to sealed closed two of the door sets.) Allowance $6500 2. Weatherstrip all remaining exterior doors. Estimated cost: $1800 3. Add weather-stripping to all Type 3 windows, which were installed to close below the sill, so care must be taken for them to remain operable. $2200 4. In conjunction with replacing the ventilation equipment (including duct work) in the 1986 building with ERV’s located above the suspended ceiling in the hallways, remove all insulation material and establish a continuous air barrier at the floor plane of the attic. This will also involve removing an unused chimney which penetrates the attic near the valley over the bus port. Blow in 15 inches of cellulose. No estimate is available for the total project at this time, though installing a plywood floor, air sealing and adding 15 inches cellulose over 10,000 square feet could cost in the range of $30-$40K. 5. In conjunction with installing ERV’s in the 2003 addition, permanently seal intake registers for the Unit Ventilators. $600 6. Surgically air seal the attic floor of the gym. $2200 7. Remove fiberglass batts above the stage and after inspecting the floor and wiring for safety, surgically air seal the horizontal decking and spray 4” closed cell foam on all vertical walls and 6” spray foam on all roof slopes. $5500 8. Air sealing the 1938 ceiling plane is also recommended though the strategy will depend , in part, on whether the ventilation equipment will be replaced as well. 7 10º N 290º W 115º E 195º S 2003 Unit Ventilators 1938 Baseboard 1987 Baseboard ? - window opening bricked in suggests the gym and cafeteria below may have been built after 1956 Radiators Part of the Bus Port was enclosed for offices, I believe during—or close to—the 2003 construction. 8 All rooms are heated with baseboard except for the 2003 addition which have six unit ventilators. 151 Library Computer lab 9 10 1938 Attic / Ceiling Planes While there is considerable depth of “insulating material”, the lack of a continuous air barrier reduces the effectiveness of low density loose fill insulation such as fiberglass. Of equal or more significance is the condition of the duct work and insulation. Note, bright areas indicate heat loss into the attic. 11 1938 Attic / Ceiling Planes The challenge here, as above the gym and the 1987 addition, is that ventilation equipment is outside the thermal envelope, unsealed and poorly insulated—and without a rigid surface to air seal, it is impossible to effect a continuous air barrier, making the insulation above less than effective. All of these conditions conspire to waste considerable energy. 12 Gym and Stage Attic / Ceiling Planes The gym attic is a similar situation, though somewhat less congested with duct work and other ceiling penetrations, it has considerable debris which compresses the fiberglass, further degrading its insulation value. The stage ceiling has large areas without any insulation, including the vertical wall ‘riser’ which serves as a major thermal bypass. (Excessive heat loss) 13 Gym and Stage Attic / Ceiling Planes Bright areas indicate heat loss from conditioned space below into the attic—in this case through the uninsulated vertical ‘riser’, gaps and disturbed loose fill, and ceiling penetrations of an ‘air barrier’. There are fewer duct runs above the gym, yet they not air sealed and the minimal insulation covering has been compromised. 14 Ceiling Planes and Attics Looking up at the ceiling from the gym balcony. Dark areas indicate insulation voids. 15 1987 Attic / Ceiling Planes The 1987 attic / ceiling plane is perhaps in the roughest shape. Again, no rigid surface exists to air seal, with many wiring and duct penetrations, in addition to two chimney’s—one active, one inactive. The image below shows an area with no insulation at all—and missing structure. Former roof encapsulated by the addition. 16 1987 Attic / Ceiling Planes It appears as if there was an attempt to enclose at least the air handler within a thermal envelope by constructing walls and a ceiling plane. Fiberglass batts had been place in the bays under the relatively flat deck. Evidently a wind and rain storm came up while the roof membrane was being installed; the workers pinned the membrane and left. Returning the next day, the membrane had lifted off and the insulation was soaked through and hung dripping. It was eventually removed and the plywood treated for mold. The remaining structure further complicates efforts to establish an air barrier at the attic floor plane. Six plus inches fiberglass batts are stapled to the joists 18” below this walking deck. Some batts are foil faced which slows vapor migration by diffusion, though far more vapor moves with warm air rising through air gaps, cracks, and large holes. 17 2003 Ceiling Plane The 2003 ceiling plane is constructed as a rigid air barrier—installed as sheetrock with seams taped— though the transition to the CMU was not sealed, but stuffed (or not) with air permeable fiberglass as has been conventional practice—though the convention is slowly shifting to using spray foam for a continuous seal. This reflects current best practices and worth the small cost premium during construction, as it is exponentially more costly to try and construct an air barrier later. It is believed that the water stained tiles are the result of a past roof leak in the corner transition from the 1938 to 2003 building. Below right shows fiberglass stuffing and air gap between the wall and the sheetrock air barrier. 18 Wall Types 1938: Rare peaks at the ceramic tiles used on the interior of the brick walls. Above are two images of a chase with access near the floor of the library’s northwest wall. To the left was taken at an interior wall and the entrance up into the attic—but it is likely these were also used to the interior of the brick and finished with plaster. Adding the value of the 10” brick, tile, plaster, and air films, the estimated performance of the 1938 walls is R6. 19 Wall Types 1938: Brick with plaster surfaces. Thermographic images of un-insulated walls, air infiltration at windows, and the baseboards hard at work to add enough supply to keep up with those losses. 20 Wall Types 2. Gym Above Grade The gym walls mat have been constructed after the original 1938 building, but are of similar construction. It appears some kind of insulating material was added in between furring strips, or perhaps it is only variations in thickness of plaster and the contrast is due to the high temperature of the wall radiator. 21 Wall Types 3. Below Grade—Cafeteria and Kitchen 22 Wall Types 4. 1987 The 1987 addition was designed by John Jordan. Typical wall section of a another Jordon building of the same vintage to the right shows CMU structure with 2” rigid foam insulation, an air space / drainage plane and brick veneer. While the rigid foam was not specified to type, variations in surface temperature suggest the possibility that it is polyisocyanurate which—on the southern wall— has been ‘wetted’ over the years. (Images next page). Overall assessment of the wall performance ranges from R6 to R13, with a majority of the wall valued at R11 as below. 37ºF 64ºF Indoor temperature: 68ºF Estimated R-value: R11 23 4. 1987 The plans called for 2” rigid foam insulation. Assuming it was installed as designed, the thermographic patterns suggest the possibility that the insulation boards may have become wet - likely from sun driven moisture—which has compromised their original thermal performance, resulting in varying degrees of heat loss. If this is the case, it is likely that the insulation was a polyisocyanurate, possibly with a fiberglass matt covering, which does not act as a weather barrier. It is ALSO possible, though less likely, that these surface temperature anomalies are caused by exterior surface variations. Note the distinct line at the ceiling plane, indicating less heat lost from the cooler, vented attic. 24 5. 2003 Addition The 2003 wall is constructed similarly as the 1987 addition, though—according to the plans - with 1.5” rigid foam. T his foam board appears to be performing far better and more consistently than its predecessor. The heat loss shown below is from exhausted conditioned air. Bath exhaust fans Ducted exhaust air above the ceiling. Unit ventilators intake 25 Doors and Air Leakage By far the highest replacement priority are the three sets of wood and single double doors to the gym. Not only is the total surface area assessed at an overall R1, but the doors do not close properly so are a large source of air infiltration and heat loss. 26 27 Windows or Glazing The chart below offers a reference for whole window u-values (as opposed to center of glass values) when manufacturer data is not available. Another important factor is about air leakage. Assuming the window still operates enough to close properly (not all do), tightness of a unit varies with operational design: the tightness is typically windows which are not operational, or ‘fixed.’ Followed by casement, awning style with effective locking mechanism, double hung, and—leakiest of all—sliders. Emittance of low e coating Single Glass none Double glass, clear, 1/2" air space none Double glass, low-e, 1/2" air space 0.2 Double glass, low-e, 1/2" air space 0.1 Double glass, low-e, 1/2" air space 0.2 Triple glass, low-e on 2 panes, 1/2" AS n/a Quadruple glass, low-e on 2 panes 1/4" 0.1 Gas between panes none none none none argon argon krypton Aluminum Aluminum Wood or Frame w/out Frame with Vinyl thermal break thermal break Frame 1.3 1.07 n/a 0.81 0.62 0.48 0.7 0.52 0.39 0.67 0.49 0.37 0.64 0.46 0.34 0.53 0.36 0.23 n/a n/a 0.22 The wall of windows below have a steel beam above for structural support. 28 Window Types 1. Double Pane, 1/8” glass, 1/2” air space; Low e coating on outer surface #3 or #4 ; double hung on ‘metal track’ - no thermal break. Rated at u=0.7 2. Eagle, double pane, 1/2” air space Low E 272—found in 0ffice expansion and 2003 addition. LoE 272 is a Cardinal Glass Trademark with a stated whole window performance of u=0.30 without gas between panes and u=0.25 with argon. 3. Narrower window, also found in pairs or multiples as in fill for 1938 rough openings. Double pane, 3/8”, clear glass, in double hung pairs with fixed pane unit above. Found in Library, computer lab, and 1938 classrooms. 29 4. “Rescue” window egress. Clear double pane glass, 1” air space”, wide metal frame with no thermal break and very leaky. Fixed side lite may have low e coating on 2nd surface but high solar heat gain. 5. Eagle sliders, egress—found in 2003 addition, first floor. 3/4” air space in double pane. 6. Basement Awning—found in cafeteria. 30 Pressure testing in 2008 Efforts were made in 2008 to estimate air leakage from pressure testing isolated areas of the building. The conclusions from a variety of testing conditions were that 1) the ceiling planes of the 1938 and 1985 buildings did not constitute an air barrier 2) the ventilation duct work is very leaky and 3) the masonry walls do constitute an air barrier, though the window and door openings also contribute to air leakage considerably. The three day testing was conducted during vacation and all ventilation systems were fully operating. The primary recommendation at that time was to investigate the ventilation system and controls, then consider envelope upgrades. Uncontrolled air leakage rates have been included in the full UA analysis. 31 Single oil fired boiler and hydronic distribution with air handler. HVAC is outside the scope of this assessment but images included below. Stairwell temperature exceeded 85 degrees on day of site visit in 2008. Improvements to controls (while this may have been corrected, remains a concern. 32 Heat Emitter Types 33
© Copyright 2026 Paperzz