EXTERIOR WALL ASSEMBLY PREAMBLE EXCERPT FROM ARTICLE BY JOSEPH LSTIBUREK Ph.D., P.Eng., is a principal of Building Science Corporation in Westford, Massachusetts. He has twenty-five years of experience in design, construction, investigation, and building science research. Joe is an ASHRAE Fellow and an internationally recognized authority on indoor air quality, moisture, and condensation in buildings. Joseph Lstiburek, Air Barriers vs. Vapor Barriers The key to moisture control is the control of air transported moisture. There is a big difference between air transported moisture and vapor diffusion. Proponents of vapor barrier systems tend to confuse these two transport mechanisms, do they control the vapor diffusion part, the air transport part or both? It is not always clear. What is clear is that air transport is far more significant than vapor diffusion. What is also clear is that you do not need a 6-mil polyethylene barrier to control air transported moisture.The key point that needs to be made is that although air barriers are a good idea everywhere, vapor barriers are not. Moisture flow by vapor diffusion is governed by the second law of thermodynamics. Moisture will flow by diffusion because of a concentration gradient as well as a temperature gradient (from "more to less" as well as "from warm to cold"). This means that it tends to go from the inside out up north and from the outside in down south. In the middle of the country part of the year it goes from inside out and part of the year it goes from outside in. You certainly do not want to put a vapor barrier on both sides of the wall. It's pretty obvious that you do not want a vapor barrier at all in most assemblies in mixed climates. "Flow-through" design makes more sense in mixed climates where vapor diffusion is slowed down, but not stopped. Hence, the term vapor retarders. Maybe we should use an insulating sheathing that is vapor semi-permeable on the outside with sufficient thermal resistance to elevate the temperature of the condensing surface during the heating season, and have a vapor permeable interior finish to permit drying to the interior? One of the problems in the building industry is that it still views the answer to all moisture problems as the installation of a polyethylene vapor barrier on the inside of buildings. This is responsible for many more building failures than building successes. BRITISH COLUMBIA BUILDING CODE REFERENCES PART 9 9.25.1. Scope 9.25.1.1. Application 1) This Section applies to thermal insulation and measures to control heat transfer, air leakage and condensation. 2) Insulation and sealing of heating and ventilating ducts shall conform to Sections 9.32. and 9.33. 9.25.1.2. General (See Appendix A.) 1) Sheet and panel-type materials shall be installed in accordance with Sentence (2), if the material a)has an air leakage characteristic less than 0.1 L/(s•m2) at 75 Pa, b)has a water vapour permeance less than 60 ng/(Pa•s•m2) when measured in accordance with ASTM E 96, “Water Vapor Transmission of Materials,” using the desiccant method (dry cup), and c)is incorporated into a building assembly required by Article 9.25.2.1. to be insulated. 2) Sheet and panel-type material described in Sentence (1) shall be installed a)on the warm face of the assembly (see also Article 9.25.4.2.), ROL FIELDWALKER architect # 408, 611 Alexander St. Vancouver, B.C. V6A 1E1 Tel: 604-813-6044 Fax: 604-266-8842 Email: rol@rolf ieldwalker.com PAGE 1 EXTERIOR WALL ASSEMBLY BRITISH COLUMBIA BUILDING CODE REFERENCES b)except as provided in Sentences (3) to (5), at a location where the ratio between the total thermal resistance of all materials outboard of its innermost impermeable surface and the total thermal resistance of all materials inboard of that surface is not less than that required by Table 9.25.1.2., or c)outboard of an air space that is vented to the outdoors and, for walls, drained. 3) Wood-based sheathing materials not more than 12.5 mm thick and complying with Article 9.23.16.2. need not comply with Sentence (1). 4) Where the mild climate indicator, determined in accordance with Sentence (6), is greater than 6 300, the position of low air- and vapour-permeance materials within the assembly relative to the position of materials providing thermal resistance shall be determined according to Part 5, where a)the intended use of the interior space requires the indoor relative humidity to be maintained above 35% over the heating season and the ventilating and air-conditioning system is designed to maintain that relative humidity, or b)the intended use of the interior space will result in an average monthly indoor relative humidity above 35% over the heating season and the ventilating and air-conditioning system does not have the capacity to reduce the average monthly relative humidity to 35% for any period over that period. 5) W here the mild climate indica tor, determined in accordance with S entence (6), is less than or equal to 6 300, the position of low a ir- and vapour-permeance ma teria ls within the a ssembly relative to the position of ma teria ls providing therm al resistance shall be determined a ccording to P art 5, where a)the intended use of the interior space requires the indoor rela tive hum idity to be m aintained above 60% over the hea ting sea son and the ventila ting and air-conditioning system is designed to ma inta in that rela tive humidity, or b)the intended use of the interior space will result in a n average monthly indoor rela tive humidity a bove 60% over the hea ting sea son and the ventila ting and air-conditioning system does not ha ve the capacity to reduce t he avera ge monthly relative humidity to 60% over tha t period. 6) The mild clima te indicator (M C I) sha ll be ca lculated a ccording to the following formula: M C I= a bs(2.5% JM T) x 200 + D D , where abs (2.5% J M T) DD = absolute value of 2.5% Ja nuary mean tempera ture, and = degree-da ys F or Lions B a y: M C I= (2.5% x19) x200 + 3000 M C I = (.475 x 200) + 3000 = 3095 MILD CLIMATE INDICATOR (MCI) FOR LIONS BAY IS 3095 ROL FIELDWALKER architect # 408, 611 Alexander St. Vancouver, B.C. V6A 1E1 Tel: 604-813-6044 Fax: 604-266-8842 Email: rol@rolf ieldwalker.com PAGE 2 EXTERIOR WALL ASSEMBLY BRITISH COLUMBIA BUILDING CODE REFERENCES Table 9.25.1.2. Ratio of Outboard to Inboard Thermal Resistance Forming Part of Sentence 9.25.1.2.(2) Heating Degree-Days of Building Location(1), Celsius degree-days up to 4 999 Minimum Ratio, Total Thermal Resistance Outboard of Material's Inner Surface to Total Thermal Resistance Inboard of Material's Inner Surface 5 000 to 5 999 0.20 0.30 6 000 to 6 999 0.35 7 000 to 7 999 0.40 8 000 to 8 999 0.50 9 000 to 9 999 0.55 10 000 to 10 999 0.60 11 000 to 11 999 0.65 12 000 or higher 0.75 ( Lions Bay has 3000 Heating Degree Days, therefore the ratio outboard to inboard thermal resistance required is 20%) Architect's Note: From the above code references in PART 9 : None of the conditions regarding Reletive Humidity described in sentence 9.25.1.2.5 apply to this project in Lions Bay BC. Lions Bay is a location with 3000 Heating Degree Days, and the RH of the interior is expected to be maintained at approx. 50% by the ventilating and air conditioning system. The amount of thermal resistance outboard of the low permeance materials in the wall assembly relative to the thermal resistance inboard required by the Part 9 criteria is a ratio of 20% , the proposed wall has a ratio of approx. 56%, and more than satisfies the BCBC 2006. The exterior wall assembly proposed, and the amount and location of the thermal resistance in the wall, has been designed by the principals for exterior wall design outlined in PART 5, and PART 5 -APPENDIX A of the BCBC 2006. ROL FIELDWALKER architect # 408, 611 Alexander St. Vancouver, B.C. V6A 1E1 Tel: 604-813-6044 Fax: 604-266-8842 Email: rol@rolf ieldwalker.com PAGE 3 EXTERIOR WALL ASSEMBLY BRITISH COLUMBIA BUILDING CODE REFERENCES 5.5.1. Vapour Barriers 5.5.1.1. Required Resistance to Vapour Diffusion (See Appendix A.) 1) Where a building component or assembly is subjected to differentials in temperature and water vapour pressure,the properties and position of the materials and components in those components or assemblies shall be such that they control vapour diffusion or permit venting to the exterior so as to minimize the accumulation of condensation in the building component or assembly. PART 5-APPENDIX A -DIVISION B A-5.3.1.2.(1) Use of Thermal Insulation or Mechanical Systems for Environmental Control. Where the exterior design temperature is mild, such as in south coastal British Columbia, the interior RH during the heating season may well be around 55%. With an exterior temperature of -7°C (19.4F), the materials in the environmental separator would have to provide a mere RSI 0.082 ( R=.46 /1/2" plywood) to avoid condensation on the interior surface. Depending on the specific properties of the material, this RSI might be provided by 10-mm plywood. Therefore, materials generally recognized as thermal insulation would not be required only to limit condensation on the warmer side of the building envelope The word “minimize” is used in Sentence 5.5.1.1.(1) because not all moisture accumulation in an assembly need be of concern. Incidental condensation is normal but should be sufficiently rare and in sufficiently limited quantities, and should dry rapidly enough, to avoid material deterioration and the growth of mould or fungi. A-5.5.1.2.(1) Vapour Barrier Materials and Installation. In the summer, many buildings are subject to conditions where the interior temperature is lower than the exterior temperature. Vapour transfer during these periods is from the exterior to the interior. In general, in Canada, the duration of these periods is sufficiently short, the driving forces are sufficiently low, and assemblies are constructed such that any accumulated moisture will dissipate before deterioration will occur. Architect's Note: For comparing the dew point locations of various exterior wall assemblies an interior design temperature of 70F with a relative humudites of 60%, 50%, and 30%; and an outside design temperture of 19F have been utilized to calculate the dewpoint locations in Diagram #1, #2, #3. With these conditions the dew point falls inside the stud space, inside the interior face of the plywood sheathing for all the code conforming configurations shown. These values have been assigned in accordance with ASHRAE standards. In Diagram #4, the indoor relative humidity is assumed to be 50%, which can be maintened by the air conditioning system proposed for the project, and the average outdoor tempertature in January in Vancouver of 39F. from the National Research Council Canadian Building Digest "Humidity in Canadian Buildings", by N.B. Hutcheons. With these conditions the dew point in the project wall asembly falls outside the plywood sheathing. ROL FIELDWALKER architect # 408, 611 Alexander St. Vancouver, B.C. V6A 1E1 Tel: 604-813-6044 Fax: 604-266-8842 Email: rol@rolf ieldwalker.com PAGE 4 EXTERIOR WALL ASSEMBLY DEW POINT DIAGRAMS 65 60 RH AT 60% / DEW POINT = 55 F 55 RH AT 50% / DEW POINT = 50 F 50 45 40 TEMPERATURE GRADIENT THRU WALL ASSEMBLY / WINTER HEATING SEASON 30 AIR BARRIER MEMBRANE / MOISTURE BARRIER "DOW WEATHERMATE PLUS HOUSEWRAP" 60 55 50 RH AT 60% / DEW POINT = 55 F TEMPERATURE GRADIENT THRU WALL ASSEMBLY / WINTER HEATING SEASON RH AT 50% / DEW POINT = 50 F RH AT 30% / DEW POINT = 37 F 35 30 PVC VAPOUR BARRIER HERE 6 MIL PVC VAPOUR BARRIER 25 MOISTURE BARRIER / 2 LAYERS 30 MIN BLDG. PAPER OVER PLYWOOD SHEATHING 20 15 10 0 65 40 25 5 70 F 45 RH AT 30% / DEW POINT = 37 F 35 TEMPERATURE GRADIENT THRU WALL ASSEMBLY /SUMMER COOLING SEASON INSIDE VENTED 1/2" AIR SPACE 70 F 1/2" PLYWOOD SHEATHING GYPSUM B'D. R 3.8 OUTBOARD INSUL.= 20% R19 INBOARD INSUL INSIDE 1/2" PLYWOOD SHEATHING In the summer with air conditioning, outside temp. at 70F, and inside temp. at 65F, TEMPERATURE GRADIENT THRU WALL RH at 60%, the Dew Point is ASSEMBLY /SUMMER COOLING SEASON approx. 10F below the temperature inside the wall, indicating no condensation will occur during the cooling season. VENTED 1/2" AIR SPACE GYPSUM B'D. R 19 "BATT INSULATION IN 2X6 STUD SPACE WALL COMPONANTS TO SCALE OF THE R VALUE OF THE INSULATION Residence at Lions Bay BC. showing dew points for standard insulated 2x6 wall with vapour barrier on inside face of studs Int. Temp 70F / RH 60% / RH55% RH 30%, Outside Design Temp 19F. DEW POINT DIAGRAM #1 WALL ASSEMBLY / DIAGRAM #1 1/2" GYPSUM BOARD 6 MIL VAPOUR BARRIER R-19 BATT INSULATION 1/2" PLYWOOD SHEATHING 2 LAYERS 30 MINUTE BLDG. PAPER 1/2" VENTED AIR SPACE 3/4" CEDAR CLADDING OUTSIDE DESIGN TEMP @ 19 F 20 15 10 6 "BATT INSULATION / R 19 IN 2X6 STUD SPACE 5 0 OUTSIDE DESIGN TEMP @ 19 F MOISTURE BARRIER / ALUMINUM FOIL ON OUTSIDE FACE OF THERMAX INSULATION WALL COMPONANTS TO SCALE OF THE R VALUE OF THE INSULATION Residence at Lions Bay BC. Int. Temp 70F / Outside Design Temp 19F/ 20% of the insulation is outboard of the low permeance barrier (plywood) as per BCBC requirements. DEW POINT DIAGRAM #2 WALL ASSEMBLY / DIAGRAM #2 1/2" GYPSUM BOARD 6 MIL VAPOUR BARRIER R-19 BATT INSULATION 1/2" PLYWOOD SHEATHING R 3.8 INSULATION 2 LAYERS 30 MINUTE BLDG. PAPER 1/2" VENTED AIR SPACE 3/4" CEDAR CLADDING Architect's Note: Both the assemblies shown in diagram #2 and #3 conform to the BCBC 2006, with a 6mil poly. vapour barrier on the inside face of studs, a min. R 20 rating for the assembly, and a 1/2" ( 10 mm) vented air space between the 2 layers of building paper on the plywood sheathing and the cladding. Both of these assemblies result in the dew points for varying reletive humidities of 60%, 50%, and 30% falling inside the stud space, for the design temperatures of 70F inside and 19F outside. If the interior vapour/air barrier has openings that allow air transported moisture, or water vapour into the stud space, condensation will occur inside the extrior wall. With the interior poly. vapor/air barrier on the inside face of the wall it is difficult for this moisture to dry to the inside. The plywood is a reletively good air/vapour barrier on the outside face, and prevents drying in this direction. It is a difficult challenge to construct a fully functioning interior air/vapour barrier, and there is likely to be some moisture in the studs and plywood from rain during construction. This moisture in the wood should be reduced to 17% before interior finshes are intalled. ROL FIELDWALKER architect # 408, 611 Alexander St. Vancouver, B.C. V6A 1E1 Tel: 604-813-6044 Fax: 604-266-8842 Email: rol@rolf ieldwalker.com PAGE 5 EXTERIOR WALL ASSEMBLY DEW POINT CALCULATIONS 1/2" PLYWOOD SHEATHING GYPSUM B'D. INSIDE INSIDE 70 F 70 F 65 50 45 40 25 TEMPERATURE GRADIENT THRU WALL ASSEMBLY / WINTER HEATING SEASON 10 50 BY CALCULATION THE TEMP AT THE INSIDE FACE OF PLYWOOD IS 41.43 F RH AT 30% / DEW POINT = 37 F MOISTURE BARRIER / ALUMINUM FOIL ON OUTSIDE FACE OF THERMAX INSULATION RH AT 60% / DEW POINT = 55 F DEW POINT = 50F / RH AT 50% TEMPERATURE GRADIENT THRU WALL ASSEMBLY / WINTER HEATING SEASON BY CALCULATION THE TEMP AT THE INSIDE FACE OF PLYWOOD IS 52.64 F 35 NO ADDITIONAL PVC VAPOUR BARRIER HERE / THIS STUD SPACE TO BE ABLE TO DRY TO THE INTERIOR TAPED 1/2" GYPSUM B'D., PAINTED. OUTSIDE DESIGN TEMP AVG FOR JAN VAN. @ 39 F 20 15 1.5 "THERMAX EXTERIOR INSULATION/ R 10 5 AIR BARRIER MEMBRANE / MOISTURE BARRIER "DOW WEATHERMATE PLUS HOUSEWRAP" 40 25 OUTSIDE DESIGN TEMP @ 19 F 3.5 "BATT INSULATION / R 13 IN 2X6 STUD SPACE 45 30 NO ADDITIONAL PVC VAPOUR BARRIER HERE / THIS STUD SPACE TO BE ABLE TO DRY TO THE INTERIOR TAPED 1/2" GYPSUM B'D., PAINTED. 20 15 55 RH AT 50% / DEW POINT = 50 F 35 30 60 MOISTURE BARRIER / ALUMINUM FOIL ON OUTSIDE FACE OF THERMAX INSULATION RH AT 60% / DEW POINT = 55 F VENTED 1/2" AIR SPACE 55 65 AIR BARRIER MEMBRANE / MOISTURE BARRIER "DOW WEATHERMATE PLUS HOUSEWRAP" 60 1/2" PLYWOOD SHEATHING In the summer with air conditioning, outside temp. at 70F, and inside temp. at 65F, RH at 60%, the Dew Point is approx. 10F below the temperature inside the wall, indicating no condensation will occur during the cooling season. TEMPERATURE GRADIENT THRU WALL ASSEMBLY /SUMMER COOLING SEASON VENTED 1/2" AIR SPACE GYPSUM B'D. 10 3.5 "BATT INSULATION / R 13 IN 2X6 STUD SPACE 1.5 "THERMAX EXTERIOR INSULATION/ R 10 5 0 0 WALL COMPONANTS TO SCALE OF THE R VALUE OF THE INSULATION Maryniak Residence at 160 mountain Drive Lions Bay BC. Int. Temp 70F / RH 60% / Outside Design Temp 19F DEW POINT DIAGRAM #3 WALL ASSEMBLY / DIAGRAM #3 1/2" GYPSUM BOARD R-12 BATTINSULATION 1/2" PLYWOOD SHEATHING R-10 "THERMAX" INSUL. WITH BONDED ALUMINUM FACE/ TAPED JOINTS "WEATHERMATE" HOUSEWRAP/ AIR BARRIER/ MOISTURE RETARDER 1/2" VENTED AIR SPACE 3/4" CEDAR CLADDING WALL COMPONANTS TO SCALE OF THE R VALUE OF THE INSULATION Maryniak Residence at 160 mountain Drive Lions Bay BC. Int. Temp 70F / RH 50% / Outside Design Temp 39 F DEW POINT DIAGRAM #4 WALL ASSEMBLY / DIAGRAM #3 1/2" GYPSUM BOARD R-12 BATTINSULATION 1/2" PLYWOOD SHEATHING R-10 "THERMAX" INSUL. WITH BONDED ALUMINUM FACE/ TAPED JOINTS "WEATHERMATE" HOUSEWRAP/ AIR BARRIER/ MOISTURE RETARDER 1/2" VENTED AIR SPACE 3/4" CEDAR CLADDING Architect's Note: For the proposed wall assembly shown in Diagrams #3,,an interior design temperature of 70F and an outside design temperture of 19F have been utilized to calculate the dewpoints . These parameters are the extreme conditions that may occur briefly on rare occasions. With these conditions the dew point for interior Relative Humidities of 50% and 60% occur in the stud space, inside the interior face of the plywood sheathing. With a relative humidity of 30%, the dewpoint falls outside the sheathing. In Diagram #4,if the indoor relative humidity is assumed to be 50%, which can be maintained by the air conditioning system, and the average outdoor tempertature in January in Vancouver of 39F is used as the outdoor design temperture The dew point falls outside the sheathing. Temperature values have been assigned in accordance with ASHRAE standards and the National Research Council Canadian Building Digest "Humidity in Canadian Buildings", by N.B. Hutcheons. With these conditions the dew point in the wall asembly falls outside the plywood sheathing. ROL FIELDWALKER architect # 408, 611 Alexander St. Vancouver, B.C. V6A 1E1 Tel: 604-813-6044 Fax: 604-266-8842 Email: rol@rolf ieldwalker.com PAGE 6 EXTERIOR WALL ASSEMBLY PROPOSED EXTERIOR WALL ASSEMBLY TYPICAL OVERHANG ASSEMBLY: 'RHEINZINC' FLAT PANELS ON "ENKA-VENT"ON TYP. MEMBRANE ON 1 1/2" FIR T&G DECK ON 3"X3 1/2" RAFTERS AT 8" O/C C CENTER LINE OF 2X6 STUDS 1'-4" 4'-0" 1'- 4 " 1'-2" 1'- 4 " 1'- 4 4 '-0 " " 8" SPRAY ON POLYURETHANE FOAM INSULATION AT WALL & ROOF INTERSECTION 8" 8" 7 3/4" 7 1/4" 8" 8" 3 1/2" 11 3 /4" 4" 1 1/2" FIR TRIMS TYPICAL WIDTH DETERMINED ON SITE 1 3/4" 1'-2" 8" WINDOW COVERING 5'-3" TYPICAL EXTERIOR WALL ASSEMBLY: 1/2 GYPSUM BOARD WITH PAINT FINISH ON 2X6 STUDS OR 1X2 STRAPPING @ 16" O/C WITH 3 1/2" FRICTION FIT BATT INSULATION (R-13) 1/2" FIRPLY SHEATHING 1/1/2" "THERMAX" EXTERIOR INSULATION (R-10)56%>20% 1 LAYER OF"WEATHERMATE PLUS" HOUSE WRAP AIR & MOISTURE BARRIER JOINTS SEALED WITH "WEATHERMATE STRAIGHT FLASHING" 1/2" PRESERVATIVE TREATED FIRPLY VENTED STRAPPING AT 16" O/C, 3/4" CEDAR CHANNEL SIDING WITH 3/4" CHANNEL TYPICAL EXTERIOR WALL AT EAST ELEVATION 4 3/4" 10 7/8" FOAM SILL GASKET UNDER ALL SILL PLATES. INSULATE TO TOP OF CONC. UPSTAND 1 1/2" TYP. MAIN FLOOR ASSEMBLY: STONE TILE ON SCHLUTER SYSTEM ON 2" CONCRETE TOPPING WITH HYDRONIC HEATING ON SILVERED PAPER ON 3/4" T&G PLYWOOD ON JOISTS .(SEE STRUCTURAL DWGS.) 6" BATT INSULATION TO CRAWL SPACE. 2 3/4" *N.B.KEEP STRUCTURAL WOOD 0" MEMBERS MIN 18" ABOVE GRADE (TYPICAL) 1'-0" 45D 1'-5" 3 1/2" FIR OR STONE TILE BASE TYPICAL 5 1/4" 8" 1 1/2" 3" 7'-2" 8'-4" 3"X8" FIR BLOCKING PIECE BETWEEN 2-3"X8" ROOF PURLINS, CAULKED & BOLTED CONNECTION. 1 1/2" RIGID OR FOAM INSULATION ON 8" CONC. FOUNDATION PINNED TO ROCK . PARGE BOTTOM OF EXCAVATION TO GIVE CONTINUOUS POSITIVE SLOPE TO DRAIN TILE. 6"DIA. PERFORATED DRAIN. USE "PRTECTOWRAP" 6" DETAIL TAPE TO SEAL BOTTOM OF CONC WALL TO PARGING CRAWL SPACE ROL FIELDWALKER WATERPROOF CONCRETE AS SHOWN ON SECTION A-A EXTERIOR WALL SECTION/ MAIN FLOOR NEAR GRID LINE 'C' architect # 408, 611 Alexander St. Vancouver, B.C. V6A 1E1 Tel: 604-813-6044 Fax: 604-266-8842 Email: rol@rolf ieldwalker.com PAGE 7 EXTERIOR WALL ASSEMBLY PROPOSED EXTERIOR WALL ASSEMBLY / SUMMARY The proposed exterior wall assembly locates the air barrier, and 56% of the insulation outside the sheathing. The "Thermax" exterior insulation proposed has an R value of 10, and a water vapour permeance ASTM E96, less than .03 perms.( BCBC calls for less than 1.05 perms (60 ng (Pa.s.m2). The air barrier, provided by "Weathermate" a housewrap, has air leakage characteristics 0 .0036 L/sqm. ( BCBC calls for less than 0 .1 l/sqm), CCMC requirement is less than .02@75 Pa). It does a allow vapour permeance of 312 ng (Pa.s.m2). The three most important aspects this wall assembly was designed to address are: 1.A very good air barrier to reduce air transported moisture into the wall, as air movement has the potential to transport much more moisture that vapour diffusion. It is easier to install and maintain the integrity of an air barrier and moisture barrier on the outside face of the exterior insulation than on the inside face of studs, where electrical fittings create potential for breaching this membrane, and the poly must be interwoven through framing members at floor intersections. This assembly limits air movement, and air transported moisture through the wall . Moisture moved by vapour diffussion into the wall is reduced by the painted gypsum board( 1140 ng(pa.s.m2) and by the fact that the stud space will be warmer, and the temperature differential driving the diffusion from the inside is reduced. 2. Arrange the insulation in such a way as to cause the dew point to fall outside the plywood sheathing. The wall is proposed for a residence where the air conditioning system is expected tol limit the interior RH to 50%.The dew point tempurature then falls outside the sheathing for a outside design temperture of 39F. 3.Reduce the thermal bridging through the studs that occur if all the insulation is in the stud space. The fact that there is R10 insulation outside the studs reduces heat loss by thermal bridging through the studs. Thermal transfer through the studs can reduce the effective R value of a wall assembly by as much as 20%. Conclusion: All the walls considered conform to the BCBC 2006. From the BCBC 2006 requirements for exterior walls and the resultant calculated dew points,the proposed wall assembly is considered to be superior to wall assemblies that have all the insulation on the interior of the sheathing and have vapour barriers on the inside face of the studs. ROL FIELDWALKER architect # 408, 611 Alexander St. Vancouver, B.C. V6A 1E1 Tel: 604-813-6044 Fax: 604-266-8842 Email: rol@rolf ieldwalker.com PAGE 7
© Copyright 2026 Paperzz