T16B

Cecomp® ThermoPro® Battery Powered Digital Temperature Indicators
OO 100 Ω Platinum RTD
OO 316 Stainless Steel Probe
OO Capture Minimum and Maximum Readings
T16B, T16BBL
OO –58.0°F to 392.0°F or –50.0°C to 200.0°C
OO NEMA 4X Housing
OO Spring-Loaded Versions for Thermowells
Specifications
Range and Resolution
User selectable °F, °C or K
–58.0°F to 392.0°F
–50.0°C to 200.0°C
220.0K to 475.0K
0.1 degree resolution
Accuracy
Includes linearity, hysteresis, repeatability
±0.3°C at 0°C
±1.1°C at 150°C
11-point linearization table
Display
4 readings per second nominal display update rate
4 digit LCD, 0.5" H
5 character 0.25" H alphanumeric
BL models: red LED backlight
Low battery voltage indication
ALARM1 under range indication on display
ALARM2 over range indication on display
Sensor
IEC-751 Class B 100 Ω Platinum RTD, 0.00385 alpha curve
1
/2" NPT male, 316L stainless steel
All wetted parts are 316L stainless steel
Thermowell required for spring-loaded versions
Spring-loaded probe fits standard thermowells
Fixed probe pressure rating: 5000 psi max.
Fixed probes are welded to hex fitting
Controls and Functions
Three front buttons for power on/off, min/max functions,
selection of °F, °C, or K, auto shutoff times, calibration and,
configuration options
User-defined pass codes for configuration and calibration to
prevent unauthorized changes
Dimensions
3.5"
2.0"
Low battery
indication
ALARM 1
XXXXX
88888
s
Turn at
hex
fitting
only!
1.37"
3.0"
ALARM 2
t
0.75"
1.25"
Hex nipple
1/2" NPT x 1/2" NPT
316 stainless
Stem
Length
L
Measured from
top of full threads
to tip of probe.
Length L =
thermowell “A”
or “element
length”
Maximum and Minimum Readings
User-configurable maximum and/or minimum temperature
indication. Factory default configuration MAX/MIN disabled.
Choice of MAX only, MIN only, MAX/MIN, or none
Option to retain or clear MAX/MIN temperatures at shutoff
Auto Shutoff Time
1, 2, 5, 10, 15, 20, 30 minutes, 1, 2, 4, 8 hours, or manual
on/off
OFF warning before shutoff to allow button reset of auto
shutoff timer
Factory default 5 minutes
Calibration
User settable pass code required to enter calibration mode
Zero and span temperature calibration
Non-interactive zero, span, and linearity, ±10% of range
Batteries, Battery Life, Low Battery Indication
B: 2 AA alkaline, approx. 1000 hours
BL: 2 AA alkaline, approx. 150 to 750 hours depending on
backlight usage
Button press activates backlighting for 1 minute
Low battery symbol on display
Weight
Product:
12 ounces (approximately)
Shipping:
1 pound (approximately)
Housing Materials
ABS/polycarbonate NEMA 4X case, rear gasket, polycarbonate
label, aluminum sensor block
Storage Temperature
–40 to 203°F (–40 to 95°C)
Operating Range
–4 to 185°F (–20 to 85°C) at housing
Thermowell
Stem
Length
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
Made in USA
See thermowell manufacturer’s specifications. Probe length
is measured from top of full threads to tip of probe.
Quick Link
cecomp.com/thermopro
Battery Replacement
How to Order
A low battery indication will be shown in the upper left-hand
corner of the display when the battery voltage falls sufficiently.
The batteries should be replaced soon after the indicator
comes on to prevent unreliable readings.
If unit does not power up, replace the batteries.
1. Loosen the 6 Phillips screws on the back of the unit until the
cover can be removed
2. Remove the battery cover and remove the batteries by lifting up the positive end of the battery (opposite the spring)
taking care not to bend the battery holder spring.
3.Discard old batteries properly, do not discard into fire,
sources of extreme heat, or in any hazardous manner.
4. Always replace both batteries at the same time with high
quality alkaline batteries. Install batteries with correct orientation. The negative (flat) end of each battery should be
inserted first facing the battery holder spring.
5. Replace the back cover, including the sealing gasket.
°F/°C, shutoff times and min/max functions are field configurable. If you require a certain configuration to be pre-set from
the factory, please indicate it on your order.
Option—add to end of model number
-CC Conformal coating on circuit board for moisture
resistance
Continuous weld
on non-spring
loaded models
0.25" dia.
Spring-loaded models
approx. 0.25" longer
to compress element
in thermowell.
0.50" max.
compression
ThermoPro T16B
Battery Powered
Temperature
Indicator
Cecomp maintains a constant effort to upgrade and improve its products.
Specifications are subject to change without notice. Consult factory for your
specific requirements.
CE C O MP Div. of ABSOLUTE PROCESS INSTRUMENTS
Model
T16B2
T16B4
T16B6
T16B9
T16B12
T16B2S
T16B4S
T16B6S
T16B9S
T16B12S
T16BBL2
T16BBL4
T16BBL6
T16BBL9
T16BBL12
T16BBL2S
T16BBL4S
T16BBL6S
T16BBL9S
T16BBL12S
Length
2.5" L fixed length
4" L fixed length
6" L fixed length
9" L fixed length
12" L fixed length
2.5" L spring-loaded
4" L spring-loaded
6" L spring-loaded
9" L spring-loaded
12" L spring-loaded
2.5" L fixed length
4" L fixed length
6" L fixed length
9" L fixed length
12" L fixed length
2.5" L spring-loaded
4" L spring-loaded
6" L spring-loaded
9" L spring-loaded
12" L spring-loaded
1220 American Way Libertyville, IL 60048
800-942-0315
Backlighting
None
Red LED display
backlight
cecomp.com
© 03-17
Cecomp ThermoPro® Battery Powered Temperature Indicator Instructions
Precautions
Read these instructions before installation. Configuration may
be easier before installation.
Install or remove thermometer using a wrench on the hex fitting
only. Do not attempt to turn by forcing the housing.
Do not exceed maximum allowable housing temperature.
The spring-loaded design must be used with a thermowell.
The fixed probe design can be used in applications with low or
no material flow. Due to the hardness of 316 stainless steel,
it is recommended that a thread sealant be used to ensure
leak-free operation.
Normal Operation
To turn the unit on, press the left front power button.
The display segments are tested.
The actual temperature and units are displayed and updated
approximately 4 times per second.
The factory default configuration is °F, 5 minute auto shutoff
and MAX/MIN disabled.
The auto shutoff timer is reset whenever any button is pressed.
To shut off the unit manually at any time, press and hold the
power button until OFF is displayed (up to about 5 seconds
total if MAX/MIN is enabled) and then release the button.
If the unit is configured with an auto shutoff time, a five second
warning period is provided prior to auto shutoff, during which
the display indicates OFF. Press any button to reset timer.
If so equipped, the optional display backlighting can be turned
on by momentarily pressing a button whenever the thermometer is on. The backlighting will turn on for one minute and then
automatically shut off. This also restarts the auto shutoff timer.
The display backlighting will not be apparent under bright
lighting conditions.
Temperature Unit Selection
To change temperature units, press and hold the s (up) button
until the temperature indication is blank and only the temperature units are displayed.
Then use the s or t buttons to select the desired temperature
units. Standard units are Fahrenheit, Celsius, and Kelvin.
When the desired units are displayed, press and release the
power button to save the selection and exit the change mode.
If no buttons are pressed for 15 seconds, the unit will automatically save the selection and exit the change mode.
Auto Shutoff Time Selection
To change the auto shutoff time, press and hold the t (down)
button until the auto shutoff time is displayed.
The auto shutoff time is shown on the upper display. AST M
indicates auto shutoff time in minutes, and AST H in hours.
Use the s or t buttons to select 0, 1, 2, 5, 10, 15, 20, or 30
minutes, or 1, 2, 4, or 8 hours.
Setting the time to zero to disables the auto shutoff timer and
the thermometer will stay on until manually shut off or until
the batteries are depleted. Use the power button to turn the
thermometer off when not in use to conserve battery life.
When the desired auto shutoff time is displayed, press and
release the power button to save the selection and exit the
change mode.
If no buttons are pressed for 15 seconds, the unit will automatically save the selection and exit the change mode.
User Configuration Mode
With the unit off, press and hold the s button. Then press the
power button. Release buttons when the display indicates CFG.
Before the unit enters the Configuration Mode, the display
initially indicates _ _ _ _ with the first underscore blinking,
and with CFGPC on the character display.
Note: The unit will automatically revert to normal operation if no
buttons are operated for approximately 15 seconds. To cancel
and return to normal operation, press and release the power
button without entering any pass code numbers.
Enter the user configuration pass code (3510 factory default):
Use the s or t buttons to set the left-most digit to 3.
Press and release the power button to index to the next position. The 3 will remain, and the next position will be blinking.
Use the s or t buttons to select 5.
Press and release the power button to index to the next position. 3 5 will remain, and the third position will be blinking.
Use the s or t buttons to select 1.
Press and release the power button to index to the next position. 3 5 1 will remain, and the fourth position will be blinking.
Use the s or t buttons to select 0.
Press and release the power button to proceed with configuration procedures. Note: If an incorrect pass code is entered, the
unit will return to the start of the pass code entry sequence.
MAX/MIN configuration
The upper display will be blank.
Use the s or t buttons to select from the following:
MX/MN Both highest and lowest values will be captured
MX/--
Only highest value measured will be captured
--/MN Only lowest value measured will be captured
--/--
Capture feature is disabled
Press and release the power button to move on to the next
parameter.
MAX/MIN memory
The upper display will indicate clr.
Use the s or t buttons to select from the following:
AUTO Maximum and Minimum values will automatically
be cleared whenever the unit shuts off.
MAN
Maximum and Minimum values will be retained
and must be cleared manually as desired.
Press and release the power button to save the user configuration and restart the unit.
Maximum and Minimum Readings
Thermometers are normally configured with maximum and
minimum capture functions disabled. One or both can be
enabled in the User Configuration mode.
If enabled, step the unit through the display modes by pressing
the power button for about 1 second until the display indicates
either MAX or MIN or degree units. The display mode cycles
through the following steps:
MAX mode: The maximum temperature is shown with the
lower display alternating between MAX and the degree units.
The thermometer may be left in this mode if a display of the
maximum reading is desired.
MIN mode: The minimum temperature is shown with the lower
display alternating between MIN and the degree units. The
thermometer may be left in this mode if a display of the minimum reading is desired.
Normal mode: The current temperature and the degree units
are displayed.
To manually reset the memory, press and continue to hold the
power button until the display indicates clr (about 3 seconds
total) and then release the button. The stored maximum and
minimum values are cleared. The unit returns to normal operation with the display indicating the current temperature.
The memory may be configured to be automatically cleared
when the unit shuts down, or may be configured to retain the
maximum and minimum values at shutoff.
Calibration Mode
Select the temperature units for calibration prior to entering the
calibration mode. The use of Fahrenheit or Celsius is assumed
in this procedure.
To enter the calibration mode, begin with the unit powered off,
and press and hold the t button. Then press the power button.
Release all buttons when the display indicates CAL.
Before the unit enters the Calibration Mode, the display initially
indicates _ _ _ _ with the first underscore blinking, and with
CALPC on the character display.
Enter the user-modifiable pass code (3510 factory default) as
described in the previous section:
The unit enters and remains in the Calibration Mode until
restarted manually or power is removed. While in the
Calibration Mode, the auto shutoff timer is disabled, the display backlight (if so equipped) is disabled, and the Max/Min
feature is disabled.
CE C O MP Div. of ABSOLUTE PROCESS INSTRUMENTS
T16B, T16BBL
The unit is calibrated at ice point and at a temperature above
ice point. For general service, the full scale temperature is
normally used for the second point. However, if a particular
temperature is of critical interest it may be used instead for
greatest accuracy at that point.
When the applied temperature is below approximately 12°C (or
54°F), the unit will automatically select the ice-point calibration mode.
Calibration Procedure
Upon successful pass code entry, the upper segments of the
display will indicate the RTD probe temperature. The lower
segments of the display will alternate as indicated below.
Note: To store the calibration parameters and exit calibration
mode at any time, press and hold the power button until the
display indicates - - - - .
Ice-point calibration: Apply 0.0°C or 32.0°F to the RTD.
The lower display will alternate between ICE and DEG C or
DEG F.
Use the s and t buttons to adjust the display to indicate
0.0°C or 32.0°F.
Span calibration
Apply full-scale temperature to the RTD. The lower display will
alternate between CAL and DEG C or DEG F.
Use the s and t buttons to adjust the upper display to indicate the desired temperature value.
To store the calibration parameters and exit calibration mode,
press and hold the power button until the display indicates
----.
Changing the User-Defined Pass Codes
Configuration pass code: With the unit off, press and hold the
s button to view and/or change the user configuration pass
code. Then press the power button. Release all buttons when
the display indicates CFG.
Calibration pass code: With the unit off, press and hold the t
button to view and/or change the user calibration pass code.
Then press the power button. Release all buttons when the
display indicates CAL.
Before the unit enters the view or change pass code mode,
the display initially indicates _ _ _ _ with the first underscore
blinking, and CFGPC or CALPC on the character display.
Note: The unit will automatically revert to normal operation if no
buttons are operated for approximately 15 seconds. To cancel
and return to normal operation, press and release the power
button without entering any pass code characters.
Enter access code 1220
Use the s and t buttons to set the left-most digit to 1.
Press and release the power button to index to the next position. The 1 will remain, and the next position will be blinking.
Use the s and t buttons to select 2.
Press and release the power button to index to the next position. 1 2 will remain, and the third position will be blinking.
Use the s and t buttons to select 2.
Press and release the power button to index to the next position. 1 2 2 will remain, and the fourth position will be blinking.
Use the s and t buttons to select 0.
Press and release the power button to proceed. Note: If an
incorrect access code was entered, the unit will return to the
start of the access code entry sequence.
Once the correct access code has been entered, the display
will indicate the existing user-defined pass code with CFGPC
or CALPC on the character display.
Operate the s or t button to select the first character of the
new pass code.
When the correct first character is being displayed, press and
release the power button to proceed to the next pass code
character.
Repeat above until the entire pass code is complete.
To exit the view or change pass code mode, press and hold the
power button. Release the button when the display indicates
– – – – to restart the unit.