fan inlet airflow sensing element fe-1050 series

FLOW
NEW!
FAN INLET AIRFLOW SENSING ELEMENT
FE-1050 SERIES
DESCRIPTION
The Paragon Controls FE-1050 is an airflow measuring
element assembly specifically designed for installation in the
inlet cone of centrifugal fans or inlet bell of vane-axial fans.
The design of these primary elements provides a means
of accurate measurement of fan capacity along with ease
of installation. Each assembly is complete with two airflow
measuring elements and pivot mounting hardware.
FEATURES
6
• Multiple total and static pressure sensing ports along
the length of the element
• Averaging internal manifold
• Insensitive to flow angle variations of as much as ±20°
when faced in the normal direction of flow
• ±2% accuracy throughout the velocity ranges of 100
fpm and over
FE-1050
Use this formula to calculate the differential pressure (∆ V)
for the transmitter.
V= 1096.7 ∗ √ ∆ P
SPECIFICATIONS
FLOW
Accuracy
Connections
Within 2% of actual flow when
installed in accordance with published
recommendations
1/4" compression, suitable for use
with thermoplastic or copper tubing;
thermoplastic tubing requires the use of
tubing inserts, which are supplied with the
fittings
Velocity Range
Operating Temperature
Operating Humidity
Materials Of Construction
Warranty
100 to 8,000 fpm
350°F (177°C) continuous operation
(in air)
400°F (204°C) intermittent operation
(in air)
0 to 100% RH, non-condensing
6063-T5 anodized aluminum (standard)
1 year
MOUNTING CONFIGURATION
Minimum Inlet Diameter Installation (Standard)
Mid-bell Installation
Notes:
• The FE-1050 assembly is designed to be installed at the minimum inlet diameter of any fan inlet cone not obstructed by inlet vanes
• FE-1050 elements should not be used on fan inlet applications where the minimum inlet diameter is less tahn 12 inches
• Paragon does not recommend installing FE-1050's at teh minimum inlet diameter when the velocity is greater than 8,000 fpm because the
pressure drop may affect the fan performance and if the velocity is greater than 8,000 fpm a mid-bell installation should be considered
• Mid-bell installation configuration will include 30° angle brackets and a split ring rolled to the exact diameter of the sensing plane for use as
a template to scribe the sensing plane location
• For sensing planes with the same diameter, only one split ring will be provided for use as a template on multiple fans
342
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
FAN INLET AIRFLOW SENSING ELEMENT
FE-1050 SERIES
DIMENSIONS
6
FLOW
Note: The 0.585 inch diameter probe is used for minimum fan inlets less than
or equal to 28 inches and the 1 inch diameter probe is used for minimum fan
inlets greater than 28 inches.
ORDERING INFORMATION
MODEL
FE-1050
March 2014
DESCRIPTION
Fan inlet airflow sensing element
DIMENSIONS
1
Inches
2
Millimeters
INLET CONFIGURATION
1
Single inlet (SWSI)
2
Double inlet (DWDI)
MOUNTING
CONFIGURATION
1 Minimum inlet diameter (standard)
2 Mid-bell installation
DIAMETER OF SENSING PLANE
SPECIFY
MATERIAL TYPE
1 Aluminum
WE MAKE IT EASY.
kele.com
888-397-5353 USA
343