FLATAIR

APPLICATION
GUIDE
FLATAIR
FMC - H
FIC - H
FSC - H
Horizontal packaged air conditioners
10  28 kW
FLATAIR AGU-MSL60-1505-E
lennoxemeia.com
INDEX
FLATAIRTM
APPLICATION GUIDE
Ref : FLATAIR AGU-MSL60-1505-E
CONTENTS
PAGE
1 - General description
2
2 - Denomination
4
3 - Range of products /technical features
5
4 - Operation limits
7
5 - Fan performances
8
6 - Sound level
9
7 - Capacities
10
9 - Electrical data
17
10 - Dimensions
18
11 - Installation
25
12 - Options
28
All the technical and technological information contained in this manual, including any drawing and technical descriptions
provided by us, remain the property of Lennox and must not be utilised (except in operation of this product), reproduced,
issued to or made available to third parties without the prior written agreement of Lennox.
Application Guide • FLATAIR-AGU-MSL60-1505-E
•1•
1 - GENERAL DESCRIPTION
1.1- GENERAL DESCRIPTION
The horizontal air conditioning units, range Flatair, cooling only or heat pump are air condensed units designed for small shopping
center and housing. They can be supplied either compact or on split system.
Due to their small dimensions they are designed for false ceiling and can be placed in air conducts both indoor and outdoor sections.
A wide range of optionals, completed-factory assembled are also available.
FURNITURE
EXCHANGER
Painted in galvanized metal furniture, high resistant to corrosion.
The units are provided with metal profiles, capable of withstanding
the unit and able as well of installing the unit hung from the ceiling
or mounted on the floor.
Panels are easily inter exchangeable, giving several air suction
and return alternatives.
An insulation with a protection of mesh is used in indoor section
with a classification of M1 and F1, certifying that the material is
auto-extinguishable and avoiding the fumes inside the room to
be aconditionned. Auto extinguishable insulation M1 is used in
outdoor units.
Made-up with copper pipes and aluminium fings, designed to
get a high heat transfer.
COMPRESSORS
All units are provided with scroll compressor, cooling by a suction gas with thermic protection inside the engine, so no other
additional protection is required.
It is mounted on anti-vibration devices both external and internal.
All compresors are R410A
In heat pump units the compressors are provided with a crankcase heater to heat the oil in the compressor so that a suitable
lubrication can take place.
AIR FILTER
Washable air filter; auto extinguishable material with M1 classification, high efficiency filtrate with G2 classification. It can be
removed through the upper part and from both sides.
Their dimensions and design of the refrigenrant circuit have
been specially worked to obtain the maximum performance of
the exchanger increasing the power of the unit and reducing
the consumption.
COOLING CIRCUIT
Carried out with welded deshydratable copper pipes with pressure intakes with schraeder valves in the suction and liquid lines
both indoors and outdoor units.
In unit 20-25-30 the pressure intakes in the outdoor section are
approachable from the outer part of the unit.
The unit is equipped with both high-low pressure switches with
an automatic reset. It also has a dehydrating filter, expansion
system with restrictors in units 10-12-15; expansion valves in
units 20-25-30. The heat pump units are equipped as well with a
suction accumulator to avoid the liquid return to the compressor,
4 way valve and no-return valve.
ELECTRICAL CIRCUIT
Designed according to EN 60204-1 normative hermetically
sealed to avoid condensation. With circuits breakers to protecto
the unit from overloading.
FAN
Outdoor and indoor fans are centrifugal with an assembled
engine, statically balancing, with a low sound level.
Those fans are assembled to the inserted panel of the units and
split from upper side of the fan with insulated materials to void
vibrations.
Flatair units are designed for false ceiling mounting, to be installed exclusively indoor. For outdoor mounting, a shelter or roof structure has to be installed, to avoid direct water entry in the sensible parts of the
unit (electrical board, joints between the indoor unit and the outdoor unit).
•2•
Application Guide • FLATAIR-AGU-MSL60-1505-E
1 - GENERAL DESCRIPTION
1.2- CONTROL
CLIMATIC 40 VERSION
CLIMATIC 60 VERSION
CLIMATIC™ 60 controller intelligently improves efficiency and
helps set up and service operations to guarantee long lasting
performance.
We have two versions of Control in Flatair units:
- The basic C40 platform, wich includes one terminal in the
unit and another DC40 remote
- The advanced platform C60 which includes one terminal
in the unit, and 3 remote terminals as in option (DC, DS,
DM)
OPTIMIZED OPERATION AND SETUP
SAVES ENERGY
CLIMATIC™ 60 is designed to provide the best energy
efficiency throughout unit’s life cycle while ensuring
reliable and consistent operation with user friendly interfaces.
This new controller constantly monitors more machine parameters
than ever to improve rooftop operation and maximize efficiency
and reliability
1.3- OPTIONS
Flatair units can be equipped with the following options:
- Main switch
- Heating electrical heater, made of blinded elements and assembled inside the unit
- Kit low ambient -15 degrees
- Kit low ambient 0 degrees (only for cooling units)
- 3 Phase controller (only for 3 phase units)
- Customer terminal DC60 (only for CLIMATIC 60 version)
- Service terminal DS60 (only for CLIMATIC 60 version)
- Remote duct sensor in return
- Ambient remote sensor (only en CLIMATIC 40 version)
- Thermostatic freecooling
- Enthalpic freecooling (only in CLIMATIC 60 version)
- Second return damper for kit freecooling
- Different airflow configurations in return and supply
- BMS communication interface (CLIMATIC 40 as standard and CLIMATIC 60 as an option)
- Echelon communication interface (CLIMATIC 60)
- Bacnet communication interface (CLIMATIC 60)
Application Guide • FLATAIR-AGU-MSL60-1505-E
•3•
2 - DENOMINATION
EXAMPLE :
F
F
M
C
0 1 5
S
N
M
1
M
M
FLATAIR
400V/3/50
Revision number
M
Compact unit
S
Outdoor unit
I
Indoor unit
C
Cooling only
H
Heat pump
X
Cooling only / heat pump
M
R410A
---
S
1 Circuit
Approximate Cooling capacity in kW
i
•4•
FMC: Cooling only unit R-410A
FMH: Heat pump unit R-410A
Application Guide • FLATAIR-AGU-MSL60-1505-E
3 - MAIN TECHNICAL FEATURES
A BOX
FCM/FCH
10
B BOX
12
15
C BOX
D BOX
20
25
30
Cooling capacity *
(cooling only)
kW
9.7
12
15
19.5
23.5
27
Heating capacity*
(heat pump)
kW
10
12.5
15.5
20.5
25
27.9
DIMENSIONS
Height
mm
495
495
595
595
645
645
Lenght
mm
1250
1250
1300
1450
1500
1500
Depth
mm
1250
1250
1330
1520
1800
1800
Kg
170
174
250
268
322
338
20
25
30
NET WEIGHT
OUTDOOR UNIT
FSC/FSH
10
12
15
1 / Scroll
Number & Type of compressor
FAN
Maximum airflow rate
m3/h
3500
3400
4500
5650
6000
5850
Minimum airflow rate
m3/h
2350
2400
3740
4095
4760
5000
Pa
100
90
120
150
160
100
kg
112
116
165
159
202
208
Height
mm
495
495
595
595
645
465
Lenght
mm
1250
1250
1300
1450
1500
1500
Depth
mm
820
820
830
900
1025
1025
Maximum available presure
(1)
NET WEIGHT
DIMENSIONS
PIPES CONNEXIONS
Liquid
m3/h
3/8"
3/8"
1/2"
5/8"
5/8"
5/8"
Gas
m3/h
3/4"
3/4"
7/8"
7/8"
1-1/8"
1-1/8"
FIC/H
2O 20
FIC/H
25
FIC/H
30
INDOOR UNIT
FIX
FIX 10 FIX 12
FIX 15
Number & Type of compressor
1 / Scroll
FAN
Maximum airflow rate
m3/h
2350
2300
3575
4850
5750
5500
Minimum airflow rate
m3/h
1500
1650
2410
2090
3455
3695
Pa
120
110
160
200
240
180
kg
58
58
85
109
121
131
Electrical heater
kg
7
7
7
7
8
8
Free-cooling 1 damper
kg
12
12
12
14
15
15
Free-cooling 2 damper
kg
24
24
24
28
30
30
Height
mm
495
495
595
595
645
645
Lenght
mm
1250
1250
1300
1450
1500
1500
Depth
mm
430
430
500
620
775
775
Maximum available presure
(1)
NET WEIGHT
OPTIONS WIEGHT
DIMENSIONS
PIPES CONNEXIONS
Liquid
m3/h
3/8"
3/8"
1/2"
5/8"
5/8"
5/8"
Gas
m3/h
3/4"
3/4"
7/8"
7/8"
1-1/8"
1-1/8"
(*)
(*)
(1)
Air intake temperature in the indoor exchanger :
27ºC DB/19ºC WB
Air intake temperature in the outdoor exchanger: :
35ºC DB
DB
WB
Dry bulb temperature
Wet bulb temperature
With admissible minimum air flow
Application Guide • FLATAIR-AGU-MSL60-1505-E
•5•
3 - MAIN TECHNICAL FEATURES
3.1 DIMENSIONS
Box
Unit
Lenght
Deep
Height
1250
1250
495
1300
1330
595
1450
1520
595
A
10-12
B
15
C
20
D
25-30
1500
1800
645
A
10-12
1250
430
495
B
15
1300
500
595
C
20
1450
620
595
D
25-30
1500
775
645
A
10-12
1250
820
495
B
15
1300
830
595
C
20
1450
900
595
D
25-30
1500
1025
645
Packaged
Indoor unit
Outdoor unit
3.2 MINIMUM, MAXIMUM AND NOMINAL AIRFLOW RATES
INDOOR UNIT
FIC/H
FIH 10
FIH 12
FIH 15
FIH 20
FIH 25
FIH 30
AIRFLOW RATE
Maximum
Nominal
Minimum
2350
2140
1500
2300
2040
1650
3575
3170
2410
4850
4500
3090
5750
5470
3455
5500
5060
3695
OUTDOOR UNIT
FSC/H
FSH 10
FSH 12
FSH 15
FSH 20
FSH 25
FSH 30
•6•
AIRFLOW RATE
Maximum
Nominal
Minimum
3500
2970
2350
3400
2890
2400
4500
4250
3740
5650
5150
4095
6000
5600
4760
5850
5400
5000
Application Guide • FLATAIR-AGU-MSL60-1505-E
3 - MAIN TECHNICAL FEATURES
3.3 WEIGHTS
FLATAIR (STANDARD)
Cooling only units
Heat pump units
MODEL
10
12
15
20
25
30
Indoor unit
FIX/FIC
58
58
85
109
121
131
Outdoor unit
FSC
112
116
165
159
202
208
Package
(indoor+outdoor)
FMC
170
174
250
268
322
338
Indoor unit
FIX/FIH
58
58
85
109
121
131
Outdoor unit
FSH
117
121
170
164
207
213
Package
(indoor+outdoor)
FMH
175
179
255
273
327
343
electrical heater
7
7
7
7
8
8
free-cooling 1 damper
12
12
12
14
15
15
free-cooling 2 damper
24
24
24
28
30
30
OPTIONS
to add indoor unit
4 - OPERATION LIMITS
OPERATION LIMITS FOR COOLING ONLY UNITS
Indoor temperature
Maximum temperatures
Minimum temperatures
32ºC DB / 23ºC WB
21ºC DB / 15ºC WB
Table 1
Standard unit : + 15ºC
0ºC(*) / -15ºC(**)
Cooling mode
Outdoor temperature
(*) With option kit low temperature 0ºC
(**) With option kit low temperature -15ºC
DB.- Dry bulb temperature
WB.- Wet bulb temperature
OPERATION LIMITS FOR HEAT PUMP UNITS
Indoor temperature
Maximum temperatures
Minimum temperatures
32ºC DB / 23ºC WB
21ºC DB / 15ºC WB
Table 1
+ 15ºC STANDARD UNIT
0ºC(*) / -15ºC(**)
27ºC DB
15ºC DB
Sizes 12-15-20-30 : 25ºC (1)
Sizes 12-25 : 23ºC
-12ºC
Cooling mode
Outdoor temperature
Indoor temperature
Heat pump mode
Outdoor temperature
(*) Active CL40 parameter to operate at 0ºC
(**) With option kit low temperature -15ºC
Application Guide • FLATAIR-AGU-MSL60-1505-E
(1) : Indoor temperature : 20°C
DB.- Dry bulb temperature
WB.- Wet bulb temperature
•7•
5 - FAN PERFORMANCES
Available static pressure (Pa)
INDOOR UNITS
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
10
12
25
30
2350
2300
3575
4850
5750
5500
2275
2250
2240
2200
3495
4785
5730
5455
3410
4715
5705
5405
2190
2150
2140
2100
3330
4645
5670
5350
3250
4575
5630
5285
2080
2025
2040
3170
4500
5580
5220
1975
3095
4425
5530
5140
1975
1925
1925
3020
4345
5470
5060
1860
2945
4260
5405
4965
1840
1800
2875
4175
5330
4870
1775
1730
2800
4090
5250
4765
1625
1650
2735
4000
5165
4655
1500
----
2665
3910
5075
4640
---
---
2600
3815
4975
4415
---
---
2535
3720
4870
4285
---
---
2470
3620
4755
4150
---
---
2410
3520
4640
4005
---
---
---
3415
4515
3855
---
---
---
3310
4380
3695
---
---
---
3200
4245
---
---
---
---
3090
4100
---
---
---
---
---
3945
---
---
---
---
---
3790
---
---
---
---
---
3625
---
---
---
---
---
3455
---
Airflow rate (m3/h)
OUTDOOR UNITS
Available static pressure (Pa)
Airflow rate (m3/h)
15
20
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
10
12
15
20
25
30
3500
3400
4500
5650
6000
5850
3410
3325
4460
5550
5920
5755
3300
3160
4410
5450
5840
5665
3190
3075
4360
5350
5760
5575
3080
2980
4310
5250
5680
5485
2970
2890
4250
5150
5600
5400
2840
2790
4190
5050
5520
5315
2700
2690
4125
4945
5445
5235
2560
2580
4055
4840
4365
5155
2410
2400
3980
47365
5290
5075
2350
---
3905
4630
5210
5000
---
---
3825
4525
5135
----
---
---
3740
4420
5060
----
---
---
---
4315
4985
----
---
---
---
4205
4910
----
---
---
---
4095
4835
----
---
---
---
---
4760
----
With option G4 additional pressure drop 50Pa
Nominal airflow rate
Keep in mind reduction on air flow and static pressure services if you use mufflers or
external air filter.
•8•
Application Guide • FLATAIR-AGU-MSL60-1505-E
6 - SOUND LEVEL
OUTDOOR UNIT
dB
Hz
Lw dB(A)
125
250
500
1000
2000
4000
8000
10
73
70
71
72.9
69.3
68.9
62.8
77
12
74
78
69
73.6
66.3
66.1
60.5
77
15
79
74
77
78.0
75.5
72.9
68.0
82
20
81
75
81
81.9
79.2
76.5
72.2
86
25
83
76
76
76.4
75.3
72.4
65.9
81
30
83
75
75
76.0
74.7
71.6
65.0
81
Size
With compressor jacket, estimated reduction of 2 Dba
INDOOR UNIT
dB
Size
Hz
Lw dB(A)
125
250
500
1000
2000
4000
8000
10
71
67
67
67.4
64.9
64.1
58.3
72
12
71
67
67
67.4
64.9
64.1
58.3
72
15
74
69
72
71.3
69.1
66.0
59.7
76
20
77
71
75
75.8
73.4
70.7
65.7
80
25
79
73
79
80.2
77.4
74.5
74.3
84
30
78
72
77
78.4
75.7
72.9
68.4
83
With compressor jacket, estimated reduction of 2 Dba
Application Guide • FLATAIR-AGU-MSL60-1505-E
•9•
7 - CAPACITIES
COOLING CAPACITIES
Air inlet temperature at condenser (dry bulb)
Indoor wet
bulb
21
24
27
24
27
30
27
30
33
21
24
27
24
27
30
27
30
33
21
24
27
24
27
30
27
30
33
1500 m3/h
16
19
22
2140 m3/h
16
19
22
16
2350 m3/h
Maximum airflow rate
Nominal airflow rate
Minimum airflow rate
Mixed air
temperature
°C
Indoor dry bulb
FMC/H 10
19
22
20 °C
25 °C
30 °C
35°C
40 °C
45 °C
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
9,56
9,56
9,60
10,46
10,45
10,48
11,46
11,44
11,45
9,96
9,98
10,03
10,90
10,90
10,94
11,93
11,92
11,94
10,00
10,02
10,18
10,95
10,95
10,99
11,99
11,98
12,00
2,80
2,80
2,80
2,84
2,84
2,84
2,88
2,88
2,88
3,05
3,05
3,05
3,09
3,09
3,09
3,13
3,13
3,13
3,15
3,15
3,16
3,19
3,19
3,19
3,24
3,24
3,24
5,88
7,21
8,41
5,78
7,14
8,33
5,61
6,98
8,18
6,61
8,36
9,97
6,46
8,27
9,91
6,22
8,08
9,76
6,83
8,71
10,18
6,68
8,62
10,40
6,42
8,43
10,26
9,29
9,30
9,35
10,15
10,15
10,18
11,12
11,10
11,11
9,65
9,67
9,75
10,55
10,56
10,60
11,55
11,54
11,57
9,67
9,70
9,91
10,59
10,60
10,64
11,59
11,59
11,62
2,96
2,96
2,96
3,00
3,00
3,01
3,05
3,05
3,05
3,21
3,21
3,22
3,26
3,26
3,26
3,31
3,31
3,31
3,31
3,31
3,33
3,36
3,36
3,36
3,41
3,41
3,41
5,75
7,07
8,27
5,65
7,00
8,19
5,48
6,85
8,05
6,48
8,21
9,75
6,34
8,12
9,74
6,11
7,95
9,61
6,70
8,55
9,91
6,56
8,47
10,23
6,32
8,30
10,11
8,96
8,98
9,03
9,79
9,79
9,83
10,71
10,70
10,72
9,28
9,31
9,45
10,15
10,16
10,21
11,11
11,10
11,14
9,29
9,32
9,59
10,17
10,18
10,24
11,14
11,14
11,18
3,16
3,16
3,16
3,21
3,21
3,21
3,26
3,26
3,26
3,40
3,40
3,42
3,46
3,46
3,46
3,52
3,52
3,52
3,51
3,51
3,54
3,57
3,57
3,57
3,63
3,63
3,63
5,60
6,91
8,09
5,51
6,84
8,02
5,35
6,70
7,89
6,32
8,02
9,45
6,20
7,95
9,54
6,00
7,79
9,43
6,54
8,35
9,59
6,42
8,29
10,01
6,21
8,14
9,91
8,57
8,59
8,66
9,36
9,37
9,42
10,25
10,25
10,28
8,85
8,89
9,09
9,68
9,70
9,76
10,60
10,61
10,65
8,85
8,89
9,21
9,69
9,71
9,77
10,62
10,63
10,67
3,41
3,41
3,41
3,46
3,46
3,47
3,52
3,52
3,52
3,65
3,65
3,68
3,72
3,72
3,72
3,78
3,78
3,78
3,77
3,76
3,80
3,84
3,84
3,84
3,90
3,90
3,90
5,43
6,71
7,87
5,35
6,65
7,81
5,21
6,53
7,70
6,14
7,79
9,09
6,04
7,74
9,30
5,86
7,61
9,21
6,36
8,11
9,21
6,25
8,07
9,75
6,07
7,95
9,68
8,12
8,15
8,22
8,88
8,90
8,95
9,73
9,73
9,77
8,37
8,41
8,68
9,16
9,18
9,25
10,04
10,05
10,10
8,35
8,40
8,79
9,15
9,18
9,32
10,05
10,06
10,11
3,74
3,74
3,74
3,80
3,80
3,81
3,87
3,87
3,87
3,98
3,97
4,02
4,06
4,06
4,06
4,14
4,14
4,14
4,11
4,10
4,14
4,19
4,19
4,21
4,27
4,27
4,27
5,23
6,47
7,61
5,17
6,43
7,57
5,06
6,34
7,48
5,93
7,52
8,68
5,85
7,49
9,00
5,71
7,39
8,94
6,13
7,82
8,79
6,06
7,80
9,32
5,91
7,72
9,39
7,62
7,66
7,73
8,34
8,36
8,42
9,15
9,16
9,20
7,82
7,87
8,22
8,57
8,61
8,68
9,42
9,44
9,49
7,79
7,84
8,31
8,56
8,59
8,77
9,42
9,44
9,49
4,21
4,20
4,20
4,29
4,29
4,28
4,36
4,36
4,36
4,44
4,43
4,49
4,55
4,54
4,54
4,64
4,64
4,64
4,59
4,58
4,63
4,71
4,70
4,73
4,80
4,80
4,79
5,00
6,19
7,29
4,96
6,18
7,27
4,88
6,11
7,22
5,68
7,19
8,22
5,63
7,19
8,64
5,52
7,13
8,62
5,87
7,47
8,31
5,82
7,48
8,77
5,72
7,44
9,04
HEATING CAPACITIES
Air inlet temperature at condenser (dry bulb)
FMH 10
2140 m3/h
2350 m3/h
1500 m3/h
Nominal
airflow
Maximum airflow rate
Minimum
airflow
Indoor Dry Bulb
15
18
20
23
25
27
15
19
20
23
25
27
15
19
20
23
25
27
NC
Net cooling capacity
(kW) :
• 10 •
-10 °C
-5 °C
0 °C
5°C
7 °C
10 °C
15 °C
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
6,40
6,40
6,41
6,43
6,45
6,48
6,62
6,61
6,61
6,63
6,65
6,67
6,84
6,83
6,83
6,84
6,86
6,88
2,44
2,60
2,71
2,88
3,01
3,15
2,50
2,70
2,76
2,93
3,05
3,18
2,49
2,69
2,74
2,90
3,02
3,14
7,39
7,36
7,36
7,35
7,36
7,37
7,66
7,62
7,62
7,61
7,61
7,62
7,90
7,86
7,85
7,84
7,84
7,85
2,62
2,77
2,89
3,07
3,20
3,34
2,63
2,83
2,89
3,06
3,18
3,31
2,61
2,80
2,85
3,01
3,12
3,24
8,37
8,32
8,30
8,27
8,26
8,26
8,69
8,63
8,61
8,58
8,57
8,56
8,95
8,88
8,87
8,84
8,82
8,81
2,79
2,95
3,07
3,26
3,39
3,54
2,76
2,96
3,02
3,19
3,31
3,44
2,73
2,92
2,97
3,12
3,23
3,35
9,34
9,27
9,23
9,18
9,16
9,14
9,72
9,63
9,61
9,55
9,52
9,50
10,00
9,90
9,88
9,82
9,79
9,77
2,96
3,13
3,25
3,45
3,59
3,74
2,89
3,10
3,15
3,32
3,45
3,58
2,84
3,03
3,08
3,24
3,35
3,47
9,73
9,65
9,60
9,55
9,51
9,49
10,13
10,02
10,00
9,94
9,90
9,87
10,42
10,31
10,28
10,22
10,18
10,15
3,03
3,20
3,32
3,53
3,68
3,83
2,94
3,15
3,21
3,38
3,50
3,64
2,89
3,08
3,13
3,29
3,40
3,52
10,31
10,21
10,16
10,09
10,05
10,01
10,75
10,62
10,59
10,51
10,47
10,43
11,04
10,91
10,88
10,80
10,76
10,72
3,13
3,31
3,44
3,65
3,80
3,97
3,02
3,23
3,29
3,47
3,59
3,73
2,96
3,15
3,20
3,37
3,48
3,60
11,27
11,15
11,08
10,99
10,93
10,88
11,76
11,60
11,57
11,47
11,41
11,35
12,08
11,92
11,88
11,78
11,71
11,66
3,31
3,50
3,64
3,87
4,03
4,21
3,16
3,37
3,43
3,62
3,75
3,89
3,08
3,28
3,33
3,50
3,62
3,75
NH
Net heating capacity
(kW) :
SC
Sensible cooling capacity
(kW) :
Compressor absorbed
AC
(kW) : power
Application Guide • FLATAIR-AGU-MSL60-1505-E
7 - CAPACITIES
COOLING CAPACITIES
Air inlet temperature at condenser (dry bulb)
Indoor wet
bulb
21
24
27
24
27
30
27
30
33
21
24
27
24
27
30
27
30
33
21
24
27
24
27
30
27
30
33
1650 m3/h
16
19
22
2040 m3/h
16
19
22
16
2300 m3/h
Maximum airflow rate
Nominal airflow rate
Minimum airflow rate
Mixed air
temperature
°C
Indoor dry bulb
FMC/H 12
19
22
20 °C
25 °C
30 °C
35°C
40 °C
43 °C
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
12,12
12,13
12,14
13,22
13,22
13,24
14,41
14,41
14,42
12,48
12,49
12,51
13,59
13,61
13,63
14,80
14,82
14,84
12,60
12,61
12,64
13,73
13,74
13,77
14,95
14,97
14,99
3,88
3,88
3,88
3,94
3,94
3,94
4,03
4,03
4,03
4,08
4,08
4,09
4,15
4,15
4,15
4,25
4,25
4,26
4,23
4,24
4,24
4,31
4,31
4,31
4,42
4,42
4,42
7,28
8,79
10,21
7,16
8,65
10,06
6,97
8,44
9,82
7,76
9,55
11,26
7,59
9,39
11,10
7,34
9,14
10,84
8,05
10,02
11,92
7,86
9,85
11,76
7,59
9,59
11,51
11,76
11,77
11,79
12,81
12,82
12,84
13,95
13,96
13,98
12,08
12,10
12,12
13,15
13,17
13,19
14,32
14,33
14,36
12,17
12,20
12,23
13,26
13,28
13,31
14,44
14,46
14,49
4,13
4,13
4,13
4,20
4,20
4,20
4,30
4,30
4,30
4,33
4,33
4,33
4,40
4,40
4,41
4,52
4,52
4,52
4,48
4,48
4,49
4,57
4,57
4,57
4,69
4,69
4,70
7,10
8,60
10,03
6,97
8,47
9,88
6,79
8,27
9,65
7,58
9,36
11,06
7,41
9,20
10,91
7,18
8,97
10,67
7,88
9,82
11,70
7,69
9,66
11,56
7,43
9,42
11,32
11,30
11,31
11,33
12,30
12,32
12,34
13,41
13,42
13,44
11,58
11,60
11,63
12,61
12,63
12,66
13,74
13,76
13,78
11,65
11,68
11,71
12,70
12,72
12,76
13,83
13,86
13,89
4,45
4,45
4,45
4,52
4,52
4,52
4,64
4,64
4,64
4,64
4,64
4,65
4,73
4,73
4,74
4,86
4,86
4,87
4,80
4,80
4,81
4,90
4,90
4,91
5,05
5,05
5,06
6,89
8,37
9,79
6,77
8,25
9,65
6,60
8,06
9,44
7,37
9,12
10,79
7,21
8,97
10,66
6,99
8,76
10,44
7,66
9,57
11,41
7,49
9,43
11,29
7,25
9,21
11,08
10,74
10,75
10,78
11,70
11,72
11,75
12,76
12,78
12,80
10,99
11,01
11,05
11,98
12,00
12,03
13,06
13,08
13,11
11,04
11,07
11,10
12,04
12,07
12,10
13,13
13,16
13,20
4,88
4,88
4,88
4,96
4,96
4,96
5,09
5,09
5,10
5,07
5,07
5,07
5,17
5,17
5,18
5,33
5,33
5,34
5,23
5,23
5,24
5,35
5,36
5,36
5,53
5,53
5,54
6,64
8,09
9,48
6,53
7,99
9,36
6,38
7,82
9,19
7,11
8,81
10,45
6,98
8,69
10,34
6,79
8,51
10,16
7,39
9,24
11,03
7,25
9,13
10,94
7,05
8,95
10,78
10,08
10,10
10,13
11,01
11,03
11,06
12,02
12,04
12,07
10,30
10,33
10,37
11,24
11,27
11,31
12,28
12,31
12,34
10,32
10,36
10,40
11,28
11,31
11,35
12,33
12,36
12,40
5,50
5,50
5,50
5,59
5,59
5,60
5,75
5,75
5,76
5,68
5,68
5,69
5,81
5,81
5,82
6,00
6,01
6,01
5,87
5,87
5,87
6,02
6,02
6,03
6,24
6,24
6,25
6,35
7,75
9,09
6,26
7,67
9,01
6,14
7,54
8,87
6,81
8,44
10,01
6,70
8,35
9,94
6,54
8,21
9,81
7,07
8,84
10,59
6,96
8,77
10,52
6,80
8,63
10,40
9,64
9,67
9,70
10,54
10,56
10,60
11,53
11,55
11,58
9,84
9,87
9,91
10,76
10,79
10,83
11,77
11,80
11,84
9,85
9,88
9,93
10,78
10,81
10,86
11,80
11,84
11,88
6,03
6,03
6,03
6,13
6,13
6,14
6,31
6,31
6,32
6,21
6,21
6,22
6,36
6,36
6,36
6,58
6,58
6,59
6,41
6,41
6,41
6,59
6,59
6,60
6,85
6,85
6,86
6,15
7,51
8,82
6,08
7,45
8,76
5,98
7,35
8,65
6,59
8,18
9,71
6,51
8,12
9,67
6,38
8,01
9,57
6,85
8,56
10,26
6,77
8,52
10,21
6,63
8,41
10,13
HEATING CAPACITIES
Air inlet temperature at condenser (dry bulb)
FMH 12
1650 m3/h
2040 m3/h
2300 m3/h
Maximum airflow rate
Nominal
airflow
Minimum
airflow
Indoor Dry Bulb
15
18
20
23
25
27
15
19
20
23
25
27
15
19
20
23
25
27
GC
Gross cooling capacity
(kW) :
-10 °C
-5 °C
0 °C
5°C
7 °C
10 °C
15 °C
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
8,31
8,40
8,46
8,57
3,31
3,58
3,78
4,12
9,51
9,56
9,60
9,68
9,73
3,57
3,85
4,06
4,40
4,66
10,69
10,71
10,73
10,77
10,80
3,83
4,12
4,33
4,69
4,96
8,41
8,51
8,53
8,62
8,69
3,23
3,57
3,66
3,96
4,19
8,50
8,58
8,61
8,68
8,74
8,80
3,26
3,59
3,68
3,98
4,20
4,44
9,65
9,70
9,72
9,78
9,82
9,87
9,77
9,81
9,82
9,87
9,90
9,94
3,47
3,80
3,90
4,20
4,42
4,67
3,48
3,80
3,89
4,18
4,40
4,63
10,88
10,89
10,89
10,91
10,94
10,96
11,03
11,02
11,02
11,03
11,05
11,07
3,69
4,04
4,13
4,44
4,66
4,91
3,69
4,01
4,10
4,39
4,61
4,84
11,85
11,84
11,84
11,85
11,86
11,88
12,09
12,05
12,04
12,03
12,03
12,04
12,26
12,21
12,20
12,18
12,17
12,17
4,10
4,40
4,62
4,99
5,27
5,58
3,92
4,27
4,37
4,68
4,92
5,17
3,89
4,22
4,31
4,61
4,82
5,06
12,31
12,29
12,28
12,27
12,28
12,28
12,56
12,51
12,50
12,48
12,47
12,47
12,75
12,68
12,67
12,64
12,62
12,61
4,21
4,51
4,74
5,12
5,41
5,72
4,01
4,37
4,46
4,78
5,02
5,28
3,97
4,30
4,40
4,69
4,91
5,15
13,00
12,96
12,93
12,91
12,90
12,89
13,28
13,20
13,18
13,14
13,12
13,10
13,48
13,39
13,37
13,31
13,29
13,26
4,37
4,68
4,92
5,32
5,61
5,95
4,15
4,51
4,61
4,94
5,18
5,45
4,10
4,43
4,53
4,83
5,05
5,30
14,13
14,05
14,01
13,95
13,92
13,89
14,45
14,33
14,30
14,23
14,18
14,14
14,69
14,55
14,52
14,43
14,38
14,34
4,65
4,99
5,24
5,67
5,99
6,35
4,39
4,77
4,87
5,22
5,47
5,76
4,31
4,66
4,75
5,07
5,30
5,56
NH
Net heating capacity
(kW) :
Application Guide • FLATAIR-AGU-MSL60-1505-E
SC
Sensible cooling capacity
(kW) :
Compressor absorbed
AC
(kW) : power
• 11 •
7 - CAPACITIES
COOLING CAPACITIES
Air inlet temperature at condenser (dry bulb)
Indoor wet
bulb
21
24
27
24
27
30
27
30
33
21
24
27
24
27
30
27
30
33
21
24
27
24
27
30
27
30
33
2410 m3/h
16
19
22
3170 m3/h
16
19
22
16
3575 m3/h
Maximum airflow rate
Nominal airflow rate
Minimum airflow rate
Mixed air
temperature
°C
Indoor dry bulb
FMC/H 15
19
22
20 °C
25 °C
30 °C
35°C
40 °C
45 °C
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
14,83
14,84
15,00
16,26
16,20
16,29
17,95
17,82
17,84
15,36
15,43
15,67
16,81
16,82
16,99
18,52
18,46
18,55
15,46
15,57
15,90
16,92
16,97
17,17
18,65
18,62
18,75
4,75
4,75
4,76
4,79
4,79
4,79
4,83
4,82
4,82
4,98
4,98
5,00
5,02
5,02
5,03
5,05
5,05
5,05
5,13
5,14
5,16
5,16
5,17
5,18
5,20
5,20
5,20
9,09
11,40
13,26
8,89
11,37
13,32
8,31
11,01
13,12
10,17
12,89
15,17
10,00
12,91
15,29
9,45
12,60
15,16
10,69
13,60
15,90
10,56
13,66
16,27
10,04
13,41
16,20
14,39
14,41
14,60
15,77
15,72
15,84
17,40
17,29
17,33
14,89
14,98
15,23
16,28
16,31
16,50
17,94
17,90
18,01
14,97
15,10
15,48
16,38
16,44
16,67
18,05
18,05
18,19
4,98
4,98
4,99
5,02
5,02
5,02
5,06
5,06
5,06
5,20
5,21
5,22
5,24
5,25
5,26
5,28
5,28
5,29
5,36
5,37
5,39
5,40
5,40
5,41
5,43
5,43
5,44
8,90
11,16
13,01
8,72
11,15
13,07
8,18
10,82
12,90
9,96
12,63
14,88
9,82
12,66
15,01
9,32
12,40
14,91
10,47
13,32
15,48
10,36
13,40
15,96
9,90
13,19
15,93
13,85
13,89
14,09
15,17
15,15
15,28
16,75
16,66
16,72
14,31
14,43
14,70
15,66
15,70
15,91
17,27
17,24
17,37
14,38
14,53
14,97
15,74
15,82
16,06
17,35
17,37
17,54
5,25
5,26
5,27
5,30
5,30
5,31
5,34
5,34
5,34
5,47
5,48
5,49
5,52
5,53
5,54
5,56
5,56
5,57
5,64
5,65
5,67
5,68
5,69
5,70
5,72
5,73
5,73
8,66
10,88
12,69
8,52
10,88
12,77
8,03
10,60
12,63
9,71
12,30
14,52
9,60
12,36
14,66
9,16
12,15
14,61
10,20
12,98
14,97
10,13
13,09
15,59
9,73
12,92
15,59
13,21
13,27
13,49
14,48
14,47
14,63
16,01
15,93
16,01
13,64
13,78
14,10
14,93
15,00
15,23
16,49
16,49
16,63
13,69
13,86
14,38
14,99
15,10
15,36
16,56
16,60
16,78
5,60
5,60
5,62
5,65
5,66
5,66
5,70
5,70
5,70
5,82
5,83
5,85
5,88
5,88
5,89
5,92
5,92
5,93
5,99
6,00
6,02
6,05
6,06
6,07
6,09
6,10
6,10
8,39
10,53
12,30
8,28
10,56
12,40
7,86
10,34
12,31
9,41
11,92
14,10
9,34
12,01
14,25
8,97
11,85
14,23
9,89
12,56
14,38
9,86
12,70
15,14
9,52
12,59
15,19
12,47
12,55
12,79
13,68
13,70
13,87
15,16
15,11
15,21
12,87
13,03
13,45
14,11
14,20
14,44
15,61
15,63
15,80
12,90
13,09
13,70
14,15
14,28
14,57
15,67
15,72
15,93
6,06
6,07
6,08
6,12
6,13
6,13
6,16
6,17
6,17
6,28
6,29
6,31
6,35
6,36
6,36
6,39
6,40
6,40
6,47
6,48
6,48
6,54
6,55
6,55
6,58
6,59
6,59
8,07
10,12
11,84
8,00
10,19
11,96
7,66
10,02
11,93
9,06
11,46
13,45
9,04
11,58
13,75
8,73
11,49
13,79
9,51
12,07
13,70
9,52
12,25
14,57
9,27
12,20
14,71
11,63
11,73
12,00
12,79
12,83
13,02
14,22
14,18
14,30
12,00
12,18
12,71
13,19
13,30
13,56
14,64
14,67
14,86
12,02
12,23
12,94
13,22
13,36
13,73
14,68
14,75
14,98
6,72
6,73
6,72
6,79
6,80
6,79
6,81
6,82
6,82
6,93
6,94
6,93
7,01
7,02
7,01
7,05
7,06
7,06
7,16
7,16
7,11
7,25
7,25
7,26
7,27
7,28
7,28
7,69
9,63
11,29
7,68
9,74
11,45
7,41
9,65
11,47
8,64
10,91
12,71
8,67
11,08
13,16
8,45
11,06
13,26
9,06
11,49
12,94
9,13
11,71
13,73
8,96
11,74
14,13
HEATING CAPACITIES
Air inlet temperature at condenser (dry bulb)
FMH 15
Minimum
airflow
2410 m3/h
Nominal
airflow
3170 m3/h
Maximum airflow rate
3575
Indoor Dry Bulb
15
18
20
23
25
27
15
19
20
23
25
27
15
19
20
23
25
27
NC
Net cooling capacity
(kW) :
• 12 •
-10 °C
-5 °C
0 °C
5°C
7 °C
10 °C
15 °C
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
10,12
10,07
10,04
9,98
9,94
9,90
10,34
10,28
10,26
10,21
10,17
10,13
10,46
10,40
10,38
10,33
10,29
10,25
4,46
4,69
4,85
5,09
5,25
5,42
4,47
4,77
4,85
5,09
5,26
5,42
4,56
4,88
4,96
5,21
5,38
5,56
11,66
11,59
11,53
11,44
11,38
11,32
11,95
11,85
11,82
11,74
11,68
11,62
12,10
12,00
11,98
11,89
11,84
11,78
4,68
4,91
5,07
5,32
5,49
5,66
4,65
4,95
5,03
5,27
5,44
5,60
4,72
5,03
5,11
5,36
5,53
5,70
13,19
13,08
13,01
12,89
12,81
12,73
13,55
13,40
13,37
13,25
13,17
13,09
13,74
13,59
13,56
13,44
13,36
13,28
4,89
5,12
5,29
5,54
5,72
5,90
4,82
5,13
5,20
5,45
5,61
5,78
4,87
5,17
5,25
5,50
5,67
5,84
14,71
14,57
14,47
14,32
14,22
14,12
15,13
14,94
14,89
14,75
14,65
14,55
15,35
15,17
15,12
14,97
14,88
14,77
5,08
5,33
5,50
5,76
5,95
6,14
4,98
5,29
5,37
5,62
5,79
5,97
5,01
5,32
5,40
5,65
5,82
5,99
15,31
15,16
15,05
14,89
14,78
14,67
15,75
15,55
15,50
15,34
15,23
15,12
15,99
15,79
15,74
15,58
15,48
15,37
5,16
5,41
5,58
5,85
6,04
6,24
5,05
5,36
5,44
5,69
5,86
6,04
5,06
5,37
5,45
5,70
5,88
6,06
16,21
16,04
15,92
15,74
15,62
15,49
16,69
16,46
16,41
16,23
16,11
15,99
16,95
16,72
16,67
16,49
16,37
16,25
5,28
5,53
5,71
5,99
6,18
6,38
5,14
5,46
5,54
5,79
5,97
6,16
5,15
5,46
5,54
5,79
5,97
6,15
17,69
17,49
17,35
17,14
17,00
16,85
18,24
17,97
17,90
17,69
17,55
17,41
18,53
18,27
18,20
17,99
17,85
17,71
5,47
5,73
5,92
6,21
6,42
6,64
5,30
5,62
5,71
5,97
6,16
6,35
5,29
5,60
5,69
5,95
6,13
6,32
NH
Net heating capacity
(kW) :
SC
Sensible cooling capacity
(kW) :
Compressor absorbed
AC
(kW) : power
Application Guide • FLATAIR-AGU-MSL60-1505-E
7 - CAPACITIES
COOLING CAPACITIES
Air inlet temperature at condenser (dry bulb)
Indoor wet
bulb
21
24
27
24
27
30
27
30
33
21
24
27
24
27
30
27
30
33
21
24
27
24
27
30
27
30
33
3090 m3/h
16
19
22
4500 m3/h
16
19
22
16
4850 m3/h
Maximum airflow rate
Nominal airflow rate
Minimum airflow rate
Mixed air
temperature
°C
Indoor dry bulb
FMC/H 20
19
22
20 °C
25 °C
30 °C
35°C
40 °C
44 °C
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
19,16
19,14
19,30
20,92
20,82
20,89
22,99
22,81
22,80
19,98
20,10
20,40
21,78
21,81
22,03
23,88
23,84
23,96
19,93
20,08
20,46
21,73
21,80
22,05
23,85
23,84
23,99
6,03
6,02
6,04
6,17
6,16
6,16
6,34
6,32
6,32
6,57
6,58
6,62
6,71
6,71
6,74
6,88
6,88
6,89
6,82
6,84
6,88
6,96
6,97
7,00
7,13
7,13
7,15
11,63
14,52
16,83
11,31
14,41
16,83
10,52
13,89
16,50
13,41
16,93
19,89
13,20
16,95
20,04
12,52
16,57
19,88
13,83
17,47
20,46
13,67
17,55
20,78
13,06
17,23
20,69
18,60
18,61
18,79
20,29
20,22
20,32
22,31
22,15
22,16
19,37
19,51
19,84
21,10
21,16
21,40
23,14
23,13
23,27
19,30
19,48
19,92
21,04
21,14
21,41
23,09
23,11
23,29
6,35
6,34
6,37
6,50
6,48
6,49
6,67
6,65
6,65
6,88
6,89
6,94
7,03
7,04
7,07
7,21
7,21
7,22
7,15
7,17
7,22
7,30
7,31
7,35
7,48
7,48
7,50
11,40
14,22
16,48
11,12
14,13
16,50
10,39
13,66
16,21
13,15
16,58
19,48
12,97
16,62
19,64
12,36
16,29
19,52
13,54
17,09
19,92
13,43
17,20
20,36
12,88
16,94
20,31
17,92
17,95
18,16
19,55
19,50
19,63
21,50
21,37
21,41
18,63
18,81
19,15
20,30
20,39
20,66
22,28
22,29
22,47
18,56
18,76
19,26
20,23
20,35
20,65
22,22
22,26
22,47
6,74
6,74
6,77
6,90
6,89
6,90
7,08
7,06
7,07
7,26
7,29
7,33
7,43
7,44
7,47
7,62
7,62
7,64
7,56
7,59
7,63
7,72
7,74
7,78
7,91
7,92
7,94
11,11
13,85
16,06
10,88
13,79
16,10
10,22
13,38
15,86
12,82
16,14
18,98
12,69
16,22
19,16
12,15
15,95
19,09
13,20
16,64
19,26
13,13
16,77
19,85
12,65
16,58
19,85
17,11
17,18
17,41
18,68
18,66
18,82
20,57
20,47
20,53
17,78
17,98
18,22
19,38
19,50
19,79
21,30
21,34
21,54
17,69
17,92
18,50
19,30
19,45
19,78
21,22
21,29
21,53
7,26
7,26
7,29
7,42
7,41
7,43
7,61
7,59
7,60
7,77
7,79
7,97
7,94
7,96
8,00
8,14
8,15
8,18
8,11
8,14
8,17
8,28
8,30
8,34
8,48
8,49
8,52
10,77
13,40
15,55
10,59
13,39
15,62
10,01
13,05
15,44
12,42
15,63
18,22
12,35
15,74
18,59
11,90
15,55
18,58
12,78
16,09
18,50
12,76
16,27
19,24
12,38
16,14
19,30
16,19
16,28
16,54
17,70
17,71
17,89
19,52
19,45
19,54
16,80
17,03
17,35
18,34
18,49
18,81
20,20
20,26
20,49
16,70
16,96
17,62
18,25
18,42
18,78
20,11
20,21
20,47
7,96
7,96
8,00
8,12
8,12
8,14
8,32
8,31
8,32
8,46
8,49
8,72
8,65
8,67
8,71
8,86
8,87
8,90
8,86
8,89
8,90
9,04
9,07
9,11
9,25
9,26
9,30
10,37
12,88
14,95
10,24
12,91
15,05
9,76
12,65
14,94
11,95
15,01
17,35
11,94
15,18
17,91
11,58
15,06
17,97
12,28
15,44
17,62
12,32
15,66
18,53
12,03
15,62
18,66
15,37
15,48
15,76
16,82
16,85
17,05
18,60
18,54
18,65
15,94
16,18
16,58
17,43
17,59
17,93
19,23
19,31
19,56
15,82
16,10
16,83
17,32
17,52
17,89
19,13
19,25
19,53
8,74
8,75
8,78
8,91
8,91
8,93
9,10
9,10
9,11
9,23
9,25
9,55
9,43
9,45
9,48
9,65
9,66
9,69
9,71
9,73
9,69
9,90
9,92
9,96
10,11
10,13
10,16
9,99
12,39
14,39
9,92
12,47
14,53
9,52
12,27
14,47
11,52
14,45
16,58
11,56
14,65
17,29
11,28
14,61
17,41
11,82
14,85
16,83
11,91
15,11
17,87
11,71
15,13
18,06
HEATING CAPACITIES
Air inlet temperature at condenser (dry bulb)
FMH 20
4500 m3/h
4850 m3/h
3090 m3/h
Nominal
airflow
Maximum airflow rate
Minimum
airflow
Indoor Dry Bulb
15
18
20
23
25
27
15
19
20
23
25
27
15
19
20
23
25
27
GC
Gross cooling capacity
(kW) :
-10 °C
-5 °C
0 °C
5°C
7 °C
10 °C
15 °C
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
13,12
13,12
13,13
13,15
13,16
13,19
13,56
13,53
13,53
13,52
13,52
13,53
13,79
13,75
13,74
13,73
13,72
13,72
5,19
5,51
5,73
6,10
6,35
6,62
5,29
5,69
5,80
6,13
6,37
6,62
5,50
5,92
6,03
6,38
6,62
6,88
15,13
15,08
15,06
15,04
15,03
15,02
15,68
15,59
15,57
15,52
15,50
15,47
15,93
15,83
15,81
15,75
15,72
15,70
5,57
5,89
6,12
6,49
6,75
7,03
5,60
5,99
6,10
6,43
6,67
6,91
5,77
6,19
6,30
6,64
6,88
7,14
17,14
17,05
17,00
16,94
16,90
16,87
17,80
17,65
17,62
17,53
17,48
17,43
18,07
17,92
17,89
17,79
17,73
17,68
5,93
6,26
6,50
6,88
7,16
7,45
5,89
6,29
6,40
6,74
6,97
7,22
6,05
6,46
6,57
6,91
7,16
7,41
19,15
19,03
18,95
18,84
18,78
18,72
19,92
19,72
19,68
19,54
19,46
19,38
20,23
20,02
19,97
19,83
19,74
19,66
6,30
6,65
6,89
7,30
7,59
7,89
6,19
6,60
6,71
7,05
7,30
7,55
6,32
6,74
6,85
7,20
7,45
7,71
19,96
19,82
19,73
19,61
19,53
19,46
20,77
20,55
20,50
20,35
20,26
20,17
21,09
20,86
20,80
20,65
20,55
20,46
6,45
6,80
7,06
7,47
7,76
8,08
6,31
6,72
6,83
7,18
7,43
7,69
6,43
6,85
6,97
7,32
7,57
7,83
21,18
21,01
20,90
20,75
20,66
20,57
22,05
21,80
21,74
21,56
21,45
21,35
22,38
22,12
22,06
21,88
21,76
21,65
6,67
7,04
7,30
7,73
8,04
8,37
6,49
6,91
7,03
7,38
7,64
7,90
6,60
7,03
7,14
7,50
7,76
8,03
23,20
22,99
22,86
22,67
22,55
22,43
24,19
23,88
23,80
23,59
23,45
23,32
24,55
24,23
24,15
23,93
23,79
23,65
7,06
7,45
7,74
8,19
8,53
8,88
6,80
7,24
7,36
7,73
8,00
8,28
6,89
7,34
7,45
7,83
8,10
8,38
NH
Net heating capacity
(kW) :
Application Guide • FLATAIR-AGU-MSL60-1505-E
SC
Sensible cooling capacity
(kW) :
Compressor absorbed
AC
(kW) : power
• 13 •
7 - CAPACITIES
COOLING CAPACITIES
Air inlet temperature at condenser (dry bulb)
Indoor wet
bulb
21
24
27
24
27
30
27
30
33
21
24
27
24
27
30
27
30
33
21
24
27
24
27
30
27
30
33
3455 m3/h
16
19
22
5470 m3/h
16
19
22
16
5750m3/h
Maximum airflow rate
Nominal airflow rate
Minimum airflow rate
Mixed air
temperature
°C
Indoor dry bulb
FMC/H 25
19
22
20 °C
25 °C
30 °C
35°C
40 °C
44 °C
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
23,00
22,91
23,05
25,15
24,97
25,01
27,60
27,31
27,25
24,31
24,44
24,80
26,43
26,46
26,73
28,84
28,77
28,93
24,01
24,17
24,56
26,12
26,19
26,48
28,53
28,49
28,67
7,15
7,13
7,15
7,29
7,27
7,27
7,49
7,46
7,46
7,92
7,93
7,97
8,09
8,10
8,13
8,32
8,32
8,34
8,37
8,39
8,43
8,54
8,55
8,58
8,77
8,77
8,80
13,63
16,87
19,43
13,21
16,71
19,42
12,18
16,02
18,96
15,92
20,01
23,44
15,65
20,02
23,62
14,79
19,51
23,37
16,20
20,34
23,84
16,01
20,43
24,09
15,24
20,01
23,94
22,35
22,28
22,45
24,42
24,25
24,32
26,77
26,51
26,46
23,55
23,70
24,08
25,58
25,63
25,92
27,90
27,86
28,03
23,23
23,41
23,82
25,26
25,34
25,66
27,57
27,56
27,76
7,54
7,53
7,55
7,68
7,67
7,68
7,89
7,87
7,87
8,28
8,30
8,35
8,47
8,48
8,52
8,72
8,73
8,76
8,79
8,81
8,86
8,97
8,99
9,03
9,22
9,23
9,26
13,33
16,52
19,05
12,94
16,38
19,04
11,97
15,72
18,62
15,59
19,60
22,98
15,35
19,63
23,16
14,57
19,17
22,95
15,86
19,91
23,36
15,69
20,01
23,62
15,00
19,64
23,50
21,55
21,50
21,68
23,52
23,38
23,46
25,79
25,54
25,52
22,63
22,80
23,20
24,57
24,65
24,95
26,80
26,78
26,97
22,30
22,50
22,93
24,24
24,34
24,67
26,46
26,47
26,69
8,03
8,03
8,06
8,18
8,17
8,19
8,40
8,39
8,39
8,75
8,78
8,83
8,96
8,98
9,02
9,23
9,25
9,28
9,32
9,36
9,41
9,53
9,55
9,60
9,81
9,83
9,87
12,98
16,08
18,56
12,63
15,97
18,58
11,73
15,37
18,21
15,19
19,08
22,40
15,00
19,14
22,60
14,29
18,75
22,44
15,43
19,37
22,75
15,31
19,50
23,02
14,70
19,19
22,95
20,58
20,55
20,76
22,47
22,34
22,45
24,64
24,42
24,42
21,55
21,75
22,17
23,41
23,50
23,82
25,55
25,54
25,75
21,21
21,43
21,90
23,05
23,18
23,53
25,19
25,21
25,46
8,67
8,69
8,72
8,83
8,83
8,86
9,06
9,06
9,08
9,36
9,40
9,47
9,60
9,63
9,68
9,91
9,94
9,98
10,05
10,09
10,06
10,28
10,32
10,37
10,60
10,63
10,68
12,56
15,55
17,97
12,25
15,48
18,01
11,45
14,96
17,70
14,70
18,46
21,68
14,56
18,55
21,91
13,95
18,24
21,81
14,92
18,71
21,90
14,85
18,88
22,29
14,33
18,65
22,28
19,46
19,45
19,67
21,25
21,15
21,28
23,34
23,14
23,15
20,32
20,53
20,97
22,08
22,19
22,54
24,13
24,14
24,38
19,95
20,19
20,79
21,71
21,85
22,23
23,75
23,80
24,06
9,57
9,60
9,65
9,73
9,75
9,79
9,98
9,99
10,03
10,22
10,28
10,35
10,49
10,54
10,60
10,85
10,90
10,95
11,09
11,15
11,01
11,36
11,41
11,48
11,73
11,78
11,84
12,06
14,92
17,26
11,82
14,89
17,34
11,11
14,46
17,10
14,12
17,71
20,82
14,04
17,85
21,08
13,53
17,62
21,05
14,30
17,92
20,79
14,30
18,13
21,41
13,88
17,99
21,47
18,44
18,45
18,69
20,17
20,08
20,22
22,18
21,99
22,03
19,21
19,44
28,25
20,90
21,03
21,39
22,88
22,91
23,16
18,83
19,09
19,80
20,52
20,68
21,07
22,49
22,56
22,84
10,61
10,65
10,71
10,75
10,80
10,85
11,01
11,06
11,11
11,21
11,27
7,35
11,51
11,58
11,65
11,92
11,99
12,06
12,32
12,39
12,09
12,62
12,70
12,77
13,05
13,13
13,20
11,59
14,34
16,60
11,41
14,35
16,71
10,80
14,00
16,53
13,58
17,01
26,61
13,56
17,20
20,31
13,14
17,04
20,34
13,73
17,19
19,80
13,78
17,44
20,60
13,44
17,37
20,72
HEATING CAPACITIES
Air inlet temperature at condenser (dry bulb)
FMH 25
5470 m3/h
5750
3455 m3/h
Nominal
airflow
Maximum airflow rate
Minimum
airflow
Indoor Dry Bulb
15
18
20
23
25
27
15
19
20
23
25
27
15
19
20
23
25
27
NC
Net cooling capacity
(kW) :
• 14 •
-10 °C
-5 °C
0 °C
5°C
7 °C
10 °C
15 °C
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
16,02
16,00
15,99
15,99
16,00
16,01
16,69
16,63
16,62
16,59
16,57
16,56
17,12
17,05
17,04
17,00
16,99
16,97
6,72
7,13
7,43
7,92
8,28
8,67
6,77
7,26
7,39
7,81
8,11
8,43
7,21
7,74
7,88
8,34
8,67
9,03
18,42
18,35
18,31
18,26
18,23
18,21
19,27
19,14
19,11
19,03
18,98
18,94
19,72
19,58
19,55
19,47
19,42
19,37
7,21
7,64
7,95
8,46
8,83
9,24
7,14
7,63
7,76
8,18
8,48
8,80
7,54
8,06
8,20
8,65
8,98
9,32
20,79
20,67
20,60
20,50
20,44
20,38
21,82
21,62
21,58
21,45
21,36
21,29
22,30
22,09
22,05
21,91
21,83
21,75
7,71
8,16
8,48
9,02
9,41
9,84
7,51
8,00
8,13
8,55
8,86
9,18
7,87
8,39
8,53
8,98
9,31
9,66
23,15
22,98
22,87
22,72
22,63
22,54
24,35
24,09
24,03
23,84
23,73
23,62
24,85
24,58
24,52
24,33
24,22
24,10
8,22
8,69
9,03
9,60
10,02
10,48
7,88
8,38
8,52
8,95
9,27
9,60
8,21
8,74
8,89
9,35
9,68
10,03
24,09
23,90
23,78
23,60
23,50
23,39
25,36
25,07
25,00
24,80
24,67
24,55
25,87
25,57
25,50
25,30
25,17
25,04
8,42
8,91
9,26
9,85
10,29
10,76
8,03
8,54
8,68
9,12
9,44
9,78
8,35
8,89
9,03
9,50
9,84
10,20
25,49
25,27
25,13
24,92
24,80
24,67
26,87
26,53
26,45
26,22
26,08
25,93
27,39
27,05
26,97
26,74
26,59
26,44
8,74
9,25
9,62
10,24
10,69
11,19
8,26
8,79
8,93
9,38
9,71
10,06
8,57
9,12
9,26
9,74
10,08
10,45
27,80
27,53
27,36
27,11
26,94
9,30
9,85
10,26
10,93
11,43
29,36
28,96
28,86
28,58
28,40
28,22
29,91
29,50
29,41
29,12
28,94
28,76
8,66
9,21
9,36
9,84
10,19
10,56
8,94
9,52
9,67
10,17
10,53
10,92
NH
Net heating capacity
(kW) :
SC
Sensible cooling capacity
(kW) :
Compressor absorbed
AC
(kW) : power
Application Guide • FLATAIR-AGU-MSL60-1505-E
7 - CAPACITIES
COOLING CAPACITIES
Air inlet temperature at condenser (dry bulb)
Indoor wet
bulb
21
24
27
24
27
30
27
30
33
21
24
27
24
27
30
27
30
33
21
24
27
24
27
30
27
30
33
3695 m3/h
16
19
22
5060 m3/h
16
19
22
16
5500 m3/h
Maximum airflow rate
Nominal airflow rate
Minimum airflow rate
Mixed air
temperature
°C
Indoor dry bulb
FMC/H 30
19
22
20 °C
25 °C
30 °C
35°C
40 °C
41 °C
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
SC
NC
AC
27,18
27,15
27,18
29,61
29,57
29,59
32,26
32,21
32,21
28,49
28,48
28,54
31,01
31,00
31,04
33,76
33,73
33,75
28,47
28,47
28,53
31,02
31,02
31,06
33,80
33,78
33,81
8,87
8,87
8,88
9,10
9,09
9,10
9,31
9,30
9,30
9,38
9,38
9,39
9,62
9,61
9,62
9,84
9,83
9,84
9,80
9,80
9,81
10,04
10,03
10,04
10,25
10,25
10,25
16,14
19,69
22,96
15,82
19,36
22,58
15,37
18,87
22,04
18,20
22,81
27,13
17,73
22,39
26,73
17,10
21,80
26,15
18,76
23,64
28,25
18,27
23,25
27,90
17,62
22,66
27,36
26,31
26,30
26,35
28,63
28,60
28,64
31,16
31,12
31,14
27,49
27,50
27,57
29,90
29,90
29,95
32,52
32,51
32,55
27,43
27,45
27,57
29,87
29,88
29,94
32,52
32,52
32,56
9,37
9,37
9,38
9,63
9,63
9,63
9,86
9,86
9,87
9,86
9,86
9,87
10,13
10,13
10,14
10,39
10,38
10,39
10,32
10,32
10,37
10,59
10,60
10,60
10,85
10,85
10,85
15,73
19,25
22,52
15,40
18,92
22,13
14,97
18,45
21,61
17,80
22,34
26,61
17,34
21,94
26,23
16,74
21,38
25,69
18,34
23,14
27,57
17,89
22,77
27,36
17,27
22,23
26,87
25,21
25,22
25,28
27,41
27,40
27,45
29,82
29,80
29,83
26,27
26,29
26,38
28,55
28,57
28,64
31,06
31,06
31,11
26,16
26,20
26,51
28,48
28,50
28,58
31,01
31,02
31,08
10,02
10,02
10,03
10,31
10,32
10,33
10,59
10,59
10,60
10,48
10,49
10,50
10,81
10,81
10,82
11,11
11,11
11,12
11,00
11,01
11,08
11,33
11,34
11,35
11,63
11,63
11,64
15,24
18,70
21,92
14,93
18,38
21,56
14,52
17,95
21,08
17,30
21,72
25,90
16,88
21,36
25,57
16,33
20,86
25,08
17,82
22,50
26,51
17,41
22,17
26,65
16,86
21,69
26,22
23,88
23,90
23,98
25,96
25,96
26,03
28,25
28,24
28,29
24,81
24,85
25,04
26,97
27,00
27,09
29,36
29,37
29,44
24,66
24,71
25,25
26,86
26,89
26,99
29,27
29,29
29,37
10,89
10,90
10,92
11,25
11,26
11,27
11,58
11,58
11,60
11,33
11,34
11,66
11,73
11,74
11,75
12,10
12,10
12,11
11,95
11,96
12,06
12,36
12,37
12,39
12,73
12,74
12,75
14,66
18,03
21,17
14,38
17,74
20,85
14,02
17,36
20,43
16,68
20,95
25,04
16,32
20,65
24,72
15,84
20,22
24,32
17,18
21,67
25,25
16,83
21,41
25,74
16,36
21,02
25,40
22,32
22,35
22,44
24,27
24,29
24,37
26,45
26,45
26,51
23,11
23,17
23,62
25,16
25,20
25,30
27,42
27,45
27,53
22,93
22,99
23,79
25,00
25,05
25,16
27,30
27,33
27,42
12,17
12,18
12,21
12,63
12,64
12,66
13,04
13,05
13,06
12,58
12,59
13,09
13,10
13,11
13,12
13,56
13,56
13,58
13,37
13,38
13,51
13,91
13,92
13,94
14,39
14,39
14,41
13,97
17,20
20,22
13,74
16,97
19,96
13,45
16,66
19,63
15,93
19,99
23,62
15,64
19,77
23,67
15,26
19,44
23,37
16,39
20,65
23,79
16,12
20,48
24,61
15,75
20,19
24,38
21,98
22,01
22,11
23,91
23,93
24,01
26,06
26,07
26,13
22,74
22,80
23,31
24,77
24,81
24,92
27,01
27,04
27,13
22,55
22,62
23,47
24,60
24,66
24,77
26,87
26,91
27,01
SC
12,50 13,82
12,52 17,01
12,54 20,01
12,99 13,60
13,00 16,80
13,02 19,77
13,42 13,32
13,43 16,51
13,45 19,45
12,90 15,76
12,91 19,77
13,46 23,31
13,45 15,49
13,46 19,57
13,48 23,43
13,94 15,13
13,94 19,26
13,96 23,16
13,74 16,21
13,76 20,42
13,89 23,47
14,32 15,96
14,33 20,27
14,35 24,35
14,82 15,61
14,83 20,00
14,84 24,15
HEATING CAPACITIES
Air inlet temperature at condenser (dry bulb)
FMH 30
50600 m3/h
5500 m3/h
2695 m3/h
Nominal
airflow
Maximum airflow rate
Minimum
airflow
Indoor Dry Bulb
15
18
20
23
25
27
15
19
20
23
25
27
15
19
20
23
25
27
GC
Gross cooling capacity
(kW) :
-10 °C
-5 °C
0 °C
5°C
7 °C
10 °C
15 °C
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
NH
AC
18,30
18,32
18,35
18,40
18,45
18,51
18,63
18,61
18,61
18,63
18,66
18,69
18,97
18,94
18,93
18,94
18,96
18,98
7,75
8,25
8,60
9,18
9,59
10,03
7,57
8,18
8,34
8,86
9,23
9,62
7,86
8,50
8,67
9,22
9,61
10,01
21,01
20,97
20,95
20,94
20,95
20,96
21,49
21,39
21,37
21,32
21,30
21,29
21,88
21,76
21,74
21,68
21,65
21,64
8,31
8,82
9,19
9,78
10,21
10,65
8,04
8,66
8,82
9,34
9,71
10,09
8,29
8,93
9,10
9,64
10,02
10,42
23,70
23,59
23,53
23,46
23,42
23,39
24,33
24,14
24,10
23,99
23,93
23,88
24,77
24,57
24,52
24,40
24,33
24,27
8,87
9,40
9,78
10,40
10,84
11,31
8,50
9,13
9,29
9,82
10,19
10,58
8,71
9,35
9,52
10,06
10,44
10,85
26,37
26,19
26,09
25,95
25,87
25,80
27,16
26,88
26,82
26,64
26,54
26,45
27,65
27,35
27,29
27,10
26,99
26,89
9,43
9,99
10,39
11,04
11,51
12,01
8,96
9,60
9,77
10,31
10,70
11,10
9,13
9,78
9,95
10,50
10,90
11,31
27,43
27,23
27,11
26,95
26,85
26,76
28,28
27,97
27,90
27,70
27,58
27,47
28,79
28,46
28,39
28,18
28,05
27,93
9,66
10,23
10,64
11,31
11,79
12,31
9,14
9,79
9,96
10,51
10,91
11,32
9,30
9,96
10,13
10,69
11,08
11,50
29,02
28,78
28,63
28,43
28,31
28,20
29,96
29,60
29,52
29,28
29,13
28,99
30,50
30,12
30,04
29,79
29,63
29,49
10,01
10,60
11,03
11,72
12,23
12,77
9,42
10,08
10,26
10,83
11,23
11,66
9,56
10,23
10,40
10,97
11,38
11,81
31,65
31,35
31,16
30,89
30,73
30,57
32,75
32,30
32,19
31,89
31,70
31,52
33,34
32,87
32,76
32,45
32,25
32,06
10,61
11,24
11,71
12,46
13,01
13,60
9,90
10,59
10,78
11,38
11,80
12,26
10,00
10,69
10,88
11,47
11,90
12,35
NH
Net heating capacity
(kW) :
Application Guide • FLATAIR-AGU-MSL60-1505-E
SC
Sensible cooling capacity
(kW) :
Compressor absorbed
AC
(kW) : power
• 15 •
7 - CAPACITIES
CORRECTION COEFICIENTS
CALCULATION OF COOLING CAPACITY DEPENDING ON AIR FLOW
INDOOR & OUTDOOR AIRFLOW RATES
Sizes 10-12-15-20
Sizes 25-30
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Cooling capacity
x 0.97
x 1.00
x 1.01
x 0.98
x 1.00
x 1.01
Sensible capacity
x 0.90
x 1.00
x 1.03
x 0.95
x 1.00
x 1.02
CALCULATION OF HEATING POWER DEPENDING ON AIR FLOW
INDOOR & OUTDOOR AIRFLOW RATES
Sizes 10-12-15-20
Sizes 25-30
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Cooling capacity
x 0.98
x 1.00
x 1.01
x 0.91
x 1.00
x 1.03
Sensible capacity
x 0.98
x 1.00
x 1.01
x 0.98
x 1.00
x 1.01
• 16 •
Application Guide • FLATAIR-AGU-MSL60-1505-E
8 - ELECTRICAL DATA
UNITS WITHOUT ELECTRICAL HEATER (STANDARD UNITS)
PACKAGED UNIT (INDOOR+ OUTDOOR)
TYPE
10-230 l
10
12
15
20
25
30
Maximum power (KW)
5,5
5,3
6,6
7,8
10,4
12,6
14,2
Maximum current (A)
31,7
13,7
16,0
18,6
23,6
30,0
31,0
Starting current (A)
90,2
34,1
39,7
49,0
75,3
82,3
86,9
LRC (A)
133,7
48,7
57,2
70,8
109,6
120,0
127,0
10
12
15
20
25
30
INDOOR UNIT
TYPE
10-230 l
Maximum power (KW)
0,4
0,4
0,4
0,8
1,0
1,3
1,3
Maximum current (A)
2,6
2,6
2,6
2,8
4,3
4,3
4,3
Starting current (A)
1,7
1,7
1,7
1,8
2,8
2,8
2,8
LRC (A)
2,6
2,6
2,6
2,8
4,3
4,3
4,3
10-230 l
10
12
15
20
25
30
Maximum power (KW)
5,1
4,9
6,1
7,0
9,4
11,3
13,0
Maximum current (A)
29,1
11,1
13,4
15,8
19,3
25,7
26,7
Starting current (A)
87,6
31,5
37,1
46,2
71,0
78,0
82,6
LRC (A)
131,1
46,1
54,6
68,0
105,3
115,7
122,7
25
30
OUTDOOR UNIT
TYPE
ELECTRICAL HEATER (add the following consumption for heat pump units)
TYPE
Power input (kW)
Maximum current (A)
Application Guide • FLATAIR-AGU-MSL60-1505-E
10-230 l
10
12
15
20
3
3
4.5
7.5
6
6
6
9
9
9
12
13.0
7.5
11.3
18.8
26.1
15
15
22.5
-
22.5
22.5
30
• 17 •
9 - DIMENSIONS
9.1 - UNIT DIMENSION
FIX 10-12
FSC / FSH 10-12
• 18 •
Application Guide • FLATAIR-AGU-MSL60-1505-E
9 - DIMENSIONS
9.1 - UNIT DIMENSION
FIX 15
FSC / FSH 15
Application Guide • FLATAIR-AGU-MSL60-1505-E
• 19 •
9 - DIMENSIONS
9.1 - UNIT DIMENSION
FIC / FIH 20
FSC / FSH 20
• 20 •
Application Guide • FLATAIR-AGU-MSL60-1505-E
9 - DIMENSIONS
9.1 - UNIT DIMENSION
FIC / FIH 25-30
FSC / FSH 25-30
Application Guide • FLATAIR-AGU-MSL60-1505-E
• 21 •
9 - DIMENSIONS
9.1 - UNIT DIMENSION
FMC/FMH 10-12
FMC/FMH 15
• 22 •
Application Guide • FLATAIR-AGU-MSL60-1505-E
9 - DIMENSIONS
9.1 - UNIT DIMENSION
FMC/FMH 20
FMC/FMH 25-30
Application Guide • FLATAIR-AGU-MSL60-1505-E
• 23 •
9 - DIMENSIONS
9.2.- DUCT POSITION
MODELS 10-12-15
SPLIT UNIT
Packaged unit
Outdoor fan
Outdoor fan
Indoor fan
Indoor fan
Electrical heater
Electrical heater
O
O
ut
co
il
Compressor
or
co
il
do
co
il
Ind
oo
r
or
co
il
do
Ind
oo
r
ut
Compressor
MODEL 20
SPLIT UNIT
Packaged unit
Compressor
Compressor
Indoor fan
Indoor fan
il
l
oi
c
or
do
co
Electrical heater
d
Electrical heater
ut
r
oo
ut
O
Outdoor fan
Ind
Ind
oo
oo
rc
rc
oil
oil
O
Outdoor fan
MODELS 25-30
Packaged unit
Indoor fan
Compressor
oo
Ind
oo
rc
il
co
l
oil
r
oo
i
co
or
do
td
Ou
Electrical heater
Outdoor fan
Outdoor fan
STANDARD
• 24 •
rc
oil
t
Ou
Electrical heater
Indoor fan
OPTION
Ind
Compressor
SPLIT UNIT
ELECTRICAL BOX
Application Guide • FLATAIR-AGU-MSL60-1505-E
10 - INSTALLATION
10.1 - REFRIGERANT CONNECTIONS
Split units are supplied with gas and liquid lines sealed with copper covers, and located 60mm from casing.
Service ports
Gas
Cupper
cover
Brazing
Terminal
block
Liquid
Split units are supplied with nitrogen gas, this must be removed and then proceed as folow:
1. Remove the nitrogen gas through the high and low 5/16” service ports located inside and provide a low vacuum for safety.
2. Remove the caps from the connecting lines.
3. Braze the piping connection lines. Select piping diameter from table 2.7.1.
(When brazing refrigerant pipes, nitrogen gas must be supplied into the pipes through the service ports to remove the air).
4. Leak test:
Add nitrogen gas, check that a pressure of 5 kg/cm2 has been reached and that there are no leaks in the circuit or brazing
by applying soapy water to the pipes which will cause the bubbles to form where there are leaks.
To detect small leaks, proceed as follows:
Add nitrogen gas and check that a pressure of 25 kg/cm2 has been reached, there are no leaks if the pressure remains the same
for at least 24 hours and the final pressure is not less than 10% below the initial pressure.
5. Ensure that the gas line is insulated.
6. Evacuation:
Remove the nitrogen gas, connect the gauge manifold and vacuum pump to both the liquid and gas lines, fully open the gauge
manifold valve and switch on the vacuum pump. Check to make sure the gauge shows a pressure of -750mm Hg. Once a level
of -750mm Hg is reached, keep the vacuum pump running for at least one hour.
7. Refrigerant charge:
- Check TABLE 3.1. and 3.2. for the amount of refrigerant charge, depending on the length and size of the pipe connections.
- Disconnect the vacuum pump and connect to the refrigerant-charging bottle. Open the charging pump and purge the air from
the hose at the pressure gauge manifold.
- Set up the amount of additional refrigerant on the weighing scale, open the high pressure and charged in the liquid state. If the
total amount of refrigerant charge has not been reached because the pressure is balanced, turn off the high side of the gauge
manifold, turn on the unit, and add the remaining amount of the refrigerant charge required slowly through the low side of the
pressure gauge. (With R-410A refrigerant, the charging bottle must be in a vertical position and charged in the liquid state).
Close the pressure gauge, disconnect it from the from the service port of the unit and fit caps on the service ports. The unit is
then ready to operate.
During installation operations, keep gas and liquid pipes covered, in order to prevent humidity and dirt,
get into them.
Take special concern about refrigerant pipes are isolated.
Avoid collapse on line installation.
Application Guide • FLATAIR-AGU-MSL60-1505-E
• 25 •
10 - INSTALLATION
10.2 - REFRIGERANT CONNECTIONS
To locate the outdoor and the indoor units, refer to the following information:
OUTDOOR UNIT
A,B,C: Units positions
L: Total length
1: Gas line
2: Liquid line
INDOOR UNIT
OUTDOOR UNIT
INDOOR UNIT
OUTDOOR UNIT
INDOOR UNIT
POSITION A:
A syphon suction must be installed on the vertical line of the gas line 1, and syphons must be installed every 8 meters upward. The
minimum speed suction must not be below 6 m/s.
POSITION B:
Tip the lines toward the outdoor unit. Make special attention to the line length longer than 10m and avoid collapse on pipe lines
installation.
w
DISPOSICIÓN C:
Install a syphon at the base of the vertical line, no more syphons are necessary.
TABLE 2.7.1.: REFRIGERANT LINES
SIZE
REFRIGERANT LINES
10
12
15
20
25
30
Liquid
3/8”
3/8”
1/2”
1/2”
5/8”
5/8”
Gas
3/4”
3/4”
7/8”
7/8”
1 1/8”
1 1/8”
Maximum vertical line length (m)
15
15
15
15
15
15
Maximum number of bends
12
12
12
12
12
12
Total length
0 to 30m
For other positions and lines lengths between 30 and 50m or longer, consult the commercial-technical department, pipe dimensions, syphon suction, isolations, refrigerant load, line lengths.
Split units are supplied with nitrogen gas.The installer should remove this gas and charge the units with the charge of refrigerant
R410A , shown in the table 2.7.2 plus the charge by additional meter shown in the table 2.7.3.
• 26 •
Application Guide • FLATAIR-AGU-MSL60-1505-E
10 - INSTALLATION
TABLE 2.7.2 : REFRIGERANT CHARGE
MODELS
Cooling only
Refrigerant charge
R-410A
Heat pump
10
12
15
20
25
30
2,14
2,57
3,55
4,46
5,38
6,15
2,5
2,93
4
4,9
6,3
7
TABLE 2.7.3 : EXTRA REFRIGERANT CHARGE R410A BY METER
Liquid
Gas
g/m
3/8”
3/4”
57
1/2”
7/8”
108
5/8”
1 1/8”
177
10.3 - ELECTRICAL CONNECTIONS
- Before making any electrical connections, ensure that all circuit breakers are open.
- In order to make the electrical connections, follow the electrical diagram supplied with the unit.
POWER SUPPLY
POWER SUPPLY 230V
SINGLE PHASE UNITS
Nº of cables x section (mm²)
SIZE
Supply without electrical
coil
Supply with electrical coil
10
3x4
3 x 16
POWER SUPPLY 400V THREE-PHASE UNITS
Nº of cables x section (mm²)
SIZE
Supply without electrical
coil
Supply with electrical coil
10
5 x 2,5
5x4
12
5 x 2,5
5x4
15
5x4
5x6
20
5x4
5 x 10
25
5x6
5 x 10
30
5x6
5 x 10
VOLTAGE OPERATING LIMITS: 342-462V
SIZE
10
12-15-20-25-30
Application Guide • FLATAIR-AGU-MSL60-1505-E
VOLTAGE
LIMIT
230V-1Ph-50 Hz
198-264 V
400V-3Ph-50 Hz
400V-3Ph-50 Hz
342-462 V
• 27 •
10 - INSTALLATION
DC 40 THERMOSTAT, ELECTRICAL CONNECTION
CONTROL PANEL
GND TX+ TX- GO
90
GND
TX+
TX-
91
92
93
G
94
GO
G
DC 40
2 x Shielded twisted pairs AWG 20. 100 m maximum.
1x Shielded twisted pair AWG20 + 2 x 1,5 mm. 200m maximum.
IMPORTANT
THE SHIELDED CONNECTING CABLE BETWEEN THE CONTROL PANEL AND THE UNIT MUST BE SEPARATED FROM
ANY OTHER TYPE OF ELECTRICAL WIRING. CONNECT IT TO THE ELECTRIC PANEL LOCATED IN THE OUTDOOR UNIT.
NOTES:
- For securing and connecting the Control Panel, consult the control panel Manual supplied with the unit.
- Connection between the DC40 and the unit must be made using shielded twisted pair cables (where the screens
are connected to the control panel and the unit Electrical box).
- The Tx+ and Tx- polarity must strictly comply with the electrical diagram supplied with the unit.
• 28 •
Application Guide • FLATAIR-AGU-MSL60-1505-E
11 - OPTIONS
ELECTRIC HEATER
Optionally, these units can contain shielded element electric heating batteries that are mounted on the inside of the
unit in the schematic opposite.
The electric heater must get its power from the unit’s electrical box.
10
1F
UNIT
STANDARD (kW)
10
3F
15
3
MEDIUM (kW)
HIGH
12
20
4.5
6
-
25
30
7.5
9
9
12
MAIN SWITCH
The main switch is located on the access panel to the electrical box in the outdoor section in such a way that the unit is disconnected when the panel is opened.
(Refer to the size diagram a pages 20 to 31 to see the position of the electrical box access panel).
Check to make sure that the main switch is large enough to handle the current for the unit if electric heaters are installed.
PHASE SEQUENCER (THREE-PHASE UNIT)
The phase sequencer is located in the electrical box in the outdoor section, thus assuring that the unit will not begin operation while
the phase connection of the compressor is not correct. Should this occur, then just switch two phase connections.
REMOTE ROOM TEMPERATURE SENSOR, REMOTE DUCT SENSOR
These sensors may be used in conjunction with remote controller, allowing the controller to be mounted in a room away from the
conditioned space.
- REMOTE DUCT SENSOR : The sensor will be located in the return air duct, detecting the air temperature of the air being air
conditioned.
- REMOTE ROOM TEMPERATURE SENSOR : The sensor will be placed in the area to be air conditioned.
KIT 0 DEGREES TEMPERATURE :
This kit includes an crankase heater in the cooling only version , to allow working with outdoor temperatures up to 0 degrees .In
heat pump orders , this crankase heater comes as standard .
KIT -15 DEGREES TEMPERATURE :
This kit includes a proportional regulation of the outdoor fan , to allow working with outdoor temperatures up to minus 15 degrees.
FREECOOLING ONE DAMPER
Fresh air damper regulated by the control , to introduce fresh air from the ambient if the temperature conditions are favourable .
SECOND DAMPER FREECOOLING
Second damper for the freecooling , to regulate the return air regarding the % of fresh air introduced in the room . This option is
only valid with the option FREECOOLING ONE DAMPER.
LOW NOISE LEVEL
Compressor jacket to reduce the sound level around 2 dBA.
AIRFLOW CONFIGURATIONS
These units have different configurations to manage the airflow , both in the indoor and outdoor section .
Application Guide • FLATAIR-AGU-MSL60-1505-E
• 29 •
lennoxemeia.com
SALES OFFICES :
BELGIUM AND LUXEMBOURG
 + 32 3 633 3045
FRANCE
 +33 1 64 76 23 23
GERMANY
 +49 (0) 211 950 79 600
ITALY
 + 39 02 495 26 200
RUSSIA
 +7 495 626 56 53
SPAIN
 +34 915 401 810
UKRAINE
 +380 44 585 59 10
UNITED KINGDOM AND IRELAND
 +44 1604 669 100
NETHERLANDS
 + 31 332 471 800
POLAND
 +48 22 58 48 610
PORTUGAL
 +351 229 066 050
OTHER COUNTRIES :
LENNOX DISTRIBUTION
 +33 4 72 23 20 20
Due to Lennox’s ongoing commitment to quality, the specifications,
ratings and dimensions are subject to change without notice and
without incurring liability.
Improper installation, adjustment, alteration, service or
maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer
and servicing agency
FLATAIR AGU-MSL60-1505-E