3 Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-TOW/WOT Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kV Class 350 kV BIL IEC 60840 72,5 kV Kit Contents: 1 Silicone Rubber Lug Seal Insulator Assembly 1 Hi-K Stress Control Assembly 1 Silicone Rubber Insulator Assembly 1 Silicone Rubber Skirted Insulator Assembly 1 Pre-formed Ground Braid Assembly 3 Constant Force Springs 1 Roll Scotch® Electrical Shielding Tape 24 6 Tubes P55/R Red Compound (Non-Silicone Grease) 1 Roll Scotch® Sealing Mastic 2229, 1" (25 mm) wide 8 Strips Hi-K Mastic (1-6" × 22", 7-2" × 11") 1 Roll Scotch® Silicone Rubber Tape 70 1 Roll Scotch® Vinyl Electrical Tape Super 88, 1½" × 44' 1 6" (150 mm) Hi-K Mastic Pad 1 3M™ Cable Cleaning Pads CC-3 1 Copper Foil Tape Strip 1181, 15" long 4 Instruction Sheets Note: Do not use knives to open plastic bags. Kit Number Primary Insulation O.D. Range Jacket O.D. Range Conductor Size Range AWG (mm2) 7672-S-8 1.94"–3.08" (49.3–75.4 mm) 2.45"–3.35" (62.2–85.1 mm) 250–1000 (120–500) Table 1 3M™ Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 4APE/VER7IRE3HIELDED#ABLE for Tape Over Wire and Wire Over Tape Shielded Cable 7672-S-8-TOW/WOT 78-8126-9536-5-B 7IRE/VER4APE3HIELDED#ABLE mCAUTION Working around energized systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all electrical systems before installing product. Correct Installation of Termination 3ILICONE2UBBER 3KIRTED)NSULATOR!SSEMBLY ! " (IGH+3TRESS#ONTROL-ASTIC 3EMI#ON)NSULATION3HIELD ! 3EMI#ON )NSULATION 3HIELD 3ILICONE2UBBER 4UBULAR)NSULATOR 3ILICONE2UBBER 4UBULAR)NSULATOR 3ILICONE2UBBER 3KIRTED)NSULATOR!SSEMBLY 3ILICONE2UBBER ,UG3EAL4UBE (IGH+3TRESS #ONTROL4UBE " (IGH+3TRESS #ONTROL-ASTIC (IGH+3TRESS #ONTROL4UBE # # (IGH+3TRESS #ONTROL-ASTIC (IGH+3TRESS #ONTROL4UBE 3ILICONE2UBBER 4UBULAR)NSULATOR 3ILICONE2UBBER 3KIRTED)NSULATOR!SSEMBLY (IGH+3TRESS #ONTROL-ASTIC 3ILICONE2UBBER ,UG3EAL4UBE 3ILICONE2UBBER 4UBULAR)NSULATOR 3ILICONE2UBBER 3KIRTED)NSULATOR !SSEMBLY 78-8126-9536-5-B I. Tape-Over-Wire Shield Cable (For Wire-Over-Tape Shield, go to section II on page 8.) Note: Check to insure all of the 3M™ Termination Assemblies QT-III will fit over the lug. If the lug will not fit through the assembly cores, this termination can not be installed using this lug. Do not remove any of the cores at this time. 1.0Prepare Cable 1.1 Check to be sure the cable fits within the kit ranges as shown in Table 1. 1.2 Prepare cable using dimensions shown in Figure 1. Be sure to allow for depth of terminal lug plus 0.5" (13 mm) plus crimp growth. Note: Provide additional exposed conductor to allow for growth of aluminum lugs or connectors during crimping. Conductor Size 250–350 400–650 750–1000 1100–2000 Growth Allowance 0.25" (6 mm) 0.5" (13 mm) 0.75" (19 mm) Field Determined Table 2 MM MM MM MM MM 3EMI#ON #ABLE*ACKET #ORRUGATED4APE3HIELD Figure 1 78-8126-9536-5-B $EPTH OFLUG MM CRIMPGROWTH )NSULATION 3HIELD7IRES #ONDUCTOR 2.0Install Ground Braid Assembly 2.1 Select the pre-formed ground braid assembly from the kit. Pass the end of the cable through the ground braid assembly loop, and position the ground braid assembly around the tape shield shown. (Figure 2) 3EMI#ON #ORRUGATED4APE3HIELD )NSULATION 3HIELD7IRES #ABLE*ACKET%DGE 3OLDER"LOCK 'ROUND"RAID!SSEMBLY Figure 2 2.2 Select the 3 constant force springs from the kit. Starting at the loop of the ground braid assembly nearest the cable jacket edge, install the 3 constant force springs, one around each ground braid loop. Cinch (tighten) the springs after wrapping the final turn. Extend the ground braid tails down the cable jacket. (Figure 3) #ONSTANT&ORCE3PRING #ABLE*ACKET%DGE 3OLDER"LOCK 'ROUND"RAID!SSEMBLY Figure 3 78-8126-9536-5-B 2.3 Select the roll of 1" ( 25 mm) wide Scotch® Sealing Mastic 2229 from the kit. Cut a length of the tape long enough to wrap around the cable jacket. Remove the release liner from the mastic and, using light tension, apply a single wrap of mastic around the cable jacket, positioned under the ground braid solder blocks. (Figure 4) Semi-Con Constant Force Springs Solder Block 1st Mastic Strip (beneath solder blocks) Figure 4 2.4 Cut four 1" (25 mm) lengths of 1" ( 25 mm) wide Scotch® Sealing Mastic 2229. Remove the release liner and roll each mastic strip into a small roll. (Figure 5) Press the mastic rolls into place on either side of the ground braid solder blocks. (Figure 6) MM -ASTIC3TRIP -ASTIC2OLLED5P Figure 5 Rolled Mastic (x4) Solder Block 1st Mastic Strip (beneath solder blocks) Figure 6 78-8126-9536-5-B Semi-Con 2.5 Select the roll of 1" (25 mm) wide Scotch® Sealing Mastic 2229 from the kit and cut a length of the mastic. Using light tension, apply a single wrap of mastic around the cable jacket over the ground braid solder blocks and the previously applied mastic. Bend wires back over applied sealing mastic. (Figure 7) ND-ASTIC3TRIP OVERSOLDERBLOCKSMASTICROLLS Figure 7 2.6 Cut a third length of sealing mastic long enough to wrap over applied mastic and solder blocks. Remove the release liner from the mastic and, using light tension, apply mastic over the shield wires and previously applied mastic. (Figure 8) 2.7 Secure the shield wires and the two tails of the ground braid assembly to the cable jacket approximately 6 inches (150 mm) from the cable jacket edge with several wraps of vinyl tape. (Figure 8) MM APPROX 6INYL 4APE7RAP RD-ASTIC3TRIP OVERSHIELDWIRESPREVIOUSMASTIC Figure 8 78-8126-9536-5-B 2.8 Wrap two half-lapped layers of highly-tensioned Scotch® Vinyl Electrical Tape Super 88 over the mastic seal and constant force springs. Cover all exposed mastic, constant force springs and tape shield, overlapping 0.25" (6 mm) onto the exposed cable semi-con. (Figure 9) Note: Take care not to cover the exposed semi-con. A minimum of 2.5" (75 mm) of semi-con must be exposed. /VERLAP3EMI#ON MM #ABLE*ACKET 6INYL4APE Figure 9 2.9 Go to Step 5.0 Install Lug or Connector (page 13). 78-8126-9536-5-B %XPOSED3EMI#ON II. Wire-Over-Tape Shield Cable 3.0Prepare Cable 3.1 Check to be sure the cable fits within the kit ranges as shown in Table 1. 3.2 Prepare cable using dimensions shown in Figure 10. Be sure to allow for depth of terminal lug plus 0.5" (13 mm) plus crimp growth. Note: Provide additional exposed conductor to allow for growth of aluminum lugs or connectors during crimping. Conductor Size 250–350 400–650 750–1000 1100–2000 Growth Allowance 0.25" (6 mm) 0.5" (13 mm) 0.75" (19 mm) Field Determined Table 3 MM MM MM MM MM 3EMI#ON #ABLE*ACKET 4APE3HIELD $EPTH OFLUG MM CRIMPGROWTH )NSULATION #ONDUCTOR 3HIELD7IRES Figure 10 78-8126-9536-5-B 4.0Install Ground Braid Assembly 4.1 Fold the shield wires back along the cable jacket. Select the pre-formed ground braid assembly from the kit. Pass the end of the cable through the ground braid assembly loop, and position the ground braid assembly around the tape shield as shown. (Figure 11) 3EMI#ON )NSULATION 3HIELD7IRES 4APE3HIELD #ABLE*ACKET%DGE 3OLDER"LOCK 'ROUND"RAID!SSEMBLY Figure 11 4.2 Select the 3 constant force springs from the kit. Starting at the loop of the ground braid assembly nearest the cable jacket edge, install the 3 constant force springs, one around each ground braid loop. Cinch (tighten) the springs after wrapping the final turn. Extend the ground braid tails down the cable jacket. (Figure 12) #ONSTANT&ORCE3PRING #ABLE*ACKET%DGE 3OLDER"LOCK 'ROUND"RAID!SSEMBLY Figure 12 78-8126-9536-5-B 4.3 Select the roll of 1" ( 25 mm) wide Scotch® Sealing Mastic 2229 from the kit. Cut a length of the tape long enough to wrap around the cable jacket. Lift the ground braid tails and shield wires. Remove the release liner from the mastic and using light tension, apply a single wrap of mastic around the cable jacket positioned under the ground braid solder blocks and shield wires. (Figure 13) #ONSTANT&ORCE3PRINGS 3OLDER"LOCK ST-ASTIC3TRIP BENEATHSOLDERBLOCKSSHIELDWIRES 3HIELD7IRES Figure 13 4.4 Select the roll of 1" ( 25 mm) wide Scotch® Sealing Mastic 2229 from the kit. Cut a length of the tape long enough to wrap around the cable jacket and previously applied mastic. Fold the ground braid tails out of the way. Remove the release liner from the mastic and, using light tension, apply a single wrap of mastic around the cable jacket, positioned over the shield wires and previously applied mastic. (Figure 14) #ONSTANT&ORCE3PRINGS ND-ASTIC3TRIP OVERSHIELDWIRESPREVIOUSLYAPPLIEDMASTIC 3HIELD7IRES Figure 14 10 78-8126-9536-5-B 4.4 Cut four 1" (25 mm) lengths of 1" ( 25 mm) wide Scotch® Sealing Mastic 2229. Remove the release liner and roll each mastic strip into a small roll. (Figure 15) Press the mastic rolls into place on either side of the ground braid solder blocks. (Figure 16) MM -ASTIC3TRIP -ASTIC2OLLED5P Figure 15 2OLLED-ASTICX 3OLDER"LOCK ND-ASTIC3TRIP BENEATHSOLDERBLOCKS Figure 16 4.6 Cut a third length of sealing mastic long enough to wrap over applied mastic and solder blocks. Remove the release liner from the mastic and, using light tension, apply mastic over the shield wires and previously applied mastic. (Figure 17) 4.7 Secure the shield wires and the two tails of the ground braid assembly to the cable jacket approximately 6 inches (150 mm) from the cable jacket edge with several wraps of vinyl tape. (Figure 17) MM APPROX 6INYL 4APE7RAP RD-ASTIC3TRIP OVERSOLDERBLOCKSPREVIOUSMASTIC Figure 17 78-8126-9536-5-B 11 4.8 Wrap two half-lapped layers of highly-tensioned Scotch® Vinyl Electrical Tape Super 88 over the mastic seal and constant force springs. Cover all exposed mastic, constant force springs and tape shield, overlapping 0.25" (6 mm) onto the exposed cable semi-con. (Figure 18) Note: Take care not to cover the exposed semi-con. A minimum of 2.5" (75 mm) of semi-con must be exposed. /VERLAP3EMI#ON MM #ABLE*ACKET 6INYL4APE %XPOSED3EMI#ON Figure 18 5.0Install Lug or Connector 5.1 Position lug/connector and crimp according to manufacturer’s directions. Remove excess oxide inhibitor and sharp crimp flashing following crimping. Refer to page 19 for 3M lug/connector crimping information up to 1000 kcmil. 6.0Clean Cable Insulation and Lug Barrel Using Standard Practice 6.1 Use only aluminum oxide abrasive to finish and polish insulation surface. 6.2 Use abrasive only on cable insulation. Do not use on semi-con. 6.3 When using abrasive, do not reduce the cable insulation diameter below that allowed by the kit. 6.4 Wipe the cable insulation clean with an approved solvent. Do not allow the solvent to touch semi-con insulation shield. Note: Remove any remaining solvent with 3M™ CC-DRY Cable Cleaning Pads (not supplied with kit) or lint-free cloth. 12 78-8126-9536-5-B 7.0Install Termination 7.1 Select the large hi-K mastic pad from the kit. Remove the liners and align the pad with 1" (25 mm) covering the semi-con, and 5" (127 mm) covering the cable insulation. Using light tension, wrap the pad around the cable insulation two times. Trim the pad to overlap the start by approximately 0.25" (6 mm). Taper the pad edge by gently pressing along the edge with your finger. (Figure 19) (I+-ASTIC0AD 3EMI#ON #ABLE)NSULATION MM MM (I+-ASTIC0AD ,AYERS #ABLE)NSULATION 4APER%DGE Figure 19 7.2 Wrap two half-lapped layers of highly-tensioned Scotch® Vinyl Electrical Tape Super 88 over the hi-K mastic pad, leaving approximately 0.125" (3 mm) of mastic exposed at each end. Taper the exposed edges of the hi-K mastic onto the cable by gently pressing along the edge with your finger. (Figure 20) MM 3EMI#ON 4APER%DGEOF (I+-ASTIC MM 4APER%DGEOF (I+-ASTIC 6INYL 4APE Figure 20 78-8126-9536-5-B 13 )NSULATION 7.3 Starting 5" (127 mm) from the cut end of the insulation, apply 2 tubes of P55/R Red Compund (non-silicone grease) over exposed insulation and vinyl tape-wrapped mastic pad. (Figure 21) #OATWITH 022ED#OMPOUND MM Figure 21 7.4 Select the Stress Control Assembly (medium length tubular assembly on white core) from the kit. Slide the Stress Control Assembly over the lug and cable with the loose core end toward the lug. Align the Stress Control Assembly Tube (not the core) with the end of the tape shield, and remove the core by pulling the loose end while unwinding counter-clockwise. Clean exposed cable insulation after installation. (Figure 22) Unwind counter-clockwise Align with step in semi-con portion of insulation adapter tube Cable Jacket Stress Control Assembly Figure 22 7.5 Select one 2' x 11" (50 mm x 280 mm) hi-K mastic strip from the kit. Remove the liners and wrap around the end of the stress control assembly and cable insulation. Position the hi-K mastic so that half covers the stress control assembly, and half covers the cable insulation. (Figure 23) #ABLE)NSULATION (I+-ASTIC 3TRESS#ONTROL!SSEMBLY4UBE Figure 23 14 78-8126-9536-5-B 7.6 Wrap two half-lapped layers of highly-tensioned Scotch® Vinyl Electrical Tape Super 88 over the hi-K mastic, leaving approximately 0.125" (3 mm) of mastic exposed at each end. Taper the exposed edges of the hi-K mastic onto the cable by gently pressing along the edge with your finger. (Figure 24) MM MM #ABLE)NSULATION 3TRESS#ONTROL !SSEMBLY4UBE 4APER%DGEOF (I+-ASTIC 4APER%DGEOF (I+-ASTIC 6INYL 4APE Figure 24 7.7 Select one or more of the 2" x 11" (50 mm x 280 mm) hi-K mastic strips from the kit. Remove the liner and fold the mastic strip twice lengthwise to form a 0.5" (12 mm) wide strip. (Figure 25) 2EMOVE,INER (I+-ASTIC -ASTIC&OLDED /VER4WICE Figure 25 7.8 Wrap the mastic strip around the exposed conductor between the cable insulation and lug. Build the mastic up to the insulation O.D. (Figure 26) $OUBLED/VER (I+-ASTIC Figure 26 78-8126-9536-5-B 15 7.9 Apply additional wrap(s) of hi-K mastic (not folded) onto the cable insulation for 1" (25 mm) and taper the hiK mastic 2" (50 mm) onto the lug barrel. (Figure 27) When using a tapered barrel lug, extend the hi-K mastic onto the barrel 2" (50 mm) past the tapered part of the barrel. (Figure 27) MM MM MM MM (I+-ASTIC 4YPICAL,UG 4APERED,UG Figure 27 7.10 Select the roll of Scotch® Silicone Rubber Tape 70 from the kit. Using moderate tension, wrap 2 half-lapped layers of tape over the hi-K mastic, leaving approximately 0.125" (3 mm) of mastic exposed at each end. Taper the exposed edges of the hi-K mastic onto the cable by gently pressing along the edge with your finger. (Figure 28) MM #ABLE)NSULATION 3TRESS#ONTROL !SSEMBLY4UBE MM 4APER%DGEOF (I+-ASTIC 4APER%DGEOF (I+-ASTIC 3COTCH¤3ILICONE2UBBER4APE Figure 28 7.11 Apply 1 tube of P/55R Red Compound (non-silicone grease) 2" (50 mm) over the lug seal area and onto the cable insulation for approximately 4 inches (100 mm). (Figure 29) #OATWITH 022ED#OMPOUND 3TRESS#ONTROL !SSEMBLY4UBE MM MM Figure 29 16 78-8126-9536-5-B 7.12 Select the Silicone Rubber Lug Seal Insulator from the kit. Slide the lug seal insulator onto the cable insulation with the loose core end toward the cable insulation. Position the lug seal insulator (not the core) 2" (50 mm) onto the lug barrel. Remove the core by pulling the loose core end while unwinding counter-clockwise. (Figure 30) 5NWINDCOUNTERCLOCKWISE MM 3TRESS#ONTROL!SSEMBLY4UBE ,UG 3ILICONE2UBBER ,UG3EAL)NSULATOR Figure 30 7.13 Apply 3 tubes of P55/R Red Compound to the exposed cable insulation and hi-K stress control assembly tube. Fill the bottom edge of the silicone rubber lug seal the the P55/R Red Compound. Do not apply P55/R Red Compound to the surface of the lug seal insulator. (Figure 31) Coat with P55/R Red Compound Stress Control Assembly Tube Fill step with P55/R Red Compound Figure 31 78-8126-9536-5-B 17 Lug Seal Assembly Tube DO NOT GREASE 3M is a trademark of 3M Company. Scotch is a registered trademark of 3M Company. Important Notice All statements, technical information, and recommendations related to 3M’s products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed. Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability associated with such use. Any statements related to the product which are not contained in 3M’s current publications, or any contrary statements contained on your purchase order shall have no force or effect unless expressly agreed upon, in writing, by an authorized officer of 3M. Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture for a period of one (1) year from the time of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M’s option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be liable for any indirect, special, incidental or consequential loss or damage arising from this 3M product, regardless of the legal theory asserted. Electrical Markets Division 6801 River Place Blvd. Austin, TX 78726-9000 800-245-3573 Fax 800-245-0329 www.3M.com/electrical Please recycle Litho in USA © 3M 2006 78-8126-9536-5-B
© Copyright 2026 Paperzz