Option X4 Additional Operator Panel AOP-2

MULTI-LINE 2
DESCRIPTION OF OPTIONS
Option X4
Additional Operator Panel AOP-2
● Description of option
● Functional description
DEIF A/S · Frisenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · [email protected] · www.deif.com
isenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · [email protected] · www.deif.com
14 9614 · Fax: +45 9614 9615 · [email protected] · www.deif.com
Document no.: 4189340484H
SW version:
Option X4 Additional Operator Panel
AOP-2 4189340484 UK
1. Delimitation
1.1. Scope of Option X4................................................................................................................................3
2. General information
2.1. Warnings, legal information and responsibility.......................................................................................4
2.1.1. Warnings and notes ......................................................................................................................4
2.1.2. Legal information and disclaimer ..................................................................................................4
2.1.3. Safety issues ................................................................................................................................4
2.1.4. Electrostatic discharge awareness ...............................................................................................4
2.1.5. Factory settings ............................................................................................................................4
3. Description of option
3.1. Option X4 – AGC 200.............................................................................................................................5
3.1.1. About the option - for AGC 200.....................................................................................................5
3.2. Option X4 – AGC 100, ECU 100, GCU 100, GC-1F/2...........................................................................5
3.2.1. About the option - for AGC 100, ECU 100, GCU 100, GC-1F/2....................................................5
3.3. Rear side view, connectors, wiring.........................................................................................................5
3.3.1. Rear side view ..............................................................................................................................5
3.3.2. Connectors ...................................................................................................................................6
4. Functional description
4.1. Principle diagram....................................................................................................................................7
4.1.1. Connection.....................................................................................................................................7
4.2. AOP-2.....................................................................................................................................................7
4.2.1. Front side view ..............................................................................................................................7
4.2.2. Wiring - cable type 1 .....................................................................................................................8
4.2.3. Wiring - cable type 2 .....................................................................................................................9
4.2.4. CAN Node ID configuration ........................................................................................................10
4.2.5. Selection of CAN ID ....................................................................................................................10
4.2.6. Status relay .................................................................................................................................10
4.2.7. Programming ..............................................................................................................................10
5. Error handling
5.1. Duplicate CAN ID.................................................................................................................................11
5.1.1. AOP-2 .........................................................................................................................................11
DEIF A/S
Page 2 of 11
Option X4 Additional Operator Panel
AOP-2 4189340484 UK
Delimitation
1. Delimitation
1.1 Scope of Option X4
This description of options covers the following products:
AGC 100 series
AGC 200 series
APU 200 series
GC-1F/2
ECU/GCU 100 series
DEIF A/S
SW version 4.0x.x or later
SW version 3.5x.x or later
SW version 3.53.x or later
SW version 1.2x.x and 2.0x.x or later
SW version 1.0x.x or later
Page 3 of 11
Option X4 Additional Operator Panel
AOP-2 4189340484 UK
General information
2. General information
2.1 Warnings, legal information and responsibility
2.1.1 Warnings and notes
Throughout this document, a number of warnings and notes with helpful user information will be presented.
To ensure that these are noticed, they will be highlighted as follows in order to separate them from the general text.
Warnings
Warnings indicate a potentially dangerous situation, which could result in death, personal injury or damaged equipment, if certain guidelines are not followed.
Notes
Notes provide general information, which will be helpful for the reader to bear in mind.
2.1.2 Legal information and disclaimer
DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how
to install or operate the engine/generator controlled by the Multi-line 2 unit, the company responsible for the
installation or the operation of the set must be contacted.
The Multi-line 2 unit is not to be opened by unauthorised personnel. If opened anyway, the warranty will be lost.
Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
2.1.3 Safety issues
Installing and operating the Multi-line 2 unit may imply work with dangerous currents and voltages. Therefore,
the installation should only be carried out by authorised personnel who understand the risks involved in working with live electrical equipment.
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement inputs as this could lead to injury or death.
2.1.4 Electrostatic discharge awareness
Sufficient care must be taken to protect the terminal against static discharges during the installation. Once the
unit is installed and connected, these precautions are no longer necessary.
2.1.5 Factory settings
The Multi-line 2 unit is delivered from factory with certain factory settings. These are based on average values
and are not necessarily the correct settings for matching the engine/generator set in question. Precautions
must be taken to check the settings before running the engine/generator set.
DEIF A/S
Page 4 of 11
Option X4 Additional Operator Panel
AOP-2 4189340484 UK
Description of option
3. Description of option
3.1 Option X4 – AGC 200
3.1.1 About the option - for AGC 200
This option includes an additional operator panel (AOP-2) which can be connected to the AGC 200 via a CAN
bus communication port. The AOP-2 has 16 configurable LEDs and eight configurable buttons, which are programmed with the PC utility software. It can be used as an interface to the AGC 200 unit for indication of
status and alarms together with buttons for, for example, alarm acknowledge and mode selection.
A maximum of five AOP-2 units can be connected to each AGC 200 unit.
3.2 Option X4 – AGC 100, ECU 100, GCU 100, GC-1F/2
3.2.1 About the option - for AGC 100, ECU 100, GCU 100, GC-1F/2
This option includes an additional operator panel (AOP-2) which can be connected to the GC-1F via the CAN
bus 2 communication port and via CAN bus B on AGC 100, ECU 100 and GCU 100. The AOP-2 has 16 configurable LEDs and eight configurable buttons, which are programmed with the PC utility software. It can be
used as an interface to the unit for indication of status and alarms together with buttons for, for example,
alarm acknowledge and mode selection.
A maximum of two AOP-2 units can be connected to each GC-1F unit, and five AOP-2 units to
each AGC 100, ECU 100 and GCU 100.
3.3 Rear side view, connectors, wiring
3.3.1 Rear side view
Additional operator´s panel AOP-2
End resistor
2
OFF
ON
DEIF A/S
1
CAN 1
CAN 2
Page 5 of 11
Option X4 Additional Operator Panel
AOP-2 4189340484 UK
Description of option
3.3.2 Connectors
CAN 1: DC supply and CAN bus communication to/from the controller.
CAN 2: CAN bus communication to/from the controller or additional AOP-2 units and status relay output.
End resistor
DEIF A/S
1 × AOP-2 unit connected:
Dip switch no. 1 on the unit should be set to ON.
2 × AOP-2 units connected:
Dip switch no. 1 on AOP-2 no. 1 should be set to OFF.
Dip switch no. 1 on AOP-2 no. 2 should be set to ON.
on AOP-2 no. 2 should be set to ON.
Page 6 of 11
Option X4 Additional Operator Panel
AOP-2 4189340484 UK
Functional description
4. Functional description
4.1 Principle diagram
4.1.1 Connection
Below is a principle diagram of the connection of the additional displays and operator panels.
AGC 100/AGC 200/GC-1F
CANbus
comm.
DC power
supply
AOP-2
DC power
supply
CANbus
comm.
AOP-2
4.2 AOP-2
4.2.1 Front side view
As shown on the drawing, the configurable LEDs are named 1 to 16, and the buttons are named 1 to 8.
DEIF A/S
Page 7 of 11
Option X4 Additional Operator Panel
AOP-2 4189340484 UK
Functional description
4.2.2 Wiring - cable type 1
Be aware that two cables can be chosen, and that there is a difference in the colour codes of
the wires. The diagrams below show how to wire up both cable types.
CAN 1
CAN 2
654321
654321
Comm. to
other units
NC
NO
Com
ON
Red/white
Bro wn/white
Red
Bro wn
Black/white
Black
1
Red/white
Bro wn/white
Red
Bro wn
Black/white
Black
2
OFF
Twi sted pair
Cable shield
Status relay
End resisto r
120
5V DC
+-
Output
CAN H
Input
CAN L
Power
supply
+-
24V DC
Terminals for CAN connection
CAN L
CAN H
CAN A
9
7
CAN B
12
10
CAN C
15
13
AGC 100/ECU 100/GCU 100
CAN B
59
57
GC-1F/2
CAN 2
59
57
AGC 200/APU 200
DEIF A/S
Page 8 of 11
Option X4 Additional Operator Panel
AOP-2 4189340484 UK
Functional description
4.2.3 Wiring - cable type 2
CAN 1
CAN 2
654321
654321
Comm. to
other units
NC
NO
Com
ON
Blue
Yell ow
Gre en
Red
Black
White
1
Blue
Yell ow
Gre en
Red
Black
White
2
OFF
Twi sted pair
Cable shield
Status relay
End resisto r
120
5V DC
+-
Output
CAN H
Input
CAN L
Power
supply
+-
24V DC
Terminals for CAN connections
CAN L
CAN H
CAN A
9
7
CAN B
12
10
CAN C
15
13
AGC 100/ECU 100/GCU 100
CAN B
59
57
GC-1F/2
CAN 2
59
57
AGC 200/APU 200
DEIF A/S
Page 9 of 11
Functional description
Option X4 Additional Operator Panel
AOP-2 4189340484 UK
It is recommended to keep a fair distance to power cables.
The maximum length of the CAN bus line is 200 m.
A DC/DC converter for the DC supply voltage and 2 × 1 m cable with an RJ12 plug in one end
and stripped wires in the other end are included in the AOP-2 delivery.
4.2.4 CAN Node ID configuration
The CAN Node ID for the AOP-2 can be set to 1-9, it is done by following this procedure:
1. Press buttons no. 7 and no. 8 at the same time to activate the CAN ID change menu, this will activate the
LED for the present CAN ID number, and LED no. 16 will be flashing.
2. Use button no. 7 (increase) and button no. 8 (decrease) to change the CAN ID according to the table below.
3. Press button no. 6 to save the CAN ID and return to normal operation.
4.2.5 Selection of CAN ID
CAN ID
Indication of CAN ID selection
0
CAN bus OFF: LED 16 flashes
1
LED 1 light steady + LED 16 flashes (default value)
2
LED 2 light steady + LED 16 flashes
3
LED 3 light steady + LED 16 flashes
4
LED 4 light steady + LED 16 flashes
5
LED 5 light steady + LED 16 flashes
Node ID 1-9 for AOP-2s and Node ID 10-64 for external I/O modules (option H8).
4.2.6 Status relay
The status relay is used for watchdog function. It will activate approximately two seconds after power up if the
CAN bus communication is OK and no internal failures are present.
4.2.7 Programming
The programming of the AOP-2 is made with the PC utility software, which can be downloaded from
www.deif.com. Please refer to the Help function in the PC utility software for instructions regarding the programming.
DEIF A/S
Page 10 of 11
Option X4 Additional Operator Panel
AOP-2 4189340484 UK
Error handling
5. Error handling
5.1 Duplicate CAN ID
5.1.1 AOP-2
If two units on the CAN bus have the same CAN ID, LED no. 1 to 4 will flash quickly. In this case, press button no. 6 to jump into the CAN ID change menu and select another CAN ID for the unit.