Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-1 Log #1170q NEC-P18 _______________________________________________________________________________________________ Russell LeBlanc, The Peterson School In articles 90 through 830, if the wording is not already there, then add the words (or other structure(s)) after the word BUILDING(S) wherever the intent of the requirement is to also include STRUCTURES as well as buildings. There is a flaw in the NEC. The term "building" is used over 1000 times in the NEC, and in most of the cases the words "or other structure" should follow and apply the same requirements to bridges, billboards, towers, tanks, and other structures that are by definition NOT BUILDINGS. One specific example I can use is section 225.10 Wiring on Buildings. I believe that this section is also intended to be applied structures, but the wording "or other structures" is not in the heading or the paragraph. There are literally thousands of other instances throughout the code that this same problem exists. This can easily be seen by doing an electronic search for the word "building". In some cases the words "or other structure" (or similar wording) are present, but in the vast majority where the requirements should also be applied to structures other than buildings, the wording is not there. The substantiation does not demonstrate a definitive problem exists with the current text. It may not be appropriate to add "or other structures" in all cases. Affirmative: 10 _______________________________________________________________________________________________ 18-2 Log #921q NEC-P18 _______________________________________________________________________________________________ Joe Tedesco, Boston, MA The term "adequate" and "adequately" and "inadequately" and "inadequate" should be replaced with terms that can be properly enforced and understood. Terms are not defined and are considered vague and unenforceable per Table 3.2.1 in the NEC Style Manaual. They are all "incorrect" 148 times in the NEC. The proposal does not specify where the terms are used nor does it suggest replacement terms. Affirmative: 10 Printed on 3/16/2012 1 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-3 Log #2889 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Revise text to read as follows: Systems of illumination utilizing fluorescent lamps, high-intensity discharge (HID) lamps, or neon tubing. Systems of illumination utilizing fluorescent lamps, high-intensity discharge (HID) lamps, or neon tubing. The defined term is referenced in several articles of the NEC: 100 I, 210, 300, 310, 410, 450, 600, In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the . Affirmative: 10 _______________________________________________________________________________________________ 18-4 Log #1483 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Revise text to read as follows: A lighting system consisting of an isolating power supply, the low voltage luminaires, and associated equipment that are all identified for the use. The output circuits of the power supply are rated for not more than 25 amperes and operate at 30 volts (42.4 volts peak) or less under all load conditions. A lighting system consisting of an isolating power supply, the low voltage luminaires, and associated equipment that are all identified for the use. The output circuits of the power supply are rated for not more than 25 amperes and operate at 30 volts (42.4 volts peak) or less under all load conditions. The defined term is referenced in several articles of the NEC: (4), , ,& In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the . Section 250.22(4) does not use the term "lighting systems operating at 30 volts or less" and Table 680.3 uses the term "site lighting systems operating at 30 volts or less." Even using the exposure in Article 680 there is only one article where this term is used and therefore the existing wording is in compliance with Section 2.2.2.1 of the 2011 edition of the NEC Style Manual. Affirmative: 10 Printed on 3/16/2012 2 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-5 Log #1482 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Revise text to read as follows: A manufactured assembly designed to support and energize luminaires that are capable of being readily repositioned on the track. Its length can be altered by the addition or subtraction of sections of track. A manufactured assembly designed to support and energize luminaires that are capable of being readily repositioned on the track. Its length can be altered by the addition or subtraction of sections of track. The defined term is referenced in several articles of the NEC: , ,& In general, Article 100 shall contain definitions of terms that appear in two or more other articles of the . Relocate the definition to Article 100 and revise text to read as follows: A manufactured assembly designed to support and energize luminaires that are capable of being readily repositioned on the track. Its length can be altered by the addition or subtraction of sections of track. The term is modified to reflect the use of the two terms in other locations in the code. Affirmative: 10 _______________________________________________________________________________________________ 18-6 Log #1188 NEC-P18 _______________________________________________________________________________________________ Marcelo M. Hirschler, GBH International Revise text to read as follows: A complete lighting unit consisting of a light source such as a lamp or lamps, together with the parts designed to position the light source and connect it to the power supply. It may also include parts to protect the light source or the ballast or to distribute the light. A lampholder itself is not a luminaire. It may also include parts to protect the light source or the ballast or to distribute the light A lampholder itself is not a luminaire. The NFPA Manual of Style requires definitions to be in single sentences. The information provided in the subsequent sentences is not really a part of the definition; it is further information that is best placed in an informational note. Because the NEC is formatted differently from other NFPA standards the CMP uses the NEC Style manual for editorial and administrative requirements. When not specified in this manual the panel complies with the NFPA Manual of Style. In reviewing section 2.2.2.2 of the NEC Style Manual and section 2.3.2 of the NFPA Manual of Style no reference to requiring definitions in one sentence exists. Affirmative: 10 Printed on 3/16/2012 3 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-7 Log #3350a NEC-P18 _______________________________________________________________________________________________ Steven R. Montgomery, 2D2C Inc. Add new text to read as follows: Equipment incorporating means to detect certain out of parameter conditions of supply voltage and load current and mitigate, by circuit interruption, the effects of (a) overload within utilization equipment; and (b) over- or under-voltage, that can pose a risk of fire ignition under certain conditions. A definition of an Out of Parameter Circuit Interrupter - Voltage/Current (OPCI-VI) is needed to describe this fire prevention technology presently manufactured by multiple suppliers and under consideration for adoption in several places elsewhere in NFPA 70. Note that sister proposals have been submitted as a new 210.13 and 406.3(D). Staff Note: This proposal has also been sent to Code-Making Panel 2 for review and action. The definition is not justified because the submitter has not specified how much the parameters must be out of specification to be able to serve as a fire prevention technology. While nothing in the Code would prevent the installation of such a Listed device, no requirement should be in place since there is no fact finding or other scientific study that correlates the amount of out of spec the parameters must be to be consider a fire prevention device. Affirmative: 10 _______________________________________________________________________________________________ 18-8 Log #1195 NEC-P18 _______________________________________________________________________________________________ Marcelo M. Hirschler, GBH International Revise text to read as follows: A receptacle is a contact device installed at the outlet for the connection of an attachment plug. A single receptacle is a single contact device with no other contact device on the same yoke. A multiple receptacle is two or more contact devices on the same yoke. A single receptacle is a single contact device with no other contact device on the same yoke. A multiple receptacle is two or more contact devices on the same yoke. The NFPA Manual of Style requires definitions to be in single sentences. The information provided in the subsequent sentences is not really a part of the definition; it is further information that is best placed in an informational note. definition style. Refer to the panel action and statement on Proposal 18-6 which addresses the submitter's issue of Affirmative: 10 Printed on 3/16/2012 4 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-9 Log #2619 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Add new text to read as follows: A general term for a complete subassembly of parts and devices for field conversion of utilization eguipment. As applied to luminaires, signs and outline lighting for conversion of illumination systems. Extensive upgrades are underway to achieve greater energy efficiency in signs and luminaires by replacing in-place illumination systems with LEDs. This largely encompasses field modification of signs or luminaires. Field modifications of utilization equipment usually require a field evaluation by a qualified electrical testing laboratory. Testing laboratories, such as Underwriter's Laboratories have developed protocols for these field conversions, such that when done within the testing laboratory parameters, do not compromise the safety profile of the listed sign or luminaire. As an example, to ensure that the parts are compatible with the field modification, Underwriters Laboratories requires all the parts for luminaire and sign conversions to be assembled into a that UL labels as . A Code definition will provide a basis for, (1) use of conversion subassemblies, (2) inclusion in applicable ANSI UL standards for producers of the retrofit kits, (3) a basis for AHJs approval of field modified wiring in listed signs and luminaires, and (4) their use by the installer. Revise the submitter's recommendation: Delete the last sentence and revise the remainder to read as follows: A general term for a complete listed subassembly of parts and devices for field conversion of utilization equipment. The inclusion of the word "listed" complies more closely with the panels intent as stated in section 410.6 and 600.3 that retrofit kits be listed. Retrofit kits are not unique to luminaires, signs and outline lighting. Affirmative: 10 Printed on 3/16/2012 5 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-10 Log #2135 NEC-P18 _______________________________________________________________________________________________ Robert Wong, BSafe Electrix, Inc. Add new definitions as follows: A protective assembly is an integral part of a device, such as a receptacle, that, when properly applied, will cut off electrical power to the load when the temperature of the device reaches a preset temperature, at which point no further heat will be generated. Therefore this assembly protects the device, wiring, outlet box and the immediate area surrounding the outlet box, from abnormal heating. The Thermal Protected may consist of one or more sensor elements as an integral or external part of the device. The words Thermally Protected or TP appearing on the device indicate that the device includes a thermal protector. Add new text as follows: 406.4(D)(7) Thermally Protected Receptacles. Thermal Protected Receptacles shall be provided where required elsewhere in the Code. Revise 550.13(3) as follows: 550.13(3) Except where supplying specific appliances, either 15- or 20-ampere, 125-volt, either single or multiple type, and except for parallel-blade attachment plugs, Thermally Protected Receptacle, or a CO/ALR Receptacle. PROBLEM TO BE RESOLVED: Electrical outlet fires continue to this day to be identified and reported in manufactured - mobile homes. According to the USFA, electrical fires in manufactured-mobile homes claim over 300 American lives and over 1000 injuries each year. Further, over the past years, incidents of such fires in manufactured homes have received the scrutiny of experts, academia researchers, including UL and the Electrical Wiring Device Industry. Such reports are numerous, and a select few reports of fire statistics are referenced in this NEC proposal. Over the past 40 years, a percentage of the electrical receptacle outlet fires each year in manufactured homes have been caused by one or more of the following combination of conditions which occur: improper wiring at first installation loose wiring connections, and the additional stress caused by the mechanical - vibration disturbance that receptacles in a manufactured home are subjected to during normal use. Other often cited causes of electrical fires are, loose connections between an appliance plugged into receptacles in mobile homes due travel/movement of the mobile home, and lack of adequate space in the mobile home hence many ignitable materials are placed near the loose appliance plugged into the receptacles. These NEC proposals will result in an increased safe use of receptacles in manufactured-mobile homes, thereby reducing future incidents of property damage and loss of life that may occur in an electrical fire, resulting from overheated receptacle outlet/wiring. It is a reality, a fact of life for the future. If these proposed NEC changes are not implemented, electrical receptacle outlet failures and the subsequent electrical fires that in many cases mask their cause and origin, will continue to occur in mobile houses. It is critical for our families' safety that an insidious receptacle overheating condition in a receptacle wall outlet be detected and mitigated prior to ignition of combustible materials in the receptacle outlet or its vicinity. The Receptacle with Thermal Protection and CO/ALR Receptacle are UL Listed devices are presently available in the market place today. UL STANDARD/ NEC BACKGROUND: UL Standard 498, Attachment Plugs and Receptacles, provides safety requirements that only address normal electrical installation conditions, but not under conditions of use. In turn, NEC Article 110.3(A) specifically states in item (5), "Heating effects under normal conditions of use and also under abnormal conditions likely to arise in service", is a consideration that is to be evaluated as a condition as it is "essesntial to safe use or proper functioning of the equipment." SUBSTANTIATION: Improper wiring in electrical wiring installations in manufactured - mobile homes was addressed years ago when aluminum wiring problems were first addressed by UL, NEMA, NBS, and others in the Industry. This fact is explicitly stated in the " " titled, " " (including " In items B and C, in the first paragraph on page 2 of the , it is noted that ". And, in the first paragraph of the , it is stated that " ". Printed on 3/16/2012 6 Report on Proposals – June 2013 NFPA 70 This " " including the " ", prepared under the auspices of an Ad Hoc Committee sponsored by Underwriters' Laboratories, Inc., is provided as an attachment to these proposals. The eleven organizations that served on the Ad Hoc Committee are listed on the last page of the Statement. This collaborative effort by NEMA, NBS, UL, Industry Members including NECA, and IBEW-NECA is testimony to the fact that " does exist in electrical installations with copper wiring in the field today and that overheating of receptacles and snap switches can occur use. Therefore, under Article 110.3(A) Item 5, Abnormal, or improper wiring installations should be considered as "conditions likely to arise in service". Thomas J. D'Agostino, PE, as a Lead Project Engineer at UL (1969-1978) in matters pertaining to connectability of wiring devices with aluminum as well as copper wiring, participated in (a) significant research projects that were the basis for the publication of the , and (b) specifically in the development of the Standard, addresses the "improperly wired - loose binding head screw connection", and vibration, conditions that occur in electrical installations in manufactured - mobile homes, and recreational vehicles. NEC PROPOSALS TO MANDATE THE USE OF THERMAL PROTECTED RECEPTACLES IN NEW MANUFACTURED (MOBILE) HOMES AND WHEN REPLACING RECEPTACLES IN EXISTING MANUFACTURED (MOBILE) HOMES TO ASSURE ADDITIONAL LEVEL OF SAFETY: Receptacles in manufactured mobile homes are subjected to more stringent conditions of abuse, such as vibration or mechanical disturbance due to travel/movement of the mobile home. The distinct performance of a Standard UL498 Listed Receptacle which has not been investigated to "abnormal conditions which might arise in service", as compared to the safer performance of a currently UL Listed Receptacle with Thermal Protection, has been demonstrated in research that has been conducted at Stony Brook University, N.Y. The Stony Brook Report demonstrates that Thermal Protected receptacles successfully cut off (interrupt) power when the temperature increases to a preset range due to loose connections and/or serial arcing. Without Thermal Protected assembly the temperature will continue to rise for an extended time, and easily surpass the allowable temperature for many materials, such as insulation materials. The Stony Brook University Research has clearly demonstrated the need for a higher level of safety - protection in receptacles that are installed in a manufactured - mobile home. The Receptacle with Thermal Protection or CO/ALR Receptacle provides this needed higher level of safety for use in manufactured - mobile homes. The receptacle with thermal protection has been investigated according to UL498 with additional thermal tests, and the CO/ALR Receptacle has been tested to both UL498 and UL1597. This proposal has also been sent to Code-Making Panel 19 for their review and action. Note: Supporting material is available for review at NFPA Headquarters. The submitter has not offered any acceptable scientific study that correlates the temperature cut-out value in a thermally protected receptacle with fire mitigating ability. While nothing in this Code precludes such a device from being installed, no mandate device should be required without a specific value of cut-off that can mitigate fires. The panel recommends the TCC refer this proposal to CMP 19. Affirmative: 10 Printed on 3/16/2012 7 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-10a Log #3235 NEC-P18 _______________________________________________________________________________________________ Mark C. Ode, Underwriters Laboratories Inc. Add new text to read as follows: Article 302 Low Voltage Suspended Ceiling Power Distribution Systems. Part I. General 302.1 Scope. This article covers the installation of low voltage suspended ceiling power distribution systems. 302.2 Definitions. Busbar. A non-insulated conductor electrically connected to the source of supply and physically supported on an insulator providing a power rail for connection to utilization equipment, such as sensors, actuators, A/V devices, low voltage luminaire assemblies and similar electrical equipment. Busbar Support. An insulator that runs the length of a section of suspended ceiling bus rail that serves to support and isolate the busbars from the suspended grid rail. Grid Bus Rail. A combination of the busbar, busbar support, and the structural suspended ceiling grid system. Connector. A term used to refer to an electro-mechanical fitting. Connector, Load. An electro-mechanical connector used for power from the busbar to utilization equipment. Connector, Pendant. An electro-mechanical or mechanical connector used to suspend low voltage luminaire or utilization equipment below the grid rail and to supply power from the busbar to utilization equipment. Connector, Power Feed. An electro-mechanical connector used to connect the power supply to a power distribution cable, to connect directly to the busbar, or from a power distribution cable to the busbar. Connector, Rail to Rail. An electro-mechanical connector used to interconnect busbars from one ceiling grid rail to another grid rail. Low Voltage Suspended Ceiling Power Distribution System. A system that serves as a support for a finished ceiling surface and consists of a busbar and busbar support system to distribute power to utilization equipment supplied by a Class 2 power supply. Power Supply. A Class 2 power supply connected between the branch circuit power distribution system and the busbar low voltage suspended ceiling power distribution system. Rail. The structural support for the suspended ceiling system typically forming the ceiling grid supporting the ceiling tile and listed utilization equipment, such as sensors, actuators, A/V devices and low voltage luminaires similar electrical equipment. Reverse Polarity Protection (Backfeed Protection). A system that prevents two interconnected power supplies connected positive to negative from passing current from one power source into a second power source. Suspended Ceiling Grid. A system which serves as a support for a finished ceiling surface and other utilization equipment. 302.6 Listing Requirements. Suspended ceiling power distribution systems and associated fittings shall be listed as in 302.6(A) or 302.6(B). (A) Listed System. Low voltage suspended ceiling distribution systems operating at 30 volts or less ac or 60 volts dc or less shall be listed as a complete system with the utilization equipment, power supply, and fittings as part of the same identified system. (B) Assembly of Listed Parts. A low voltage suspended ceiling power distribution system assembled from the following parts, listed according to the appropriate function, shall be permitted: (1) Listed low voltage utilization equipment (2) Listed Class 2 power supply (3) Listed or identified fittings, including connectors and grid rails with bare conductors (4) Listed low voltage cables in accordance with 725.179, conductors in raceways, or other fixed wiring methods for the secondary circuit. II. Installation 302.10 Uses Permitted. Low voltage suspended ceiling power distribution systems shall be permanently connected and shall be permitted as follows: (1) For listed utilization equipment capable of operation at a maximum of 30 volts ac (42.4 volts peak) or 60 volts dc (24.8 volts peak for dc interrupted at a rate of 10 to 200 Hz) and limited to Class 2 power levels in Table 11(A) and Table 11(B) for lighting, control, and signaling circuits Printed on 3/16/2012 8 Report on Proposals – June 2013 NFPA 70 (2) In indoor dry locations (3) For residential, commercial, and industrial installations (4) In other spaces used for environmental air in accordance with 300.22(C), electrical equipment having a metal enclosure or with nonmetallic enclosure and fittings, shall be listed for use within an air handling space and, have adequate fire-resistant and low-smoke-producing characteristics, and associated wiring material suitable for the ambient temperature Informational Note: One method of defining adequate fire resistant and low-smoke producing characteristics for electrical equipment with a nonmetallic enclosure is in ANSI/ UL 2043-2008, Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces. (5) For lighting in general or critical patient care areas 302.12 Uses Not Permitted. Suspended ceiling power distribution systems shall not be installed in the following: (1) In damp or wet locations (2) Where subject to corrosive fumes or vapors, such as storage battery rooms (3) Where subject to physical damage (4) In concealed locations (5) In hazardous (classified) locations (6) As part of a fire-rated floor ceiling or roof-ceiling assembly, unless specifically listed as part of the assembly 302.14 Installation (A) General Requirements. Support wiring shall be installed in a neat and workmanlike manner. Cables and conductors installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a manner that the cable is not be damaged by normal building use. Such cables shall be supported by straps, staples, hangers, cable ties, or similar fittings designed and installed so as not to damage the cable. Informational Note: Suspended ceiling low voltage power grid distribution systems should be installed by qualified persons in accordance with the manufacturer’s installation instructions. (B) Insulated Conductors. Exposed insulated secondary circuit conductors shall be listed and of the type, and installed as described in 302.14(B)(1) or (B)(2): (1) Class 2 cable supplied by a Listed Class 2 power source and installed in accordance with Parts I and III of Article 725 (2) Wiring methods described in Chapter 3 302.21 Disconnecting Means. (A) Location. A disconnecting means for the Class 2 supply to the power grid system shall be located so as to be accessible and within sight of the Class 2 power source for servicing or maintenance of the grid system. (B) Multiwire Branch Circuits. Where connected to a multiwire branch circuit, the disconnecting means shall simultaneously break all the supply conductors to the power supply in accordance with 210.4(B). 302.30 Securing and Supporting. (A) Attached to Building Structure. A suspended ceiling low voltage power distribution system shall be secured to the mounting surface of the building structure by hanging wires, screws, or bolts in accordance with the installation and operation instructions. Mounting hardware, such as screws or bolts, shall either be packaged with the suspended ceiling low voltage lighting power distribution system or the installation instructions shall specify the types of mounting fasteners to be used. (B) Attachment of Power Grid Rails. The individual power grid rails shall be mechanically secured to the overall ceiling grid assembly. 302.40 Connectors and Enclosures. (A) Connectors. Connections to busbar grid rail, cables, and conductors shall be made with listed insulating devices and these connections shall be accessible after installation. A soldered connection shall be made mechanically secure before being soldered. Other means of securing leads, such as push-on terminals and spade-type connectors, shall provide a secure mechanical connection. The following connectors shall be permitted to be used as connection or interconnection devices: (1) Load connectors shall be used for power from the busbar to listed utilization equipment. (2) A pendant connector shall be permitted to suspend low voltage luminaires or utilization equipment below the grid rail and to supply power from the busbar to the utilization equipment. (3) A power feed connector shall be permitted to connect the power supply directly to a power distribution cable and to the busbar. (4) Rail-to-rail connectors shall be permitted to interconnect busbars from one ceiling grid rail to another grid rail. Informational Note: For quick-connect terminals; see UL 310, Standard for Electrical Quick-Connect and for mechanical splicing devices, and see UL 486A and 486B, Standard for Wire Connectors. Printed on 3/16/2012 9 Report on Proposals – June 2013 NFPA 70 (B) Enclosures. Where made in a wall, connections shall be installed in an enclosure in accordance with Parts I, II and III of Article 314. 302.45 Overcurrent and Reverse Polarity (Back Feed) Protection. (A) Overcurrent Protection. The listed Class 2 power supply or transformer primary shall be protected at not greater than 20 amperes. (B) Interconnection of Power Sources. Listed Class 2 sources shall not have the output connections paralleled or otherwise interconnected, unless listed for such interconnection. (C) Reverse Polarity (Back Feed) Protection of DC Systems. A suspended ceiling low voltage power distribution system shall be permitted to have reverse polarity (back feed) protection of DC circuits by one of the following means: (1) If the power supply is provided as part of the system, the power supply is provided with reverse polarity (back feed) protection; or (2) If the power supply is not provided as part of the system, reverse polarity or back feed protection can be provided as part of the grid rail busbar or as a part of the power feed connector. 302.56. Splices. A busbar splice shall be provided with insulation and mechanical protection equivalent to that of the grid rail busbars involved. 302.57. Connections. Connections in busbar grid rails, cables, and conductors shall be made with listed insulating devices and be accessible after installation. Where made in a wall, connections shall be installed in an enclosure in accordance with Parts I, II, and III of Article 314, as applicable. 302.60 Grounding. (A) Grounding of Supply Side of Class 2 Power Source. The supply side of the Class 2 power source shall be connected to an equipment grounding conductor in accordance with the applicable requirements in Part IV of Article 250. (B) Grounding of Load Side of Class 2 Power Source. Class 2 load side circuits for suspended ceiling low voltage power grid distribution systems shall not be grounded. III. Construction Specifications 302.104. Sizes and Types of Conductors (A) Load Side Utilization Conductor Size. Current-carrying conductors for load side utilization equipment shall be copper and shall be 18 AWG minimum. Exception: Conductors of a size smaller than 18 AWG but not smaller than 24 AWG shall be permitted to be used for Class 2 circuits. Where used, these conductors shall be installed in a Chapter 3 wiring method, totally enclosed, shall not be subject to movement or strain, and shall comply with the ampacity requirements in Table 522.22. (B) Power Feed Bus Rail Conductor Size. The power feed bus rail shall be 16 AWG minimum or equivalent. For a busbar with a circular cross section, the diameter shall be 0.051 in. (1.29 mm) minimum, and, for other than circular 2 2 busbars, the area shall be 0.002 in. (1.32 mm ) minimum. The growing interest in alternative energy sources (e.g. photovoltaics, wind turbines, batteries, fuel cells, etc.) and the proliferation of low voltage, low power devices (sensors, LV lighting, IT equipment, AV equipment, etc.), has created a significant need for adequate language supporting the practical safeguarding of circuits and electrical equipment operating at 30 Volts AC or 60 Volts dc or less. The current code has specific requirements for power distribution at 30 volts or less for listed lighting devices and their associated listed components (as covered by Article 411 with reference to Article 725), but there is no similar requirements for power distribution at 30 volts or less for listed non-lighting systems and their associated listed components. The code is silent on the requirements for power distribution at 30 volts or less when non-lighting and lighting devices are connected in the same 30 volts or less power distribution system. Thus, the current code implies (although it does not specifically demand) that separate power distribution systems must be deployed in order to perform the identical task of low voltage power distribution at 30 volts or less. Due to equipment, wiring and overall system redundancy, this position is likely to be extremely wasteful from both an energy and economy viewpoints. This purposed article provides the specific requirements for the safe installation of low voltage, power limited power distribution, providing power to lighting and non-lighting loads. Drawing largely from Articles 411 and 725 this purposed article slightly expands the scope of these systems with the addition of low voltage/power limited (Class 2) non-lighting loads while maintaining the clear requirements necessary for safe installation. As technology changes, the construction and commercial office industry, as well as the various Codes and Standards affecting the buildings, must respond to provide a safe and reliable method of providing the appropriate flexibility of power for lighting, sensors, temperature control, and other functional aspects of the building. The low voltage grid distribution system is a very viable and important part of this flexible power distribution system. Printed on 3/16/2012 10 Report on Proposals – June 2013 NFPA 70 This proposal was developed as a part of a larger effort to provide clear and specific requirements in NFPA 70 regarding the use of dc power. There is a growing interest in the use of alternative energy sources (e.g. photovoltaics, wind turbines, batteries, fuel cells, etc.) this coupled with the reality that many of the loads installed ultimately use electricity in its dc form has renewed an interest in dc power and its distribution in buildings. While many parts of the Code cover dc power with specific requirements, other portions are not as clear. This proposal was developed by a subgroup of the NEC DC Task Force of the Technical Correlating Committee. The Task Force is chaired by John R. Kovacik, Underwriters Laboratories, the Subtask Group that developed this proposal consisted of the following people: Panel 3 Chairman Paul Casparro, representing the JATC of the International Brotherhood of Electrical Workers and Panel 3; Subtask Group Chairman Wendell Whistler, representing Intertek, Inc. and Panel 3; Lawrence S. Ayer representing Biz Com Electric of the Independent Electrical Contractors Association and Panel 3; Mike O’boyle, representing Philips Inc. and Panel 18; Mark C. Ode representing Underwriters Laboratories Inc. and Panel 3; Audi Spina, representing Armstrong Ceiling Inc. and special expert on low voltage ceiling grids; and Randy Wright, representing RKW Consulting and Panel 18. Affirmative: 10 _______________________________________________________________________________________________ 18-11 Log #1064 NEC-P18 _______________________________________________________________________________________________ James A. Gates, J. A. Gates Co. LLC Add new text to read as follows: All 110-120v plugs and receptacles to include "ELECTRICAL PLUG ALIGNMENT INDICATORS" . People often have difficulty aligning the wide blade side of a plug with the wide blade side of a receptacle. This is especially true for sight challenged people or when a receptacle is out of sight because of darkness or obscured by furniture. This becomes a safety issue with small children whose fingers can fit between the blades of the plug. Electrical plug alignment indicators are small bumps on the wide blade side of the plug and corresponding small bumps on the wide blade side of the receptacles or extension cords. These bumps provide a tactile signal to the user to help align the plug and receptacle without placing their fingers on the plug blades. Note: Supporting material is available for review at NFPA Headquarters. The UL/ANSI Standard requires receptacles to reject the improper insertion of a plug cap. If the plug does not go insert in one orientation, then it will go in when reversed. Affirmative: 10 Printed on 3/16/2012 11 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-12 Log #2704 NEC-P18 _______________________________________________________________________________________________ Steven Orlowski, National Association of Home Builders Revise text to read as follows: Replacement of receptacles shall comply with 406.4(D)(1) through (D)(6), as applicable. Where a receptacle outlet is supplied by a branch circuit that requires arc-fault circuit interrupter protection as specified elsewhere in this , a replacement receptacle at this outlet shall be one of the following: (1) A listed outlet branch circuit type arc-fault circuit interrupter receptacle (2) A receptacle protected by a listed outlet branch circuit type arc-fault circuit interrupter type receptacle (3) A receptacle protected by a listed combination type arc-fault circuit interrupter type circuit breaker This requirement becomes effective January 1, 2014. Once again, a new provision requiring an untested and unavailable technology has been introduced into the 2011National Electrical Code. There was a time when manufacturers would have been called out on using the national model code to promote a product or give them a market advantage on a technology that they had the sole capability to produce, sadly this is becoming the norm. This new provision will require an existing receptacle that becomes damaged or simply needs to be replaced with a receptacle that is either protected by AFCI breaker or be a listed AFCI receptacle. Where is the problem with replacing the receptacle with the same type or better yet where is the risk with replacing the receptacle with the same type? At this time only one manufacturer is rumored to have produced a receptacle that meets the code and it is not commercially available. Several comments were submitted during the last cycle, requesting the technical committee to reject this proposal based on the fact that the technology for these devices did not exist, much less that there weren’t any devices that had been listed by any testing agency meeting this requirement. Other reasons given by some well respected members of several other technical committees included the fact that many common and acceptable wiring techniques in existing homes could create problems and would be incompatible with an AFCI receptacle or AFCI breakers. For example many existing panelboards cannot accommodate an AFCI breaker. This means if a homeowner needed to replace a single broken receptacle in the home and the AFCI receptacle are still not available, they would then have to replace the entire panelboard and all the associated breakers within the dwelling. Another problem would arise with existing homes that were wired using multiwire branch circuits throughout which cannot be feed by a typical AFCI Breaker. A huge expense to meet a requirement that was not based on any significant technical substation regarding the number of fires or injuries that would be diverted. Until these devices have been rigorously tested not to suffer the same nuisance tripping that the AFCI breakers have and proven to meet the claims made by manufactures, we urge the removal of this requirement from the National Electrical Code. NAHB also urges the NEC code making panels to begin rejecting any and all proposals that would mandate the use of any new technology that does not include a cost benefit analysis in the substantiation. As of this time TWO manufacturers have Listed AFCI receptacles. During the last cycle, Panel 18 postponed the effective date until 2014, therefore commercial devices are not needed at this time. Also, the Coalition of AFCI receptacle manufacturers has demonstrated real devices at the ROP meeting. Section 90.4 of this Code allows the AHJ to revert to the previous Code if the device is unavailable at the time of inspection. Affirmative: 10 Printed on 3/16/2012 12 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-13 Log #3268 NEC-P18 _______________________________________________________________________________________________ Brian E. Rock, Hubbell Incorporated Revise 406.3(D) main text to read as follows: Receptacles incorporating an isolated grounding conductor connection intended for the reduction of electrical noise (electromagnetic interference) as permitted in 250.146(D) shall be identified by an orange triangle located on the face of the receptacle; such identification shall be visible after installation. Although 406.3(D) requires specific marking identification of isolated ground receptacles, the installation requirements in 406.3(D) and 250.146(D) make no mention that such identification be visible to the user after installation to coordinate with installation and use instructions of plug-and-cord-connected Listed instrumentation and equipment to comply with 110.3(B). The current wording of this section clearly states "shall be identified by an orange triangle located on the face of the receptacle." It does not seem possible that a receptacle can be installed where the face is not visible. Affirmative: 10 Printed on 3/16/2012 13 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-14 Log #3357 NEC-P18 _______________________________________________________________________________________________ Steven R. Montgomery, 2D2C Inc. Add new text to read as follows: Out of Parameter Circuit Interrupter - Voltage/Current (OPCI-VI) protected receptacles shall be provided where replacements are made at receptacle outlets that are required to be so protected elsewhere in this . Resistive heating and arcing faults ignite most of the major residential electrical fires. Resistive heating faults ignite 59% of the fires, in spite of branch circuit over-current protection (see “Electrical Ignition Causes of Fires in Ontario 2002-2007,” Electrical Safety Authority (ESA) report, 2008). The latest code enhancements, including Arc Fault Circuit Interrupters (per UL Std. 1699), are not designed to protect against resistive heating from current flowing through poor branch circuit connections (high resistance points), overloaded appliances and open neutral conditions. New homes may have aged and potentially faulty appliances, extension cords and lighting fixtures brought in by homeowners. The 2006 NFPA report titled “Selected Residential Electrical Fires” indicates these faults have resulted in numerous fire fatalities. Out of Parameter Circuit-Interrupter (OPCI-VI) technology is designed to provide primary protection against resistive heating ignition mechanisms including high resistance points in branch circuit wiring (cause of 23% of residential electrical fires, per the attached ESA 2008 report), appliance overloads (cause of 17% of the electrical fires), and open neutral conditions (cause of 2% of the electrical fires). OPCI-VI also provides supplementary protection against overloaded circuits (cause of 7% of the electrical fires) and insulation damage that leads to arc tracking (cause of 7% of the electrical fires). A large portion of residential electrical ignitions are caused by resistive heating that cannot be protected by branch circuit overcurrent devices but can be protected by OPCI-VI. OPCI-VI technology has been previously referred to as Electrical Fault Circuit Interrupter (EFCI), which is itself formerly known as the combination of Overload Fault Circuit Interrupter (OFCI) and Power Fault Circuit Interrupter (PFCI) technologies. Some previous documentation refers to the old nomenclature. OPCI-VI protection must be located at the junction between the load and branch circuit wiring to detect these faults and cannot be located at the panelboard. OPCI-VI technology is a superior approach compared all relevant alternatives. (see “Alternatives to Electrical Fault Circuit Interrupter (EFCI) Technology”, Wayne Hartill, 2D2C Inc., 2008.) Two Fact Finding Reports from independent NRTL’s substantiate the performance of OPCI-VI technology. (see “Descriptive Report and Test Results”, Todd Hamden, CSA International, Feb 2006 & “Descriptive Report and Test Results”, Intertek Testing Services NA Ltd., Jan 2006). A third NRTL Fact Finding Report has been request from Underwriters Laboratories (UL). Products containing OPCI-VI technology have NRTL certification against UL 498 and UL 498A standards and have been available for sale in the marketplace since 2006. Multiple producers of OPCI-VI technology exist in the marketplace. With a mandate more producers will likely enter the marketplace. A mandate of OPCI-VI technology is required because the net safety benefit to society is far greater than that of voluntary sales alone. Please review submitted letters of support from the following fire forensics experts including: ● Vytenis Babrauskas, Ph.D., President of Fire Science and Technology Inc. and author of the “Ignition Handbook”. ● John S. Robison, President of Robison Forensic Consulting, previously Alabama State Fire Marshal, and previous President of International Fire Marshals Association. ● Chris W Korinek, P.E., President of Synergy Technologies and author of Chapter 10 of “Kirks Fire Investigation” book. ● Doug Crawford, Deputy Fire Marshal of the Ontario Office of the Fire Marshal. Note that sister proposals have been submitted as a new 100 and 210.13. Printed on 3/16/2012 14 Report on Proposals – June 2013 NFPA 70 As of this time no UL/ANSI standard exists that correlates the parameters in question with fire mitigating ability. Nothing in this Code precludes the use of such a listed device. Affirmative: 10 _______________________________________________________________________________________________ 18-15 Log #748 NEC-P18 _______________________________________________________________________________________________ Vince Baclawski, National Electrical Manufacturers Association (NEMA) Add new text to read as follows: All nonlocking-type, 125-volt, 15- and 20-ampere receptacles that are controlled by an automatic control device or incorporate control features that remove power from the outlet for the purpose of energy management or building automation shall be marked with the symbol shown below placed on the controlled receptacle outlet where visible after installation. ******Insert Figure 406.3(E) Here****** New energy management codes that are currently being widely adopted such as ASHRAE 90.1 require that up to 50% of 125 volt 15 and 20 ampere receptacles be automatically controlled. The control could be an energy management system, timer or sensor. The occupant or end user needs to know which receptacle outlets will be automatically controlled to avoid plug-in appliances or other loads from being unintentionally turned on or off. Previous automated systems typically control identified loads such as lighting or HVAC and the consequences are known and understood. The uncertainty of what is plugged into a controlled receptacle outlet can raise concerns regarding safety as well as convenience thus it is important to be able to readily identify receptacle outlets that will be automatically powered on and off. Affirmative: 10 Printed on 3/16/2012 15 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-16 Log #147 NEC-P18 _______________________________________________________________________________________________ Ronald Deering, City of Portage Add new text to read as follows: All 15 and 20 ampere duplex receptacles, being installed and connected to branch circuit conductors, shall be installed using a side termination method, utilizing a set-screw that is firmly seated over a conductor wrapped clockwise around the screw head, or a screw head firmly seated after a conductor has been installed into a listed side-wired receptacle. Please accept this statement of a problem that has concerned me since I began working in the trade in 1970. As an apprentice, I had been trained by more than one electrical contractor, to be concerned that the stab-in feature of receptacles was a safety concern. The electrical contractor was concerned for his customer's safety, yes, but also was looking out for his business. He did not want to send his employees out on a costly repair, nor did he want his reputation ruined by an electrical contractor who just a year later was called to this new home to re-wire the devices, once one had quit working. As an electrical inspector, I have found that the stab-in feature, especially when conductors are installed in series, has become a common occurrence. Electrical contractors treat this repair as if they were simply correcting a poorly installed wire-nut or correcting a fault caused by a loose device that has slid to one side or the other of a steel box, causing a fault condition. The repair is not documented, as a traffic accident would be and the device tossed aside. Therefore, it is impossible to come up with piles of documentation to support the argument. The fact that it is such a common occurrence that is not documented, makes this unsafe condition an issue that may never be addressed. When questioning electricians, I find every single one has several stories to tell. I have been sending contractor emails to my NEMA representative and the NFPA, as the contractor finds the time to do so, with the hope that committee members might be able to enlighten the electrical Industry of an age old issue. I think the problem is primarily a manufacturer issue, but in light of my NEMA representative's recommendation, I submit this as a proposal. I hope that at the very least, the electrical industry's awareness of the problem can be raised. As of this time UL/ANSI standard 498 allows the back-wire push-in connection. No UL/ANSI proposal has been accepted that removes this Listed termination method. Affirmative: 10 Printed on 3/16/2012 16 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-17 Log #2082 NEC-P18 _______________________________________________________________________________________________ Phil Simmons, Simmons Electrical Services Revise text to read as follows: Receptacle outlets shall be located in branch circuits in accordance with Part III of Article 210. General installation requirements shall be in accordance with 406.4(A) through (F). Except as provided in (D), receptacles installed on 15- and 20-ampere branch circuits shall be of the grounding type. Grounding-type receptacles shall be installed only on circuits of the voltage class and current for which they are rated, except as provided in Table 210.21(B)(2) and Table 210.21(B)(3). Receptacles and cord connectors that have equipment grounding conductor contacts shall have those contacts connected to an equipment grounding conductor. The equipment grounding conductor contacts of receptacles and cord connectors shall be grounded by connection to the equipment grounding conductor of the circuit supplying the receptacle or cord connector. Informational Note: For installation requirements for the reduction of electrical noise, see 250.146(D). The branch-circuit wiring method shall include or provide an equipment grounding conductor to which the equipment grounding conductor contacts of the receptacle or cord connector are connected. Informational Note No. 1: See 250.118 for acceptable grounding means. Informational Note No. 2: For extensions of existing branch circuits, see 250.130. Replacement of receptacles shall comply with 406.4(D)(1) through (D)(6), as applicable. Where a grounding means exists in the receptacle enclosure or an equipment grounding conductor is installed in accordance with 250.130(C), grounding-type receptacles shall be used and shall be connected to the equipment grounding conductor in accordance with 406.4(C) or 250.130(C). Grounding-type receptacles shall be installed at locations specified in 250.114 and if required in the installation instructions provided by the equipment or appliance manufacturer. At locations other than provided in (D)(1) and where attachment to an equipment grounding conductor does not exist in the receptacle enclosure, the installation shall comply with (D)(2)(a), (D)(2)(b), or (D)(2)(c). (a) A non–grounding-type receptacle(s) shall be permitted to be replaced with another non–grounding-type receptacle(s). (b) A non–grounding-type receptacle(s) shall be permitted to be replaced with a ground-fault circuit interrupter-type of receptacle(s). These receptacles shall be marked “No Equipment Ground.” An equipment grounding conductor shall not be connected from the ground-fault circuit-interrupter-type receptacle to any outlet supplied from the ground-fault circuit-interrupter receptacle. (c) A non–grounding-type receptacle(s) shall be permitted to be replaced with a grounding-type receptacle(s) where supplied through a ground-fault circuit interrupter. Grounding-type receptacles supplied through the ground-fault circuit interrupter shall be marked “GFCI Protected” and “No Equipment Ground.” An equipment grounding conductor shall not be connected between the grounding-type receptacles. No changes to the remainder of 406.4 are included in this proposal. The proposed changes to (A) and (B), are intended to be editorial including making exceptions complete sentences as required by the NEC Style Manual. No changes are proposed to (C). The proposed change to (D)(1) is intended to require grounding-type receptacles if the receptacle is located where the manufacturer requires equipment be supplied from a grounding-type receptacle or branch circuit. If the receptacle does not provide an equipment grounding conductor connection, a violation of the manufacturer installation instruction occurs and a violation of 110.3(B) occurs. In addition, a list of equipment or appliances that are required to be grounded is included in 250.114. If a receptacle is located where these equipment or appliances will be supplied, a receptacle connected to an equipment grounding conductor is required. Since the NEC is the minimum standard for safety, failing to comply with the requirements of 110.3(B) or 250.114 will Printed on 3/16/2012 17 Report on Proposals – June 2013 NFPA 70 result in an installation that is unsafe. Section 406.4 should not permit an unsafe practice. Accept the change in part (A). The remainder is rejected. The changes in part (B) are not editorial and require substantiation. Reject the proposed change to part (D) as the majority of the time installation instructions are not available at the time of receptacle installation. Submitter has not provided substantiation for the change. In accordance with 4.3.3(d) of NFPA Regulations Governing Committee Projects the unaccepted parts are rejected. Affirmative: 10 _______________________________________________________________________________________________ 18-18 Log #910 NEC-P18 _______________________________________________________________________________________________ Michael J. Johnston, National Electrical Contractors Association Add a new last sentence to read as follows: The arc-fault circuit-interrupter(s) shall be installed in a readily accessible location. This proposal seeks to align the readily accessible requirement for GFCI devices covered in 210.8(A) and (B) with the rules for arc-fault circuit-interrupter protective devices required by 406.4(D). Favorable action by CMP-2 on Proposal 2-77 and Comment 2-29 in the 2010 ROP and ROC resulted in a new readily accessible requirement for GFCIs. Justification for the new rule is primarily related to occupant or user accessibility to the monthly testing and reset features of the device. Arc-fault circuit-interrupter protection can also be accomplished by circuit breaker types or device types which have the same test and reset features and requirements for monthly testing. Accessibility to these protective devices should not be different than for GFCI devices. Add a new last sentence to read as follows: Arc-fault circuit-interrupter and ground-fault circuit-interrupter type receptacles shall be installed in a readily accessible location. Although both AFCIs and GFCIs are covered in 406.4(D) only AFCIs are covered by the proposal. The revised text addresses only receptacle-type applications. Affirmative: 10 Printed on 3/16/2012 18 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-19 Log #1287 NEC-P18 _______________________________________________________________________________________________ Michael J. Farrell III, Lucas County Building Regulations Add new text to read as follows: (4) Arc-Fault Circuit- Interrupter Protection. (5) Tamper-Resistant Receptacles. (6) Weather-Resistant Receptacles. Exception to (4), (5), and (6) For receptacles supplied by a branch circuit that does not contain an equipment grounding conductor or where attachment to an equipment grounding conductor does not exist in the receptacle enclosure the provisions of 406.4(D)(2) shall apply. These devices contain equipment grounding conductor termination points. For a branch circuit containing no equipment grounding conductor a potential for installation of a device with a grounding terminal where no actual grounding means exists is possible. The requirements found in Article 406.4(D)(2) provide a safer alternative to installing AFCI,Tamper-Resistant, and Weather-Resistant receptacle devices on such branch circuits. An AHJ may mistakenly require the use of such devices based on the requirement as currently written. An exception to the requirement for existing wiring systems that were installed with no EGC is needed for clarity. The requirements of 406.4(D)(2) are the only safe alternative for replacement of receptacle devices where no grounding means is provided with the branch circuit or receptacle enclosure. The substantiation provided does not adequately support the recommendation and prove that the lack of a ground on the AFCI, tamper resistant, or weather resistant receptacle creates a hazard. Affirmative: 10 CARPENTER, F.: The existing wording is clear that 406.4(D)(2) is the only section that addresses receptacle installation when the equipment grounding conductor does not exist in the receptacle enclosure. Printed on 3/16/2012 19 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-20 Log #1797 NEC-P18 _______________________________________________________________________________________________ Mark Shapiro, Farmington Hills, MI Revise text to read as follows: 406.4(D)(2)(b) A non–grounding-type receptacle(s) shall be permitted to be replaced with a ground-fault circuit interrupter-type of receptacle(s) or protected by a ground-fault circuit interrupter. These receptacles shall be marked “No Equipment Ground.” An equipment grounding conductor shall not be connected from the ground-fault circuitinterrupter-type receptacle to any outlet supplied from the ground-fault circuit-interrupter receptacle. Is there any reason why GFCI circuit breakers should be prohibited here? Alternately, the sentence could be shortened to, “(b) A non–grounding-type receptacle(s) shall be permitted to be replaced with a grounding-type receptacle that is protected by a ground-fault circuit interrupter-type of receptacle(s).” The potential problem with that wording is that it could be read as saying that the GFCI must be upstream of the receptacle in question. Experience has taught us all that if there is a way to misread a code requirement, it will take place. Article 406 addresses “receptacles, cord connectors and attachment plugs (caps). Ground fault circuit interrupters of the circuit breaker type are covered under article 250, not Article 406. Affirmative: 10 CARPENTER, F.: The existing language in 406.4(D)(2)(c) addresses the submitters concern. _______________________________________________________________________________________________ 18-21 Log #2149 NEC-P18 _______________________________________________________________________________________________ Mike Weitzel, Central Washington Electrical Education Revise text to read as follows: Ground-fault circuit-interrupter protection protected receptacles shall be provided where replacements are made at receptacle outlets that are required to be so protected elsewhere in this . Where a circuit breaker GFCI device is used, protected receptacles shall be installed in accordance with 210.8, and marked in accordance with 406.4(D)(2) (b) or (c). Circuit breaker or receptacle protection should be permitted for this application, as both a circuit breaker and a receptacle are required to be a Class A device by UL 943 Standard. This improves accessibility, in compliance with Section 210.8 requirements that all GFCI devices be installed in a readily accessible location. As long as the receptacles are GFCI protected and marked as such, as well as whether or not an equipment grounding conductor exists on the circuit, the practice of using a GFCI breaker in lieu of a GFCI receptacle should be permitted, as it provides an equivalent level of safety. replacement. The submitter fails to realize that this section deals only with receptacle replacement, not breaker Affirmative: 10 Printed on 3/16/2012 20 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-22 Log #1637 NEC-P18 _______________________________________________________________________________________________ Robert G. Wilkinson, IEC Texas Gulf Coast Delete 406.4(D)(4)(1). A listed outlet branch-circuit type AFCI does not exist. Currently, no manufacturer produces this type of device and there is no UL standard developed for this product. The major manufacturers have stated that they have no plans to produce or market this device. Refer to panel action and statement on Proposal 18-12 which address the same issue. Affirmative: 10 _______________________________________________________________________________________________ 18-23 Log #1638 NEC-P18 _______________________________________________________________________________________________ Robert G. Wilkinson, IEC Texas Gulf Coast Delete 406.4(D)(4)(2). A listed outlet branch-circuit type AFCI does not exist. Currently, no manufacturer produces this type of device and there is no UL standard developed for this product. The major manufacturers have stated that they have no plans to produce or market this device. Refer to panel action and statement on Proposal 18-12 which addresses the same issue. Affirmative: 10 _______________________________________________________________________________________________ 18-24 Log #1643 NEC-P18 _______________________________________________________________________________________________ Charles Palmieri, Cohasset, MA Where a receptacle outlet is supplied by a branch circuit that requires arc-fault circuit interrupter protection as specified elsewhere in this , a replacement receptacle at this outlet shall be one of the following: (1) A listed outlet branch circuit type arc-fault circuit interrupter receptacle installed in accordance with 210.12(B). (2) A receptacle protected by a listed outlet branch circuit type arc-fault circuit interrupter type receptacle installed in accordance with 210.12(B). I am submitting this proposal to insure correlation with proposals that I have submitted to this Code Panel and panels 1 and 2. Code Panel 2 adopted language in 2011 requiring GFCI receptacles be readily accessible. The substantiation was clear. Manufactures instructions require periodic testing. These devices must be accessible for such testing. If my proposal to CMP 1 is rejected then the requirement that GFCI Receptacles to be readily accessible should also apply to a listed outlet branch circuit type AFCI. Please see my proposals to sections 110. (B), 210.8 and 210.12 (B)(2). Refer to the panel action and statement on Proposal 18-18 which meets the intent of the recommendation as supported by the substantiation. Affirmative: 10 Printed on 3/16/2012 21 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-25 Log #1644 NEC-P18 _______________________________________________________________________________________________ Charles Palmieri, Cohasset, MA Where a receptacle outlet is supplied by a branch circuit that requires arc-fault circuit interrupter protection as specified elsewhere in this , a replacement receptacle at this outlet shall be one of the following: (1) A readily accessible listed outlet branch circuit type arc-fault circuit interrupter receptacle. (2) A receptacle protected by a readily accessible listed outlet branch circuit type arc-fault circuit interrupter type receptacle. I am submitting this proposal to insure correlation with proposals that I have submitted to this Code Panel and panels 1 and 2. Code Panel 2 adopted language in 2011 requiring GFCI receptacles be readily accessible. The substantiation was clear. Manufactures instructions require periodic testing. These devices must be accessible for such testing. If my proposal to CMP 1 is rejected then the requirement that GFCI Receptacles to be readily accessible should also apply to a listed outlet branch circuit type AFCI. Please see my proposals to sections 110.3 (B), 210.8 and 210.12(B)(2). recommendation. Refer to the panel action and statement on Proposal 18-18 which meets the intent of the Affirmative: 10 _______________________________________________________________________________________________ 18-26 Log #2500 NEC-P18 _______________________________________________________________________________________________ Terry W. Cromer, NC Association of Electrical Contractors Delete entire text in 406.4(D)(4). 1) Presently there is not a wiring device manufacture that has placed into production an AFCI receptacle and it has been a common thread that wiring device manufactures may not produce AFCI receptacles unless CMP 2 changes the requirement found in Section 210.12(A) 2) Prior to the requirement, in the NEC, for AFCI protection of the branch circuit most homes were wired using multi-wire NM cable and at present time there is no manufacture that has in production a combination type multipole circuit breaker and there are many homes that have fusible panels which cannot accept an AFCI circuit breaker. Making this requirement retroactive in the NEC is not feasible. Refer to panel action and statement on Proposal 18-12 which addresses the same issue. Affirmative: 10 Printed on 3/16/2012 22 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-27 Log #1078 NEC-P18 _______________________________________________________________________________________________ Mario L. Mumfrey, Cincinnati, OH Add new text to read as follows: (G) Receptacles shall not be installed above permanent space-heating units such as baseboard and/or wall mounted heaters, electric or hot-water type, unless specifically approved for the use with the heaters. Exception: Where non-related receptacle(s) are installed on a wall at least 6 1/2 ft above permanent space-heating equipment. This code revision would stand alone and make it clear to installers that although there is an existing wall mounted heater of any type, a receptacle shall not be installed above these units. Many times these heaters are older and obtaining installation instructions are near impossible. The instructions are limited to where a permanent wall or baseboard heater is being installed "new". The contractor is quick to point that these units are existing and the receptacle is what's new. The exception would allow for such examples as a receptacle for a window AC unit where there is an existing baseboard heater below this window and now below this outlet. The likelihood of both in use at the same time is unlikely, however, not all window AC units are removed during a season change and the cord is subjected to damage. The receptacle would need to be installed at a point where the appliance cord could not contact the heater while plugged in. This change is not limited to electrical heaters only and will allow for more than informational notes in 210.52 and 424.9 to ensure safety. The submitter has not provided substantiation sufficient to support the change. As the submitter points out many of these receptacle installations are done after the installation of the heating unit and thus enforcement would be difficult and unlikely. In all cases the heater listing installation instructions should be followed in accordance with 110.3(B). Affirmative: 10 _______________________________________________________________________________________________ 18-28 Log #274 NEC-P18 _______________________________________________________________________________________________ Stanley J. Folz, Morse Electric Company Revise text to read as follows: Receptacles shall be mounted in identified boxes or assemblies designed for the purpose, and such boxes or assemblies shall be securely fastened in place unless otherwise permitted elsewhere in this Code. The TCC Usability Task Group is comprised of Stanley Folz, James Dollard, Bill Fiske and David Hittinger. This task group was assigned by the TCC Chair to review the use of the phrase “designed for the purpose” throughout the NEC. There are twelve instances of its use. By definition, identified equipment is suitable for its intended purpose (see definition of Identified in Article 100). Many things not defined for a specific purpose are nonetheless suitable for that purpose, and are thus "identified." Substituting "identified" for the word(s) to be replaced conforms to 3.2.4 of the NEC Style Manual, that says, "recognized or defined terms are to be used in preference to similar terms that do not have such recognition." Affirmative: 10 Printed on 3/16/2012 23 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-29 Log #548 NEC-P18 _______________________________________________________________________________________________ Lawrence W. Forshner, Bard, Rao & Athanas Consulting Engineers, LLC Receptacles shall be mounted in boxes or assemblies designed for the purpose, and such boxes or assemblies shall be securely fastened in place unless otherwise permitted elsewhere in this code. Receptacles identified as hospital grade, and where installed as required by other sections of this code, shall be supported by outlet boxes in metal stud partitions by a bar type bracket that supports the outlet box by engaging two or more framing members. As designers of electrical systems in health care facilities, we have found that sheet metal type box supports that are bent at 90 percent, attach to one stud and are intended to provide box and device support by being in contact with the opposite wall of the partition, to be inadequate. Head wall partitions in hospital patient rooms are often not of standard depth, the receptacles require more pressure to insert a plug and they get more use than office receptacles during normal hospital operations and especially during emergencies. The sheet metal brackets often do not reach the opposite wall or the sheet metal will deflect after installation requiring the wall to be opened to repair and properly fasten the box. Added language in this section to qualify and describe how to securely fasten outlet boxes in hospitals is needed. It may also, at the discretion of Code-Making Panel 15, be appropriate to add an Informational Note in Article 517. The proposed change is not under the purview of CMP 18. It is recommended that the TCC refer this proposal to CMP 15 for action. Affirmative: 10 Printed on 3/16/2012 24 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-30 Log #833 NEC-P18 _______________________________________________________________________________________________ Michael J. Johnston, National Electrical Contractors Association Include an additional sentence as follows: Screws installed for the receptacles fastened to the box, shall be machine screws matching the thread gage or size that is integral to the box. Use of drywall screws for fastening receptacles to boxes is not acceptable and can result in damage to the box and inadequate support of the devise can result. It is recognized that installers should follow the manufacturer’s installation instructions, but having the additional text will help clarify this requirement. A similar proposal is also being submitted to Articles 404 restricting use of drywall screws for installing snap switches to boxes. The panel intends that the new sentence by placed after the existing sentence. Affirmative: 8 Negative: 2 BER, M.: In order to implement the provisions of this proposal the AHJ is now going to be required to make a “pre-final” inspection before the receptacle covers are installed or he is going to have to remove each and every cover to insure compliance with this new requirement. While it may be obvious when a sheet rock screw is utilized, is an untrained AHJ going to be able to discern the difference between a 6-32 and an 8-32 machine screw just from looking at the head? What about a sheet metal screw that has the same style head as a machine screw? Let us not forget that Section 110.3B requires installation of listed products in compliance with that listing and Section 110.12 further requires that these installations be made in a “neat and workmanlike manner”. Aren't these provisions of the NEC sufficient to require a Code compliant installation and also adequate to allow an AHJ red tag when not complied with. If additional emphasis is required in this area wouldn't we be better served by just adding a useless unenforceable term like “Securely Fastened”? And finally, can anyone argue with the superior holding ability of a sheet rock or a sheet metal screw in a plastic box with stripped out threads? CARPENTER, F.: We support the intent to eliminate the use of drywall screws for mounting receptacles, but the code text would eliminate other listed assemblies that do not use machine screws. NEMA would support the proposed text if the phrase “or as fastened in listed assemblies or systems” was added to the end of the new sentence. _______________________________________________________________________________________________ 18-31 Log #1667 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Revise text to read as follows: Receptacles shall be mounted in boxes or assemblies designed for the purpose,. The and such boxes or assemblies shall be securely fastened in place unless otherwise permitted elsewhere in this . [delete comma, replace with period] Remove archaic language. NEC style manual: 3.3.4 Word Clarity. Words and terms used in the shall be specific and clear in meaning, and shall avoid jargon, trade terminology, industry-specific terms, or colloquial language that is difficult to understand. language shall be brief, clear, and emphatic. The following are examples of old-fashioned expressions and word uses that shall not be permitted: "...and such...". Affirmative: 10 Printed on 3/16/2012 25 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-32 Log #2269 NEC-P18 _______________________________________________________________________________________________ Leo F. Martin, Sr., Martin Electrical Consulting Revise text to read as follows: Receptacles shall not be installed in a face up position in countertops or similar work surfaces. Receptacles shall not be installed in a face up position in countertops or similar work surfaces. The same spillage hazards exist and the rule should apply to all countertops or similar work surfaces, not to dwelling units only. The panel also refers the panel action on Proposal 18-34. Affirmative: 10 _______________________________________________________________________________________________ 18-33 Log #2504 NEC-P18 _______________________________________________________________________________________________ Mark T. Rochon, Peabody, MA Revise text to read as follows: Receptacles in countertops and similar work surfaces in dwelling units all applications. In other than dwellings it is excepted to face up the receptacles. The same problems of liquids, loose particles such as food, wood, plastic and metal scraps enter the receptacle impairing the electrical connection. See panel action on Proposal 18-34 which meets the intent of the submitter. Affirmative: 10 Printed on 3/16/2012 26 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-34 Log #3363 NEC-P18 _______________________________________________________________________________________________ James T. Dollard, Jr., IBEW Local 98 Revise text to read as follows: Editorially revise 406.5 (F) and (G) to 406.5(G) and (H) as follows: Receptacles shall not be installed in a face-up position in countertops or similar work surfaces. Receptacles shall not be installed in a face-up position in floors, seating areas or similar surfaces unless they are part of an assembly listed for the application. (No change) (No change) Receptacles are presently not permitted to be installed in a face-up position in countertops or similar work surfaces of dwelling units. There is no prohibition to installing a standard receptacle in a standard device box in the floor of a dwelling unit or any other occupancy. Assemblies that are listed for the application, such as a doghouse style assembly are readily available. We have recently seen benches in public areas with receptacles installed that you could sit on. These were obviously installed so that someone could sit and use the 125-volt outlet for a laptop computer or to charge a phone or other device. These represent a hazard. Where there is a need to install receptacles in a floor or other similar surface, it should be done with an assembly listed for the application to prevent damage and potential exposure to energized conductors or circuit parts. 1) Accept the change proposed for (E). 2) Accept the change proposed for new (F) except delete the word "floors" in both places. 3) Retain and renumber existing (F) and (G). Floor boxes are listed but such listings do not include wiring devices supplied as part of their listing. Listed floor boxes are investigated for water penetration. Affirmative: 10 Printed on 3/16/2012 27 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-35 Log #3483 NEC-P18 _______________________________________________________________________________________________ Jim Burch, Orange County Division of Building Safety Revise text to read as follows: 15- and 20-ampere, 125 and 250-volt receptacles installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted for other than one or two family dwellings, an outlet box hood installed for this purpose shall be listed, and where on an enclosure supported from grade as described in 314.23(B) or described in 314.23(F) shall... Proposal to strike the words "other thanone or two family dwellings. "I am an electrical inspector. Since requiring "in use" covers for outdoor outlets. I have encountered hundreds of broken or missing covers on temporary power poles, on all sizes of residential and commercial job sites. To require "extra duty" covers on all temp poles will reduce this hazard. Refer to the panel action on Proposal 18-37 which meets the intent of the submitter. Affirmative: 9 Negative: 1 BER, M.: See my Explanation of Negative on Proposal 18-30 (Log #833). CARPENTER, F.: The correct section reference for this proposal is 406.9(B)(1) . Printed on 3/16/2012 28 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-36 Log #1537 NEC-P18 _______________________________________________________________________________________________ Vince Baclawski, National Electrical Manufacturers Association (NEMA) Add the following new text in Section 406.9 (B)(1): 15- and 20-ampere, 125- and 250-volt receptacles installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. For other than one- or two-family dwellings, an outlet box hood installed for this purpose shall be listed, and where installed on an enclosure supported from grade as described in 314.23(B) or as described in 314.23 (C), (F) or (G) shall be identified as “extra-duty.” All 15- and 20-ampere, 125- and 250-volt nonlocking-type receptacles shall be listed weather-resistant type. Informational Note No. 1: Requirements for extra-duty outlet box hoods are found in ANSI/UL 514D-2000, . Informational Note No. 2: The types of receptacles covered by this requirement are identified as 5-15, 5-20, 6-15, and 6-20 in ANSI/NEMA WD 6-2002, National Electrical Manufacturers Association . Every outlet box hood installed as part of a rigidly mounted weatherproof enclosure in a wet location as described in 406.9 (B)(1), except in one- or two-family dwellings, should be required to be of the “extra-duty” type. The same rationale used in the 2011 proposal (18-54) applies equally to enclosures rigidly mounted as described in Section 314.23 (B), (C), (F) and (G). Refer to the panel action on Proposal 18-37 which expands the requirement and includes the submitters intention of adding 314.23(C) and (G). Affirmative: 9 Negative: 1 BER, M.: See my Explanation of Negative on Proposal 18-30 (Log #833). Printed on 3/16/2012 29 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-37 Log #1553 NEC-P18 _______________________________________________________________________________________________ David Clements, International Association of Electrical Inspectors Revise text to read as follows: 15- and 20-ampere, 125- and 250-volt receptacles installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. For other than one- or two-family dwellings, an outlet box hood installed for this purpose shall be listed, and where installed on an enclosure supported from grade as described in 314.23(B) or as described in 314.23(F) and shall be identified as “extra-duty.” If it’s in a wet location, what difference can it possibly make how the enclosure or device box is installed or supported? Revise text to read as follows: 15- and 20-ampere, 125- and 250-volt receptacles installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. For other than one- or two-family dwellings, aAn outlet box hood installed for this purpose shall be listed, and where installed on an enclosure supported from grade as described in 314.23(B) or as described in 314.23(F) and shall be identified as “extra-duty.” [Retain the remaining text.] The panel has modified the text to correlate with the action on other proposals. The panel clarifies that the remaining text is retained. Affirmative: 9 Negative: 1 BER, M.: What is an “extra duty” cover or hood? We have been saddled with this term since the 2011 NEC and a definition and a description still eludes us. The following publications have been consulted: a) NFPA 70 National Electrical Code, Article 100 and the Index. b) NFPA's Illustrated Dictionary of Electrical Terms. c) UL's White Book. The only place where this term can be located is in the NEC in Section 406.9B1, Ah, but let us not panic, the Informational Note has the solution, consult ANSI/UL Standard 514D. A quick internet search will find a copy of this standard available from “Techstreet” for a mere $1032.00. Searching a little further finds the UL Standard at the Bargain Basement price of only $716.00 from “Comm 2000”. How is the installer supposed to use an item dictated to him by the NEC when there are no pictures, no description, no definitation, no explanation and no economical way to let him in on the big secret as what makes an “extra duty” cover. This section of the Code must be changed to eliminate this unknown term and its Informational Note. Printed on 3/16/2012 30 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-38 Log #3491 NEC-P18 _______________________________________________________________________________________________ Susan Newman Scearce, Halls, TN Revise text to read as follows: (1) 15- and 20-Ampere Receptacles in a Wet Location. 15- and 20-ampere, 125- and 250-volt receptacles installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. For other than one- or two-family dwellings, an outlet box hood installed for this purpose shall be listed, and where installed on an enclosure supported from grade as described in 314.23(B) or as described in 314.23(F) shall be identified as “extra-duty.” All 15- and 20-ampere, 125- and 250-volt nonlocking-type receptacles shall be listed weather-resistant type. See related UL Informational Note No. 1: Requirements for extra-duty outlet box hoods are found in ANSI/UL 514D-2000, Cover Plates for Flush-Mounted Wiring Devices. Informational Note No. 2: The types of receptacles covered by this requirement are identified as 5-15, 5-20, 6-15, and 6-20 in ANSI/NEMA WD 6-2002, National Electrical Manufacturers Association Standard for Dimensions of Attachment Plugs and Receptacles. Exception: 15- and 20-ampere, 125- through 250-volt receptacles installed in a wet location and subject to routine high-pressure spray washing shall be permitted to have an enclosure that is weatherproof when the attachment plug is removed. In studying the cause for a required standard on the “In Use Covers”, the problem was substantiated with more than 90% malfunctions of the cover on “one and two family dwellings”. The absence of an extra-duty cover has left receptacles exposed to all weather conditions and caused greater harm to device. The “in-use cover” without a standard of extra-duty with any significant contact will cause hinge to dislocate and device will be left unprotected. Reject the addition of the words "See related UL". The panel rejects the addition of the words "See related UL" which appears to be a typo. The panel only accepts the changes shown with a strikethrough. Also refer to the panel action on Proposal 18-37. Affirmative: 9 Negative: 1 BER, M.: See my Explanation of Negative on Proposal 18-30 (Log #833). Printed on 3/16/2012 31 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-39 Log #1495 NEC-P18 _______________________________________________________________________________________________ Russell LeBlanc, The Peterson School Revise text to read as follows: Receptacles shall not be installed within(the space created by the adjacent walls, curtains or doors that surround the tub or shower stall,) or directly over a bathtub or shower stall. To quote the wording from the NEC handbook I agree with that reasoning about those “SPACES”, but there is a problem with the literal wording in the actual requirement. The word “SPACES” was removed in the 2005 NEC (see 2004 ROP 18-41 (Log#1514), pg. 1057) and should be reinstated. The Handbook still uses the word “spaces” in its explanation. The wording “directly over ” is problematic because it literally permits a receptacle to be installed on a small lip, shelf or recess built on the wall above the tub but set back slightly from the outside edge of the tub( perhaps even only a few inches) as long as it is not “directly above” the tub or shower stall. I have seen this done to allow a flat screen TV to be installed in the slightly recessed wall space above the tub. Because the receptacle was not “ directly over” or “within” the tub itself this was not a violation. If the receptacle is set back a few inches from the edge of the tub, but still within the SPACE that is created by the tub and the walls and curtain, then it should be a violation. This IS the intent of the code, but the literal wording permits it to be done. I believe my proposed wording will help clarify the intent. Definitions should not be included into text. See NEC Style Manual 3.1.3 and 3.2.4 Affirmative: 10 _______________________________________________________________________________________________ 18-39a Log #CP1801 NEC-P18 _______________________________________________________________________________________________ Code-Making Panel 18, Revise the Informational Note following 406.10(E) to read as follows: Informational Note: See 250.126 for identification of grounding conductor terminals. The revision to the informational note corrects the reference and uses the proper terminology "grounding". Affirmative: 10 Printed on 3/16/2012 32 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-40 Log #90 NEC-P18 _______________________________________________________________________________________________ Matthew D. Frederick, City of Mattoon Add new text to read as follows: 406.11 (A) Dwelling Units. (Keep current wording) (B) Other than dwelling units. (1) Where installed in dining areas, receptacles shall be listed tamper-resistant receptacles. (2) Where installed accessible to the public, receptacles shall be listed tamper-resistant receptacles. Commercial dining area receptacles, combined with dining utensils present an undeniable temptation and definite risk to the safety of children. Children often insert objects into receptacles, in a dining setting I feel it is amplified by the presence of utensils. My jurisdiction already requires these receptacles be listed tamper-resistant type. Furthermore, any receptacle accessible to the public presents a possible hazard for curious children. Areas such as waiting rooms, coffee shops and the like often contain pre-occupied parents and bored children, coupled with an accessible receptacle; I feel this poses a safety hazard. The minor increase in cost is far outweighted by the life safety benefits realized by making this change. The panel recognizes the submitter meant 406.11 of 2008 NEC. Panel 18 modified the use of tamper resistant receptacles in the 2011 NEC. The submitter has provided no definitive substantiation for the expansion of tamper resistant receptacles to dining areas or all public areas. Affirmative: 10 _______________________________________________________________________________________________ 18-41 Log #166 NEC-P18 _______________________________________________________________________________________________ Curtis B. Frank, Frank Professional Electrical Engineers Revise text to read as follows: In referencing Article 406.11 to Article 210.52, all outlets of a dwelling are interpreted as required to be Tamper-Resistant, including areas requiring GFCI protection. The protection afforded by Tamper-Resistant outlets is easily defeated with multiple insertions of small objects. The protection afforded by GFCI protected outlets cannot be defeated with any insertion(s) affording the GFCI protected outlet(s) a higher level of protection to the individual. In addition, outlets outdoors as well as those for garages requiring GFCI protection would not normally be considered within the unsupervised play areas of small children. I propose that an exception to Article 406.11 be included whereas GFCI protected outlets would be excluded from the requirement of also being Temper-Resistant. Panel recognizes the submitter meant 406.12 and it is the direction of the panel to include GFCI outlets. The submitter has given no clear text and no substantiation of a problem. Further, tamper resistant GFCI receptacles are commercially available Affirmative: 10 Printed on 3/16/2012 33 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-41a Log #CP1800 NEC-P18 _______________________________________________________________________________________________ Code-Making Panel 18, Delete in it's entirety 406.13 and 406.14. Revise 406.12 to read as follows: 406.12 Tamper Resistant Receptacles. (A) Dwelling Units. In all areas specified in 210.52, all nonlocking-type 125-volt, 15- and 20-ampere receptacles shall be listed tamper-resistant receptacles. (B) Guest Rooms and Guest Suites of Hotels and Motels. All nonlocking-type 125-volt, 15- and 20-ampere receptacles located in guest rooms and guest suites of hotels and motels shall be listed tamper-resistant receptacles. (C) Child Care Facilities. In all child care facilities, all nonlocking-type 125-volt, 15- and 20-ampere receptacles shall be listed tamper-resistant receptacles. to (A), (B), and (C): The panel combined panel action on Proposals 18-44, 18-46, and 18-49. The panel agrees with this reorganization and the application of the existing exceptions to all subsections. Affirmative: 10 _______________________________________________________________________________________________ 18-42 Log #555 NEC-P18 _______________________________________________________________________________________________ Victor V. Timpanaro, Technical Seminars LLC Revise text to read as follows: In all areas specified in Section 210.52, all nonlocking-type 125, 15 and 20 ampere receptacles shall be listed tamper-resistant receptacles where child care business is conducted only. I believe it isunnecessary to require tamper-resistant receptacles in dwellings where only the household children reside. Their protection is parents responsibility and code should not develop codes except where safety of children is critical in a business environment. prudent. Since parents cannot be in all places at all times, the use of Tamper Resistant Receptacle seems Affirmative: 10 Printed on 3/16/2012 34 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-43 Log #674 NEC-P18 _______________________________________________________________________________________________ Matthew D. Frederick, City of Mattoon Revise text to read as follows: 406.12 (A) Dwelling Units. (Keep current wording) (B) Other than dwelling units. (1) Where installed in dining areas, receptacles shall be listed tamper-resistant receptacles. (2) Where installed accessible to the public, receptacles shall be listed tamper-resistant receptacles. Commercial dining area receptacles, combined with dining utensils present an undeniable temptation and definite risk to the safety of children. Children often insert objects into receptacles, in a dining setting I feel it is amplified by the presence of utensils. My jurisdiction already requires these receptacles be listed tamper-resistant type. Furthermore, any receptacle accessible to the public presents a possible hazard for curious children. Areas such as waiting rooms, coffee shops and the like often contain preoccupied parents and bored children, coupled with an accessible receptacle; I feel this poses a safety hazard. The minor increase in cost is far outweighed by the life safety benefits realized by making this change. The submitter has provided no definitive substantiation of a problem beyond anecdotal information. Affirmative: 10 Printed on 3/16/2012 35 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-44 Log #834 NEC-P18 _______________________________________________________________________________________________ Michael J. Johnston, National Electrical Contractors Association Revise text to read as follows: 406.12 Tamper Resistant Receptacles. in Dwelling Units. (A) Dwelling Units. In all areas specified in 210.52, all nonlocking-type 125-volt, 15- and 20-ampere receptacles shall be listed tamper-resistant receptacles. (B) Guest Rooms and Guest Suites. All nonlocking-type 125-volt, 15- and 20-ampere receptacles located in guest rooms and guest suites shall be listed tamper-resistant receptacles. (C) Child Care Facilities. In all child care facilities, all nonlocking-type 125-volt, 15- and 20-ampere receptacles shall be listed tamper-resistant receptacles. This proposal has two parts. The first is a reorganization of the installation standards for tamper-resistant receptacles so that the exceptions provided in 406.12 for dwelling units also apply to guest rooms and child care facilities. These exceptions should apply to all occupancies where tamper-resistant receptacles are required. The second is an exemption for multi-outlet assemblies mounted under the upper cabinet as is frequently used in residences. This location is sufficiently protected to reduce the risk of children accessing the receptacle. 1) Reject the addition of item 5 of the exception. 2) Modify the balance as shown in the recommendation of Proposal 18-41a. The submitter has not made the case how a multi outlet assembly mounted on the underside of a cabinet is not a hazard. Refer to the panel recommendation on Proposal 18-41a which incorporates the balance of the intended recommendation on this proposal. Affirmative: 10 _______________________________________________________________________________________________ 18-45 Log #2296 NEC-P18 _______________________________________________________________________________________________ John Rheinheimer, Denver, CO I propose that is should be acceptable in 406.12 as well as 517.18(c) to use tamper resistant covers or receptacles. The issue is that if it is deemed acceptable to pediatric hospital locations, why not in dwelling units as well? The conditions of maintenance in a hospital location are different from a dwelling unit. Removal of the cover would remove the tamper resistant protection in a dwelling unit. However in a hospital location normal maintenance would quickly discover its removal and cause its replacement. Also see panel action and statement on Comment 18-9 of the A2007 cycle. Affirmative: 10 Printed on 3/16/2012 36 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-46 Log #3214 NEC-P18 _______________________________________________________________________________________________ Darryl Hill, Wichita Electrical JATC Revise text to read as follows: . . In all areas specified in 210.52, all nonlocking-type 125-volt, 15- and 20-ampere receptacles shall be listed tamper-resistant receptacles. . All nonlocking-type, 125-volt, 15- and 20-ampere receptacles located in guest rooms and guest suites shall be listed tamper-resistant receptacles. . In all child care facilities, all nonlocking-type, 125-volt, 15- and 20-ampere receptacles shall be listed tamper-resistant receptacles. Remove Sections 406.13 and 406.14. The exceptions that have been added in the 2011 NEC for Dwelling units were needed, but they are also needed for the locations in Guest Rooms, Guest Suites, and Child Care Facilities. These locations whether in a dwelling or guest room or child care facility are out of reach of small children and should be an exception as such. Also for clarity and usability and without trying to repeat the same exceptions 3 times, Sections 406.13 and 406.14 have st been removed and placed as 1 level sub-divisions (B) and (C) under Section 406.12 which is just titled st “Tamper-Resistant Receptacles.” 1 level sub-division (A) would now cover requirements for dwellings. It makes more sense to come to one location or one Section for all Tamper-Resistant Receptacles and their requirements and locations and this would allow the same exception to cover multiple locations if needed. Note: The language in 406.13 and 406.14 was not changed, just moved, so therefore I didn’t underline that text in this proposal. Refer to the recommendation of Proposal 18-41a, which meets the intent of the submitter. Affirmative: 10 _______________________________________________________________________________________________ 18-47 Log #335 NEC-P18 _______________________________________________________________________________________________ David E. Shapiro, Camar, MD Revise text to read as follows: "...more than 1.7 m (5 1/2 ft) 1.12 m (3 ft 8 m)... 1 ADA limits force needed to 5 LBF (22.2N) . Tamper-resistant receptacles require more by a long shot 2 3 ADA also limits adult reach to 48 in. - but child reach to 36 in. So allowing non-tamper-proof receptacles to comply with 210.52(4) would serve weak/disabled adults. 1 2 3 309.4, 4.27.4 308.2.1 e.g., 604.9.5 The submitter has not shown a hazard that this situation creates. Lowering the height to 1.12 m does not foresee a child standing on a box or stool. Affirmative: 10 Printed on 3/16/2012 37 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-48 Log #1070 NEC-P18 _______________________________________________________________________________________________ Joseph Penachio, Peabody, MA Revise text to read as follows: . All non locking-type, 125-volt, 15- and 20-ampere receptacles located in guest rooms and guest suites shall be listed tamper-resistant receptacles, except as permitted in 406.12 Exceptions (1) - (4). The same exception for dwelling units should apply to tamper-proof receptacles in guest rooms and guest suites because these receptacles are less likely to be tampered with. See sister proposal for 406.14 in Child Care Facilities. Refer to the recommendation of Proposal 18-41a which meets the intent of the submitter. Affirmative: 10 _______________________________________________________________________________________________ 18-49 Log #3228 NEC-P18 _______________________________________________________________________________________________ Mark C. Ode, Underwriters Laboratories Inc. Revise text to read as follows: 406.13 Tamper-Resistant Receptacles in Guest Rooms and Guest Suites of Hotels and Motels All nonlocking-type, 125-volt, 15- and 20-ampere receptacles located in guest rooms and guest suites of hotels and motels shall be listed tamper-resistant receptacles. In an attempt to over simplify the requirements for receptacles located in guest rooms and suites, the new text now does not differentiate between guest rooms and guest suites in single family homes, bed and breakfasts and other similar residential facilities. Adding the phrase “of hotels and motels” will bring the requirement back to the original intent of this and similar text in other locations. The panel has incorporated the suggested change in the recommendation of Proposal 18-41a. Affirmative: 10 Printed on 3/16/2012 38 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-50 Log #3225 NEC-P18 _______________________________________________________________________________________________ Mark C. Ode, Underwriters Laboratories Inc. Add a new exception as follows: 406.13 Tamper-Resistant Receptacles in Guest Rooms and Guest Suites All nonlocking-type, 125-volt, 15- and 20-ampere receptacles located in guest rooms and guest suites shall be listed tamper-resistant receptacles. Exception: Receptacles in the following locations shall not be required to be tamper-resistant: (1) Receptacles located more than 1.7 m (51/2 ft) above the floor. (2) Receptacles that are part of a luminaire or appliance. (3) A single receptacle or a duplex receptacle for two appliances located within dedicated space for each appliance that, in normal use, is not easily moved from one place to another and that is cord-and-plug connected in accordance with 400.7(A)(6), (A)(7), or (A)(8). (4) Nongrounding receptacles used for replacements as permitted in 406.4(D)(2)(a). The same exception that applies to dwelling units for tamper resistant receptacles also applies to guest rooms and guest suites of hotels and motels. Refer to the recommendation of Proposal 18-41a which meets the intent of the submitter. Affirmative: 10 _______________________________________________________________________________________________ 18-51 Log #1071 NEC-P18 _______________________________________________________________________________________________ Joseph Penachio, Peabody, MA Revise text to read as follows: . In all child care facilities all non locking-type, 125-volt, 15and 20-ampere receptacles shall be listed tamper-resistant receptacles, except as permitted in 406.12 Exceptions (1) (4). The same exception for dwelling units should apply to tamper-proof receptacles in child care facilities because these receptacles are less likely to be tampered with. See sister proposal for 406.13 in guest rooms and guest suites. Refer to the recommendation of Proposal 18-41a which meets the intent of the submitter. Affirmative: 10 Printed on 3/16/2012 39 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-52 Log #3226 NEC-P18 _______________________________________________________________________________________________ Mark C. Ode, Underwriters Laboratories Inc. Add a new exception as follows: 406.14 Tamper-Resistant Receptacles in Child Care Facilities In all child care facilities, all nonlocking-type, 125-volt, 15- and 20- ampere receptacles shall be listed tamper-resistant receptacles. Exception: Receptacles in the following locations shall not be required to be tamper-resistant: (1) Receptacles located more than 1.7 m (51/2 ft) above the floor. (2) Receptacles that are part of a luminaire or appliance. (3) A single receptacle or a duplex receptacle for two appliances located within dedicated space for each appliance that, in normal use, is not easily moved from one place to another and that is cord-and-plug connected in accordance with 400.7(A)(6), (A)(7), or (A)(8). (4) Nongrounding receptacles used for replacements as permitted in 406.4(D)(2)(a). The same exception in 406.12 would also apply to receptacles in child care facilities and should be added. Refer to the recommendation of Proposal 18-41a which meets the intent of the submitter. Affirmative: 10 _______________________________________________________________________________________________ 18-53 Log #469 NEC-P18 _______________________________________________________________________________________________ Mario L. Mumfrey, Inspection Bureau Inc. Add text to read as follows: Receptacles on Dimmer Control. Only such receptacles that are listed and approved for the use shall be permitted to be supplied by a dimmer control device. There appears to be a consensus among some contractors that it is permitted to dim a receptacle for such items as 120v cord-and-plug connected low voltage lighting or rope lights. Many of the luminaries are installed under shelving or cabinets. The manufactured ambient lighting effect is said to be too bright. The manufacturer can introduce a dimming feature that is listed with their product where the consumer may demand it. Strict code language will ensure standard grade receptacles are not controlled from any dimming or voltage drop device. Revise the submitter's recommendation: Add new 406.15 to read as follows: Dimmer Controlled Receptacles. A receptacle supplying lighting loads shall not be connected to a dimmer unless the plug/receptacle combination is a nonstandard configuration type that is specifically listed and identified for each such unique combination. This change achieves the intent of the submitter while maintaining a positive language. Affirmative: 10 Printed on 3/16/2012 40 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-54 Log #2575 NEC-P18 _______________________________________________________________________________________________ Wendell Whistler, Dallas, OR Add new text as follows: 406.15 Tamper-Resistant Receptacles in Elementary Schools In all elementary school classrooms ( Kindergarten through Second grade) all non-locking type, 125-volt 15 and 20 ampere receptacles shall be listed tamper-resistant receptacles. These classrooms typically have 20 or more students with only one teacher. By installing tamper –resistant receptacles, safety of the children would be provided similar to that in a day care facility. Note that in many cases only one adult is overseeing at of the students without additional help. It is the intent of the panel that a "Child Care Facility" in the text covers the classroom situations mentioned. See the definition located in 406.2. Affirmative: 10 _______________________________________________________________________________________________ 18-55 Log #2727 NEC-P18 _______________________________________________________________________________________________ Wade Schlie, Schie Inspections Add text to read as follows: 406.15 In bedrooms and areas generally accessible to residents in limited care facilities that only provide services to individuals with Alzheimer’s disease, dementia and chronic brain injury, all nonlocking-type, 125-volt, 15- and 20ampere receptacles shall be listed tamper-resistant. Individuals in facilities that provide specialty care for individuals with Alzheimer’s disease and other forms of dementia as well as chronic brain injury do not recognize the dangers of electricity and need additional protection. Generally, these individuals have the natural curiosity of a child as well as the physical ability to expose themselves to harm. The submitter has provided no documentation of a hazard to Alzheimer’s disease, dementia and chronic brain injury patients. Affirmative: 9 Negative: 1 CARPENTER, F.: It is foreseeable that individuals with Alzheimer's disease, dementia or chronic brain injury would benefit by the added safety that Tamper-Resistant devices provide. Printed on 3/16/2012 41 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-56 Log #1872 NEC-P18 _______________________________________________________________________________________________ Michael Dempsey, Municipal Code Inspections Revise text to read as follows: Horizontal distance of 12 in. or the width of the shelf. The horizontal distance of 12 in. from both sides and back wall shall apply whether shelves are installed or not. To make it clear that the installation of shelves, the size or if only one shelf is installed, does not change the minimum 12 in. requirement from both sides and back wall of the closet storage space. Panel 18 has provided for the concern of the submitter by stating "…, and continuing vertically to the closet ceiling parallel to the walls at a horizontal distance of 300 mm (12 in.) or the width of the self, whichever is greater, …". So the 12 in. is the minimum even though a shelf is not installed. Affirmative: 11 _______________________________________________________________________________________________ 18-57 Log #1213 NEC-P18 _______________________________________________________________________________________________ Marcelo M. Hirschler, GBH International Revise text to read as follows: The volume bounded by the sides and back closet walls and planes extending from the closet floor vertically to a height of 1.8 m (6 ft) or to the highest clothes-hanging rod and parallel to the walls at a horizontal distance of 600 mm (24 in.) from the sides and back of the closet walls, respectively, and continuing vertically to the closet ceiling parallel to the walls at a horizontal distance of 300 mm (12 in.) or the width of the shelf, whichever is greater; for a closet that permits access to both sides of a hanging rod, this space includes the volume below the highest rod extending 300 mm (12 in.) on either side of the rod on a plane horizontal to the floor extending the entire length of the rod. See Figure 410.2. : See Figure 410.2. The NFPA Manual of Style requires definitions to be in single sentences. The information provided in the subsequent sentences is not really a part of the definition; it is further information that is best placed in an informational note. See also alternate proposal recommending deletion of definition (which contains requirements not normally allowed in definitions) and incorporation of requirements into section 410.16. The figure is part of the definition. NFPA style manual 2.3.2.2 states that "Definitions shall be in the format of a bold term followed by the definition phrase to form a single paragraph unit." Nowhere does it say that the definition must be a single sentence. Affirmative: 11 Printed on 3/16/2012 42 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-58 Log #1214 NEC-P18 _______________________________________________________________________________________________ Marcelo M. Hirschler, GBH International Revise text to read as follows: The volume bounded by the sides and back closet walls and planes extending from the closet floor vertically to a height of 1.8 m (6 ft) or to the highest clothes-hanging rod and parallel to the walls at a horizontal distance of 600 mm (24 in.) from the sides and back of the closet walls, respectively, and continuing vertically to the closet ceiling parallel to the walls at a horizontal distance of 300 mm (12 in.) or the width of the shelf, whichever is greater; for a closet that permits access to both sides of a hanging rod, this space includes the volume below the highest rod extending 300 mm (12 in.) on either side of the rod on a plane horizontal to the floor extending the entire length of the rod. See Figure 410.2. Only luminaires of the following types shall be permitted in a closet: (1) Surface-mounted or recessed incandescent or LED luminaires with completely enclosed light sources (2) Surface-mounted or recessed fluorescent luminaires (3) Surface-mounted fluorescent or LED luminaires identified as suitable for installation within the closet storage space Incandescent luminaires with open or partially enclosed lamps and pendant luminaires or lampholders shall not be permitted. Closet storage space shall be considered to be the volume bounded by the sides and back closet walls and planes extending from the closet floor vertically to a height of 1.8 m (6 ft) or to the highest clothes-hanging rod and parallel to the walls at a horizontal distance of 600 mm (24 in.) from the sides and back of the closet walls, respectively, and continuing vertically to the closet ceiling parallel to the walls at a horizontal distance of 300 mm (12 in.) or the width of the shelf, whichever is greater. For a closet that permits access to both sides of a hanging rod, this space shall include the volume below the highest rod extending 300 mm (12 in.) on either side of the rod on a plane horizontal to the floor extending the entire length of the rod. See Figure 410.16. The minimum clearance between luminaires installed in clothes closets and the nearest point of a closet storage space (in accordance with 410.16 C) shall be as follows: (1) 300 mm (12 in.) for surface-mounted incandescent or LED luminaires with a completely enclosed light source installed on the wall above the door or on the ceiling. (2) 150 mm (6 in.) for surface-mounted fluorescent luminaires installed on the wall above the door or on the ceiling. (3) 150 mm (6 in.) for recessed incandescent or LED luminaires with a completely enclosed light source installed in the wall or the ceiling. (4) 150 mm (6 in.) for recessed fluorescent luminaires installed in the wall or the ceiling. (5) Surface-mounted fluorescent or LED luminaires shall be permitted to be installed within the closet storage space where identified for this use. This proposal recommends relocation of the definition of closet storage space from section 410.2 into section 410.16 and to be made into a proper code requirement. The NFPA Manual of Style requires definitions to be in single sentences. The information provided in the subsequent sentence is not really a part of the definition; it is further information that is best placed in an informational note. NFPA definitions should not contain requirements, and the requirements are now in section 410.16. See also alternate proposal that simply makes the second sentence into an informational note. location. "Clothes closet" is a definition per the NEC Style Manual section 2.2.2.2 and is in the correct Affirmative: 11 Printed on 3/16/2012 43 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-59 Log #2621 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Revise text to read as follows: Listing Required. All luminaires, and lampholders, and retrofit kits shall be listed. • The changing of illumination systems in luminaires presents hazards for electricians doing maintenance after the conversion. As an example, the AHJ in Washington State requires a label near the conversion subassembly, warning about the risk of an electrical hazard: (Labor & Industries Electrical Currents, March 2011 ) LEDs and LED power sources must be replaced like with like to ensure electrical safety and avoid compromising the listing profile of the luminaire and creating a hazard. • Inasmuch as the conversion will likely be made by others than the luminaire manufacturer, identifying the installer provides the basis for legal relief for the retrofit kit supplier, in the event the rework is not performed in accordance with the retrofit kit installation instructions, and there is a catastrophic failure resulting in injury or property damage. The installers name also provides a source for the retrofit kit installation instructions that may be required by maintenance personnel. Affirmative: 11 _______________________________________________________________________________________________ 18-60 Log #2620 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Add new text to read as follows: Luminaires with field installed conversion assemblies shall be labeled to indicate 1 that the original illumination system has been modified. The marking shall be in letters at least 6 mm ( /4 in.) high, permanently installed. and located where visible during servicing. CAUTION. RETROFIT KIT INSTALLED (Date) BY (Company Name). The changing of illumination systems in luminaires presents hazards for electricians doing maintenance after the conversion. As an example, the AHJ in Washington State requires a label near the conversion subassembly, warning about the risk of an electrical hazard: (Labor & Industries Electrical Currents, March 2011) LEDs and LED power sources must be replaced like with like to ensure electrical safety and avoid compromising the listing profile of the luminaire and creating a hazard. • In as much as the conversion will likely be made by others than the luminaire manufacturer, identifying the installer provides the basis for legal relief for the retrofit kit supplier, in the event the rework is not performed in accordance with the retrofit kit installation instructions, and there is a catastrophic failure resulting in injury or property damage. The installers name also provides a source for the retrofit kit installation instructions that may be required by maintenance personnel. The submitter has not provided definitive substantiation for the inclusion of the installing company name and date. The intent of this proposal is covered by the product safety standard. See panel action on Proposal 18-59. Affirmative: 11 Printed on 3/16/2012 44 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-61 Log #2023 NEC-P18 _______________________________________________________________________________________________ Charles Li, Tres West Engineers (NEW) 410.9 Capacity. If the lighting branch circuit is supplied through a device that limits its current, the load shall be permitted to be calculated based on the rating of the device used to limit the current. This is an adaption of Proposal 2-335 Log #148 that CMP-2 Accepted in Principle during the last revision cycle and builds upon the concept of Proposal 2-320 Log #3751. CMP-2 re-crafted the submitter's original language that sought recognition of the practical effect of ASHRAE 90.1 and IECC. If the circuit is supplied through a device that limits the current -- such as an lighting monitoring system -- fire safety considerations are managed but the larger hazard -- too much electrical energy brought into a building due to out-dated demand and diversity requirements in Article 220 -- is circumvented. Arguably, the most knowledgeable people in lighting technology are the experts on the Article 410 panel. The scope of Article 410 which, stated in 410.1 is "the wiring and equipment forming part of such products and lighting installations" and therefore the proposal for of this nature is appropriate to present to this panel for inclusion in Article 410. Tres West Engineers is a full-service engineering services firm with experience in electrical system design in domestic and international markets. We recommend that the NFPA establish a Task Force to develop options for Owners and consultants to reconcile the competing requirements of economy and safety with regard to rapidly-evolving energy codes and the need to manage flash hazard and wiring fire safety. The proposed change involves the application of calculations and is not under the purview of CMP 18. It is recommended that the TCC refer this proposal to CMP 2 for action. Affirmative: 11 Printed on 3/16/2012 45 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-62 Log #2092 NEC-P18 _______________________________________________________________________________________________ Donald R. Cook, Shelby County Development Services Revise text to read as follows: Fluorescent and high intensity discharge luminaires, LED lighting power supplies and self ballasted lamps installed in dwelling units shall comply with the requirements for an FCC Part 15 Class B Digital Device or the Part 18 limits for Consumer ISM Equipment. Compliance with the FCC requirements shall be marked on the luminaire, power supply or lamp as required by the FCC. Luminaires, power supplies or lamps that do not comply shall be marked “Not for use in dwellings”. Section 210.12(A) requires Arc-Fault Circuit-Interrupter (AFCI) protection in “all 120-volt, single phase, 15- and 20-ampere branch circuits supplying outlets installed in dwelling unit family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas”. The NEC defines an outlet as “a point on the wiring system at which current is taken to supply utilization equipment”, therefore, the requirement includes lighting circuits. 47 CFR Ch. I (10–1–98 Edition) Part 15—Radio Frequency Devices defines a Class B Digital Device as, “A digital device that is marketed for use in a residential environment notwithstanding use in commercial, business and industrial environments.” It further defines a digital device as, “An unintentional radiator (device or system) that generates and uses timing signals or pulses at a rate in excess of 9,000 pulses (cycles) per second and uses digital techniques; inclusive of telephone equipment that uses digital techniques or any device or system that generates and uses radio frequency energy for the purpose of performing data processing functions, such as electronic computations, operations, transformations, recording, filing, sorting, storage, retrieval, or transfer.” Electronic ballasts and switching power supplies meet this definition. Part 15 requires that Class B devices be labeled, “This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.” 47 CFR Ch. I (10–1–98 Edition) Part 18—Industrial, Scientific, and Medical Equipment defines Consumer ISM Equipment as, “A category of ISM equipment used or intended to be used by the general public in a residential environment, notwithstanding use in other areas.” Equipment meeting the consumer ISM limits must be marked with a compliance statement or the “FCC” logo. Electronic ballasts and switching power supplies meet this definition. While it is believed that fluorescent and high intensity discharge luminaires, or more specifically their electronic ballasts, LED lighting power supplies and self ballasted lamps need to meet the Part 18 requirements if installed in a dwelling unit, some manufacturers declare that their products meet the Part 15 Class B requirements. The incidence of AFCI unwanted tripping due to interoperability problems with such products is low, however, even though the UL 1699 standard for AFCIs requires unwanted tripping tests, unwanted tripping in the field does occasionally occur. When it does occur, homeowners become understandably annoyed and frustrated if they or their electrical contractor are unable to resolve the problem. Sometimes the cause of the tripping is not readily evident, leading the electrical contractor or homeowner to resolve the problem by replacing the AFCI with a standard thermal-magnetic circuit breaker. This violates the NEC requirement for AFCI protection and increases the risk of an electrical fire in the dwelling unit. AFCI manufacturers have made great strides in improving their product designs to reduce the probability of unwanted tripping; however, field investigations have revealed that sometimes luminaires with electronic ballasts, low voltage lighting switching power supplies and CFLs that do not comply with the previously referenced FCC requirements cause unwanted AFCI tripping. Such incidents have been successfully resolved by replacing the non-compliant product with one that does meet the FCC requirements. Contractors and homeowners can report unwanted AFCI tripping events on the AFCIsafety.org web site. A study of the reports filed over the past three years showed that 18% of the reports named some sort of lighting as either the sole load or one of the loads on the branch circuit at the time the tripping occurred. One AFCI manufacturer has documented 13 cases over the past three years where replacing a ballast with an FCC compliant model solved the unwanted tripping problem. Another AFCI manufacturer has documented at least five cases. In a 200 dwelling unit university dormitory with approximately 1000 AFCIs installed, unwanted tripping was experienced only on the 200 circuits feeding fluorescent lighting. This proposal is intended to reduce the possibility that luminaire or lamp operation may result in unwanted AFCI tripping by requiring that fluorescent and high intensity discharge luminaires, LED lighting power supplies and self ballasted lamps that do not comply with the aforementioned FCC requirements be marked NOT FOR USE IN DWELLINGS on the luminaire, power supply or lamp. This will help contractors select the correct luminaire for the application and help Printed on 3/16/2012 46 Report on Proposals – June 2013 NFPA 70 electrical inspectors check to insure that the appropriate luminaire, power supply or lamp has been installed. The end result will be increased safety, Code compliance and customer satisfaction. It should be noted that one of the nationwide homecenters has signage on their ballast display that reads, “Choose the right ballast. Step 1: Is it for residential or commercial use?” The sign indicates that the ballast carton labels are color coded. The residential and commercial ballast carton labels are color coded accordingly and the residential ballast labels have an FCC Part 18 consumer limits compliance statement. The NEMA white paper developed to provide the designers of home electrical products with information on the operating parameters of AFCIs, with the purpose of avoiding conditions in which the HEP could cause the unwanted operation of an AFCI, calls for compliance with the referenced FCC requirements. Comparable proposals have been submitted to revise Articles 210, 411 and 422. Refer to the panel action and statement on Proposal 18-63 which addresses the submitter's issue. Affirmative: 10 Negative: 1 LOWRANCE, JR., A.: See my Explanation of Negative Vote on Proposal 18-63. Printed on 3/16/2012 47 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-63 Log #2701 NEC-P18 _______________________________________________________________________________________________ David Clements, International Association of Electrical Inspectors Add new text to read as follows: Fluorescent and high intensity discharge luminaires, LED lighting power supplies and self ballasted lamps installed in dwelling units shall not generate electro-magnetic interference that will cause undesired operation of protective devices. Luminaires, power supplies or lamps that do not comply shall be marked “Not for use in dwellings”. Informational Note. See FCC Part 15 Class B Digital Device or the Part 18 limits for Consumer ISM Equipment for information on allowed electro-magnetic emissions. Section 210.12(A) requires Arc-Fault Circuit-Interrupter (AFCI) protection in “all 120-volt, single phase, 15- and 20-ampere branch circuits supplying outlets installed in dwelling unit family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas”. The NEC defines an outlet as “a point on the wiring system at which current is taken to supply utilization equipment”, therefore, the requirement includes lighting circuits. 47 CFR Ch. I (10–1–98 Edition) Part 15—Radio Frequency Devices defines a Class B Digital Device as, “A digital device that is marketed for use in a residential environment notwithstanding use in commercial, business and industrial environments.” It further defines a digital device as, “An unintentional radiator (device or system) that generates and uses timing signals or pulses at a rate in excess of 9,000 pulses (cycles) per second and uses digital techniques; inclusive of telephone equipment that uses digital techniques or any device or system that generates and uses radio frequency energy for the purpose of performing data processing functions, such as electronic computations, operations, transformations, recording, filing, sorting, storage, retrieval, or transfer.” Electronic ballasts and switching power supplies meet this definition. Part 15 requires that Class B devices be labeled, “This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.” 47 CFR Ch. I (10–1–98 Edition) Part 18—Industrial, Scientific, and Medical Equipment defines Consumer ISM Equipment as, “A category of ISM equipment used or intended to be used by the general public in a residential environment, notwithstanding use in other areas.” Equipment meeting the consumer ISM limits must be marked with a compliance statement or the “FCC” logo. Electronic ballasts and switching power supplies meet this definition. While it is believed that fluorescent and high intensity discharge luminaires, or more specifically their electronic ballasts, LED lighting power supplies and self ballasted lamps need to meet the Part 18 requirements if installed in a dwelling unit, some manufacturers declare that their products meet the Part 15 Class B requirements. The incidence of AFCI unwanted tripping due to interoperability problems with such products is low, however, even though the UL 1699 standard for AFCIs requires unwanted tripping tests, unwanted tripping in the field does occasionally occur. When it does occur, homeowners become understandably annoyed and frustrated if they or their electrical contractor are unable to resolve the problem. Sometimes the cause of the tripping is not readily evident, leading the electrical contractor or homeowner to resolve the problem by replacing the AFCI with a standard thermal-magnetic circuit breaker. This violates the NEC requirement for AFCI protection and increases the risk of an electrical fire in the dwelling unit. AFCI manufacturers have made great strides in improving their product designs to reduce the probability of unwanted tripping; however, field investigations have revealed that sometimes luminaires with electronic ballasts, low voltage lighting switching power supplies and CFLs that do not comply with the previously referenced FCC requirements cause unwanted AFCI tripping. Such incidents have been successfully resolved by replacing the non-compliant product with one that does meet the FCC requirements. Contractors and homeowners can report unwanted AFCI tripping events on the AFCIsafety.org web site. A study of the reports filed over the past three years showed that 18% of the reports named some sort of lighting as either the sole load or one of the loads on the branch circuit at the time the tripping occurred. One AFCI manufacturer has documented 13 cases over the past three years where replacing a ballast with an FCC compliant model solved the unwanted tripping problem. Another AFCI manufacturer has documented at least five cases. In a 200 dwelling unit university dormitory with approximately 1000 AFCIs installed, unwanted tripping was experienced only on the 200 circuits feeding fluorescent lighting. This proposal is intended to reduce the possibility that luminaire or lamp operation may result in unwanted AFCI tripping by requiring that fluorescent and high intensity discharge luminaires, LED lighting power supplies and self ballasted lamps that do not comply with the aforementioned FCC requirements be marked NOT FOR USE IN Printed on 3/16/2012 48 Report on Proposals – June 2013 NFPA 70 DWELLINGS on the luminaire, power supply or lamp. This will help contractors select the correct luminaire for the application and help electrical inspectors check to insure that the appropriate luminaire, power supply or lamp has been installed. The end result will be increased safety, Code compliance and customer satisfaction. It should be noted that one of the nationwide homecenters has signage on their ballast display that reads, “Choose the right ballast. Step 1: Is it for residential or commercial use?” The sign indicates that the ballast carton labels are color coded. The residential and commercial ballast carton labels are color coded accordingly and the residential ballast labels have an FCC Part 18 consumer limits compliance statement. The NEMA white paper developed to provide the designers of home electrical products with information on the operating parameters of AFCIs, with the purpose of avoiding conditions in which the HEP could cause the unwanted operation of an AFCI, calls for compliance with the referenced FCC requirements. Comparable proposals have been submitted to revise Articles 210, 411 and 422. The use of the term “dwelling unit” does not correlate to the FCC requirements. FCC Parts 15 and 18 have different EMC measurement thresholds for consumer & non-consumer applications, not for dwellings & non-dwellings. The FCC requirements never address dwellings. Accordingly, using “dwelling unit” to denote “consumer” is not accurate and will cause confusion. There are commercial dwellings, such as extended stay hotels and assisted living facilities, where FCC Part 15 Class A or Part 18 (non-consumer) is acceptable. Additionally, in the future, AFCI applications could be expanded into even more non-consumer applications, AFCI immunity to non-consumer FCC limits would then become a necessity. The standard for AFCIs, UL1699, does not evaluate the immunity level of AFCIs to FCC requirements. While some AFCI manufactures indicate that they test for immunity to certain FCC limits, there is no standard requiring this of all AFCI devices. Accordingly, even if FCC limits are somehow used to correlate AFCI immunity to a source of false tripping, there is no apparent mechanism in place to assure that this will correlate this to all AFCI devices. A review of UL1699 requirements for unwanted tripping tests reveal that the test conducted to show compatibility with fluorescent lighting does not provide any specifications for the ballast used in the test. Likewise the UL1699 requirements to show compatibility with electronic power supplies or HID products do not seem to adequately address modern lighting technologies. In any case, no UL1699 correlation to lighting ballasts or power supplies is provided. It seems that the issue is not a luminaire issue but rather an AFCI immunity issue and it appears that UL1699 should be revised to better address AFCI compatibility with common electrical products and possibly include labeling requirements for cases of known incompatibility. This is especially appropriate since it is the panel’s understanding that different AFCI manufacturers use different arc detection technologies so the only way of having consistent immunity to a false tripping source is to address the issue at the AFCI level. The panel is aware of some AFCI false trips being created by a 12V switching type power supply that contained no line filtering. The manufacturer of this device admitted that it did not comply with any FCC requirements and was aware of AFCI incompatibility with their product. However, no empirical data has been presented showing a FCC compliant ballast (consumer or non-consumer) nor FCC compliant power supply causing false AFCI tripping. Accordingly, the reports that the proposer addresses in his rational statement may have been misinterpreted as being caused by ballasts when they were actually caused by other equipment. This cannot be analyzed since the AFCI false tripping reports were sent directly to the AFCI manufacturer involved and are not available for public review on www.afcisafety.org. If AFCIs have an immunity issue with certain FCC compliant products like Class- A ballasts. It seems that it is the duty of the AFCI manufacturer to make this clear to their customers. Accordingly, if would seem appropriate to mark the AFCI with known incompatibility instead of expecting the luminaire industry to add additional markings to their products, especially since the FCC already require ballast & power supplies to be labeled. Affirmative: 10 Negative: 1 LOWRANCE, JR., A.: TThe Panel should have accepted this proposal in principle by revising the Informational Note as follows: Informational Note. FCC Part 15 Class B Digital Device or the Part 18 limits for Consumer ISM Equipment defines electro-magnetic emissions and marking requirements for devices and equipment intended to be used in dwellings. I disagree with the Panel Statement that the use of the term “dwelling unit” does not correlate to the FCC requirements. This is a semantics argument of no substance. The NEC uses the term “dwelling unit” and the FCC the term “residential environment”. Part 18 defines Consumer ISM equipment as, “A category of ISM equipment used or intended to be used by the general public in a residential environment.” The Panel Statement references extended stay hotels and assisted living facilities. Article 100 defines a dwelling unit as, “A single unit, providing complete and independent living facilities for one or more persons, including permanent Printed on 3/16/2012 49 Report on Proposals – June 2013 NFPA 70 provisions for living, sleeping, cooking, and sanitation.” The units in an extended stay hotel are therefore defined by the NEC as dwelling units and must be equipped with AFCIs. Units in an assisted living facility may or may not require AFCIs depending on whether or not they are dwelling units. But from an FCC perspective, a case could be made that both are a “residential environment” and therefore products meeting the Part 15 Class A and Part 18 non-consumer ISM requirements are not acceptable. The Panel Statement also mentions future AFCI applications, however, the Code does not require the use of AFCIs in such applications and the AFCIs on the market today have not been designed and tested for application in non-dwelling units, so this is not an issue today. Regarding the immunity level of AFCIs to FCC requirements the UL 1699 standard requires testing electromagnetic field immunity to IEC 61000-4-3 and conducted disturbance to RF fields to IEC 61000-4-6. These standards are commonly used to test various types of electronic devices, including GFCIs and circuit breaker electronic trip units. While UL 1699 requires unwanted tripping testing, and manufacturers may conduct additional tests beyond these requirements, actual field conditions may be different from the results in the lab. The electrical distribution and utilization equipment in a home form a system. It is unrealistic to expect components in one part of the system to work properly when other components in the system are allowed to do anything they please. The Panel Statement also mentions future AFCI applications, however, the Code does not require the use of AFCIs in such applications and the AFCIs on the market today have not been designed and tested for application in non-dwelling units, so this is not an issue today. Regarding the immunity level of AFCIs to FCC requirements the UL 1699 standard requires testing electromagnetic field immunity to IEC 61000-4-3 and conducted disturbance to RF fields to IEC 61000-4-6. These standards are commonly used to test various types of electronic devices, including GFCIs and circuit breaker electronic trip units. While UL 1699 requires unwanted tripping testing, and manufacturers may conduct additional tests beyond these requirements, actual field conditions may be different from the results in the lab. The electrical distribution and utilization equipment in a home form a system. It is unrealistic to expect components in one part of the system to work properly when other components in the system are allowed to do anything they please. _______________________________________________________________________________________________ 18-64 Log #332 NEC-P18 _______________________________________________________________________________________________ Mitch Miller, City of Aspen Revise text to read as follows: No parts of cord-connected luminaires, chain-, cable·, or cord-suspended luminaires, lighting track, pendants, or ceiling-suspended (paddle) fans shall be located within a zone measured 900 mm (3 ft) horizontally and 2.5 m (8 ft) 3 m (10 ft) vertically from the top of the bathtub rim or shower stall threshold. This zone is all encompassing and includes the space directly over the tub or shower stall. All Luminaires located directly over the tub or shower stall to 3 m (10 ft vertically from the top of the bathtub rim or shower stall threshold shall be marked for wet locations. Luminaires located within the actual outside dimension of the bathtub or shower to a height of 2.5 m (8 ft) 3 m (10 ft) vertically from the top of the bathtub rim or shower threshold shall be marked for damp locations, or marked for wet locations where subject to shower spray. As an Electrical Inspector I see many instances in which directly over the tub or shower is an enclosed unit. Many ceilings above the units exceed 8 ft. While most applications do not meet the requirements of subject to shower spray the amount of steam produced can exceed damp location type definition. There are instance when one could conclude the area is actually saturated from the steam which is defined as a wet location. The code is lacking in personal protection without a code change. The submitter has not provided definitive substantiation that a hazard exists. The definition of a wet location does not include exposure to steam. Affirmative: 11 Printed on 3/16/2012 50 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-65 Log #1280 NEC-P18 _______________________________________________________________________________________________ Paul Esposti, Hamilton Township Add text to read as follows: Outdoor luminaries requiring a trench for the wiring method, regardless of the wiring method utilized, shall be labeled on drawings with a unique alpha/numeric or combination of alpha/numeric designation at each luminaire. After installation each luminaire shall be permanently labeled with same alpha/numeric or combination of alpha/numeric designation. Labeling shall be at least 1 in. high and visible from grade. Frequently, trench inspections are done in segments and over a period of time. It can be difficult to keep track of which trenches have been inspeted on large projects with multiple inspections. Recording inspections will be more accurate with luminare designations. Also, for maintenance issues it will be easier to schedule and keep a record of when maintenance is needed and when done. The submitter has provided no definitive substantiation that a hazard exist to cause this change. Affirmative: 11 O'BOYLE, M.: 90.1(B) indicates that compliance with the Code does not necessarily result in an efficient or convenient installation. _______________________________________________________________________________________________ 18-66 Log #2737 NEC-P18 _______________________________________________________________________________________________ James H. Maxfield, City of Dover Fire & Rescue Proposal to read: Luminaires installed in expose or concealed locations under metal - corrugated sheet roof decking, shall be installed and supported so there is not less than 38 mm (1 1/2 in.) measured from the lowest surface of the roof decking to the top of the luminaire. Informational Note: Roof decking material is often repaired or replace after the initial roofing installation and may be penetrated by the screws or other mechanical devices designed to provide "hold down strength of the waterproof membrane or roof insulating material. Physical damage is not limited to only cables, raceways and boxes installed within this area. The luminaire itself, conductors and its associated equipment such as the ballast(s) and transformer within the equipment are also subject to teh same physical damage. Section 300.4(D) of the NEC does not permit the cables, raceways and boxes to be installed within this area therefore the addition of this new section would also prevent the same damage to the luminare. Panel 3 currently recognizes the physical damage and potential hazard to the electrical installation within this area and Panel 18 should also recognize the same potential hazards. Note: Supporting material is available for review at NFPA Headquarters. The rejected part is the informational note. The informational note is already covered in 300.4(E). Affirmative: 11 Printed on 3/16/2012 51 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-67 Log #3142 NEC-P18 _______________________________________________________________________________________________ Marcus R. Sampson, Lysistrata Electric Revise text to read as follows: The minimum clearance between luminaires installed in clothes closets and the nearest point of a closet storage space shall be as follows: (1) 300 mm (12 in.) for surface-mounted incandescent or LED luminaires with a completely enclosed light source installed on the wall above the door or on the ceiling. (2) 150 mm (6 in.) for surface-mounted or fluorescent luminaires installed on the wall above the door or on the ceiling. (3) 150 mm (6 in.) for recessed incandescent or LED luminaires with a completely enclosed light source installed in the wall or the ceiling. (4) 150 mm (6 in.) for recessed fluorescent luminaires installed in the wall or the ceiling. (5) Surface-mounted fluorescent or LED luminaires shall be permitted to be installed within the closet storage space where identified for this use. Both subsection (A) in the positive and subsection (B) in the negative, located directly above part (C) make it clear that surface-mounted incandescent or LED luminaires must have completely enclosed light sources. Restating it in the “list” in subpart (C) is unnecessary. CMP18 recognizes that the wording is redundant but did this intentionally for clarity. Affirmative: 11 _______________________________________________________________________________________________ 18-68 Log #1536 NEC-P18 _______________________________________________________________________________________________ Vince Baclawski, National Electrical Manufacturers Association (NEMA) Add the following new sentence in Section 410.20: Canopies and outlet boxes taken together shall provide sufficient space so that luminaire conductors and their connecting devices are capable of being installed in accordance with 314.16. To be included in the total box volume calculation, canopies shall be marked with their internal volume. Luminaire canopies are seldom, if ever, marked with their internal volume. Yet, they are often relied upon as wiring space, particularly with shallow pan boxes. This new language will make clear that a luminaire canopy has to be marked with its internal volume in order to be included in the total box volume calculation. Add the following new sentence in Section 410.20: Canopies and outlet boxes taken together shall provide sufficient space so that luminaire conductors and their connecting devices are capable of being installed in accordance with 314.16. Only canopies marked with internal volume shall be included in the total box volume calculation. The submitter's new sentence is modified for clarity. Affirmative: 11 Printed on 3/16/2012 52 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-69 Log #1594 NEC-P18 _______________________________________________________________________________________________ Edward Joseph, Underwriters Laboratories Inc. Revise text to read as follows: Any combustible wall or ceiling finish exposed between 2 2 the edge of a luminaire canopy or pan and an outlet box, having a surface area of 1160 mm (180 in ) or more, shall be covered with noncombustible material. This proposed revision to Section 410.23 aligns the requirements in the NEC and ANSI/UL1598 for “listed” luminaires and serves to further support Section 410.6 which requires the installation of “listed” luminaires. Questions have been raised by inspection authorities concerning Section 410.23 as to whether or not there is a need to additionally cover combustible mounting surfaces as defined within in the Article, when installing a “listed” ceiling mounted or wall mounted canopy style luminaire that does not have a back-plate or back-cover . Based on explanatory notes in 2008 NEC handbook, Section 410.23 was written to address overheating of combustible surfaces. The note states the following: ” Luminaires must be designed and installed not only to prevent overheating of conductors but to prevent overheating of adjacent combustible wall or ceiling finishes. Hence, it is required that any combustible finish between the edge of a luminaire canopy and an outlet box be covered with a noncombustible material or luminaire accessory. See 314.20 for the requirements covering combustible finishes. Where luminaires are not directly mounted on outlet boxes, suitable outlet box covers are required." Listed luminaires are evaluated to the requirements of the Standard for Luminaires, ANSI/ UL1598. Based on requirements in the ANSI/UL 598 standard, “listed” canopy style surface or ceiling mounted luminaires do not require a 2 back-plate or back-cover provided the total area of the surface being covered by the canopy is less than 1160 mm 2 (180 in ). In addition, these “listed” canopy style luminaires are evaluated based on requirements in the standard to ensure that temperatures on wall or ceiling surfaces on which the luminaire is mounted do not exceed 90 degrees centigrade. This 90 degrees centigrade limit, is the limit that both the luminaire standard and the NEC assigns for continuous heating of combustible materials. These requirements have been in effect for “listed” luminaires for several decades. In summary, the requirements for “listed” luminaires fulfills the requirement of Section 410.23 and therefore, does not warrant the need for additional protection of a combustible mounting surface beyond what the “listed” luminaire provides . This proposed revision to Section 410.23 will provide the needed clarification. Affirmative: 11 _______________________________________________________________________________________________ 18-70 Log #1852 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Revise text to read as follows: . Electric-discharge and LED luminaires supported independently of the outlet box shall be connected to the branch circuit through metal raceway, nonmetallic raceway, Type MC cable, Type AC cable, Type MI cable, nonmetallic sheathed cable (NM), or by flexible cord as permitted in 410.62(B) or 410.62(C). "nonmetallic sheathed cable" is referred to in several ways: "nonmetallic sheathed cable", "type NM" "type MNC" "type NMS" "NM" .... Nonmetallic sheathed also appears to be used for other than NM cable in some cases. Suggest that "NM" be added to all references. This will make finding all references to "nonmetallic sheathed cable" easier and more reliable. The submitter has not provided definitive substantiation for the change. The panel does not agree that adding the type abbreviations will make the code easier to use. Affirmative: 11 Printed on 3/16/2012 53 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-71 Log #3301 NEC-P18 _______________________________________________________________________________________________ Elliot Rappaport, Coconut Creek, FL Replace the phrase “equipment grounding conductor” with the phrase “equipment bonding conductor” in the Articles and Sections as identified below. Replacement of “grounding” or “ground” when used separately is covered in separate proposals. 410.30(B)(5); 410.42; 410.44 & Excs. 1, 2, & 3; 410.46; 410.59; 410.82(B)(4); 410.151(D). This proposal is one of a series of proposals to replace, throughout the Code, the term “grounding” with “bonding” where appropriate. As used in the Code, “grounding” is a well defined term and refers to connecting to the earth or ground for any one of a number of reasons. Similarly, “bonding” is the connection of two bodies together to form a continuous electrical path. The term “equipment grounding conductor” has a definite purpose that is not uniquely expressed in the term. As a result, there is a misconception that “grounding” will make a system safe. On the contrary, connecting equipment to ground without providing the bonding connection back to the source can make the equipment less safe. The purpose of the “equipment grounding conductor (EGC) is to provide a low impedance path from a fault at equipment “likely to become energized” to the source of the electrical current (transformer, generator, etc,). If it is argued that the purpose is to connect the equipment to ground, then the requirement of 250.4(A)(5) that “the earth shall not be considered as an effective ground fault path” would no longer be valid because fault current would then be intended to flow to the ground (earth). From the conductor sizing requirements of 250.122, and specifically 250.122(B), it is apparent that the purpose of the EGC is related to connection (bonding) to the source of power rather than connection to ground. If the principle purpose was the connection to ground, then the sizing requirements would be less important since near equipotential conditions can be achieved with much smaller conductors. The fundamentals of these proposals are to clearly state that “systems” are “grounded” and “equipment” is “bonded”. The fact that the bonding conductor may be grounded also is secondary to the primary function of bonding. This proposal proposes changing the word “grounding” to “bonding”, where appropriate, throughout the Code. It is clear that there are many places where “grounding” is used to identify the connection to earth (grounding electrode conductor) and “grounding” should remain. Additionally, the expression “EGC” should be changed to “EBC”, “equipment bonding conductor” for consistency. The term "Equipment Grounding Conductor" is correct and defined. Equipment Bonding Conductor is not defined in the code. Affirmative: 11 Printed on 3/16/2012 54 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-72 Log #895 NEC-P18 _______________________________________________________________________________________________ William Blaha, Ideal Industries Inc. Add new paragraph (7) to 410.30(B) as follows: (7) An inline disconnecting means shall be provided that is accessible, mounted in the pole base or in a handhole immediately adjacent to the pole base. The inline disconnecting means shall be a listed inline device that: (a) Prevents unintentional contact with exposed energized conductors by persons or animals. (b) Safely disconnects the supply conductors to the pole. (c) Allows for the safe servicing of the luminaire(s) and associated wiring. (d) Is capable of being manually disconnected to allow servicing of the luminaire. (e) Is rated for the luminaire current. An electrical shock hazard exists when roadway, parking lot, or area lighting poles are either knocked down or serviced. When the pole is knocked down and the subsequent servicing occurs there are potentially full-voltage energized conductors protruding from the luminaire base, pedestal, or junction box. At this point, any person or animal can come into contact with these energized conductors. Unintentional contact by a motor vehicle, person, or animal may result in electrical shock and/or property damage. This protective product conforms with the American Association of State Highway and Transportation Officials (AASHTO) Roadway Lighting Design Guide (Chapter 8, October 2005) and is presently specified and used by a large number of the states' Departments of Transportation in roadway lighting installations. Since 2005, the NEC has required similar protection for the servicing of ballast-type fluorescent luminaires (Section 410.130(G)). Though servicing of the ballast is typically performed by a trained electrician, a disconnect requirement was still inserted into the NEC to prevent shock hazard. To protect vehicle occupants, AASHTO standards require certain lighting poles in roadway installations to “break away” when struck by a vehicle; however, poles located in areas with significant pedestrian traffic, such as parking lots, are designed to remain standing. The roadway lighting poles that the submitter describes are not within the scope of the code per 90.2. Affirmative: 10 Negative: 1 COSTELLO, P.: The submitter of this proposal recognizes an electrical shock hazard associated with servicing of pole mounted luminaires. The submitter's substantiation briefly cites servicing of the pole mounted luminaires and explains in more detail the instances where a pole is knocked down exposing conductors. The panel did discuss the requirements associated with the American Association of State and Highway and Transportation Officials Roadway Lighting with reference to the pole being struck by a vehicle as the submitter describes. The panels statement informs the submitter that the roadway lighting poles described are not within the scope of the code per 90.2. The panel did have a lengthily discussion concerning servicing of luninaires mounted on poles and identified a number of issues a worker faces when performing this task. Incorporating an accessible disconnecting means at the pole would permit the worker to put the luminaire into an electrically safe working condition. I would encourage the submitter to comment more on the protection of servicing pole mounted luminaires with a disconnecting means being within the pole. O'BOYLE, M.: In the situation the submitter describes, where a lighting pole is knocked down, resulting damage to conductors and in-line disconnects could expose hazardous live parts. The presence of a local in-line disconnect might provide a false sense of security and result in a delay in properly disconnecting power to the damaged installation. Also, digging through a damaged pole and wiring in search of an in-line disconnect, without first de energizing the branch circuit or donning protective gear, could pose a risk of electrical shock. Also, the submitter did not provide definitive substantiation for this change. 410.130(G) requires disconnects only for fluorescent luminaires utilizing double ended lamps. This is due to an extremely limited accident report involving this particular type of product. Double ended fluorescent lamp luminaires typically allow easy tool-less access to wiring compartments and are sometimes serviced or retrofitted by unqualified personnel. There are many millions of installed Printed on 3/16/2012 55 Report on Proposals – June 2013 NFPA 70 ballasts that periodically require replacement. Outside the limited accident report involving double ended fluorescent luminaires, there has been no empirical data presented to indicate that a problem exists. In my opinion, local disconnects may actually present a hazard. The anticipation of an internal disconnect may cause even a qualified service person to open an electrical enclosures without first disconnecting power to the circuit feeding the luminaires or using proper protective gear. In such situations, there may be conditions ( as simple as a dislodged twist on wire connector ) that will expose the service personnel to hazardous power. I believe that the best course of action is to always disconnect power to the circuit feeding the luminaires or use proper personal protective equipment when servicing. _______________________________________________________________________________________________ 18-72a Log #CP1802 NEC-P18 _______________________________________________________________________________________________ Code-Making Panel 18, Revise the informational note for 410.52 to read as follows: Informational Note: For ampacity of fixture wire, maximum operating temperature, voltage limitations, minimum wire size, and other information, see Article 402. The panel editorially revised the informational note to replace the words "so forth" with "other information." Affirmative: 11 _______________________________________________________________________________________________ 18-73 Log #810 NEC-P18 _______________________________________________________________________________________________ Dennis Alwon, Alwon Electric Inc. Add new text to read as follows: Stranded conductors shall be used for wiring on luminaire chains and on other moveable or flexible parts. Exception: Where run in a flexible cable, cord or raceway As written the section will not allow MC or other cables to be run down to a fluorescent fixture that is hung from jack chain. It does not appear to be the intent however as written it is interpreted that way in some areas. This method of wiring fluorescents has been common practice for as long as I can remember and I have never seen an issue with this type of install. Part VI, "Wiring of Luminaires" does not apply to the wiring to the luminaire just the wiring of the luminaire itself. Refer to Chapter 3 for Wiring Methods. Affirmative: 11 Printed on 3/16/2012 56 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-74 Log #3088 NEC-P18 _______________________________________________________________________________________________ Frederic P. Hartwell, Hartwell Electrical Services, Inc. Add parent text to (C) and revise (1) ; make no change to (2) or (3), as follows Electric discharge luminaires shall comply with (1), and also with (2) or (3) or both as specifically apply to the application. A luminaire or a listed assembly in compliance with any of the conditions in (a) through (c) shall be permitted to be cord connected provided the following conditions are met: (1) The luminaire is located directly below the outlet or busway (2) The cord is not be subject to strain or physical damage (3) The cord is visible over its entire length except at terminations. If the following conditions apply: (1) The luminaire is located directly below the outlet or busway. (a) Plug-Connected. A luminaire shall be permitted to be connected with a cord terminating in a grounding-type attachment plug or busway plug. (b) Strain Relief and Canopy Provided. A luminaire assembly equipped with a strain relief and canopy shall be permitted to use a cord connection between the luminaire assembly and the canopy. The canopy shall be permitted to include a section of raceway not over 150 mm (6 in.) in length and intended to facilitate the connection to an outlet box mounted above a suspended ceiling. (c) Manufactured Wiring Systems. Listed assemblies incorporating manufactured wiring system connectors in accordance with 604.6(C), shall be permitted to be cord connected. (2) The flexible cord meets all the following: a. Is visible for its entire length outside the luminaire b. Is not subject to strain or physical damage c. Is terminated in a grounding-type attachment plug cap or busway plug, or is a part of a listed assembly incorporating a manufactured wiring system connector in accordance with 604.6(C), or has a luminaire assembly with a strain relief and canopy having a maximum 152 mm (6 in.) long section of raceway for attachment to an outlet box above a suspended ceiling This is a resubmittal of Proposal 18-134 in the 2011 cycle, with all technical objections noted by CMP 18 fully addressed, and a provision in (1) reformatted as a list. The principal issue with this part of the Code is paragraph c. This is an almost incomprehensible 62-word run-on sentence that is extremely difficult to follow. CMP 18 opined that this was just the opinion of the submitter and refused to act in the 2011 cycle. Recent history shows otherwise. Until recently (2005 NEC) 240.5(B)(1) directly conflicted with this section because it only recognized flexible cord with a “portable lamp.” This submitter attempted to get this changed, and cited the conflict with this section. CMP 10 responded with a rejection (see Comment 10-25 for the 2005 NEC), saying in part “The fixture cords in question as applied per 410.30(C)(1) are not hard wired and are required to be terminated in a grounding-type plug. This allows the fixture to be easily moved, meaning that the fixture is of a portable nature.” It took another code cycle to reverse the CMP 10 position. The submitter’s Proposal 10-15 in the 2008 cycle explained the way this provision actually worked, requiring almost an entire column of small print to dissect the numerous allowances within this 62-word sentence and to cover the history of this section and the one in Article 240 in order to show that the conflict was real. CMP 10 did reverse course on this for the 2008 NEC and the conflict has disappeared. However, if an entire code making panel proved unable to correctly interpret this provision over the course of a code making cycle, and it required a half page of explanatory information to sort this out, how can we expect ordinary users to do so in the field? T he NEC Style Manual in 3.3.1 at its second topic states the following: “Use simple declarative sentence structure, and keep sentences short. Writing rules in long sentences full of commas, dependent clauses, and parenthetical expressions often creates confusion and misunderstanding. The requirement can often be written in two or more short sentences, expressed using a list or table, or both.” This Code provision is perhaps the leading poster child for violations of this common-sense editorial requirement Even a code making panel misinterpreted it. It is long past time to fix this, and if this proposal fails, the Correlating Committee should take action to police the use of the Style Manual in this case. The proposed change does not add clarity and is additionally incorrect; 410.62(C)(1), (2), and (3) are independent requirements. Printed on 3/16/2012 57 Report on Proposals – June 2013 NFPA 70 Affirmative: 11 _______________________________________________________________________________________________ 18-75 Log #835 NEC-P18 _______________________________________________________________________________________________ Michael J. Johnston, National Electrical Contractors Association Insert new text following 410.62(C)(1)(2)(c): This proposal will clarify that electric-discharge and LED luminaires are not excluded from the allowances stated in 462.62(B). Some inspectors have enforced the requirements of 410.62(C)(1)(2) on adjustable electric-discharge luminaires. The exception is not necessary because 410.62(B) and (C) are independent requirements. Affirmative: 11 _______________________________________________________________________________________________ 18-76 Log #387 NEC-P18 _______________________________________________________________________________________________ T. J. Woods, Wyoming Electrical JATC Revise text to read as follows: Feeder and branch-circuit conductors within 75 mm (3 in.) of a ballast, LED driver, power supply, or transformer shall have an insulation temperature rating not lower than 90°C (194°F), unless supplying a luminaire marked as suitable for a different insulation temperature. , or if the insulation type is acceptable in Table 310.104(A). 410.68 should include this language to help clarify another condition. According to Table 310.104(A,) THW insulation is also allowed within 75 mm (3 in.) of a ballast; however, it is 75°C insulation. Table 310.104(A) states that THW under certain conditions is rated 90°C. Affirmative: 11 _______________________________________________________________________________________________ 18-77 Log #465 NEC-P18 _______________________________________________________________________________________________ Robert Welborne, R & R Electric Company Exception: Internal or external disconnects are not required if existing luminaires are retrofitted with fully encapsulated LED lamps that bypass or eliminate the ballast(s). I am recommending a new "Exception" be added to the present article exempting the need for a disconnect where LED lamps that are fully encapsulated are installed. Some manufacturers are manufacturing UL listed T8 lamps 120 volts and 277 volts that have the LED drivers fully enclosed within the tube. Therefore, eliminating the need for any existing ballast(s). Presently, the way the Code reads, a disconnect whether internal or external is required for a double ended lamp holder that contain a ballast(s). Since removal of the ballast(s) are required to complete installation for the new LED lamps, there is no need to require a disconnect. Luminaires without a fluorescent ballast would not be required to have disconnects. Affirmative: 11 Printed on 3/16/2012 58 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-78 Log #693 NEC-P18 _______________________________________________________________________________________________ Roger Zieg, Zieg Electric Delete text to read as follows: Exception No. 4: A disconnecting means shall not be required in industrial establishments with restricted public access where conditions of maintenance and supervision ensure that only qualified persons service the installation by written procedures. The purpose of the is the practical safeguarding of persons and property from hazards arising from the use of electricity. Qualified person is defined in the , but the meaning is certainly open to interpretation. Some states and/or local jurisdictions do not require the licensing of industrial electricians and leave it to the individual industrial establishment to define the meaning of the qualified person. It is my belief that this exception should be deleted because it does not provide practical safeguarding for the qualified person. Why should the qualified person be offered less protection, especially in this day of electrical safe work practices? Refer to the panel action and statement on Proposal 18-80 which addresses the same issue. Affirmative: 8 Negative: 3 COSTELLO, P.: See my Explanation of Negative Vote on Proposal 18-78. GRAY, B.: See my Explanation of Negative Vote on Proposal 18-79. LOWRANCE, JR., A.: This exception should be deleted because it does not provide practical safeguarding for qualified persons. A person doing maintenance should have every possibility of safety in his job. The deletion of this exception adds another layer of safety. Printed on 3/16/2012 59 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-79 Log #1370 NEC-P18 _______________________________________________________________________________________________ Charles M. Trout, Maron Electric Company Delete Exception No. 4 in its entirety. The basic rule for safety is to not work on energized equipment. This Exception encourages workmen to work on energized equipment. It is in direct opposition to the "safety in the workplace" rules promoted by NFPA 70E. Refer to the panel action and statement on Proposal 18-80 which addresses the same issue. In addition with reference to the submitter's substantiation, the requirements of NFPA 70E, , should be followed. Affirmative: 8 Negative: 3 COSTELLO, P.: I agree with the submitter and this proposal should be accepted. There should not be an exception that permits a worker to perform an unsafe task in an “industrial establishment” that they would otherwise not be able to perform in other locations code by this article. The panel is in agreement that the requirements of NFPA 70E, apply and shall be followed. Applying the requirements of Article 130.2 of NFPA 70E, energized electrical conductors shall be put into an electrically safe work condition before an employee performs work. This is exactly what is being met by deleting the exception the submitter proposed. Servicing luminaries while energized does not appear to meet the requirements of NFPA 70E, Article 130.2(A) which recognize tasks that (1) introduce a Greater Hazard, (2) is Infeasible due to its equipment design or operational limitations, or (3)operating at Less Than 50 Volts. GRAY, B.: The Panel Action should have been to Accept. The Panel Statement implies that NFPA 70E provides an option for not deenergizing exposed electrical conductors. In fact, both OSHA (29CFR1910.333(a)(1)) and NFPA 70E (130.2(A)) require exposed energized part to be deenergized before a worker can approach nearer than a safe distance to the parts. The rule is designed to apply to qualified workers since qualified workers are the only workers allowed to approach exposed energized parts (NFPA 70E, 130.4(D)). By exempting the requirement to place a disconnecting means in a convenient location to meet these requirements, the Panel has provided a motivation to not comply. According to NIOSH (PUB 98-131), industrial workplaces in manufacturing facilities account for 12% (third highest) of fatalities in US workplaces due to electrocution. To grant these workplaces special relief from controls that are designed to protect from electrocution seems irresponsible to me. LOWRANCE, JR., A.: See my Explanation of Negative Vote on Proposal 18-78. Printed on 3/16/2012 60 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-80 Log #1554 NEC-P18 _______________________________________________________________________________________________ David Clements, International Association of Electrical Inspectors Delete text as follows: Exception No 4: A disconnecting means shall not be required in industrial establishments with restricted public access where conditions of maintenance and supervision ensure that only qualified persons service the installation by written procedures. The purpose of the is the practical safeguarding of persons and property from hazards arising from the use of electricity. Qualified person is defined in the , but the meaning is certainly open to interpretation. Some states and/or local jurisdictions do not require the licensing of industrial electricians and leave it to the individual establishment to define the meaning of a qualified person. It is my belief that this exception should be deleted because it does not provide practical safeguarding for the qualified person. Why should the qualified person be offered less protection, especially in this day of electrical safe work practices? Panel 18 accepts that not all Authorities having Jurisdiction require licensing but in an industrial establishment the definition of qualified persons is defined by OSHA in 1910.399 Subpart S and as defined in Article 100. Qualified Persons. One who has received training in and has demonstrated skills and knowledge in the construction and operation of electric equipment and installations and the hazards involved. Affirmative: 8 Negative: 3 COSTELLO, P.: See my Explanation of Negative on Proposal 18-79. GRAY, B.: See my Explanation of Vote on Proposal 18-79. LOWRANCE, JR., A.: See my Explanation of Negative vote on Proposal 18-78. O'BOYLE, M.: In my opinion, local luminaire disconnects may actually present a hazard. The anticipation of an internal disconnect may cause even a qualified service person to open an electrical enclosures without first disconnecting power to the circuit feeding the luminaires or using proper protective gear. In such situations, there may be conditions ( as simple as a dislodged twist on wire connector ) that will expose the service personnel to hazardous power. I believe that the best course of action is to always disconnect power to the circuit feeding the luminaires or use proper personal protective equipment when servicing. In industrial establishments, where qualified personnel service equipment following written procedures, proper disconnection of the branch circuit or use of protective equipment should not be ignored. Printed on 3/16/2012 61 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-81 Log #2166 NEC-P18 _______________________________________________________________________________________________ Marcelo M. Hirschler, GBH International Revise text to read as follows: Informational Note: Combustible low-density cellulose fiberboard includes sheets, panels, and tiles that have a density 3 3 of 320 kg/m (20 lb/ft ) or less and that are formed of bonded plant fiber material but does not include solid or laminated 3 3 wood or fiberboard that has a density in excess of 320 kg/m (20 lb/ft ) or is a material that has been integrally treated with fire-retarding chemicals to the degree that the flame spread index in any plane of the material will not exceed 25, determined in accordance with tests for surface burning characteristics of building materials. See ANSI/ASTM E84-2011b 1997, . ASTM E84 has an updated date – the measurement by ASTM E84 is flame spread index and not just flame spread (editorial issue). Affirmative: 11 _______________________________________________________________________________________________ 18-82 Log #2791 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Revise text to read as follows: Wired luminaire sections are paired, with a ballast(s) supplying a lamp or lamps in both. For interconnection between paired units, it shall be permissible to use metric designator 12 (trade size 3/8) flexible metal conduit (FMC) in lengths not exceeding 7.5 m (25 ft), in conformance with Article 348. Luminaire wire operating at line voltage, supplying only the ballast(s) of one of the paired luminaires shall be permitted in the same raceway as the lamp supply wires of the paired luminaires. "Flexible Metal Conduit" is also referred to as “FMC” Suggest that “(FMC)” be added to all references. This will make finding all references to "Flexible Metal Conduit" easier and more reliable. The submitter has not provided definitive substantiation for the change. The panel does not agree that adding the type abreviations will make the code easier to use. Affirmative: 11 Printed on 3/16/2012 62 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-83 Log #285 NEC-P18 _______________________________________________________________________________________________ Stanley J. Folz, Morse Electric Company Revise text to read as follows: The switch or circuit breaker shall be located within sight from the luminaires or lamps, or it shall be permitted to be located elsewhere if it is provided with a means for locking in the open position. The provisions for locking or adding a lock to the disconnecting means must remain in place at the switch or circuit breaker whether the lock is installed or not. Portable means for adding a lock to the switch or circuit breaker shall not be permitted. lockable in accordance with 110.25. This proposal has been developed by the Usability Task Group assigned by the Technical Correlating Committee. The committee members were Stanley Folz, James Dollard, William Fiske, David Hittinger, Andy Juhasz, Amos Lowrance, Susan Newman-Scearce, Marc Bernsen and Vincent Zinnante. Requirements for a disconnecting means to be lockable in the open position exist in numerous locations in the NEC. A new section has been proposed in Article 110 to consolidate the requirements for a disconnecting means required to be “capable of being locked in the open position” in a single section for clarity. It is understood that this requirement includes more than disconnecting and locking electrical power sources. This proposal is intended to facilitate a lockout/tagout scenario. It is equally important to ensure that the means for placing the lock remain in place. The concept suggested by this proposal is necessary to provide correlation throughout the NEC with respect to the capability of placing a lock on a disconnecting means to secure it in the open position. Affirmative: 11 Printed on 3/16/2012 63 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-84 Log #862 NEC-P18 _______________________________________________________________________________________________ Michael J. Johnston, National Electrical Contractors Association Add a new last sentence as follows: The caution sign(s) or label(s) shall comply with 110.21(B). This proposal is one of several coordinated companion proposals to provide consistency of danger, caution, and warning sign or markings as required in the NEC. The proposed revision will correlate this caution marking requirement with proposed 110.21(B) and the requirements in ANSI Z 535.4. Affirmative: 9 Negative: 2 BER, M.: To realize the full extent of this proposal it is necessary to review Proposal 1-114 as “Accepted in Principle in Part” by CMP-1. Also, remember that Proposal 18-84 is only concerned with “Caution” Labels as required by 410.146. Note that 110.21B is limited to “Field-Applied Markings”, which means that these labels are intended to be applied in the field and must comply with the multitude of stringent requirements in the proposal and in the ANSI Standard The only way that the field installer is going to be able to meet the conditions of this proposal is to maintain a huge inventory of preprinted labels and signs in a multitude of colors, with various messages, in many different sizes, and made from different materials and having specific types of glue to be “suitable for the environment where it is installed”. But once again we have an Informational Note that directs us to a specific ANSI Standard that apparently provides the parameters for these signs and labels. Good thing as the wording of the proposal is not clear as to how we obtain a “yellow and white” background. Fortunately, the cost of this standard is only $89.00 from the ANSI Standards Store. Unfortunately, few electricians are going to run right out and purchase copies of this standard, but maybe the municipalities will add this to their budgets so the local inspector can provide the necessary guidance and determination as to the compliance of each sign or label. This is another one of those well intentioned proposals that introduces so much new unneeded overly complex material into this section of the Code as to make it virtually unusable. This proposal appears to have little relevance to or effect on safety, it only serves to complicate the code, adds to its enforcement difficulty and therefore results in less compliance. O'BOYLE, M.: 410.146 addresses factory applied markings, supplied as part of the listing required by 410.140. The submitter makes reference to his proposal 1-114, which is being balloted as Accept in Principle & Part. In that proposal, 110.2(B) applies to Field-Applied Markings. _______________________________________________________________________________________________ 18-84a Log #CP1803 NEC-P18 _______________________________________________________________________________________________ Code-Making Panel 18, Delete the Informational Note and revise the text of 410.151(B) as follows: The connected load on lighting track shall not exceed the rating of the track. Lighting track shall be supplied by a branch circuit having a rating not more than that of the track. The load calculation in 220.43(B) does not limit the length of track on a single branch circuit, and it does not limit the number of luminaires on a single track. requirement. The panel has incorporated the informational note into the text of 410.151(B) because it contains a Affirmative: 11 Printed on 3/16/2012 64 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-85 Log #2938 NEC-P18 _______________________________________________________________________________________________ Michael S. O'Boyle, Philips-Lightolier Revise text to read as follows: This article covers lighting systems operating at 30 volts or less and their associated components. This article also covers lighting equipment connected to a Class 2 power source. A lighting system consisting of an isolating power supply, the low-voltage luminaires, and associated equipment that are all identified for the use. The output circuits of the power supply are rated for not more than 25 amperes and operate at 30 volts (42.4 volts peak) or less under all load conditions. Lighting equipment marked for connection to a Class 2 power source rated in conformance with Chapter 9 Table 11(A) or 11(B). Lighting systems operating at 30 volts or less shall comply with 411.3(A) or 411.3(B). Lighting equipment connected to Class 2 power sources shall be listed. Lighting systems operating at 30 volts or less shall comply with 411.3(A) or 411.3(B). Lighting systems operating at 30 volts or less shall be listed as a complete system. The luminaires, power supply, and luminaire fittings (including the exposed bare conductors) of an exposed bare conductor lighting system shall be listed for the use as part of the same identified lighting system. A lighting system assembled from the following listed parts shall be permitted: (1) Low-voltage luminaires (2) Low-voltage luminaire power supply (3) Class 2 power supply (4) (3) Low-voltage luminaire fittings (5) (4) Cord (secondary circuits) for which the luminaires and power supply are listed for use. (6) (5) Cable, conductors in conduit, or other fixed wiring method for the secondary circuit. Lighting systems operating at 30 volts or less covered by this Article shall be supplied from a maximum 20-ampere branch circuit. This proposal was developed by a subgroup of the NEC DC Task Force of the Technical Correlating Committee. The Task Force is chaired by John R. Kovacik, Underwriters Laboratories, the subgroup members are Michael O’Boyle – Philips Lightolier (subgroup lead) and Mark Ode – Underwriters Laboratories, Michael Shulman – Underwriters Laboratories, Audie Spina – Armstrong Building Products and Michael Stelts – Panasonic. When Article 411 was added to the Code in 1996, the products it addressed were 30V ac, 25 amp maximum, lighting systems that were Listed in compliance with UL1838 (Standard for Landscape Lighting) or the outline of investigation that later became UL2108 (Standard for Low Voltage Lighting Systems). The voltage limit given in 411.2, 30 volts (42.4 Vpk), refers to alternating current and no direct current value is given. In the 2008 Code, provisions for Class-2 systems were added to article 411. At the time, most of these systems operated at 30 volts or less so there was no apparent need to revise article 411 to correlate with Chapter 9 tables 11(A) or 11(B). With the advent of new lighting technologies such as solid state lighting and direct current distribution systems, the need to better correlate article 411 with article 725 and chapter 9 tables 11(A) & 11(B) to more accurately address direct current class-2 lighting equipment is evident; especially in regard to class-2 DC voltages above 30V. Additionally, the nationally recognized lighting equipment standards including UL1598 and UL2108, allow lighting equipment to be Listed for connection to Class-2 power supplies without the need for the equipment to be evaluated as a system. Accordingly, the task group subgroup prepared the suggested revisions to accomplish the Code clarification to align the requirements with Class-2 limits and the product standards. Printed on 3/16/2012 65 Report on Proposals – June 2013 NFPA 70 Revise the Title, 411.1, 411.2, 411.3 (main paragraph), 411.3(B), and 411.6 as follows (other sections are unaffected by this change): This article covers lighting systems operating at 30 volts or less and their associated components. This article also covers lighting equipment connected to a Class 2 power source. A lighting system consisting of an isolating power supply, the low-voltage luminaires, and associated equipment that are all identified for the use. The output circuits of the power supply are rated for not more than 25 amperes and operate at 30 volts (42.4 volts peak) or less under all load conditions. Lighting equipment marked for connection to a Class 2 power source rated in conformance with Chapter 9 Table 11(A) or 11(B). Lighting systems operating at 30 volts or less shall comply with 411.3(A) or 411.3(B). Class 2 power sources and lighting equipment connected to Class 2 power sources shall be listed. A lighting system assembled from the following listed parts shall be permitted: (1) Low-voltage luminaires (2) Low-voltage luminaire power supply (3) Class 2 power supply (4) (3) Low-voltage luminaire fittings (5) (4) Cord (secondary circuits) for which the luminaires and power supply are listed for use. (6) (5) Cable, conductors in conduit, or other fixed wiring method for the secondary circuit. The luminaires, power supply, and luminaire fittings (including the exposed bare conductors) of an exposed bare conductor lighting system shall be listed for use as part of the same identified lighting system. Lighting systems operating at 30 volts or less covered by this Article shall be supplied from a maximum 20-ampere branch circuit. The panel does not accept the reference to "generic" Class 2 power sources and requires the power source to be listed. The panel removed the redundant 411.3. The panel recognizes that the change to the scope section falls under the jurisdiction of the TCC and requests approval. Affirmative: 11 Printed on 3/16/2012 66 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-86 Log #1215 NEC-P18 _______________________________________________________________________________________________ Marcelo M. Hirschler, GBH International Revise text to read as follows: A lighting system consisting of an isolating power supply, the low-voltage luminaires, and associated equipment that are all identified for the use. The output circuits of the power supply are rated for not more than 25 amperes and operate at 30 volts (42.4 volts peak) or less under all load conditions. : The output circuits of the power supply are rated for not more than 25 amperes and operate at 30 volts (42.4 volts peak) or less under all load conditions. The NFPA Manual of Style requires definitions to be in single sentences. The information provided in the subsequent sentences is not really a part of the definition; it is further information that is best placed in an informational note. definition style. Refer to the panel action and statement on Proposal 18-6 which addresses the submitter's issue of Affirmative: 11 Printed on 3/16/2012 67 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-87 Log #2698 NEC-P18 _______________________________________________________________________________________________ David Clements, International Association of Electrical Inspectors Add new text to read as follows: Power supplies installed in dwelling units shall not generate electro-magnetic interference that will cause undesired operation of protective devices. power supplies that do not comply shall be marked “Not for use in dwellings”. Informational Note. See FCC Part 15 Class B Digital Device or the Part 18 limits for Consumer ISM Equipment for information on allowed electro-magnetic emissions. Section 210.12(A) requires Arc-Fault Circuit-Interrupter (AFCI) protection in “all 120-volt, single phase, 15- and 20-ampere branch circuits supplying outlets installed in dwelling unit family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas”. The NEC defines an outlet as “a point on the wiring system at which current is taken to supply utilization equipment”, therefore, the requirement includes lighting circuits. 47 CFR Ch. I (10–1–98 Edition) Part 15—Radio Frequency Devices defines a Class B Digital Device as, “A digital device that is marketed for use in a residential environment notwithstanding use in commercial, business and industrial environments.” It further defines a digital device as, “An unintentional radiator (device or system) that generates and uses timing signals or pulses at a rate in excess of 9,000 pulses (cycles) per second and uses digital techniques; inclusive of telephone equipment that uses digital techniques or any device or system that generates and uses radio frequency energy for the purpose of performing data processing functions, such as electronic computations, operations, transformations, recording, filing, sorting, storage, retrieval, or transfer.” Switching power supplies meet this definition. Part 15 requires that Class B devices be labeled, “This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.” 47 CFR Ch. I (10–1–98 Edition) Part 18—Industrial, Scientific, and Medical Equipment defines Consumer ISM Equipment as, “A category of ISM equipment used or intended to be used by the general public in a residential environment, notwithstanding use in other areas.” Equipment meeting the consumer ISM limits must be marked with a compliance statement or the “FCC” logo. Switching power supplies meet this definition. While it is believed that power supplies need to meet the Part 18 requirements if installed in a dwelling unit, some manufacturers may declare that their products meet the Part 15 Class B requirements. The incidence of AFCI unwanted tripping due to interoperability problems with such products is low, however, even though the UL 1699 standard for AFCIs requires unwanted tripping tests, unwanted tripping in the field does occasionally occur. When it does occur, homeowners become understandably annoyed and frustrated if they or their electrical contractor are unable to resolve the problem. Sometimes the cause of the tripping is not readily evident, leading the electrical contractor or homeowner to resolve the problem by replacing the AFCI with a standard thermal-magnetic circuit breaker. This violates the NEC requirement for AFCI protection and increases the risk of an electrical fire in the dwelling unit. AFCI manufacturers have made great strides in improving their product designs to reduce the probability of unwanted tripping; however, field investigations have revealed that sometimes luminaires with electronic ballasts, low voltage lighting switching power supplies and CFLs that do not comply with the previously referenced FCC requirements cause unwanted AFCI tripping. Such incidents have been successfully resolved by replacing the non-compliant product with one that does meet the FCC requirements. Contractors and homeowners can report unwanted AFCI tripping events on the AFCIsafety.org web site. A study of the reports filed over the past three years showed that 18% of the reports named some sort of lighting as either the sole load or one of the loads on the branch circuit at the time the tripping occurred. One AFCI manufacturer has documented 13 cases over the past three years where replacing a ballast with an FCC compliant model solved the unwanted tripping problem. Another AFCI manufacturer has documented at least five cases. While the reports filed by homeowners and contractors are not always specific, some have referenced low voltage lighting. This proposal is intended to reduce the possibility that the operation of low voltage lighting may result in unwanted AFCI tripping by requiring that power supplies that do not comply with the aforementioned FCC requirements be marked NOT FOR USE IN DWELLINGS on the power supply. This will help contractors select the correct product for the application and help electrical inspectors check to insure that the appropriate power supply has been installed. The end result will be increased safety, Code compliance and customer satisfaction. The NEMA white paper developed to provide the designers of home electrical products with information on the Printed on 3/16/2012 68 Report on Proposals – June 2013 NFPA 70 operating parameters of AFCIs, with the purpose of avoiding conditions in which the HEP could cause the unwanted operation of an AFCI, calls for compliance with the referenced FCC requirements. Comparable proposals have been submitted to revise Articles 210, 410 and 422. Refer to the panel action and statement on Proposal 18-63 which addresses the submitter's issue. Affirmative: 10 Negative: 1 LOWRANCE, JR., A.: See my Explanation of Negative Vote on Proposal 18-63. Printed on 3/16/2012 69 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-88 Log #2094 NEC-P18 _______________________________________________________________________________________________ Donald R. Cook, Shelby County Development Services Revise text to read as follows: Power supplies installed in dwelling units shall comply with the requirements for an FCC Part 15 Class B Digital Device or the Part 18 limits for Consumer ISM Equipment. Compliance with the FCC requirements shall be marked on the power supply as required by the FCC. Power supplies that do not comply shall be marked “Not for use in dwellings”. Section 210.12(A) requires Arc-Fault Circuit-Interrupter (AFCI) protection in “all 120-volt, single phase, 15- and 20-ampere branch circuits supplying outlets installed in dwelling unit family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas”. The NEC defines an outlet as “a point on the wiring system at which current is taken to supply utilization equipment”, therefore, the requirement includes lighting circuits. 47 CFR Ch. I (10–1–98 Edition) Part 15—Radio Frequency Devices defines a Class B Digital Device as, “A digital device that is marketed for use in a residential environment notwithstanding use in commercial, business and industrial environments.” It further defines a digital device as, “An unintentional radiator (device or system) that generates and uses timing signals or pulses at a rate in excess of 9,000 pulses (cycles) per second and uses digital techniques; inclusive of telephone equipment that uses digital techniques or any device or system that generates and uses radio frequency energy for the purpose of performing data processing functions, such as electronic computations, operations, transformations, recording, filing, sorting, storage, retrieval, or transfer.” Switching power supplies meet this definition. Part 15 requires that Class B devices be labeled, “This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.” 47 CFR Ch. I (10–1–98 Edition) Part 18—Industrial, Scientific, and Medical Equipment defines Consumer ISM Equipment as, “A category of ISM equipment used or intended to be used by the general public in a residential environment, notwithstanding use in other areas.” Equipment meeting the consumer ISM limits must be marked with a compliance statement or the “FCC” logo. Switching power supplies meet this definition. While it is believed that power supplies need to meet the Part 18 requirements if installed in a dwelling unit, some manufacturers may declare that their products meet the Part 15 Class B requirements. The incidence of AFCI unwanted tripping due to interoperability problems with such products is low, however, even though the UL 1699 standard for AFCIs requires unwanted tripping tests, unwanted tripping in the field does occasionally occur. When it does occur, homeowners become understandably annoyed and frustrated if they or their electrical contractor are unable to resolve the problem. Sometimes the cause of the tripping is not readily evident, leading the electrical contractor or homeowner to resolve the problem by replacing the AFCI with a standard thermal-magnetic circuit breaker. This violates the NEC requirement for AFCI protection and increases the risk of an electrical fire in the dwelling unit. AFCI manufacturers have made great strides in improving their product designs to reduce the probability of unwanted tripping; however, field investigations have revealed that sometimes luminaires with electronic ballasts, low voltage lighting switching power supplies and CFLs that do not comply with the previously referenced FCC requirements cause unwanted AFCI tripping. Such incidents have been successfully resolved by replacing the non-compliant product with one that does meet the FCC requirements. Contractors and homeowners can report unwanted AFCI tripping events on the AFCIsafety.org web site. A study of the reports filed over the past three years showed that 18% of the reports named some sort of lighting as either the sole load or one of the loads on the branch circuit at the time the tripping occurred. One AFCI manufacturer has documented 13 cases over the past three years where replacing a ballast with an FCC compliant model solved the unwanted tripping problem. Another AFCI manufacturer has documented at least five cases. While the reports filed by homeowners and contractors are not always specific, some have referenced low voltage lighting. This proposal is intended to reduce the possibility that the operation of low voltage lighting may result in unwanted AFCI tripping by requiring that power supplies that do not comply with the aforementioned FCC requirements be marked NOT FOR USE IN DWELLINGS on the power supply. This will help contractors select the correct product for the application and help electrical inspectors check to insure that the appropriate power supply has been installed. The end result will be increased safety, Code compliance and customer satisfaction. The NEMA white paper developed to provide the designers of home electrical products with information on the operating parameters of AFCIs, with the purpose of avoiding conditions in which the HEP could cause the unwanted operation of Printed on 3/16/2012 70 Report on Proposals – June 2013 NFPA 70 an AFCI, calls for compliance with the referenced FCC requirements. Comparable proposals have been submitted to revise Articles 210, 410 and 422. Refer to the panel action and statement on Proposal 18-63 which addresses the submitter's issue. Affirmative: 11 _______________________________________________________________________________________________ 18-89 Log #1235 NEC-P18 _______________________________________________________________________________________________ Marcelo M. Hirschler, GBH International Revise text to read as follows: A sign or outline lighting system, shipped as subassemblies, that requires field-installed wiring between the subassemblies to complete the overall sign. The subassemblies are either physically joined to form a single sign unit or are installed as separate remote parts of an overall sign. : The subassemblies are either physically joined to form a single sign unit or are installed as separate remote parts of an overall sign. The NFPA Manual of Style requires definitions to be in single sentences. The information provided in the subsequent sentences is not really a part of the definition; it is further information that is best placed in an informational note. definition style. Refer to the panel action and statement on Proposal 18-6 which addresses the submitter's issue of Affirmative: 11 _______________________________________________________________________________________________ 18-89a Log #CP1804 NEC-P18 _______________________________________________________________________________________________ Code-Making Panel 18, Delete the informational note and revise the definition of neon tubing in 600.2 as follows: Neon Tubing. Electric-discharge luminous tubing, including cold cathode luminous tubing, that is manufactured into shapes to illuminate signs, form letters, parts of letters, skeleton tubing, outline lighting, other decorative elements, or art forms and filled with various inert gases. The informational note contains part of the definition and therefore was incorporated into the body of the definition. Affirmative: 11 Printed on 3/16/2012 71 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-90 Log #2623 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Revise text to read as follows: Electric signs, section signs, and outline lighting, retrofit kits and skeleton tubing, fixed , mobile, or portable, regardless of voltage, shall be listed and installed in conformance with that listing , unless otherwise approved by special permission. The test in 600.3 is modified to include LED retrofit field conversion subassemblies and skeleton tubing • Energy conservation is driving changes of illumination systems to LEDs in existing/installed signs or outline lighting. This requires field replacement of electrical components and power sources that modify the original electrical system in the sign listed under UL 48. Logically, it follows that conversions should not compromise the original safety profile of the listed sign. A complete subassembly, a kit that has been certified by a qualified electrical testing laboratory as compatible with the profile of the listed sign being converted, provides a basis for the AHJ to accept the modification without requiring a field evaluation. As an example, UL's The White Book, describes UL's certification procedure under UL 879A, Outline of Investigation for LED Kits. UL's Classified Kit includes all the components and installation instructions to safely modify a sign. UL's Product Guide to Inspections, says, "Classification complies with the definition of "Listed" in model installation codes." th The 15 Edition of UL 48, published in September 2011 includes skeleton tubing within the scope of UL 48, thereby nullifying the basis for the exception. (UL 48.1 .2) Revise the submitter's recommendation to remove the words "and skeleton tubing" and revise to read as follows: Fixed, mobile or portable electric signs, section signs, outline lighting, and retrofit kits, regardless of voltage, shall be listed and installed in conformance with that listing, unless otherwise approved by special permission. Adding skeleton tubing in this section would make it mandatory that it be listed. Skeleton tubing signs are not restricted from being listed such as window and beer signs commonly used today. For skeleton tubing to be listed it would require plant assembly before shipment. There is no technical substantiation provided based on safety to support this change. The change would restrict this product from areas where inspection and listing is required. Article 600 Part II currently covers the component and installation requirements for field installed skeleton tubing signs. The panel has provided addition revisions to clarify the requirement. Affirmative: 10 Negative: 1 KOCHAN, M.: Skeleton Neon Tubing is now Incorporated into UL 48 15th Edition dated 09/02/2011. Article 4.4.11.2 of UL 48 states "wiring for Skeleton Neon Tubing signs or Outline Lighting is not required before it leaves the factory, as implied in the panel statement. CARPENTER, F.: We agree with the action taken by the panel but the panel took conflicting action on proposal 18-91. We believe that the correct wording for 600.3 should be: 600.3 Listing. Fixed, mobile or portable electric signs, section signs, outline lighting, and retrofit kits, regardless of voltage, shall be listed, provided with installation instructions, and installed in conformance with that listing, unless otherwise approved by special permission. Printed on 3/16/2012 72 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-91 Log #3407 NEC-P18 _______________________________________________________________________________________________ Randall K. Wright, RKW Consulting Revise text to read as follows: 600.3.Listing. Electric signs, section signs, and outline lighting fixed, mobile, or portable, regardless of voltage shall be listed, provided with installation instructions and installed in conformance with that listing, unless otherwise approved by special permission. All signs should be provided with installation instructions. It is clear in 110.3 (B) that the installation “shall be installed and used in accordance with any instructions included in the listing or labeling.” The new UL standard will require these instructions but have no way of enforcing their delivery to the electrical inspector. Placing this language in 600.3 should require site delivery of installation instructions for all signs and not affect the balance of the installations. Revise text to read as follows: 600.3.Listing. Electric signs, section signs, and outline lighting that are fixed, mobile, or portable, regardless of voltage shall be listed, provided with installation instructions and installed in conformance with that listing, unless otherwise approved by special permission. The panel has editorially revised the text so that it is clear that "fixed, mobile and portable" applies to all types of signs. Affirmative: 11 CARPENTER, F.: We agree with the action taken by the panel but the panel took conflicting action on proposal 18-90. We believe that the correct wording for 600.3 should be: 600.3 Listing. Fixed, mobile or portable electric signs, section signs, outline lighting, and retrofit kits, regardless of voltage, shall be listed, provided with installation instructions, and installed in conformance with that listing, unless otherwise approved by special permission. _______________________________________________________________________________________________ 18-92 Log #158 NEC-P18 _______________________________________________________________________________________________ Don Hursey, Jade Learning Revise text to read as follows: Visibility. The markings required in 604.4(A) and listing labels shall not be required to be visible after installation. but shall be permanently applied in a location visible during servicing. This requirement makes it even more difficult for an electrical inspector to perform his/her duties when the markings and labels can be concealed after installation. The new sections 600.4(c) and 600.4(D) were added in the last cycle as a panel proposal with the following substantiation: "CMP 18 clarified the long standing issue that the labels required in 600.4(A) are not required to be visible - only available - after installation." The submitter has documented no hazard arising from this requirement. Affirmative: 11 Printed on 3/16/2012 73 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-93 Log #2624 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Revise text to read as follows: Section All signs, outline lighting, skeleton tubing systems and retrofit kits shall be marked to indicate that field-wiring and installation instructions are required. (1) Exception: Portable, cord connect signs are not required to be marked. Present wording applies only to section signs. Except for portable cord connected signs, all listed sign, th outline lighting and skeleton tubing systems require installation instructions to be in harmony with UL 48, 15 Edition, 8.1 - 8.1.5 inclusive and 110.(3)(B). Installation instructions are required by UL's Subject 879A, Outline of Investigation For LED Kits. Additionally, 600.12 requires skeleton tubing to be installed in accordance with installation instructions. Affirmative: 10 Negative: 1 CARPENTER, F.: The submitter's statement that 110.3(B) requires installation instructions is incorrect. While we acknowledge that UL 48 requires all signs to be supplied with installation instructions, there is no justification to require marking all signs with a statement indicating that installation instructions have been provided. The current edition of UL 48 states in clause 7.7.1(e) that the marking “Installation and assembly required, see installation instructions” is required. This clause of the UL standard only applies to Section Signs since they frequently require significant field wiring. Many complete signs are significantly simpler in construction and requiring a similar marking for all signs has not been substantiated. _______________________________________________________________________________________________ 18-94 Log #2625 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Add new text to read as follows: Signs and outline lighting with field installed conversion subassemblies shall be labeled to 1 indicate that the original illumination system has been modified. The marking shall be in letters at least 6 mm ( /4 in .) high. on a label permanently installed . and shall be located where visible during servicing. CAUTION. RETROFIT KIT INSTALLED (Date) BY (Company Name) • The changing of illumination systems in signs and luminaires presents hazards for work-persons doing post installation maintenance. The AHJ in Washington requires a label near the conversion subassembly, warning about the risk of an electrical hazard: (Labor & Industries Electrical Currents, March 201 1) For signs, this is particularly applicable to conversions of fluorescent lamps to tubular LEDs. LED systems lack standardization with different secondary load specifications, such as 10 volts AC to 50 volts DC. LEOs must be replaced like with like to ensure electrical safety and avoid compromising the listing profile of the sign. • Inasmuch as the conversion may be made by parties other than the sign manufacturer, identifying the installer provides the basis of legal relief for the original sign manufacturer, in the event the rework is not performed in accord with the installation instructions and there is a catastrophic failure resulting in injury or property damage. The installer's name also provides a source for the retrofit installation instructions that may be required by maintenance personnel. The submitter has not provided definitive substantiation for the inclusion of the installing company name and date. The intent of this proposal is covered by the product safety standard. See panel action on Proposal 18-90. Affirmative: 11 Printed on 3/16/2012 74 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-95 Log #2626 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Revise text to read as follows: Branch circuits that supply signs and outline lighting shall be rated in accordance with 600.5(B)(1) or (B)(2) and shall be considered to be continuous loads for the purposes of calculations. Branch circuit rules apply to outline lighting as well as to signs. Including outline lighting in the scope of the rule is for consistency with other sections of 600. The proposed requirement is already covered in 600.5(B)(2). Affirmative: 11 _______________________________________________________________________________________________ 18-96 Log #1139 NEC-P18 _______________________________________________________________________________________________ Russell LeBlanc, The Peterson School Revise first sentence to read: Each sign and outline lighting system, feeder circuit or branch circuit supplying a sign, outline lighting system, or skeleton tubing shall be controlled by connected to a disconnecting means which shall be an externally operable switch or circuit breaker that opens all ungrounded conductors and controls disconnects no other load. The present wording is simply not correct usage of terminology. See Article 100 definitions of "controller" and "disconnect". The switch or circuit breaker that is required is intended to be a "disconnecting means", NOT a "controller" by definition. This proposal is only to clarify the intent of the requirement. The definition found in article 100 is for a controller, a noun, and the use of control in section 600.6 is a verb, and is not a controller. Affirmative: 11 Printed on 3/16/2012 75 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-97 Log #301 NEC-P18 _______________________________________________________________________________________________ Stanley J. Folz, Morse Electric Company Revise text to read as follows: The disconnecting means shall be within sight of the sign or outline lighting system that it controls. Where the disconnecting means is out of the line of sight from any section that is able to be energized, the disconnecting means shall be capable of being locked in the open position. The provision for locking or adding a lock to the disconnecting means must remain in place at the switch or circuit breaker whether the lock is installed or not. Portable means for adding a lock to the switch or circuit breaker shall not be permitted. shall be lockable in accordance with 110.25. This proposal has been developed by the Usability Task Group assigned by the Technical Correlating Committee. The committee members were Stanley Folz, James Dollard, William Fiske, David Hittinger, Andy Juhasz, Amos Lowrance, Susan Newman-Scearce, Marc Bernsen and Vincent Zinnante. Requirements for a disconnecting means to be lockable in the open position exist in numerous locations in the NEC. A new section has been proposed in Article 110 to consolidate the requirements for a disconnecting means required to be “capable of being locked in the open position” in a single section for clarity. It is understood that this requirement includes more than disconnecting and locking electrical power sources. This proposal is intended to facilitate a lockout/tagout scenario. It is equally important to ensure that the means for placing the lock remain in place. The concept suggested by this proposal is necessary to provide correlation throughout the NEC with respect to the capability of placing a lock on a disconnecting means to secure it in the open position. Affirmative: 11 _______________________________________________________________________________________________ 18-98 Log #481 NEC-P18 _______________________________________________________________________________________________ Edward G. Kroth, Verona, WI Delete text as follows: The provisions for locking or adding a lock to the disconnecting means shall be installed and shall remain in place whether the lock is installed or not. Portable means for adding a lock to the switch or circuit breaker shall not be permitted. The rest of this section is to remain the same. This is a companion proposal to one submitted to Code-Making Panel 1 and should be accepted only if said proposal or some equivalent proposal is accepted by Code-Making Panel 1. Said proposal is to put the criteria for a lockable disconnecting means in Article 110 and, thus, be able to eliminate similar repetitions in at least 19 different sections of the NEC. It would also help to standardize the usage of the term "capable of being locked" which has at least four variations in the 2011 NEC. Refer to the panel action on Proposal 18-97 which meets the intent of the submitter. Affirmative: 11 Printed on 3/16/2012 76 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-99 Log #2627 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Add new text to read as follows: The disconnect shall be located at the point the feeder circuit or branch circuit(s) supplying a sign or outline lighling system enters a sign body or enclosure. ) (3) • For many years, the industry has been attaching disconnects on a sign body or sign enclosure without respect to the location where supply conductors enter the sign in relationship to the disconnecting means. Disconnects randomly located on a sign create a false sense of security for service personnel because it is assumed that the disconnect or disconnects de-energizes all conductors within the sign. In reality, supply conductors traversing within the sign cabinet to the supply side of the randomly located disconnect remain energized. Only the conductors from the disconnect to the power source are de-energized when the disconnect is opened . There is anecdotal precedence where service personnel have been electrocuted while working on a sign meeting the foregoing description. As recently as 12 October 2011, a master electrician was electrocuted while performing maintenance in a sign in Centerville, MN. While the exact cause of the fatality is unknown, the accident illustrates the risk associated with working on a sign that has energized conductors. The rule in 210.4(B) and 600.6 require multiwire branch circuits to be de-energized where the branch circuit originates to prevent these calamities. No consideration has been given to the location of disconnects for other feeders or branch circuit conductors that don't fit into the definition of multiwire branch circuit conductors within or on a sign. 600.6 mandates that a feeder circuit or branch circuit supplying a sign shall have a single disconnecting means that "opens all ungrounded conductors." This does not say the ungrounded conductors must be de-energized before they enter a sign body or enclosure. OSHA rules covered in NFPA 70E preclude working on energized equipment except under emergency and special circumstances. A written procedure for the service person is required to cover such circumstances, as would be the real time situation described in this dialogue. • Edit. Revise third level numeric sequence to accommodate location of new rule. Add new 600.6(A)(1) to read as follows [retain and renumber current (1) and subsequent paragraphs]: (1) At Point of Entry to a Sign Enclosure. The disconnect shall be located at the point the feeder circuit or branch circuit(s) supplying a sign or outline lighting system enters a sign enclosure and shall disconnect all wiring where it enters the enclosure of the sign. Exception. A disconnect is not required for branch or feeder circuits passing through the sign where enclosed in a Chapter 3 listed raceway. This change accomplishes the intent of the submitter with a higher level of clarity. Affirmative: 10 Negative: 1 GRAY, B.: I am not opposed to the Panel Action to Accept in Principle, but am opposed to the addition of the exception in the Panel Meeting Action. First, the exception is not needed because the rule applies to “feeder circuit or branch circuit(s) supplying a sign or…” The exception applies to circuits that do not supply the sign. Second, by exempting feeders or branch circuits that pass through the sign structure, the Panel has effectively incorporated an exemption to 225.31. Since the affected circuits do not supply the sign, it is my opinion they are outside the scope of Article 600 and therefore outside the scope of CMP 18. Finally, the accepted wording does not provide any prohibition on those circuits supplying loads within the sign enclosure. So, technically, the circuits could feed a load inside the sign enclosure before continuing to pass through the sign, which is not the intent of the Panel. If the Panel continues to keep the exception, wording should be added with a comment to prohibit any transition within the enclosure. In addition, a comment should be presented to CMP 4 to add an exception to 225.31 pointing to 600.6(A)(1) for correlation. Printed on 3/16/2012 77 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-100 Log #482 NEC-P18 _______________________________________________________________________________________________ Edward G. Kroth, Verona, WI Delete text as follows; The provisions for locking or adding a lock to the disconnecting means must remain in place at the switch or circuit breaker whether the lock is installed or not. Portable means for adding a lock to the switch or circuit breaker shall not be permitted. The rest of this section is to remain the same. This is a companion proposal to one submitted to Code-Making Panel 1 and should be accepted only if said proposal or some equivalent proposal is accepted by Code-Making Panel 1. Said proposal is to put the criteria for a lockable disconnecting means in Article 110 and, thus, be able to eliminate similar repetitions in at least 19 different sections of the NEC. It would also help to standardize the usage of the term "capable of being locked" which has at least four variations in the 2011 NEC. Refer to the panel action on Proposal 18-102 which meets the intent of the submitter. Affirmative: 11 _______________________________________________________________________________________________ 18-101 Log #1974 NEC-P18 _______________________________________________________________________________________________ Jonathan R. Althouse, Michigan State University Delete the words “permitted to be” from the first line to read as follows: (1) The disconnecting means shall be permitted to be located within sight of the controller or in the same enclosure with the controller. The meaning of this paragraph is not clear. It seems to be saying the disconnecting means can be located anywhere in the circuit. If that is the intent, then this section is not needed. If the disconnecting means is to be located in sight of the controller then that needs to be clearly stated. Affirmative: 11 Printed on 3/16/2012 78 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-102 Log #302 NEC-P18 _______________________________________________________________________________________________ Stanley J. Folz, Morse Electric Company Revise text to read as follows: (3) The disconnecting means shall be designed such that no pole can be operated independently and shall be capable of being locked in the open position. The provisions for locking or adding a lock to the disconnecting means must remain in place at the switch or circuit breaker whether the lock is installed or not. Portable means for adding a lock to the switch or circuit breaker shall not be permitted. lockable in accordance with 110.25. This proposal has been developed by the Usability Task Group assigned by the Technical Correlating Committee. The committee members were Stanley Folz, James Dollard, William Fiske, David Hittinger, Andy Juhasz, Amos Lowrance, Susan Newman-Scearce, Marc Bernsen and Vincent Zinnante. Requirements for a disconnecting means to be lockable in the open position exist in numerous locations in the NEC. A new section has been proposed in Article 110 to consolidate the requirements for a disconnecting means required to be “capable of being locked in the open position” in a single section for clarity. It is understood that this requirement includes more than disconnecting and locking electrical power sources. This proposal is intended to facilitate a lockout/tagout scenario. It is equally important to ensure that the means for placing the lock remain in place. The concept suggested by this proposal is necessary to provide correlation throughout the NEC with respect to the capability of placing a lock on a disconnecting means to secure it in the open position. The panel clarifies that the correct code citation is 600.6(A)(2)(3). Affirmative: 11 _______________________________________________________________________________________________ 18-102a Log #CP1805 NEC-P18 _______________________________________________________________________________________________ Code-Making Panel 18, Delete the informational note. The reference in the informational note is not needed for clarity. Affirmative: 11 Printed on 3/16/2012 79 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-103 Log #2628 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Revise text to read as follows: Signs and mMetal equipment of signs, outline lighting, and skeleton tubing systems shall be grounded by connection to the equipment grounding conductor of the supply branch circuit(s) or feeder using the types of equipment grounding conductors specified in 250.118. Skeleton neon tubing systems operate at voltages over 1000 volts and are field assembled similar to section signs with neon illumination . Remote dead metal parts, such as through·wall neon tubing receptacles, transformer enclosures, and metal conduit used for secondary conductors have potential to be energized. Metal equipment in these systems requires bonding for electrical safety. Affirmative: 11 _______________________________________________________________________________________________ 18-104 Log #2048 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Revise text to read as follows: Where listed nonmetallic conduit (PVC) is used to enclose the secondary circuit conductor from a transformer or power supply and a bonding conductor is required, the bonding conductor shall be installed separate and remote from the nonmetallic conduit (PVC) and be spaced at least 38 mm (11/2 in.) from the conduit when the circuit is operated at 100 Hz or less or 45 mm (13/4 in.) when the circuit is operated at over 100 Hz. Other than at the location of connection to a metal enclosure or sign body, nonmetallic conduit (PVC) or flexible nonmetallic conduit shall be spaced no less than 38 mm (11/2 in.) from grounded or bonded parts when the conduit contains a conductor operating at 100 Hz or less, and shall be spaced no less than 45 mm (13/4 in.) from grounded or bonded parts when the conduit contains a conductor operating at more than 100 Hz. (2) 15 m (50 ft) where installed in nonmetallic conduit (PVC) "Rigid Polyvinyl Chloride Conduit" is also referred to as “PVC” and sometimes as “rigid nonmetallic conduit” Suggest that "PVC" be added to all references. This will make finding all references to easier and more reliable. The submitter has not provided definitive substantiation for the change. The panel does not agree that adding the type abbreviations will make the code easier to use. Affirmative: 11 Printed on 3/16/2012 80 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-105 Log #2803 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Revise text to read as follows: Listed flexible metal conduit (FMC) or listed liquidtight flexible metal conduit that encloses the secondary circuit conductor from a transformer or power supply for use with neon tubing shall be permitted as a bonding means if the total accumulative length of the conduit in the secondary circuit does not exceed 30 m (100 ft). Conductors shall be installed in rigid metal conduit, intermediate metal conduit, PVC conduit, RTRC, liquidtight flexible nonmetallic conduit, flexible metal conduit (FMC), liquidtight flexible metal conduit, electrical metallic tubing, metal enclosures, on insulators in metal raceways, or other equipment listed for use with neon secondary circuits over 1000 volts. "Flexible Metal Conduit" is also referred to as “FMC” Suggest that “(FMC)” be added to all references. This will make finding all references to "Flexible Metal Conduit" easier and more reliable. The submitter has not provided definitive substantiation for the change. The panel does not agree that adding the type abbreviations will make the code easier to use. Affirmative: 11 _______________________________________________________________________________________________ 18-106 Log #2836 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Revise text to read as follows: Listed flexible metal conduit or listed liquidtight flexible metal conduit (LFMC) that encloses the secondary circuit conductor from a transformer or power supply for use with neon tubing shall be permitted as a bonding means if the total accumulative length of the conduit in the secondary circuit does not exceed 30 m (100 ft). Conductors shall be installed in rigid metal conduit, intermediate metal conduit, PVC conduit, RTRC, liquidtight flexible nonmetallic conduit, flexible metal conduit, liquidtight flexible metal conduit (LFMC), electrical metallic tubing, metal enclosures, on insulators in metal raceways, or other equipment listed for use with neon secondary circuits over 1000 volts. "Liquidtight Flexible Metal Conduit" is also referred to as “LFMC” Suggest that “(LFNC)” be added to all references. This will make finding all references to " Liquidtight Flexible Metal Conduit " easier and more reliable. The submitter has not provided definitive substantiation for the change. The panel does not agree that adding the type abbreviations will make the code easier to use. Affirmative: 11 Printed on 3/16/2012 81 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-107 Log #3408 NEC-P18 _______________________________________________________________________________________________ Randall K. Wright, RKW Consulting Revise text to read as follows: (B) Pedestrians. Neon tubing, other than listed dry-location portable signs, readily accessible to pedestrians shall be protected from physical damage. Informational Note: See 600.41(D) for additional requirements. The word listed may be redundant with 600.3 but is worth repeating to ensure the portable sign we all lean against in a drinking institution is at least listed. The word listed is repeated under the wet section but not the dry. Affirmative: 11 _______________________________________________________________________________________________ 18-108 Log #3136 NEC-P18 _______________________________________________________________________________________________ Marcus R. Sampson, Lysistrata Electric Revise text to read as follows: The manufacturer of Pportable or mobile signs shall be provided with factory-installed ground-fault circuit-interrupter protection for personnel. The ground-fault circuit interrupter shall be an integral part of the attachment plug or shall be located in the power-supply cord within 300 mm (12 in.) of the attachment plug. The term “factory-installed” is unenforceable and doesn’t accurately describe the requirement for GFCI protection installed by the manufacturer at the time the unit is assembled. Affirmative: 10 Negative: 1 WRIGHT, R.: The manufacturer of the portable sign is not capable of building the power cord with the GFI. This is a part that is purchased by the portable sign manufacturer. Changing this section could lead to the sign manufacturer trying to build it into the sign or cord and defect the safety provided by an integral part of the cord. The proposer provided no safety issue with the current requirement. The proposer states its unenforceable but the AHJ with certainly know if its an integral part of the cord. _______________________________________________________________________________________________ 18-109 Log #2631 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Revise text to read as follows: Field installed secondary circuit wiring for electric signs, retrofit kits, outline lighting systems, and skeleton tubing systems shall in accordance with their installation instructions. Retrofit Kits require field wiring for the same reason as skeleton tubing systems and electric signs. UL 879A, Outline of Investigation for LED Kits, 22.1, describes the required content of installation instructions for retrofit kits. The insertion of retrofit kits is to establish harmony with the revision proposed for 600.4(E). The panel advises that only the underlined wording modifies 600.12. Affirmative: 11 Printed on 3/16/2012 82 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-110 Log #2629 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Revise text to read as follows: Neon Ssecondary econdary circuit wiring of 1000 volts or less shall comply with 600.31. Neon Ssecondary circuit wiring over 1000 volts shall comply with 600.32. Both (A) and (B) requirements are specific to neon and not general field wiring of sign secondary circuits. The text change harmonizes the referenced rule with the rules title in 600.31 and 600.32, respectively. Reject the changes to (A). 600.12 (A) refers to secondary wiring for fluorescent, HID and other types of wiring. Affirmative: 10 Negative: 1 KOCHAN, M.: Article 600.(12A) Secondary Circuits 1000 volts of less. Electric Signs, Outline Lighting and Skeleton Tubing. NOT Fluorescent and HID,as suggested in the panel statement. The code pane agrees that Part (B) to Neon 1000 volts for consistency for 600.32. Then logically the same should apply to 600.12(A) for consistency. _______________________________________________________________________________________________ 18-111 Log #2630 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Revise text to read as follows: Where the installation complies with 600.33 45 and the power source provides a Class 2 output that complies with 600.24, either of the following wiring methods shall be permitted as determined by the installation conditions. Reorganize Part 11. Move and re-number 600.33 . The mantra of Code Making Panels has been to organize Code rules in a logical manner for ease of use. The arrangement of 600.32 and 600.33 is illogical and doesn't meet this expectation. During the 2008 Code Cycle, 600.33 was inserted between rules associated with neon secondary circuits and rules for neon tubing. A user of the Code would expect 600.41, Neon Tubing and 600.42, Electrode Connections to be congruent with 600.32. The placement of 600.33 is correct and appropriate. This section follows the current wiring in order and is placed where secondary wiring is, which is the intent of the section and the code panel. Affirmative: 11 Printed on 3/16/2012 83 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-112 Log #3409 NEC-P18 _______________________________________________________________________________________________ Randall K. Wright, RKW Consulting Revise text to read as follows: (C) Class 2. Where the installation complies with 600.33 and the power source provides a Class 2 output that complies with 600.24, either of the following wiring methods shall be permitted as determined by the installation instructions and conditions. By adding the word “instructions” it clarifies that the installation conditions and the manufacturer’s wishes on the installation need satisfied. Affirmative: 11 _______________________________________________________________________________________________ 18-113 Log #2633 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Revise text to read as follows: Ballasts, transformers, electronic power supplies, and Class 2 Power Sources shall be of the self contained type or be enclosed by placement in a listed sign body or separate enclosure. Class 2 power sources used in LED sign and outline lighting systems may also be field installed in locations described in subsections of 600.21 . The omission of Class 2 power sources from 600.21 suggests they don't have the same installation requirements as other power sources. Adding Class 2 ensures that Scope of this Section applies equally to Class 2 power sources. Only transformers and power supplies incorporating an integral enclosure are permitted to be located outside an enclosure (600.8). Other types of transformers and power sources must be in a listed sign body. The addition of this subsection is in harmony with UL 48 and clarifies that the rule isn't limited to wet locations as is implied now. It also is inclusive of all field instal led transformers and power sources used with section signs, outline lighting, and skeleton tubing. Accept the recommendation but modify to add the word "listed" in front of "separate enclosure." The change is made to ensure the integrity of the enclosure. Affirmative: 11 Printed on 3/16/2012 84 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-114 Log #2632 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Revise text to read as follows: Ballasts, transformers, and electronic power supplies. and Class 2 Power Sources shall be located where accessible and shall be securely fastened in place. Ballasts, transformers, and electronic power supplies, and Class 2 Power Sources shall be installed as near to the lamps or neon tubing as practicable to keep the secondary conductors as short as possible. Ballasts, transformers, and electronic power supplies, and Class 2 Power Sources used in wet locations shall be of the weatherproof type or be of the outdoor type and protected from the weather by placement in a sign body or separate enclosure. A working space at least 900 mm (3 ft) high, 900 mm (3 ft) wide, by 900 mm (3 ft) deep shall be provided at each ballast, transformer, and electronic power supply, and Class 2 Power Source or at its enclosure where not installed in a sign. Ballasts, transformers, and electronic power supplies, and Class 2 Power Sources shall be permitted to be located in attics and soffits, provided there is an access door at least 900 mm by 562.5 mm (36 in. by 1 22 /2 in.) and a passageway of at least 900 mm (3 It) high by 600 mm (2 It) wide with a suitable permanent walkway at least 300 mm (12 in.) wide extending from the point of entry to each component. At least one lighting outlet containing a switch or controlled by a wall switch shall be installed in such spaces. At least one point of control shall be at the usual point of entry to these spaces. The lighting outlet shall be provided at or near the equipment requiring servicing. Ballasts, transformers, and electronic power supplies, and Class 2 Power Sources shall be permitted to be located above suspended ceilings, provided their enclosures are securely fastened in place and not dependent on the suspended ceiling grid for support. Ballasts, transformers, and electronic power supplies installed in suspended ceilings shall not be connected to the branch circuit by flexible cord. For continuity of electrical safety rules, Class 2 power sources instal led in locations (A) through (F) should be required to meet the same requirements as those for ballasts, transformers and electronic power supplies. Affirmative: 11 Printed on 3/16/2012 85 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-115 Log #2622 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Revise text to read as follows: A. Field Installed Skeleton Tubing. Field installed skeleton tubing shall not be required to be listed where installed in conformance wiith this Code. (B) Outline Lighting. Exception: Outline lighting shall not be required to be listed as a system when it consists of listed luminaires wired in accordance with Chapter 3. • Skeleton tubing exception is outdated and unnecessary. This exception to the Code for listing all signs th and outline lighting was inserted in the 1996 NEC® Article 600.3 because at the time, the scope of ANSI UL 48, 14 Edition, did not include field-assembled skeleton neon tubing. CMP 18 Substantiation for the 1996 exception to listing in 600.3 is recorded in the NFPA 70 - A95 ROP: th The 15 Edition of UL 48, published in September 2011 includes skeleton tubing within the scope of UL 48, thereby nullifying the basis for the exception. (UL 48.1.2) • Outline Lighting is changed to an Exception to 600.3, in compliance with the hierarchy suggested by the NEC Style Manual Removing field installed skeleton tubing in this section would make it mandatory that it be listed. Skeleton tubing signs are not restricted from being listed such as window and beer signs commonly used today. For skeleton tubing to be listed it would require plant assembly before shipment. There is no technical substantiation provided based on safety to support this change. Article 600 Part II currently covers the component and installation requirements for field installed skeleton tubing signs. Affirmative: 11 _______________________________________________________________________________________________ 18-116 Log #3410 NEC-P18 _______________________________________________________________________________________________ Randall K. Wright, RKW Consulting Revise text to read as follows: (E) Protection of Leads. Bushings listed for the purpose shall be used to protect wires passing through an opening in metal. To insure the correct product is used for the purpose and to be consistence with other bushing requirements in this section. The purpose of the listing is not indicated. The requirements for bushings are contained in the product standard for signs. Affirmative: 11 Printed on 3/16/2012 86 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-117 Log #2384 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Add text to read as follows: Secondary conductors shall be separated from each other and from all objects other than insulators or neon tubing by a spacing of not less than 38 mm (11/2 in.). GTO cable installed in metal conduit or tubing requires no spacing between the cable insulation and the conduit (PVC) or tubing. "Rigid Polyvinyl Chloride Conduit" is also referred to as “PVC” and sometimes as “rigid nonmetallic conduit”. Suggest that "PVC" be added to all references. This will make finding all references to easier and more reliable. The submitter has not provided definitive substantiation for the change. The panel does not agree that adding the type abbreviations will make the code easier to use. Affirmative: 11 _______________________________________________________________________________________________ 18-117a Log #CP1807 NEC-P18 _______________________________________________________________________________________________ Code-Making Panel 18, Revise 600.32(A)(1) as follows: Conductors shall be installed in rigid metal conduit, intermediate metal conduit, PVC conduit, RTRC, liquidtight flexible nonmetallic conduit, flexible metal conduit, liquidtight flexible metal conduit, electrical metallic tubing, metal enclosures, on insulators in metal raceways, or other equipment listed for use with neon secondary circuits over 1000 volts. The panel provides clarification to remove the acronyms PVC and RTRC inadvertently placed in the 2008 version of 600.32 (A)(1). Section 600.32 refers to secondary wiring over 1000 volts and is designed for the use of a special conductor called GTO wire rated at 105 degrees C and GTO wire with integral sleeving rated at 120 degrees C. Neither of these conduits is rated for these temperatures. Under special condition the code allows the use of nonmetallic conduit for these conductors but only with special spacing from ground based on its ability to control capacitive coupling. Use of these materials will create an immediate fire hazard when placed near a ground plane. Supporting material available at NFPA Headquarters Affirmative: 11 Printed on 3/16/2012 87 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-118 Log #1823 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Revise text to read as follows: Conductors shall be installed in rigid metal conduit, intermediate metal conduit, PVC conduit, RTRC, liquidtight flexible nonmetallic conduit, flexible metal conduit, liquidtight flexible metal conduit, electrical metallic tubing (EMT), metal enclosures, on insulators in metal raceways, or other equipment listed for use with neon secondary circuits over 1000 volts. "electrical metallic tubing" is also referred to as “EMT” Suggest that "EMT" be added to all references. This will make finding all references to "electrical metallic tubing" easier and more reliable. [The following files are related: 100_EMT, 225_EMT, 230_EMT, 250_EMT, 300_EMT, 334_EMT, 374_EMT, 392_EMT, 398_EMT, 424_EMT, 426_EMT, 427_EMT, 430_EMT, 502_EMT, 503_EMT, 506_EMT, 517_EMT, 520_EMT, 550_EMT, 551_EMT, 552_EMT, 600_EMT, 610_EMT, 620_EMT, 645_EMT, 680_EMT, 695_EMT, 725_EMT, 760_EMT] The submitter has not provided definitive substantiation for the change. The panel does not agree that adding the type abbreviations will make the code easier to use. Affirmative: 11 Printed on 3/16/2012 88 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-119 Log #2412 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Add text to read as follows: Conductors shall be installed in rigid metal conduit, intermediate metal conduit (IMC), PVC conduit, RTRC, liquidtight flexible nonmetallic conduit, flexible metal conduit, liquidtight flexible metal conduit, electrical metallic tubing, metal enclosures, on insulators in metal raceways, or other equipment listed for use with neon secondary circuits over 1000 volts. Secondary conductors shall be separated from each other and from all objects other than insulators or neon tubing by a spacing of not less than 38 mm (11/2 in.). GTO cable installed in metal conduit or tubing requires no spacing between the cable insulation and the conduit (IMC) or tubing. metal conduit (IMC) or tubing. . The insulation on all conductors shall extend not less than 65 mm (21/2 in.) beyond the (1) 6 m (20 ft) where installed in metal conduit (IMC) or tubing "Intermediate Metal Conduit" is also referred to as “IMC” “Metallic Conduit” Suggest that "IMC" be added to all references. This will make finding all references to “Intermediate Metal Conduit" easier and more reliable. The submitter has not provided definitive substantiation for the change. The panel does not agree that adding the type abbreviations will make the code easier to use. Affirmative: 11 Printed on 3/16/2012 89 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-120 Log #2440 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Revise text to read as follows: Conductors shall be installed in rigid metal conduit (RMC), intermediate metal conduit, PVC conduit, RTRC, liquidtight flexible nonmetallic conduit, flexible metal conduit, liquidtight flexible metal conduit, electrical metallic tubing, metal enclosures, on insulators in metal raceways, or other equipment listed for use with neon secondary circuits over 1000 volts. Secondary conductors shall be separated from each other and from all objects other than insulators or neon tubing by a spacing of not less than 38 mm (11/2 in.). GTO cable installed in metal conduit (RMC) or tubing requires no spacing between the cable insulation and the conduit or tubing. The insulation on all conductors shall extend not less than 65 mm (21/2 in.) beyond the metal conduit (RMC) or tubing. (1) 6 m (20 ft) where installed in metal conduit (RMC) or tubing "Rigid Metal Conduit" is also referred to as “RMC” “Metallic Conduit” Suggest that "RMC" be added to all references. This will make finding all references to "Rigid Metal Conduit" easier and more reliable. The submitter has not provided definitive substantiation for the change. The panel does not agree that adding the type abbreviations will make the code easier to use. Affirmative: 11 _______________________________________________________________________________________________ 18-121 Log #2863 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Revise text to read as follows: Conductors shall be installed in rigid metal conduit, intermediate metal conduit, PVC conduit, RTRC, liquidtight flexible nonmetallic conduit, flexible metal conduit, liquidtight flexible metal conduit (LFNC), electrical metallic tubing, metal enclosures, on insulators in metal raceways, or other equipment listed for use with neon secondary circuits over 1000 volts. "Liquidtight Flexible Nonmetallic Conduit" is also referred to as “LFNC” Suggest that “(LFNC)” be added to all references. This will make finding all references to "Liquidtight Flexible Nonmetallic Conduit" easier and more reliable. The submitter has not provided definitive substantiation for the change. The panel does not agree that adding the type abbreviations will make the code easier to use. Affirmative: 11 Printed on 3/16/2012 90 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-122 Log #2389 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Add text to read as follows: Secondary conductors shall be separated from each other and from all objects other than insulators or 1 neon tubing by a spacing of not less than 38 mm (1 /2 in.). GTO cable installed in metal conduit or tubing requires no spacing between the cable insulation and the conduit or tubing (EMT). 1 The insulation on all conductors shall extend not less than 65 mm (2 /2 in.) beyond the metal conduit or tubing (EMT). (1) 6 m (20 ft) where installed in metal conduit or tubing (EMT) "electrical metallic tubing" is also referred to as “EMT” Suggest that "EMT" be added to all references. This will make finding all references to "electrical metallic tubing" easier and more reliable. [The following files are related: 100_EMT, 225_EMT, 230_EMT, 250_EMT, 300_EMT, 334_EMT, 374_EMT, 392_EMT, 398_EMT, 424_EMT, 426_EMT, 427_EMT, 430_EMT, 502_EMT, 503_EMT, 506_EMT, 517_EMT, 520_EMT, 550_EMT, 551_EMT, 552_EMT, 600_EMT, EMT_600_32_E, 610_EMT, 620_EMT, 645_EMT, 680_EMT, 695_EMT, 725_EMT, 760_EMT] The submitter has not provided definitive substantiation for the change. The panel does not agree that adding the type abbreviations will make the code easier to use. Affirmative: 11 _______________________________________________________________________________________________ 18-123 Log #2634 NEC-P18 _______________________________________________________________________________________________ Richard D. Gottwald, International Sign Association Revise text to read as follows: Reorganize Part II. Move and re-number 600.33. The mantra of Code Making Panels has been to organize Code rules in a logical manner for ease of use. The arrangement of 600.32 and 600.33 is illogical and doesn't meet this expectation. During the 2008 Code Cycle, 600.33 was inserted between rules associated with neon secondary circuits and rules for neon tubing. A user of the Code would expect 600.41, Neon Tubing and 600.42, Electrode Connections to be congruent with 600.32. Refer to the panel action and statement on Proposal 18-111 which addresses the same issue. Affirmative: 11 Printed on 3/16/2012 91 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-124 Log #3237 NEC-P18 _______________________________________________________________________________________________ Mark C. Ode, Underwriters Laboratories Inc. Add the phrase “as applicable” to the end of the introductory sentence as follows: 600.33 LED Sign Illumination Systems, Secondary Wiring. The wiring methods and materials shall be installed in accordance with the sign manufacturer’s installation instructions using any applicable wiring methods from Chapter 3 and the requirements for Class 2 circuits contained in Part III of Article 725, as applicable. Only the wiring methods and materials that apply within Chapter 3 and Part III of Article 725 should be used since Part III, for example, has many different wiring methods that may be used but not all are applicable for this use. Affirmative: 11 _______________________________________________________________________________________________ 18-125 Log #1904 NEC-P18 _______________________________________________________________________________________________ James F. Williams, Fairmont, WV Revise text to read as follows: Class 2 cable used in a wet location shall be identified for use in wet locations or have a moisture-impervious metal sheath Type MI. “Mineral-Insulated Metal-Sheathed Cable” is also referred to as “MI” and “Article 332” Suggest that "MI" be added to all references. This will make finding all references to " Mineral-Insulated Metal-Sheathed Cable" easier and more reliable. The submitter has not provided definitive substantiation for the change. The panel does not agree that adding the type abbreviations will make the code easier to use. Affirmative: 11 Printed on 3/16/2012 92 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-125a Log #CP1808 NEC-P18 _______________________________________________________________________________________________ Code-Making Panel 18, Revise text to read as follows: ARTICLE 605 Office Furnishings 605.1 Scope. This article covers electrical equipment, lighting accessories, and wiring systems used to connect, or contained within, or installed on office furnishings. 605.2 Definition. Office Furnishing. Cubicle panels, partitions, study carrels, work stations, desks, shelving systems, and storage units that may be mechanically and electrically interconnected to form an office furnishing system. 605.3 General. Wiring systems shall be identified as suitable for providing power for lighting accessories and utilization equipment used within office furnishings. A wired partition shall not extend from floor to ceiling. Exception: Where permitted by the authority having jurisdiction, these relocatable wired partitions shall be permitted to extend to, but shall not penetrate, the ceiling. (A) Use. These assemblies shall be installed and used only as provided for by this article. (B) Hazardous (Classified) Locations. Where used in hazardous (classified) locations, these assemblies shall comply with Articles 500 through 517 in addition to this article. 605.4 Wireways. All conductors and connections shall be contained within wiring channels of metal or other material identified as suitable for the conditions of use. Wiring channels shall be free of projections or other conditions that might damage conductor insulation. 605.5 Office furnishing Interconnections. The electrical connection between office furnishings shall be a flexible assembly identified for use with office furnishings or shall be permitted to be installed using flexible cord, provided all the following conditions are met: (1) The cord is extra-hard usage type with 12 AWG or larger conductors, with an insulated equipment grounding conductor. (2) The office furnishings are mechanically contiguous. (3) The cord is not longer than necessary for maximum positioning of the office furnishing but is in no case to exceed 600 mm (2 ft). (4) The cord is terminated at an attachment plug-and-cord connector with strain relief. 605.6 Lighting Accessories. Lighting equipment shall be listed and identified for use with office furnishings and shall comply with 605. 6(A), (B), and (C). (A) Support. A means for secure attachment or support shall be provided. (B) Connection. Where cord-and-plug connection is provided it shall comply with all of the following: (1) The cord length shall be suitable for the intended application but shall not exceed 2.7 m (9 ft) in length. (2) The cord shall not be smaller than 18 AWG (3) The cord shall contain an equipment grounding conductor, except as specified in (4) (4) Cords on the load side of a listed Class 2 power source are not required to contain an equipment grounding conductor. (5) The cord shall be of the hard usage type, except as specified in (6). (6) A cord provided on the load side of a listed Class 2 power source shall be of the type provided with the listed luminaire assembly or of the type specified in Section 725.130. (7) Connection by other means shall be identified as suitable for the conditions of use. (C) Receptacle Outlet. Receptacles shall not be permitted in lighting accessories. 605.7 Fixed-Type Office Furnishings. Office furnishings that are fixed (secured to building surfaces) shall be permanently connected to the building electrical system by one of the wiring methods of Chapter 3. 605.8 Freestanding-Office Furnishings. Office furnishings of the freestanding type (not fixed) shall be permitted to be connected to the building electrical system by one of the wiring methods of Chapter 3. 605.9 Freestanding-Type Office Furnishings, Cord-and-Plug-Connected. Individual office furnishings of the freestanding type, or groups of individual office furnishings that are electrically connected, are mechanically contiguous, and do not exceed 9.0 m (30 ft) when assembled, shall be permitted to be connected to the building electrical system by a single flexible cord and plug, provided all of the conditions of 605.9(A) through (D) are met. (A) Flexible Power-Supply Cord. The flexible power supply cord shall be extra-hard usage type with 12 AWG or larger conductors with an insulated equipment grounding conductor and shall not exceed 600 mm (2 ft) in length. (B) Receptacle Supplying Power. The receptacle(s) supplying power shall be on a separate circuit serving only the Printed on 3/16/2012 93 Report on Proposals – June 2013 NFPA 70 office furnishing and no other loads and shall be located not more than 300 mm (12 in.) from the office furnishing that is connected to it. (C) Receptacle Outlets, Maximum. Individual office furnishing or groups of interconnected individual office furnishings shall not contain more than thirteen 15-ampere, 125-volt receptacle outlets. (D) Multiwire Circuits, Not Permitted. Individual office furnishings or groups of interconnected office furnishings shall not contain multiwire circuits. The panel has combined the panel actions on Proposals 18-126, 127 and 128 to provide a correlated package and has made changes to eliminate exceptions and provide clarity. The panel has modified the scope section of this article and requests that the TCC approve this change. Affirmative: 10 Printed on 3/16/2012 94 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-126 Log #1658 NEC-P18 _______________________________________________________________________________________________ Eugene W. Wirth, Underwriters Laboratories Inc. Revise text to read as follows: This article covers electrical equipment, lighting accessories, and wiring systems used to connect, or contained within, or installed on relocatable wired partitions office furnishings. Cubicle panels, partitions, study carrels, work stations, desks, shelving systems, and storage units that may be mechanically and electrically interconnected to form an office furnishing system. Wiring systems shall be identified as suitable for providing power for lighting accessories and appliances utilization equipment used within office furnishings. in wired partitions. A wired These partitions shall not extend from floor to ceiling. These assemblies shall be installed and used only as provided for by this article. Where used in hazardous (classified) locations, these assemblies shall comply with Articles 500 through 517 in addition to this article. All conductors and connections shall be contained within wiring channels of metal or other material identified as suitable for the conditions of use. Wiring channels shall be free of projections or other conditions that may damage conductor insulation. The electrical connection between partitions office furnishings shall be a flexible assembly identified for use with wired partitions office furnishings or shall be permitted to be installed using flexible cord, provided all the following conditions are met: (1) The cord is extra-hard usage type with 12 AWG or larger conductors, with an insulated equipment grounding conductor. (2) The partitions office furnishings are mechanically contiguous. (3) The cord is not longer than necessary for maximum positioning of the partitions office furnishing but is in no case to exceed 600 mm (2 ft). (4) The cord is terminated at an attachment plug-and-cord connector with strain relief. Lighting equipment shall be listed and identified for use with wired partitions office furnishings and shall comply with 605.56(A), (B), and (C). A means for secure attachment or support shall be provided. Where cord-and-plug connection is provided the cord length shall be suitable for the intended application but shall not exceed 2.7 m (9 ft) in length. The cord shall not be smaller than 18 AWG, shall contain an equipment grounding conductor, and shall be of the hard usage type. Connection by other means shall be identified as suitable for the condition of use. Receptacles shall not be permitted in lighting accessories. Office Furnishings Wired Partitions Office furnishings that are fixed (secured to building surfaces) shall be permanently connected to the building electrical system by one of the wiring methods of Chapter 3. Office Furnishings Partitions Office furnishings of the freestanding type (not fixed) shall be permitted to be connected to the building electrical system by one of the wiring methods of Chapter 3. Office Furnishings Individual partitions office furnishings of the freestanding type, or groups of individual partitions office furnishings that are electrically connected ,are mechanically connected contiguous and do not exceed 9.0 m (30 ft) when assembled, shall be permitted to be connected to the building electrical system by a single flexible cord and plug, provided all of the conditions of 605.89(A) through (D) are met. The flexible powersupply cord shall be extra-hard usage type with 12 AWG or larger conductors with an insulated equipment grounding conductor and shall not exceed 600 mm (2 ft) in length. The receptacle(s) supplying power shall be on a separate circuit serving only panels the office furnishing and no other loads and shall be located not more than 300 mm (12 in.) from the partitions office furnishing that is connected to it. Individual partitions office furnishing or groups of interconnected individual Printed on 3/16/2012 95 Report on Proposals – June 2013 NFPA 70 partitions office furnishings shall not contain more than thirteen 15-ampere, 125-volt receptacle outlets. Individual partitions office furnishings or groups of interconnected partitions office furnishings shall not contain multiwire circuits. Informational Note: See 210.4 for circuits supplying partitions in 605.67 and 605.78. Manufacturers are moving away from traditional office panels to interconnected desk and storage systems. These office furnishings are powered with the same type of electrical distribution systems utilized in the office panels so that the complete office furnishing system can be electrically interconnected. This proposal revises the title, scope, and references from “wired partitions” to “office furnishings.” A definition is proposed to identify the type of office furnishings intended to be covered by Article 605. This addition requires renumbering the remaining Sections of Article 605. It is also proposed that, in 605.2 (renumbered to 605.3 in the proposal), the term “appliances” be revised to “utilization equipment” to more accurately describe the type of equipment intended to supplied by the office furnishing electrical system. The panel has modified the recommendation for clarity and for correlation with the action on Proposals 18-127 and 128. Refer to the recommendation on 18-125a which meets the intent of the submitter. Affirmative: 10 Printed on 3/16/2012 96 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-127 Log #1696 NEC-P18 _______________________________________________________________________________________________ Michael Everhart, Steelcase Inc. Revise text to read as follows: ARTICLE 605 Office Furnishings (Consisting of Lighting Accessories and Wired Partitions) 605.1 Scope. This article covers electrical equipment, lighting accessories, and wiring systems used to connect, or contained within, or installed on relocatable wired partitions office furnishings. 605.2 General. Wiring systems shall be identified as suitable for providing power for lighting accessories and appliances utilization equipment in wired partitions for office furnishings. These partitions shall not extend from floor to ceiling. Exception: Where permitted by the authority having jurisdiction, these relocatable wired partitions shall be permitted to extend to, but shall not penetrate, the ceiling. (A) Use. These assemblies shall be installed and used only as provided for by this article. (B) Other Articles. Except as modified by the requirements of this article, all other articles of this Code shall apply. (C) Hazardous (Classified) Locations. Where used in hazardous (classified) locations, these assemblies shall comply with Articles 500 through 517 in addition to this article. 605.3 Wireways. All conductors and connections shall be contained within wiring channels of metal or other material identified as suitable for the conditions of use. Wiring channels shall be free of projections or other conditions that may damage conductor insulation. A wiring channel that is separate from the channel containing the branch circuits for light and power may be provided within the system components for the routing of communications, signaling, and fiber optic cables. 605.4 Partition Office Furnishing Interconnections. The electrical connection between partitions office furnishings shall be a flexible assembly identified for use with wired partitions office furnishings or shall be permitted to be installed using flexible cord, provided all the following conditions are met: (1) The cord is extra-hard usage type with 12 AWG or larger conductors, with an insulated equipment grounding conductor. (2) The partitions office furnishings are mechanically contiguous. (3) The cord is not longer than necessary for maximum positioning of the partitions office furnishing but is in no case to exceed 600 mm (2 ft). (4) The cord is terminated at an attachment plug-and-cord connector with strain relief. 605.5 Lighting Accessories. Lighting equipment shall be listed for the purpose and identified for use with wired partitions and shall comply with 605.5(A), (B), and (C). (A) Support. A means for secure attachment or support shall be provided. (B) Connection. Where cord-and-plug is provided, the cord length shall be suitable for the intended application but shall not exceed 2.7 m (9 ft) in length. The cord shall not be smaller than 18 AWG, shall contain an equipment grounding conductor, and should be of the hard usage type. Connection by another means shall be identified as suitable for the condition of use. (C) (A) Receptacle Outlet. Convenience receptacles shall not be permitted in lighting accessories. 605.6 Fixed-Type Partitions. Office Furnishings Wired partitions Office Furnishings that are fixed (secured to building surfaces) shall be permanently connected to the building electrical system by one of the wiring methods of Chapter 3. Multiwire branch circuits supplying power to the partition office furnishing shall be provided with a means to disconnect simultaneously all ungrounded conductors at the panelboard where the branch circuit originates. 605.7 Freestanding Type Partitions Office Furnishings. Partitions Office Furnishings of the freestanding type (not fixed) shall be permitted to be connected to the building electrical system by one of the wiring methods of Chapter 3. Multiwire branch circuits supplying power to permanently connected freestanding partitions shall be provided with a means to disconnect simultaneously all ungrounded conductors at the panelboard where the branch circuit originates. 605.8 Freestanding-Type Partitions Office Furnishings, Cord-and-Plug-Connected. Individual partitions office Printed on 3/16/2012 97 Report on Proposals – June 2013 NFPA 70 furnishings of the freestanding type, or groups of individual partitions office furnishing that are electrically connected, are mechanically contiguous connected, and do not exceed 9.0 m (30 ft) when assembled, shall be permitted to be connected to the building electrical system by a single flexible cord and plug, provided all of the conditions of 605.8(A) through (D) are met. (A) Flexible Power-Supply Cord. The flexible power-supply cord shall be extra-hard usage type with 12 AWG or larger conductors with an insulated equipment grounding conductor and shall not exceed 600 mm (2 ft) in length. (B) Receptacle Supplying Power. The receptacle(s) supplying power shall be on a separate circuit serving only panels office furnishings and no other loads and shall be located not more than 300 mm (12 in.) from the partition office furnishing that is connected to it. (C) Receptacle Outlets, Maximum. Individual partitions office furnishings or groups of interconnected individual partitions office furnishings shall not contain more than thirteen 15-ampere, 125-volt receptacle outlets. (D) Multiwire Circuits, Not Permitted. Individual partitions office furnishings or groups of interconnected individual partitions office furnishings shall not contain multiwire circuits. To align industry terminology with the UL1286 Standard "Office Furnishings". 605.2 The statement "These partitions shall not extend from floor to ceiling" and then having an exception that allows it, provides no value. There are no additional safety implications related to a floor to ceiling office furnishing that are not addressed with a partial height office furnishing that could go 1 inch from the ceiling. Ultimately, the product will be "Listed for the purpose" and will need to be acceptable to the AHJ. 605.5 Would like to remove these construction details from the NEC and rely on the industry standards (UL 1286 and UL 153) to control their construction. New low voltage LED technology has been restricted from use due to the power cord requirements. The current requirement of a grounded SJT type cord makes no sense with a low voltage LED fixture. The panel rejects removal of the exception in 605.2. The submitter has not provided definitive substantiation for the deletion. The panel modifies the balance of the recommendation for clarity. Refer to the recommendation on 18-125a which meets the intent of the submitter. Affirmative: 10 Printed on 3/16/2012 98 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-128 Log #1657 NEC-P18 _______________________________________________________________________________________________ Eugene W. Wirth, Underwriters Laboratories Inc. Revise text to read as follows: Lighting equipment shall be listed and identified for use with wired partitions and shall comply with 605.5(A), (B), and (C). A means for secure attachment or support shall be provided. Where cord-and-plug connection is provided it shall comply with all of the following:, (1) The cord length shall be suitable for the intended application but shall not exceed 2.7 m (9 ft) in length. (2) The cord shall not be smaller than 18 AWG (3) The cord shall contain an equipment grounding conductor, Exception: Cords on the load side of a Class 2 transformer are not required to contain an equipment grounding conductor. (4) and The cord shall be of the hard usage type. Exception: A cord provided on the load side of a listed Class 2 power supply may be of the type provided with the listed luminaire assembly or of the type specified in Section 725.130. (5) Connection by other means shall be identified as suitable for the condition of use. Low voltage Class 2 lighting systems have become common and the present requirements in section 605.5 can be interpreted as to require a hard usage cord between the Class 2 power supply and the Class 2 luminaire. The requirement for a hard usage cord is excessive especially when consideration is given to the presence of lap tops, phone chargers and other line voltage products electrically connected with non-jacketed SPT cord located within the same office environment as the Class 2 powered luminaire. Grounding is not required on the load side of a Class 2 supply due to the isolation the supply provides. An exception has been added to remove the requirement for a ground conductor within the cord between the Class 2 power supply and Class 2 luminaire. The panel has modified the recommendation for clarity and correlation with Proposals 18-126 and 127. Refer to the recommendation on 18-125a which meets the intent of the submitter. Affirmative: 10 _______________________________________________________________________________________________ 18-129 Log #1975 NEC-P18 _______________________________________________________________________________________________ Jonathan R. Althouse, Michigan State University At the end of this paragraph delete the words “is connected to” and replace with “it supplies” so the paragraph reads as follows: The receptacle(s) supplying power shall be on a separate circuit serving only panels and no other loads and shall be located not more than 300 mm (12 in.) from the partition that is connected to it supplies. This is an editorial suggestion to improve the sentence. This is not editorial and does not improve the sentence. Other circuits may be connected to the partition and not supply it. Affirmative: 10 Printed on 3/16/2012 99 Report on Proposals – June 2013 NFPA 70 _______________________________________________________________________________________________ 18-129a Log #CP1806 NEC-P18 _______________________________________________________________________________________________ Code-Making Panel 18, Delete the informational note. The informational note does not provide clarity. Affirmative: 10 Printed on 3/16/2012 100
© Copyright 2026 Paperzz