GF630/LF620,GF632/LF622

GF630 /LF620
GF632 /LF622
15 to 600 mm (1/2" to 24")
Field Intelligent Device – Premium Value Series
Electromagnetic Flowmeter
Introduction
The electromagnetic flowmeter uses Faraday’s Law of
electromagnetic induction to measure the process flow.
The device consists of two units: a detector, through
which the fluid to be measured flows and in which
low-level signals proportional to flow rates are
obtained; and a converter, which supplies excitation
current to the detector, and amplifies the signals from
the detector and then processes and converts the signals
into the 4–20mAdc current signal or communication
signal. Combined with a multi-functional converter
LF620 (combined type) or LF622 (separate type)
equipped with its original patented noise-suppression
circuit and advanced algorithms. The GF630 has a very
high tolerance to noise, giving the unit a very stable
output even for slurry fluid measurement. IR (Infrared)
switches enable the parameter setting of the converter
without removing the cover. Flow direction can be set
in either way, and its unique 128 x 128 dot matrix LCD
display allows the LCD to be rotated electronically to
90, 180 and 270 degrees without opening the cover.
The terminal block in LCD side make easy to wire in
case of the combined type.
The AF900 hand-held terminal (HART*1
communicator) can be used to communicate with the
flowmeter from a remote place. PROFIBUS-PA*2 or
Modbus*3 interface is available as an option.
*1:
HART protocol (Highway Addressable Remote Transducer) is a communication
GF630/LF620
GF630/LF600
GF630/LF620F
LF602
LF622
LF622F
GF632
GF632
Figure2. GF630 Premium Value series
Flowmeters
Certification
number
Z01207
Certification
No. PM09896
For PU lined flowmeter
Specifications
protocol for industrial sensors recommended by the HCF (HART Communication
Foundation).
Overall Specifications
*2: PROFIBUS is the communication protocol for factory and process automation that
the PROFIBUS Organization recommends. Instead of analog control with a
conventional analog signal (4-20mA), it is fieldbus which digitizes all signals.
Flowmeters support PROFIBUS-PA.
*3:Modbus is the communication protocol that Modicon Inc. developed. Physical
layer is RS485.
Measurement range in terms of flow velocity:
0 – 0.3 m/s to 0 –10 m/s (0 –1.0 ft/s to 0 – 32.8 ft/s).
0 – 0.1 m/s to 0 – 0.3 m/s (0 – 0.3 ft/s to 0 – 1.0 ft/s)
range is available optionally for meter size 1/2” to
18” (15 to 450 mm).
Accuracy:
< 1/2" to 18” (15 mm to 450 mm) >
±0.2 % of Rate *1.
Combined type
GF630/LF620
GF630/LF620F
Separate type
GF632/LF622
GF632/LF622F
* This pulse output error result is established under standard
operating conditions at Toshiba's admitted flow calibration
facility.
* Individual meter measurement error may vary up to ±0.5% of
Rate at 1.64 ft/s (0.5m/s) or more. Or it may vary up to ±0.3%
of rate ±0.039 inch/s (1mm/s) at 1.64 ft/s (0.5m/s) or less.
* Current output: plus ± 8µA (0.05% of span).
* Refer to individual calibration data for each individual meter's
measurement error.
Figure 1. Configuration
1
EJL-140D
GF630/LF620 GF632/LF622
< 20" and 24” (500 mm and 600 mm) >
±0.3 % of Rate *2.
*2 This pulse output error result is established under standard
operating conditions at Toshiba's flow calibration facility,
Fuchu Japan.
*2 Individual meter measurement error may vary up to ±0.5% of
Rate at 3.28 ft/s (1.0 m/s) or more. Or it may vary up to ±0.3%
of rate ±0.079 inch/s (2 mm/s) at 3.28 ft/s (1.0 m/s) or less.
*2 Current output: plus ± 8µA (0.05% of span).
*2 Refer to individual calibration data for each individual meter's
measurement error.
Fluid conductivity: 5µS/cm minimum
Fluid temperature:
-20 to +100 °C: FEP lining
(-4 to 212 °F)
-20 to +120 °C: PTFE lining
(-4 to 248 °F)
-20 to +60 °C: Polyurethane lining
(-4 to 140 °F)
Ambient temperature:
-20 to +60 °C (-4 to 140 °F)
Structure:
Standard-IP 67 and NEMA 4X Watertight
EN 1092-1 PN 16 :15 to 600mm (1/2” to 24”)
Principal materials:
Case — carbon steel
Flange material — carbon steel
Linings —
FEP : Meter sizes 15 to 250mm (1/2” to 10”)
PTFE : Meter sizes 300 to 600mm(12” to 24”)
Polyurethane(PU) : Meter sizes 15 to 400mm
(1/2” to 16”)
Electrodes —
Type - Super smooth, polished with self
cleaning finish, and non stick shape
316L stainless steel
(for PU lining)
Hastelloy C equivalent (for FEP, PTFE lining).
Measuring tube material — 304 stainless steel
Terminal box — Aluminum alloy
(for separate type)
Grounding ring —
PU, FEP lining::None (std.)
316 stainless steel (opt.)
PTFE lining::316 stainless steel (std.)
Option-IP68 and NEMA 6P Watertight
Coating: Corrosion resistant resin coating (std.),
pearl-gray colored
Power consumption:
Dimensions and weights: See Figure 3 and 4.
Cable connection port: for separate type detectors.
Standard:10W(14VA)
at AC100V and Excitation current:0.2A
MAX:15W (22VA)
MAX:17W(24VA) with PROFIBUS
Approved hazardous location certifications:
Model: GF630/LF620F and GF632/LF622F
cFMus Nonincendive for use in
hazardous (classified) locations:
Class I, II, III, Division 2, Groups A-G
Model GF630 and GF632 Detector
Mounting style:
Flange connection type, ISO13359 for direct
replacement of existing ISO13359 magmeters
Fluid pressure:
0 to 1 MPa (0 to 150 psi, or 0 to 10 bar)
(To be within the applicable flange limitation)
Connection flange standards:
ASME B 16.5 class 150 :15 to 600 mm
(1/2” to 24”)
JIS B 2220 10K
2
EN 1092-1 PN 10 :15 to 600mm (1/2” to 24”)
:15 to 600 mm (1/2” to 24”)
Applicable diameter — 11 to 13mm
(0.433 to 0.512 inch)
Cable glands —
GF632 without cFMus Approval :
Provided as standard, G1/2 male screws
GF632 with cFMus Approval :
Not provided
1/2-14NPT male screws are required.
GF630/LF620 GF632/LF622
Model LF620 and LF622 converters
Input signals
Analog signal — the voltage signal from detector,
proportional to process flow rate (for LF622
separate type converter).
Digital input DI
Signal type: 20 to 30Vdc voltage signal
Input resistance: 2.7k
Number of inputs: one point
Note: DI cannot be used with the Modbus
communication.
DI function — One of the following functions
can be assigned to the DI signal.
Range switching — Selects either the higher or
lower range in the unidirectional or
bidirectional 2-range setting.
Totalizer control — Starts and stops the built-in
totalizer.
Fixed-value outputs —Outputs fixed-values for
current and pulse outputs.
Zero adjustment — Executes zero adjustment
(on-stream at zero flow rate).
Output signals
Current output:
4–20mAdc (load resistance 0 to 750 )
Note: The current output cannot be used with
the PROFIBUS-PA ccommunication.
Digital outputs — Two points are available as
follows.
Digital output DO1 :
Output type: Transistor open collector
Number of outputs: One point
Output capacity: 30Vdc, 200mA maximum
Note: DO1 cannot be used if Modbus
communication connection is 3 lines.
DO1 and DO2 functions — One of the following
functions can be assigned to DO1 and/or DO2.
• Pulse output (available only for DO1,DO2)
Pulse rate: Max 10kHz (10,000pps) (DO1)
Max 100Hz ( 100pps) (DO2)
(Over 1kpps, auto-setting)
Pulse width: 0.3 to 500ms (but less than half of
the period for 100% flow rate)
Note: The same and simultaneous pulse is not
available between DO1 and DO2.)
• Multi-range selection outputs (Note 1)
• High, High high, Low, and/or Low low alarm
outputs (Note 2)
• Empty pipe alarm output (Note 2)
• Digital Output Active Status (DO1 and DO2)
(Note 2)
• Preset count output
• Converter failure alarm output
Note 1: Two outputs (DO1 and DO2) are needed
for 4-range switching and forward/reverse
2-range switching.
Note 2: Normal Open (default set) or Normal
Close is selected for alarm outputs when
programming.
When power failure occurs, unit will be fault to
Normal Open.
Digital output DO2 :
Output type: Solid-state relay output (non
polarity)
Number of outputs: One point
Output capacity: 150Vdc, 150mA maximum or
150Vac (peak to peak), 100mA maximum
Note: DO2 cannot be used with the Modbus
communication.
3
GF630/LF620 GF632/LF622
Communications output :
• HART (std.)
Digital signal is superimposed on 4–20mAdc
current signal as follows:
Conforms to HART protocol
Load resistance: 240 to 750
Load capacitance: 0.25µF maximum
Load inductance: 4mH maximum
• PROFIBUS (opt.)
Protocol : PROFIBUS-PA
Baud rate : 31.25kbps
Bus voltage : 9-30VDC
Consumption electric current of bus:less than 16mA
Manufacture Ident-No. : 093BHEX
Standard Ident-No. : 9740HEX
Slave address : 0-126 (Default address is 126)
Profile : Profile Ver.3.01 for Process Control
Devices
Function blocks : AI(Flow)×1 , Totalizer×1
•Modbus(opt.)
Physical layer : RS485
Protocol : Modbus
Mode : RTU
Baudrate : 4800, 9600, 19200bps
Data length : 8bit
Parity bit : None, Odd, Even
Stop bit : 1bit, 2bit
Error check : CRC-16
Max. station number : 32(with Master device)
Max. cable length : 1.2km (Note)
Note: This length is specification of 3 line
connection.
LCD display:
Full dot-matrix 128×128 dot LCD display
(back–light provided)
The data on the LCD inside the converter can
rotate to 90, 180, and 270 degrees by a software,
without rotating the indicator itself. (Combined
type only)
Parameter settings — Parameters can be set as
follows:
• IR Switches: Three key switches are provided to
set configuration parameters.
• Digital communication: The AF900 hand-held
terminal or PROFIBUS, Modbus is needed to
set parameters.
•Zero adjustment: Zero point adjustment can be
started by pressing the switch in the converter.
Damping:
0.5 to 60 seconds (selectable in one second
increments)
4
Zero and span calibration:
Built-in calibration signal source allows converter
unit check.
Conditions when power fails:
Parameter setting values are stored in
non–volatile memory and the values will be
restored when the power returns to normal
condition. The outputs and display will remain as
follows when power fails.
• Current output: 0mAdc
• Digital output: OFF
• LCD display: No display
• PROFIBUS: No communication
Power supply:
One of the following can be selected:
• 100 to 240Vac, 50/60Hz (std.)
(allowable voltage 80 to 264Vac)
• 24Vdc (allowable voltage 18 to 36Vdc)
• 110Vdc (allowable voltage 90 to 130Vdc)
Surge protection:
Arresters are installed in the power supply and a
current signal output circuit to help protect the
meter from lightning and improve personnel
safety.
Case: Aluminum alloy (equal to IP 67)
Coating: Acrylic resin-baked coating, pearl–gray
colored
Cable connection port:
Cable glands —
LF620 and LF622 without cFMus Approval:
Provided as standard, G 1/2 male
screws.
OD of cableφ11 to 13mm
Material Nylon 66
G 1/2 male screws.
Note: When PROFIBUS or Modbus option
are specified , cable glands size is φ6∼
8mm for signal cable, φ11∼13mm for
power cable.
LF620F and LF622F with cFMus Approval:
Not provided, 1/2–14NPT male
screws are required.
Applicable diameter —
11 to 13mm (0.433 to 0.512 inch)
Note: When PROFIBUS option is specified, cable
gland size is φ6∼8mm for signal cable, φ
11∼13mm for power cable.
GF630/LF620 GF632/LF622
Vibration resistance:
No resonance to the following levels of vibration:
• 10 to 150Hz with acceleration of 9.8m/s2
• Vibration of 30Hz with 29.4 m/s2 in 4h in each
direction will not cause any defect to unit.
Note: Avoid using the flowmeter in an
environment with constant vibration.
Converter LF622 Dimensions and Weights:
See Figure 4 (for separate type)
MTBF:
Converter: 220,000 hours (25 years) at 25 °C
(77 °F) based on strict military specification
MIL-HDBK-217F
Detector: 350,000 hours (40 years) at 25 °C
(77 °F) based on strict military specification
MIL-HDBK-217F
5
GF630/LF620 GF632/LF622
Installation
Dimensions
Combined type GF630/LF620 and GF630/LF620F
Note1
Note2
Note1:
Note2:
Note3:
Note4:
Note5:
Unit
(inch)
:
Eye bolts are provided at the flange
for flowmeters sized 200mm (8") or
above.
Cable glands are not provided for
GF630/LF620F cFMus approved
type. Refer to the part Cable
connection port at detector.
L1 of PTFE lining contains the
thickness of grounding rings.
The weight of PTFE lining includes
the weight of grounding rings.
1 inch = 25.4mm
Note3
mm
Size
(mm)
L1
(mm)
L2
(mm)
15
25
32
40
50
65
80
100
125
150
200
250
300
350
400
450
500
600
200
200
200
200
200
200
200
250
250
300
350
450
500
550
600
600
600
600
205
215
220
225
235
248
253
264
284
299
324
344
369
391
419
441
466
521
JIS B 2220 10K
L3
No. of Weight (kg) approx.
(mm) bolts FEP PTFE PU
253
4
7
7
278
4
8
8
288
4
10
10
295
4
11
11
313
4
12
12
335
4
15
15
345
8
16
16
369
8
23
23
409
8
29
29
439
8
34
34
489
12
48
48
544
12
70
70
591
16
101
93
636
16
137
127
699
16
149
136
751
20
171
804
20
185
919
24
253
Size
(inch)
1/2
1
1-1/4
1-1/2
2
2-1/2
3
4
5
6
8
10
12
14
16
18
20
24
L1
(inch)
7.9
7.9
7.9
7.9
7.9
7.9
7.9
9.8
9.8
11.8
13.8
17.7
19.7
21.7
23.6
23.6
23.6
23.6
ASME B 16.5 class 150
L2
L3
No. of Weight (lbs) approx.
PU
(inch) (inch) bolts FEP PTFE
8.1
10.0
4
16
16
8.5
10.9
4
18
18
8.7
11.3
4
20
20
8.9
11.6
4
23
23
9.3
12.3
4
29
29
9.8
13.2
4
34
34
10.0
13.6
4
42
42
10.4
14.5
8
56
56
11.2
16.1
8
71
71
11.8
17.3
8
84
84
12.8
19.3
8
128
128
13.5
21.4
12
188
188
14.5
23.3
12
292
274
15.4
25.0
12
349
327
16.5
27.5
16
430
402
17.4
29.6
16
468
18.3
31.7
20
538
20.5
36.2
20
741
GF630/LF620
Size
(mm)
L1
(mm)
L2
(mm)
15
25
32
40
50
65
80
100
125
150
200
250
300
350
400
450
500
600
200
200
200
200
200
200
200
250
250
300
350
450
500
550
600
600
600
600
205
215
220
225
235
248
253
264
284
299
324
344
369
391
419
441
466
521
L3
(mm)
PN 10 PN 16
253
253
273
273
291
291
300
300
318
318
340
340
353
353
374
374
409
409
442
442
494
494
542
547
591
599
644
651
702
709
749
761
801
824
911
941
EN 1092-1 PN10 and PN16
No.of
Weight (kg) approx.
Bolts
FEP
PTFE
PU
PN 10
PN 16
PN 10 PN 16
PN 10 PN 16
PN 10
PN 16
4
4
10
10
10
10
4
4
10
10
10
10
4
4
13
13
13
13
4
4
15
15
15
15
4
4
16
16
16
16
4
4
19
19
19
19
8
8
21
21
21
21
8
8
29
29
29
29
8
8
33
33
33
33
8
8
39
39
39
39
8
12
59
59
59
59
12
12
77
83
77
83
12
12
122
137
115
130
16
16
157
175
151
169
16
16
162
186
156
180
20
20
177
222
20
20
197
267
20
20
267
372
Figure 3. GF630/LF620 and GF630/LF620F combined type flowmeters
Meter sizes 15mm (1/2") t 600mm (24")
6
GF630/LF620 GF632/LF622
Separate type GF632/LF622 and GF632/LF622F
36 (1.42)
φ98 (φ3.86)
124
Note1:
Note2
Note1
L3
L2
Note2:
Note3:
Note4:
Note5:
L1
Unit :
(inch)
Eye bolts are provided at the flange
for flowmeters sized 200mm (8") or
above.
Cable glands are not provided for
GF632/LF622F cFMus approved
type. Refer to the part Cable
connection port at detector.
L1 of PTFE lining contains the
thickness of grounding rings.
The weight of PTFE lining includes
the weight of grounding rings.
1 inch = 25.4mm
Note3
mm
Size
(mm)
15
25
32
40
50
65
80
100
125
150
200
250
300
350
400
450
500
600
L1
(mm)
200
200
200
200
200
200
200
250
250
300
350
450
500
550
600
600
600
600
L2
(mm)
172
182
187
192
202
215
220
231
251
266
291
311
336
358
386
408
433
488
JIS B 2220 10K
L3
No. of Weight (kg) approx.
(mm) bolts FEP PTFE PU
220
4
5
5
245
4
6
6
255
4
8
8
262
4
9
9
280
4
10
10
302
4
13
13
312
8
14
14
336
8
21
21
376
8
27
27
406
8
32
32
456
12
46
46
511
12
68
68
558
16
99
91
603
16
135
125
666
16
147
134
718
20
169
771
20
183
886
24
251
Size
(inch)
1/2
1
1-1/4
1-1/2
2
2-1/2
3
4
5
6
8
10
12
14
16
18
20
24
L1
(inch)
7.9
7.9
7.9
7.9
7.9
7.9
7.9
9.8
9.8
11.8
13.8
17.7
19.7
21.7
23.6
23.6
23.6
23.6
ASME B 16.5 class 150
L2
L3 No. of Weight (lbs) approx.
PU
(inch) (inch) bolts FEP PTFE
4.9
8.5
4
12
12
5.1
9.3
4
14
14
5.3
9.7
4
16
16
5.4
10.1
4
18
18
5.7
10.9
4
25
25
6.1
11.9
4
29
29
6.2
12.4
4
38
38
6.5
13.6
8
51
51
7.1
14.9
8
67
67
7.5
15.9
8
80
80
8.2
18.2
8
124
124
8.8
20.2
12
183
183
9.5
22.7
12
287
269
10.1
24.6
12
344
322
10.9
26.9
16
426
397
11.5
28.6
16
463
12.2
30.8
20
534
13.8
35.2
20
737
GF632/LF622
Size
(mm)
L1
(mm)
L2
(mm)
15
25
32
40
50
65
80
100
125
150
200
250
300
350
400
450
500
600
200
200
200
200
200
200
200
250
250
300
350
450
500
550
600
600
600
600
172
182
187
192
202
215
220
231
251
266
291
311
336
358
386
408
433
488
L3
(mm)
PN 10 PN 16
220
220
240
240
258
258
267
267
285
285
307
307
320
320
341
341
376
376
409
409
461
461
509
514
558
566
611
618
669
676
716
728
768
791
878
908
EN 1092-1 PN10 and PN16
No.of
Weight (kg) approx.
FEP
PTFE
PU
Bolts
PN 10
PN 16
PN 10 PN 16
PN 10 PN 16
PN 10
PN 16
4
4
8
8
8
8
4
4
8
8
8
8
4
4
11
11
11
11
4
4
13
13
13
13
4
4
14
14
14
14
4
4
17
17
17
17
8
8
19
19
19
19
8
8
27
27
27
27
8
8
31
31
31
31
8
8
37
37
37
37
8
12
57
57
57
57
12
12
75
81
75
81
12
12
120
135
113
128
16
16
155
173
149
167
16
16
160
184
154
178
20
20
175
220
20
20
195
265
20
20
265
370
Figure 4. Separate type detectors GF632 Meter sizes 15mm (1/2") to 600mm (24")
7
GF630/LF620 GF632/LF622
Attachment
LCD display
I/O cable ground
Excitation
ground
cable
Plat
e
Power supply
cable ground
Signal cable ground
Option cable ground
Unit : mm (inch)
IR Switch
Note : Cable glands are not provided for LF622F
cFMus approved type. Refer to the part Cable
connection port at detector.
Figure 5. Separate type converter LF622 and LF622F
External Connections
Combined type GF630//LF620 and GF630/LF620F flowmeter
Instrument panel : Ordered separately
Grounding with 100Ω or less
ground resistance
Power switch
(External double-pole power switch)
Ⅳ wire 5.5mm2 or
more
Grounding with 100Ω or less
ground resistance
Power supply
Current output (4∼20mAdc)
or PROFIBUS
Digital input (20∼30Vdc)
or Modbus
Digital output 2
Signal common for DI and DO
Digital output 1
Grounding with 100Ω or less
ground resistance
NOTE:
In the case of the integral type, the signal line
( A, B, G ) and the excitation line ( E, X, Y ) are
the connector joints.
I/O cable Power cable
Figure 6. Combined type GF630/LF620 and GF630/LF620F flowmeters Wiring Diagram
8
GF630/LF620 GF632/LF622
・Separate type GF632/LF622 and GF632/LF622F flowmeter
Instrument panel : Ordered separately
Ⅳ wire 5.5mm2 or more
Grounding with 100Ω or less
ground resistance
Power switch
(External double-pole power switch)
Power supply
Current output (4∼20mAdc)
or PROFIBUS
Digital input (20∼30Vdc)
or Modbus
Digital output 2
Signal common for DI and DO
Digital output 1
Grounding with 100Ω or less
ground resistance
Grounding with 100Ω or less
ground resistance
Thick walled steel conduit
Signal cable
(2-wire shielded hard-rubber sheathed cable)
Excitation cable
(3-wire shielded hard-rubber cable)
I/O cable
Power cable
Connected detector
Figure 7. Separate GF632/LF622 and GF632/LF622F type Converter Wiring Diagram
*1 Locate an external double-pole power switch on the power line near the flowmeter within easy reach of operation.
Use the appropriate switch rating as shown below:
Switch rating: 250Vac, 6A or more In rush current: 15A or more
Table 1. LF620, LF620F, LF622 and LF622F Converters Signal Table
Symbol
L1 (+)
L2 (−)
GND
FG
DI
DO1
DO2
COM
Description
Cable
Power supply
Power cable
Ground (for arrester)
Frame ground
Digital Input (20∼30Vdc)
Digital Output 1
Digital Output 2
Signal Common for DI, DO1, DO2
I/O cable
+
Current Output (4∼20mAdc)
or PROFIBUS
−
X
Y
E
A
B
G
Shielded cable for
PROFIBUS-PA
Excitation Output
Excitation cable
(for LF622, LF622F only)
Signal Input
Signal cable
(for LF622, LF622F only)
Note: Symbol of the terminal is changed as follows for Modbus.
DO2 → T+, DI → T-, COM → TG
Symbol
T+
TTG
Description
Modbus(+)
Modbus(-)
Modbus(GND)
Cable
Twist-pair polyethylene
insulated vinyl sheath cable
(JKEV,AWG24(0.2mm2))
9
GF630/LF620 GF632/LF622
Wiring Precautions (PROFIBUS or Modbus)
(1) For wiring path, avoid places near electrical
equipment that may cause electromagnetic
induction or electrostatic induction interference
(such as a motor, transformer and wireless
transmitter).
(2) Use a PROFIBUS-PA cable or a RS485
twist-pair cable for signal cable. In addition,
make sure to use a shielded cable to improve
noise resistance. Furthermore, installation of
signal cable in metal conduit is recommended.
(3) General cables are designed for indoor use where
cables are not exposed to humidity, rain, etc.
When you install cables, make sure to check the
operating conditions such as the operating
temperature range of the cable by contacting its
manufacturer.
(4) When you carry out cable end treatment of cable,
use a dedicated cable stripper etc. so that the core
wire of the cable will not be nicked or damaged.
In addition, for cables, be careful of allowable
maximum bend diameter etc. (Basically, do not
install cables in a way cables are twisted or
bent.).
(5) Consider installing a PROFIBUS-PA arrester in
the communication path of PROFBUS-PA so
that the electromagnetic flowmeter will not be
affected by lightning etc.
(6) The electromagnetic flowmeter is not equipped
with terminating resistors.Use the terminating
resistor unit for PROFIBUS-PA or junction box,
if necessary.
10
(7) Only one PROFIBUS-PA cable goes through a
cable gland of the Electromagnetic Flowmeter.
Use the junction box at system configuration.
(8) Install a terminator to flowmeter that connected
to end of Modbus network.
Allowable cable length (m)
Wiring Precautions
(1) Explosion proof type flowmeters are not
provided cable glands.
Refer to the part Cable connection port at
detector and converter.
(2) Connect the grounding wire (IV wire 5.5mm² or
more) to a good earth ground (100 or less
ground resistance). Make the wire as short as
possible. Do not use a common ground shared
with other equipment where earth current may
flow. An independent earth ground is
recommended.
(3) The allowable cable lengths between the
detector and converter for the separate type
flowmeter depend on the electrical conductivity
of the object fluid. See Figure 8.
(4) DO1, DO2, and DI use the same common
terminal (COM). This COM can not connect to
other equipments which have their own ground
terminal. (Power supply for connecting to DI or
DO, etc…) Need to wire separately.
300
200
100
50
30
20
10
5
3
3
5
10 20 30 50 100 200
Conductivity ( S/cm)
Figure 8. Electrical Conductivity and
Cable Length
Meter Size
To select the meter size:
See Table 2 to 3 and find meter sizes within the
velocity of 0.1 to 10m/s for a specified full-scale
(measuring range high limit) flow. Select one that
has its full-scale velocity between 1 and 3m/s.
Note: Make sure the full-scale flow rate used for the
final planning stage stays within 10m/s in terms
of flow velocity.
GF630/LF620 GF632/LF622
Table 2. Flow Rate and Flow velocity (SI unit)
3
Unit: m /h
Size
(mm)
15
25
32
40
50
65
80
100
125
150
200
250
300
350
400
450
500
600
0.1 m/s
0.0636
0.1767
0.2895
0.4523
0.7067
1.195
1.809
2.827
4.417
6.361
11.31
17.67
25.45
34.64
45.23
57.25
−
−
Flow rate
0.3 m/s 1.0 m/s
0.1908
0.6361
0.5301
1.767
0.8686
2.895
1.357
4.523
2.120
7.067
3.583
11.95
5.428
18.09
8.482
28.27
13.25
44.17
19.08
63.61
33.93
113.1
53.01
176.7
76.34
254.5
103.9
346.4
135.7
452.3
171.7
572.5
212.1
706.9
305.4
1,018
3 m/s
1.908
5.301
8.686
13.57
21.20
35.83
54.28
84.82
132.5
190.8
229.3
530.1
763.4
1,039
1,357
1,717
2,121
3,054
10 m/s
6.361
17.67
28.95
45.23
70.67
119.5
180.9
282.7
441.7
636.1
1,131
1,767
2,545
3,464
4,523
5,725
7,069
10,180
Table 3. Flow Rate and Flow velocity (U.S. unit)
Unit: gal/min
Size
(inch)
1/2'
1
1¼
1½
2
2½
3
4
5
6
8
10
12
14
16
18
20
24
0.3ft/s
0.2801
0.7781
1.275
1.992
3.112
5.260
7.967
12.45
19.45
28.01
49.80
77.81
112.0
152.5
199.2
252.1
−
−
0.98ft/s
0.8403
2.334
3.824
5.975
9.337
15.78
23.90
37.35
58.35
84.03
149.4
233.4
336.1
457.5
597.5
756.3
933.7
1,344
Flow rate
3ft/s
2.561
7.115
11.66
18.21
28.46
48.09
72.85
113.8
177.9
256.1
455.3
711.5
1,025
1,394
1,821
2,305
2,846
4,098
10ft/s
8.532
23.72
38.86
60.71
94.86
160.3
242.8
379.4
592.9
853.8
1,518
2,372
3,415
4,648
6,071
7,684
9,486
13,660
32.8ft/s
28.01
77.81
127.5
199.2
311.2
526.0
796.7
1,245
1,945
2,801
4,980
7,781
11,200
15,250
19,920
25,210
31,120
44,820
Calibration Range
If the calibration range is not specified, the standard
range as shown below will be used. If the range is
specified, we will use the specified range for
calibration.
Table 4. Standard Flow Range
Meter size
mm (inch)
15 (1/2)
25 (1)
32 (1 1/4)
40 (1 1/2)
50 (2)
65 (2 1/2)
80 (3)
100 (4)
125 (5)
150 (6)
200 (8)
250 (10)
300 (12)
350 (14)
400 (16)
450 (18)
500 (20)
600 (24)
Flow rate
(m³/h)
2
6
10
15
25
40
60
100
150
200
300
600
900
1,200
1,600
2,500
3,000
4,000
Standard flow range
Flow
Flow rate
velocity
(gal/min)
(m/s)
3.144
25
3.395
75
3.454
125
3.316
175
3.537
300
3.348
475
3.316
650
3.537
1,000
3.395
1,750
3.144
2,500
2.653
4,500
3.395
7,000
3.537
10,000
3.465
12,000
3.537
16,000
4.366
20,000
4.244
25,000
3.930
40,000
Flow
velocity
(ft/s)
29.283
31.625
32.171
28.826
31.625
29.629
26.766
26.354
31.625
29.283
29.649
29.517
28.283
25.817
26.354
26.029
26.354
29.283
Note: The unit of "gal/min" is not exchanged
(converted) by "m3/h".
11
GF630/LF620 GF632/LF622
Piping Precautions
(1) Design piping so that the flowmeter detector pipe is
always filled with the fluid being measured,
whether the fluid is flowing or not.
(2) The detector has no adjustable piping mechanism.
Install an adjustable short pipe where needed.
(3) The required straight pipe length should comply
with the requirements as follows.
(4) Be sure to ground the flowmeter according to
the flow meter instruction manual.
Required straight pipe length
When using 90-dgree bend, tee, L ≥ 5D
diffuser or fully opened valve
When using other types of L ≥ 10D
valves
Downstream When no valve plate protrudes L ≥ 0
side
into the detector pipe
Upstream
side
L: Required straight pipe length, D: Meter size
Piping materials (to be ordered separately)
Mating flanges:
The flowmeter must be mounted with its detector
pipe connected between the flanges in the pipeline. If
no flanges are used where the flowmeter is to be
mounted, mating flanges are needed.
Adjustable short pipe:
When both the upstream and downstream pipe
sections cannot be adjusted laterally along the pipeline,
an adjustable short pipe may be needed.
Reducers:
When the flowmeter with its Meter size smaller than
that of the pipeline should be installed, reducers are
needed on both ends of the flowmeter detector.
Reducers with pipe extensions:
Reducers with adjustable piping mechanism.
Gasket :
Gasket is needed for piping. In the case of the
detector with grounding ring and Teflon lining,
additional gasket is needed between grounding ring
and lining face.
12
About establishment environment
Do not store or install the flowmeter :
• Where there is direct sunlight.
• Where excessive vibration or mechanical shock
occurs.
• Where high temperature or high humidity
conditions exist.
• Where corrosive atmospheres exist.
• Places that can be submerged under water.
• Where there is a sloped floor. To put the flowmeter
temporarily on the floor, place it carefully with
something, such as a block, to support it so that the
flowmeter will not topple over.
In areas like the following, there may be the case that
infrared switches do not function correctly. (If these
are unavoidable, use an appropriate cover.)
(1) Where unit (operation panel) is exposed to direct
sunlight, reflection of light onto window pane and
diffused light reflection.
(2) Where smoke and steam may occur.
(3) Where exposed to direct snow, ice or mud.
GF630/LF620 GF632/LF622
Ordering Information
1. When ordering the GF630 series flowmeters, refer
to Tables 6 to 8 (Type Specification Codes).
An entry must be made for each of the columns in
each of these tables.
2. Fluid characteristics:
(1) Type of fluid to be measured and its characteristics
(2) Fluid temperature
(3) Fluid pressure
(4) Electrical conductivity of the fluid
3. Measuring range
4. I/O function setting
5. Ordering scope:
Flow calibration data: (required or not)
6. Other items
Specifications other than standard items
Consult a Toshiba representative before ordering
when choosing materials of the wetted parts such
as lining, electrodes, and grounding rings.
Ordering Grounding rings
When you purchase the grounding ring, refer to
Table 5.
Table 5. Arrangement code of the Grounding ring
MeterMeter
size size
ASME B 16.5
JIS B 2220
10K
JIS10K
classANSI150
150
mm mminchInch
15 151/2”1/2”
5P8A1544P001
5P8A1544P001
25 25 1” 1”
5P8A1544P002
5P8A1544P002
32 321-1/4”
5P8A1544P003
1-1/4”
5P8A1544P003
40 401-1/2”
5P8A1544P004
1-1/2”
5P8A1544P004
50 50 2” 2”
5P8A1544P005
5P8A1544P005
65 652-1/2”
5P8A1544P006
5P8A1544P106
2-1/2” 5P8A1544P006
5P8A1544P106
80 80 3” 3” 5P8A1544P007
5P8A1544P107
5P8A1544P007
5P8A1544P107
100 100 4” 4”
5P8A1544P008
5P8A1544P008
125 125 5” 5”
5P8A1544P009
5P8A1544P009
150 150 6” 6”
5P8A1544P010
5P8A1544P010
200 200 8” 8” 5P8A1544P011
5P8A1544P111
5P8A1544P011
5P8A1544P111
250 25010” 10”5P8A1544P012
5P8A1544P112
5P8A1544P012 5P8A1544P112
300 30012” 12”5P8A1544P013
5P8A1544P113
5P8A1544P013
5P8A1544P113
350 35014” 14”5P8A1544P014
5P8A1544P114
5P8A1544P014 5P8A1544P114
400 40016” 16”5P8A1544P015
5P8A1544P115
5P8A1544P015
5P8A1544P115
450 45018” 18”5P8A1544P016
5P8A1544P116
5P8A1544P016 5P8A1544P116
500 50020” 20”5P8A1544P017
5P8A1544P117
5P8A1544P017
5P8A1544P117
600 60024” 24”5P8A1544P019
5P8A1544P119
5P8A1544P019
5P8A1544P119
700
28”
5P8A1544P021 5P8A1544P121
750
30”
5P8A1544P022 5P8A1544P122
800
32”
5P8A1544P023 5P8A1544P123
900
36”
5P8A1544P025 5P8A1544P125
13
GF630/LF620 GF632/LF622
N
(Number of tabs)
T
ΦD2
ΦD1
Meter size
JIS B 2220 10K (Unit: mm)
ASME B 16.5 class 150
(Unit: inch)
EN 1092-1 PN10 and PN16 (Unit: mm)
2
ΦD1
PN10
PN16
42
ΦD2
PN10
PN16
16
0.16
2
60
0.16
2
70
1.65
0.12
2
mm
inch
ΦD1
ΦD2
T
N
ΦD1
ΦD2
T
N
15
1/2
42
16
3
2
1.65
0.63
0.16
25
1
60
27
3
2
2.36
1.06
32
1-1/4
70
34
3
2
2.76
1.34
40
1-1/2
77
42
3
2
3.03
T
N
3
2
27
3
2
34
3
2
77
42
3
2
50
2
95
52
3
2
3.74
2.05
0.12
2
95
52
3
2
65
2-1/2
115
67
3
2
4.69
2.44
0.12
2
115
67
3
2
80
3
125
82
3
2
5.08
3.03
0.12
2
125
82
3
2
100
4
150
104
3
2
5.91
4.09
0.12
2
150
104
3
2
125
5
185
129
3
2
7.28
5.08
0.12
2
185
129
3
2
150
6
215
154
3
2
8.46
6.06
0.12
2
215
154
3
2
200
8
265
204
3
4
10.43
8.03
0.12
4
265
204
3
4
250
10
325
255
3
4
13.11
10.04
0.12
4
325
255
3
4
300
12
372
305
3
4
15.59
12.01
0.12
4
305
3
4
350
14
416
333
3
4
17.32
13.11
0.12
4
416
440
333
3
4
400
16
479
384
3
4
19.8
15.12
0.12
4
479
503
384
3
4
450
18
534
433
3
4
21.34
17.05
0.12
4
534
542
433
3
4
500
20
589
483
3
4
23.58
19.02
0.12
4
589
599
483
3
4
600
24
691
584
3
4
27.95
22.99
0.12
4
691
720
584
3
4
372
Figure 9. Grounding ring Meter sizes 15mm (1/2") to 600mm (24")
14
GF630/LF620 GF632/LF622
Table 6. Specification Code (Flange type detector GF630 (Combined type) )
Model
1 2 3 4 5
G F 6 3 0
6
0
0
0
0
0
0
0
1
1
1
2
2
3
3
4
4
5
6
7
Specification Code
8 9 10 11 12 13 14
Combined (Integral) type
Meter size
15 mm (½")
25 mm (1")
32 mm (1-¼")
40 mm (1-½")
50 mm (2")
65 mm (2-½")
80 mm (3")
100 mm (4")
125 mm (5")
150 mm (6")
200 mm (8")
250 mm (10")
300 mm (12")
350 mm (14")
400 mm (16")
450 mm (18")
500 mm (20")
600 mm (24")
Connection flange standard
ASME B 16.5 class 150
JIS B 2220 10K
EN 1092-1 PN10
EN 1092-1 PN16
Lining
Polyurethane
FEP
PTFE (Note1)
Electrode Material
316L stainless steel
Hastelloy C (Equivalent)
Flow and calibration velocity range
1
2
3
4
5
6
8
0
2
5
0
5
0
5
0
5
0
0
A
J
D
E
U
F
P
B
F
A
B
C
: Standard
PU
Lining
FEP PTFE
-
-
-
-
-
-
-
-
0.3 to 10 m/s (standard range calibration)
0.3 to 10 m/s (specified range calibration)
0.1 to 10 m/s (specified range calibration)
1
2
Code explanation:
Description
Without Grounding Ring
With Grounding Ring
: Option
–: Not available
Note: The grounding rings are provided to PTFE Lining, which material is 316 stainless steel
and gasket material is EPDM rubber.
15
GF630/LF620 GF632/LF622
Table 7. Specification Code (Flange type detector GF632 (Separate type) )
Model
Specification Code
Description
1 2 3 4 5 6 7 8 9 10 11 12 13 14
G F 6 3 2
Separate (Remote) type
Meter size
0 1
15mm (½")
0 2
25mm (1")
0 3
32mm (1¼")
0 4
40mm (1½")
0 5
50mm (2")
0 6
65mm (2½")
0 8
80mm (3")
1 0
100mm (4")
1 2
125mm (5")
1 5
150mm (6")
2 0
200mm (8")
2 5
250mm (10")
3 0
300mm (12")
3 5
350mm (14")
4 0
400mm (16")
4 5
450mm (18")
5 0
500mm (20")
6 0
600mm (24")
Connection flange standard
A
ASME B 16.5 class 150
J
JIS B 2220 10K
D
EN 1092-1 PN10
E
EN 1092-1 PN16
Lining
U
Polyurethane(PU)
F
FEP
P
PTFE (Note1)
Electrode Material
B
316L stainless steel
F
Hastelloy C (Equivalent)
Flow and calibration velocity range
Cable glands and cFMus
0.3 to 10 m/s (standard range calibration)
A
1/2-14NPT connection port
0.3 to 10 m/s (specified range calibration)
B
without cable glands.
0.1 to 10 m/s (specified range calibration)
C
With cFMus logo.
0.3 to 10 m/s (standard range calibration)
H
G1/2 connection port with
0.3 to 10 m/s (specified range calibration)
J
cable glands.
0.1 to 10 m/s (specified range calibration)
K
Without cFMus logo.
1
Without Grounding Ring
2
With Grounding Ring
Code explanation:
: Standard
: Option
–: Not available
Note: The grounding rings are provided to PTFE Lining, which material is 316 stainless steel
and gasket material is EPDM rubber.
EJL-140D
PU
Lining
FEP PTFE
-
-
-
-
-
-
-
-
GF630/LF620 GF632/LF622
Table 8. Specification Code for LF620/LF622 converters
Model
Specification Code
Contents
1 2 3 4 5 6 7 8 9 10 11 12 13 14
L F 6 2
Electromagnetic flowmeter converter
0
Combined (Integral) type
2
Separate (Remote) type
Purpose
A
Standard
F
cFMus class I, Division 2 approved
Shape
A
Standard type with case
Converter mounting fitting
A
None
C
Panel, Accessory for wall mounting (BNP material: SUS304)
E
Accessory for pipe installation (BNP material: SUS304)
Digital input/output
2
Digital output points 2 (DO1+DO2) +Digital input point 1 (DI)
Current output and Communication function(Note1)
1
Current output + HART communication
2
PROFIBUS communication
3
Current output + Modbus (RS485) communication
LF622
type
–
–
–
–
Power supply(Note2)
100Vac-240Vac, 50/60Hz
24Vdc
110Vdc
Instruction manual
English
1
2
3
F
Code explanation:
LF620
type
: Standard
: Option
–: Not available
Note 1: When Modbus communication is provided, digital output points 1(DO1) and digital output points(DO2), digital input point
1(DI), HART communication cannot be used.
When PROFIBUS communication is provided, current output(4-20mA) and HART communication cannot be used.
Check Table 9 for the details.
Note 2: Select 110Vdc for test report inspected under the condition of 110Vdc.
Table 9. Communication function and output selection table
Selection of Function
Code
Selected
(10th digit)
Communication
1
HART
2
PROFIBUS
3
Modbus
Code explanation:
Availability of outputs
4-20mAdc
DO1
DO2
DI
X
X
X
(Note)
:Available X:Not Available
Note :When digital output 1 function and Modbus communication function are used at one time, TG (signal ground) of
the Modbus communication function cannot be connected (2 line connection).
17
GF630/LF620 GF632/LF622
Table 10. Specification Code (Exciting Cable and Signal Cable for Separate type only)
Model
Specification Code
1 2 3
4
5
6
7
8
A C C
Description
Dedicated preformed cable
Nominal cross-sectional area of Exciting cable (Note 1)
1.25 mm²
2 mm²
Nominal cross-sectional area of Signal cable (Note 2)
0.75 mm²
A
B
A
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
2
2
3
3
4
4
5
6
1
2
3
4
5
6
7
8
9
0
5
0
5
0
5
0
5
0
0
Cable length
1m
2m
3m
4m
5m
From 1 to 10 meters (3.3 to 32.8 feet),
6m
cable can be ordered in 1 meter increments.
7m
8m
9m
10 m
15 m
20 m
25 m
30 m
From 10 to 50 meters (32.8 to 164 feet),
35 m
cable can be ordered in 5 meters increments
40 m
45 m
50 m
60 m
From 50 to 300 meters (164 to 984 feet),
cable can be ordered in 10 meters increments.
300 m
3
0
0
Notes:
1. Exciting cable is a 3-wire chloroprene sheathed cable. For a nominal cross-sectional area of 1.25 mm², the overall diameter will be
12 mm (15/32 inch): for 2 mm², 13 mm(1/2 inch).
2. Signal cable is a 2-wire shielded chloroprene sheathed cable with a nominal cross-sectional area of 0.75 mm² and an overall diameter
of 12 mm (15/32 inch).
3.Relation between exciting cable length and its nominal cross-sectional area and overall diameter is as follows.
Exciting cable length
Nominal cross-sectional area
1.25 mm²
12 mm
210 to 300 m
2 mm²
13 mm
ISO9001 and ISO14001 certified.
Misuse of this product can result in damages to property or human injury.
Read related manuals carefully before using this product.
EJL-140D
Overall diameter
1 to 200 m
Specifications are subject to change without notice.
Printed in Japan 2011-5 (TDOC)
© TOSHIBA Corporation 2011
All Rights Reserved.