CD-LV-F1 CIRCULAR DISSIPATIVE LOW VELOCITY SILENCER (<1500 FPM) HOW TO SPECIFY: EXAMPLE SILENCER SHEETS 24 X CD-LV-F1 X 72 Silencer Duct Connection Model Size Insertion Loss (IL) + : “forward flow” where noise & airflow move in same direction (e.g. supply side) - : “reverse flow” where noise & airflow move in opposite directions (e.g. return side) DC (in.) SL (in.) (ft. per min.) FACE VEL. 12 24 0 24 48 36 72 48 96 60 120 - 1000 + 1000 DC (in.) SL (in.) (ft. per min.) 7 12 36 0 24 72 36 108 48 144 60 180 11 18 28 39 44 43 31 7 11 16 26 35 42 43 31 33 45 46 11 17 27 37 - 1000 7 12 25 34 + 1000 7 12 23 32 43 10 17 29 40 45 0 7 - 1000 10 + 1000 10 0 12 24 17 30 17 28 21 15 46 43 44 39 13 23 36 23 24 37 0 13 38 43 33 + 1000 20 44 21 23 35 35 12 13 45 37 + 1000 - 1000 20 43 36 35 45 43 45 31 35 39 21 12 43 47 39 12 41 47 43 47 - 1000 0 DC - Duct Connection Size (inches) SL - Silencer Length (inches) OCTAVE BAND - Hz/D.I.L. (dB) 63 125 250 500 1000 2000 4000 8000 7 35 24 15 19 14 34 19 41 32 19 41 29 17 30 28 15 24 45 33 20 14 14 17 13 17 13 13 Silencer Length FACE VEL. - 1000 + 1000 OCTAVE BAND - Hz/D.I.L. (dB) 63 125 250 500 1000 2000 4000 8000 8 15 26 8 15 24 8 15 25 41 40 39 57 60 60 46 53 60 60 46 55 60 DUCT SILENCER SILENCER CONNECT. OUTER LENGTH WEIGHT SIZE (in.) DIA. (in.) (in.) (lbs) 12 12 24 24 36 36 48 48 60 28 28 40 40 52 52 64 64 76 24 36 48 72 72 108 96 144 126 164 363 487 726 995 1233 1689 10 18 38 49 60 60 49 29 + 1000 10 18 36 47 59 58 49 29 13 24 0 10 - 1000 13 + 1000 13 0 18 37 48 60 56 36 23 24 41 56 59 54 36 23 52 59 59 49 29 57 53 + 1000 18 32 51 58 54 60 32 - 1000 18 33 55 + 1000 18 33 53 18 33 120 1890 500 1000 1500 2000 2500 3000 0.02 0.08 0.19 0.33 0.52 0.74 0.09 0.15 0.08 0.13 0.09 0.12 0.08 0.10 0.20 0.33 0.19 0.29 0.20 0.27 0.19 0.23 0.36 0.59 0.33 0.51 0.36 0.48 0.33 0.42 0.57 0.92 0.52 0.80 0.57 0.74 0.52 0.65 0.82 1.33 0.74 1.15 0.82 1.07 0.74 0.94 60 76 180 2599 0.03 0.10 0.23 0.40 0.63 0.90 Pressure drops are reported in accordance with ASTM E477 methods and are based upon IDEAL flow conditions (5 diameters of straight duct on silencer inlet and 10 on outlet). Less than ideal conditions will result in an increase in pressure drop due to System Effects. See Silencer System Effects Data on page 4.19. Generated Noise (GN) @ 3 sq.ft. face area LENGTH FACE VELOCITY (inches) (feet per minute) ALL - 1500 - 1000 + 1000 + 1500 GN correction chart at right must be used to correct GN to other face areas. OCTAVE BAND - Hz/GENERATED NOISE (dB re 10 -12 watts) 63 125 250 500 1000 2000 4000 59 54 53 58 52 47 46 51 FACE AREA (sq.ft.) Questions? 1-800-565-8401 dB We reserve the right to improve our designs and data at any time without notice. 44 39 39 44 1.5 -3 43 38 37 42 3 0 5.143 45 40 37 42 6 +3 47 42 39 44 12 +6 44 39 37 42 24 +9 29 58 43 32 0 49 44 18 18 59 24 - 1000 0 60 60 60 60 57 55 50 43 26 44 60 57 42 3500 1.11 1.81 1.01 1.56 1.11 1.46 1.01 1.28 29 29 60 59 36 48 60 FACE VELOCITY (feet per minute) / Pressure Drop (in.w.g.) 0.02 0.04 0.02 0.03 0.02 0.03 0.02 0.03 46 - 1000 See pages 4.1 - 4.25 for selection information. DIL above 50dB may be limited due to noise flanking around the silencer or along the duct walls. If more than 50dB DIL is required, contact your local Vibro-Acoustics Representative or call 1-800-565-8401. Pressure Drop (PD) 60 23 21 21 21 26 20 26 20 20 : Acceptable (0 - 0.35”) : Caution (>0.35”) Pressure Drop may be too high for certain applications 1.01 1.23 8000 42 37 35 40 48 +12 Copyright © 2010 Vibro-Acoustics CD-LV-F1 CD-LV-F2 CIRCULAR DISSIPATIVE LOW VELOCITY SILENCER (<1500 FPM) HOW TO SPECIFY: EXAMPLE SILENCER SHEETS 24 X CD-LV-F2 X 72 Silencer Duct Connection Model Size Insertion Loss (IL) + : “forward flow” where noise & airflow move in same direction (e.g. supply side) - : “reverse flow” where noise & airflow move in opposite directions (e.g. return side) DC (in.) SL (in.) 12 24 24 48 36 72 48 96 60 120 FACE VEL. OCTAVE BAND - Hz/D.I.L. (dB) 125 250 500 1000 2000 4000 8000 (ft. per min.) 63 - 1000 4 7 + 1000 4 7 0 - 1000 0 + 1000 - 1000 0 + 1000 - 1000 0 + 1000 4 4 4 4 16 28 39 44 43 31 14 26 35 42 43 31 33 45 7 15 8 22 34 20 32 43 25 40 45 8 21 8 6 11 26 6 11 24 7 14 6 7 7 11 14 31 14 27 41 39 45 30 44 29 43 37 47 47 43 45 43 41 43 35 20 45 35 20 38 24 15 39 37 + 1000 8 15 30 44 39 28 41 14 17 30 45 19 29 43 15 15 19 46 20 24 32 33 32 31 24 19 15 15 35 34 8 8 31 47 46 - 1000 0 43 17 13 12 36 24 72 108 48 14 13 SL (in.) 36 14 17 DC (in.) 13 144 60 180 Silencer Length DC - Duct Connection Size (inches) SL - Silencer Length (inches) FACE VEL. OCTAVE BAND - Hz/D.I.L. (dB) 125 250 500 1000 2000 4000 8000 (ft. per min.) 63 - 1000 5 + 1000 5 0 - 1000 5 10 10 10 6 12 23 22 41 40 60 46 60 59 49 29 33 49 48 - 1000 8 16 38 58 8 16 - 1000 11 21 + 1000 8 16 0 11 21 - 1000 11 22 + 1000 0 + 1000 11 21 11 22 11 22 31 37 36 46 45 DUCT SILENCER SILENCER CONNECT. OUTER LENGTH WEIGHT SIZE (in.) DIA. (in.) (in.) (lbs) 12 12 24 24 36 36 48 48 20 20 32 32 44 44 56 56 60 68 60 68 24 36 48 72 72 108 96 144 87 114 279 379 589 798 1026 1416 120 1589 180 2232 0.02 0.04 0.02 0.03 0.02 0.03 0.02 0.03 0.02 0.03 1000 1500 0.08 0.19 0.09 0.15 0.08 0.13 0.09 0.12 0.08 0.10 0.10 0.20 0.33 0.19 0.29 0.20 0.27 0.19 0.23 0.23 2000 0.36 0.59 0.33 0.51 0.36 0.48 0.33 0.42 0.33 0.40 2500 49 29 57 60 55 36 23 60 60 50 29 56 59 56 54 59 59 60 60 44 57 42 47 60 0.57 0.92 0.52 0.80 0.57 0.74 0.52 0.65 0.52 0.63 3000 0.82 1.33 0.74 1.15 0.82 1.07 0.74 0.94 0.74 0.90 Pressure drops are reported in accordance with ASTM E477 methods and are based upon IDEAL flow conditions (5 diameters of straight duct on silencer inlet and 10 on outlet). Less than ideal conditions will result in an increase in pressure drop due to System Effects. See Silencer System Effects Data on page 4.19. Generated Noise (GN) @ 3 sq.ft. face area LENGTH FACE VELOCITY (inches) (feet per minute) ALL - 1500 - 1000 + 1000 + 1500 GN correction chart at right must be used to correct GN to other face areas. OCTAVE BAND - Hz/GENERATED NOISE (dB re 10 -12 watts) 63 125 250 500 1000 2000 4000 59 54 53 58 52 47 46 51 FACE AREA (sq.ft.) Questions? 1-800-565-8401 dB We reserve the right to improve our designs and data at any time without notice. 44 39 39 44 1.5 -3 43 38 37 42 3 0 5.144 45 40 37 44 6 +3 47 42 39 42 12 +6 44 39 37 42 24 +9 29 58 60 60 57 59 FACE VELOCITY (feet per minute) / Pressure Drop (in.w.g.) 500 49 59 58 46 60 47 44 48 60 49 3500 1.11 1.81 1.01 1.56 1.11 1.46 1.01 1.28 36 36 29 48 29 43 26 See pages 4.1 - 4.25 for selection information. DIL above 50dB may be limited due to noise flanking around the silencer or along the duct walls. If more than 50dB DIL is required, contact your local Vibro-Acoustics Representative or call 1-800-565-8401. Pressure Drop (PD) 46 60 32 0 46 60 53 12 12 60 60 39 6 6 60 21 0 + 1000 57 55 23 23 21 21 21 26 20 26 20 20 : Acceptable (0 - 0.35”) : Caution (>0.35”) Pressure Drop may be too high for certain applications 1.01 1.23 8000 42 37 35 40 48 +12 Copyright © 2010 Vibro-Acoustics CD-LV-F2
© Copyright 2026 Paperzz