Rothera Container 81 DSF Dry Lab British Antarctic Survey In partnership with Royal Netherlands Institute for Sea Research Manufacturer: JM Services Date: 21-09-2011 Table of Contents Chapter 1. Container design 2. Heat pump installation 3. Laboratory 4. Ventilation 5. Control cabinet 6. Touch screen display 7. Usable conditions 8. Specifications 9. Maintenance 10. Malfunctions 11. Settings 12. Drawings Page 2 3-5 6 7 8, 9 10, 11 12 12 13 - 17 18 - 20 21 - 22 23 - 24 1 Container design Container 81 is part of the project Rothera. This project is located in Antarctica and placed in a special built station. Because of the ecological aspects and the fuel supply it is recommended to acclimatize the laboratory by using a heat pump system in combination with a heat recovery installation. This, in comparison with electric heating, will save a lot of energy. There is no air recirculation, because of the fume cupboard, so all the air will be refreshed continuously. In normal conditions (fume cupboard switched off) the ventilation depends on the carbon dioxide percentage. If this value increases by people’s breathing or an opened nitrogen valve, the ventilation system automatically increases the airflow to a maximum of 400m3 per hour till the CO2 percentage will descend below 1000 p.p.m. Below this value the ventilation automatically decrease to the minimum of 150 m3 per hour. If the fume cupboard is switched on by switch 14S16, the ventilation will increases to 400m3 per hour. When the laboratory lights are switched off, the ventilation decreases to the minimum of 150 m3 per hour. Beside the heat pump, the installation has also been provided with a heat recovery system. The exhausted warm air flows through a heat exchanger and gives off its energy to the heat transfer fluid. In the supply airflow another heat exchanger is located. The heat transfer fluid will preheat the supplied air before the main heat exchanger provides the desired laboratory temperature. To get and maintain a constant laboratory temperature the container has also been provided with a floor heating system. If floor heating is used a mass is necessary which can contain energy, therefore this container is provided with an epoxy-sand floor. Most of the loss of heat is caused by the steel construction under the floor. The space in the laboratory is meticulously utilized so that there is maximum room for the researcher and his research work. In the corner of the container a laminar cross flow unit with electronically controlled fan is placed. Three Spectrolab-Plus valves are mounted on the work tables for nitrogen distribution. The pressure is adjustable by means of the pressure control valve to a maximum of 10 bar. The sink at the left side of the laboratory is provided with a water tap. The water pipe has been provided with an insulated tape heating element (tracing) and is controlled by the plant controller, which gets its information from a pipe probe mounted on the water pipe in the technical room. A removable splash screen is mounted near the water tap. The fume cupboard is placed to the left of the sink. It is suitable for research with acid gasses. The exhaust fan is of a special explosion proof type. The lighting of the laboratory consists of long-life fluorescent tubes with high-frequency start. The lifetime of the tubes is up to 60,000 operating hours. The installation will be explained more detailed in the following chapters. 2 Heat pump installation Refrigerant system The working of the heat pump installation is based on the exchange of heat. An air cooler (evaporator) is mounted in an outdoor niche on the top of the container. Refrigerant liquid (R507A) evaporate to gas in this air cooler, controlled by an electronic stepper valve (ETS 12.5). The required heat for evaporation comes from the outdoor air. The air is blown through the evaporator by fans and gives off its energy. The compressor (Bitzer 2DC-3.F1Y-40S) in the technical room compresses the refrigerant gas to a high pressure. The high pressurised gas flows into two parallel connected heat exchangers and gives off its energy to the Ethylene Glycol / water mixture. The high pressurised refrigerant gas will now condensate to refrigerant fluid and flow to the stock vessel and from there to the air cooler again. The compressor bearings and pistons are lubricated with an Ester oil (Emkarate RL 32 H). This oil also circulates through the refrigerant system and decreases the heat transmission in the copper pipes. To counterbalance this effect an oil separator is mounted in the discharge pipe. Most of the oil will be separated from the high pressurised gas and flows back to compressor sump. To prevent the refrigerant from dissolving in the oil during standstill of the compressor, a crankcase heating element is mounted. This element will heat the oil to 25 – 28 ºC, controlled by the plant controller. The temperature is measured by a probe on the crankcase. To check the refrigerant quantity a sight-glass is mounted in the liquid pipe-line after the filter/dryer. The sight-glass has to be full during compressor operation. If there are bubbles in the sight-glass, there could be a refrigerant leakage or the filter/dryer might be saturated. In this case the indicator on the sight-glass will usually be yellow. Under normal conditions the indicator will be green, which means that there is no water in the refrigerant. A solenoid valve is mounted in the pipe-line after the sight-glass. This safety valve prevents the liquid from flowing into the compressor if the electric power shuts off while the electronic stepper valve is still open. The solenoid valve is open during compressor operation. A suction filter is mounted in the suction pipe-line before the compressor. This filter protects the compressor against dirt and possible refrigerant liquid drops. In the refrigerant pipes between the compressor and the wall vibration absorbers are mounted to reduce the vibrations on the wall. Under the compressor feet specially selected vibration absorbers are mounted to reduce the vibration to a minimum. Two measuring hoses are connected to the compressor. One is for measuring the low (suction) pressure (LP). This pressure is controlled by the plant controller, which gets its information from an electronic pressure transmitter and a mechanical pressure switch. The rotation speed of the compressor is controlled by a frequency inverter mounted on the compressor, depending on the required suction pressure. The suction pressure is shown on the low pressure gauge. The other hose is for measuring the high (discharge) pressure (HP). This pressure is controlled in the same way as the low pressure. If the discharge pressure is rising to a critical height, the rotation speed of the compressor is decreased automatically. The discharge pressure is shown on the high pressure gauge. 3 Heating system In the technical room a buffer stock vessel is placed filled with 450 L of glycol/water mixture. In this vessel the heat will be accumulated. The warm mixture (fluid) leaves the vessel at the top through 2-way or 3-way valves to several heat exchangers. At the foot of the vessel the cold mixture returns. The mixture circulates continually. If each 2-way or 3-way valve is closed, the mixture flows through the overpressure bypass (0.4 bar) so the main pump will not be blocked. The pressure in the heating system depends on the temperature of the mixture. When the container starts up in a cold situation (buffer stock vessel temperature around 0ºC) the pressure will be around 0.5 bar. When the buffer stock vessel temperature is below zero the pressure will be 0.0 bar. During the start of a cold installation the malfunction signal “Low fluid pressure heating system” is blocked. Under these conditions neither pump nor ventilator will start until the temperature (20-25ºC) and fluid pressure (1.5 – 2.5 bar) of the buffer stock vessel will be in range. The fluid pressure is measured by a pressure switch (cut out: 0.5 bar / cut in: 1.1 bar) The pressure variations are absorbed by an expansion vessel (Flexcon 25 L). When the laboratory temperature is below the set point, measured by the laboratory probe and the air sock supply probe, the 3-way valve of the heat exchanger will open proportionally to reach the required temperature of the supply air. During an installation start-up or air flow variations the temperature of the supply air can fluctuate a bit. The floor heating system is controlled by the floor probe and the floor liquid probe. The floor heating unit controls its floor liquid temperature to the required value by means of a proportional 2-way valve. During a compressor operation, moisture will frost the outdoor cooler fins. After three hours of compressor operation the cooler will be defrosted until it reaches the temperature of 20 ºC, or for a maximum time of 45 minutes. If the defrost time exceeds this maximum a malfunction will be generated. The defrost-interval and final temperature of the cooler, mentioned above, are depend on the outdoor-humidity percentage and -temperature. These two parameters are adjustable in the parameter list in consultation with JM Services only!! When a mixture leakage occurs, the leak has to be closed and the installation refilled. Refilling is only allowed with a mixture of 40% Ethylene Glycol and 60% water. Other mixtures are not allowed and will damage the installation. Refill to a maximum of 1.9 bar by 20 ºC. The pressure is shown by the pressure gauge of the heating system. The concentration of 40% Ethylene Glycol guarantees that the mixture will remain liquid till a temperature of -26ºC. From -26ºC till -37ºC the mixture changes to slush without making the pipes burst. Below -37ºC the mixture will be solid and cause damage. If the installation is overfilled, the overpressure valve will open and reduces the pressure to 3 bar. The surplus mixture runs into the drain pipe. It is possible that the overpressure valve does not close completely after a overpressure situation. So it is important to prevent overfilling! Pressure variations of the mixture are absorbed by an expansion vessel. 4 Heat recovery system In the supply as well as in the exhaust air canal a heat exchanger has been mounted. In this system the supply air will be preheated by the relative warm mixture (fluid) from the exhaust air exchanger, circulated by a pump. The relatively cold mixture returns to the exhaust air heat exchanger. The heat recovery system is filled with a mixture (40% Ethylene Glycol and 60% water). The pressure in the system depends on the temperature of the mixture. Because of the small mixture volume the pressure fluctuates little. The pressure variations are absorbed by an expansion vessel (Flexcon 12 L). The fluid pressure is measured by a pressure switch (cut out: 0.5 bar / cut in: 1.1 bar). If the fluid pressure descends below 0.5 bar a malfunction signal “Low fluid pressure heat recovery” will be generated. When a mixture leakage occurs, the leak has to be closed and the installation refilled. Refill is only allowed with a mixture of 40% Ethylene Glycol and 60% water. Other mixtures are not allowed and will damage the installation. Refill to a maximum of 2.0 bar by 20 ºC. The pressure is shown by the pressure gauge of the heat recovery system. The concentration of 40% Ethylene Glycol guarantees that the mixture will remain liquid till a temperature of -26ºC. From -26ºC till -37ºC the mixture changes to slush without making the pipes burst. Below -37ºC the mixture will be solid and creates damage. If the installation is overfilled, the overpressure valve will open and reduces the pressure to 3 bar. The surplus mixture runs into the drain pipe. It is possible that the overpressure valve does not close completely after a overpressure situation. So it is important to prevent overfilling! Pressure variations of the mixture are absorbed by an expansion vessel. The pump is thermally protected against overload. Overload will generate a malfunction signal: “Pump heat recovery thermal”. When the malfunction is accepted and solved, restart is possible by pressing the reset button on the control cabinet. 5 Laboratory The laboratory is provided with two work tables. On the right a worktable with an control cabinet and a laminar cross flow cabinet. On the left a fume cupboard and a sink. The laminar flow cabinet can be switched on by a touch button and controlled by a potentiometer. The minimum airflow in the container is 150 m3 per hour. The air leaves the laboratory through the fume cupboard. When the CO2-percentage increases the ventilation will increase slowly to a maximum of 400 m3 per hour till the CO2-percentage has decreased below the minimum value (1000 p.p.m.). When the fume cupboard is switched on, the ventilation will increase rapidly to the maximum of 400 m3 per hour. The fluorescent tube will switch on automatically. The fume cupboard is suitable for research with acid gasses. Before using the laboratory, a sheet of glass should be placed in the top of the fume cupboard to create a laminar airflow. The sink at the left side of the laboratory has been provided with a water tap. The water supply should be connected to the coupling in the niche at the front of the container. The water pipe has been provided with an insulated tape heating element (tracing) and is controlled by the plant controller, which gets its information from a pipe probe mounted on the water pipe in the technical room. The drain should also be connected in the outdoor niche. The swan’s neck under the sink is provided with a removable cup. Near the drink water tap a removable splash screen is mounted. Three Spectrolab-Plus valves are mounted on the work tables for nitrogen distribution. The pressure is adjustable by means of the pressure control valve to a maximum of 10 bar. The nitrogen supply should also be connected in the niche at the front of the container. 6 Ventilation The air in the container is constantly refreshed to ensure a clean atmosphere in the laboratory. The supply air flows through a G4 air filter before entering the air distribution system (air sock). After having been filtered the supply air is preheated in the heat recovery exchanger and flows through the heat exchanger to the air distribution system. The air distribution sock will spread the air equally throughout the container. The airflow is controlled by an air speed transmitter which controls the supply fan speed via the controller. If the G4 air filter gets dirty a pressure difference meter will generate a malfunction signal: “Air filter dirty”. It is important to replace the dirty air filter in time to guarantee a proper working. The air leaves the laboratory through the fume cupboard and the heat recovery exchanger. The exhaust air flow is measured by an air speed transmitter which controls the exhaust fan speed via the controller. The exhaust fan is explosion proof and controlled by the inverter in the technical room. 7 Control cabinet All the electricity in the container is supplied by the control cabinet. In the wiring diagram each electric component in the container is encoded. The code has been built up as follows: Example: 14S16, 15R17 The first number is the page number of the diagram. The capital letter indicates the type of the component. S = Switch, manual M = Motor X = Universal component Y = Electric valve M = Motor E = Heating element F = Fuse K = Relay Z = Lamp R = Resistance (transmitter, temperature probe) The last number indicates the column where the component can be found. The plant controller in the control cabinet controls the heat pump installation and the ventilation. All the values are shown in different tabs of the touch screen display. The operation of the touch screen is explained in detail in the following chapter. The main components are fused and monitored separately. Both controllers run on 24VAC and are double fused. The stepper valve needs a separate power supply, also 24VAC. The main power 3 x 400Volts is guarded by a phase sequence relay. This relay switches off the installation release under the following circumstances: Phase sequence wrong (Phase sequence should turn to the right) Phase off line (one or two phases are cut off) If the voltage varies more than 10% for longer than 8 seconds If the phases are asymmetric more than 10% for longer than 8 seconds When the power supply is connected to the container it is important to verify that the voltage between any phase and zero is about 230V, before switching on the reverse main switch! If the phase sequence is incorrect an alarm will be generated and the main switch has to be reversed. When the container starts up at a temperature below 5ºC it is necessary to wait to switch on the fuse 6F13 (control power) till the control cabinet is heated up to about 20ºC by the heating element in the cabinet. Below 5 ºC the controller cannot operate reliably! 8 In the top of the control cabinet a patch panel is mounted. From the niche at the front of the container two data cables are connected to the patch panel (81-1 and 81-2). Four data outlets are installed in the laboratory, which are also connected to the patch panel (81-3, 81-4, 81-5, 81-6). Next the patch panel a router is mounted. In Antarctica this router is unnecessary because the Plant controller is directly connected to the data switch. But on board a ship or at other locations this router could be necessary. The router is pre-configured for data communication with the Plant controller. The data switch is mounted beside the router. This switch connects the right IP-address to the right appliance. Ask the local IT-administrator for more information about this connection. 9 Touch screen display At the front of the control cabinet a touch screen display is mounted. On this touch screen several values and parameters are shown and sometimes adjustable. On the main screen, shown above, three values are shown and one parameter is adjustable. Left half top: CO2 value in Parts Per Million. If this value increases to over 1000 PPM the ventilation will increase automatically. Left half bottom: Outdoor temperature in ºC. The outdoor temperature is measured in the supply air flow before the airfilter. Right half left: Relative humidity. The relative humidity is measured at the ceiling of the laboratory. This value cannot be adjusted. Right half right: Laboratory temperature set point. The laboratory temperature can be adjusted by the slider. Because of the slow reaction of the floor heating system it is recommended to keep this set point steady. If the lights and fume cupboard have been switched off for more than three days (72 hours), the laboratory temperature set point will switch to the winter set point (10 ºC). When the lights or fume cupboard are switched on again, the previous set point will be activated. By touching the top of the screen the menu will be opened. At the left side of the menu six tabs are shown. Touch the top again to return to the main screen. 10 Inputs In this tab the inputs of the controller are shown. The screen is refreshed every five seconds. It is possible to scroll up and down through the values in each of the tabs. Outputs In this tab the outputs of the controller are shown. State No data Parameters In this tab each parameter can be adjusted. For changing a parameter, contact JM Services. Alarms During normal operation conditions the status indicator over the screen is blue. If an alarm is directed to the display the indicator will flash red and a sounder will be active. Once the alarm has been accepted the red status indicator remains on permanently until the alarm will be cleared. The sounder is off . 11 Design demands The container is designed for the following demands: Outdoor temperature: Outdoor relative humidity: Laboratory temperature: + 5ºC 0% + 15ºC / / / -25 ºC 90 % +25 ºC Deployment: Indoor – horizontal The maximum stand still time of the container is one month. The roof of the container has to be free of ice and snow so that the air can flow through the cooler easily. Specifications Owner: Manufacturer: Container number: Container dimensions (mm): Container tare weight (kg): Allowable stacking weight (kg) : Next container inspection: NIOZ JM Services NIOU 00081-2 6058 x 2438 x 2591 6100 192000 04/2015 Refrigerant: Required electrical power (front niche): Data communication connection (front niche): Fire alarm connection (front niche): Water pipe connection H2O (front niche): Nitrogen pipe connection N2 (front niche): Drain pipe connection (front niche): Earth connection (front niche): Cable conduit screw cap internal Ø (front niche): R507a – 10,0 kg 3 x 400V – 25 A 2 x RJ 45 Direct connection ½” internal thread DIN 2986 ½” internal thread DIN 2986 1” external thread DIN 2986 M10 bolt 103.6 mm 12 Maintenance The installation in the container requires periodic maintenance to minimize malfunctions. This is shown in the following schedule: Installation part Air filter (supply air) Fluid pressure heating system Fluid pressure heat recovery system Oil level compressor Icing in cooler (outdoor roof niche) General inspection Maintenance interval Weekly Weekly Weekly Weekly Daily Daily Details Replace if dirty About 2 bar (20 ºC) About 2 bar (20 ºC) ¼ - ¾ of the sight glass The fins should be free of ice Visual Replacing air filter When the air filter is dirty it has to be replaced. It is not necessary to stop the ventilation. 1. 2. 3. 4. 5. Unscrew the wing nuts of the supply ventilation door. Fasten the door in open position by the nylon door fastener. Pull the air filter out of the slides in a horizontal movement. Push a new air filter into the slides. Be sure the airflow arrow points at the supply fan! Close the door and screw on the wing nuts carefully. 13 Refilling heating system When a low fluid pressure heating system alarm occurs, because of a leak, the installation has to be refilled after repair. 1. Switch off the installation. 2. Repair the leak. 3. Mix the 100% Ethylene Glycol with drinking water to a mixture of 40% Glycol - 60% drinking water. 4. Use the hand pump to refill the installation. Be sure that the filling hose is free of air. 5. Pump the mixture into the installation until the system pressure gauge shows a value of at most 1.9 bar by a buffer stock vessel temperature of 20 ºC. Do not overfill! 6. The installation is provided with bleeding plugs to let the air out of the installation. Use the bleeding key and hose to led this air out. 7. Restart the installation. 8. Repeat the bleeding procedure a few hours later. It is not necessary to stop the installation than. The positions of the bleeding plugs: Outdoor roof niche: Three plugs at the left side of the container (looking to the front door). 14 Supply fan niche: (Left door above the laboratory inner door).One plug. Technical room: Two plugs. Attention: Do not bleed the refrigerant system, this is a vapour / liquid system. 15 Refilling heat recovery system When a low fluid pressure heating system alarm occurs, because of a leak, the installation has to be refilled after repair. 1. Switch off the installation. 2. Repair the leak. 3. Mix the 100% Ethylene Glycol with drinking water to a mixture of 40% Glycol - 60% drinking water. 4. Use the hand pump to refill the installation. Be sure that the filling hose is free of air. 5. Pump the mixture into the installation until the system pressure gauge shows a value of at most 1.9 bar by a sytem temperature of 20 ºC. Do not overfill! 6. The installation is provided with bleeding plugs to let the air out of the installation. Use the bleeding key and hose to led this air out. 7. Restart the installation. 8. Repeat the bleeding procedure a few hours later. It is not necessary to stop the installation than. Supply fan niche: (Left door above the laboratory door) Two plugs. 16 Technical room: One plug. In some cases it might be necessary to bleed the pump. This can be done by removing the screw at the front of the pump during operation. Attention: Do not bleed the refrigerant system, this is a vapour / liquid system. 17 Malfunctions The heat pump installation has a built in auto reset function. When a fault has occurred, the controller will try to eliminate the interference by a reset procedure. After several attempts the controller will create a fault message in the touch screen display, shown in the table below: Fault message: Description: 1 Reset button blocked The reset button has been pressed for more than 20 seconds . 2 Compressor inverter The inverter generates a fault. 3 Compressor thermistor Compressor high/low pressure Compressor coil overheated (130ºC). The pressostat is switched off by a high or low refrigerant pressure. 5 Compressor low oil-level The oil level of the compressor carter is critically low. 6 Compressor oillevel detector The oil-level detector at the back of the compressor is disconnected. 7 Discharge pipe temperature high The compressor discharge pipe temperature is too high (130ºC). 8 Low superheat The refrigerant superheat of the outdoor cooler is too low. 9 High superheat The refrigerant superheat of the outdoor cooler is too high. 4 Solution: Reset by touch screen parameters. Contact JM Services. Connect the Danfoss display LCP 2800 to the inverter. Reset by compressor main fuse. Reset by reset button . Contacts JM Services. Reset by fuse control power. Contact JM Services. Check the refrigerant liquid level in the sight glass of the vessel. (Check for closed screw/ball valves). Reset pressostat by a built in reset button. Reset by reset button . Check for oil leakage (or closed oil ball valve). Check the temperature probes. Reset by reset button . Screw the detector onto the compressor carter. Reset by reset button. Check the buffer stock vessel temperature probe. Reset by reset button. Check the suction pipe temperature probe and the ETS stepper connection. Reset by reset button . Check the refrigerant level in the sight glass of the liquid line during operation. The sight glass has to be filled up completely. Check the working of the refrigerant solenoid valve. Reset by reset button . Installation blocked Yes Yes Yes Yes Yes Yes Yes Yes Yes 18 Fault name: Description: 10 Low suction pressure The suction pressure of the compressor is too low. 11 High discharge pressure The compressor discharge pressure is too high (60 ºC). 12 Air filter dirty 13 Supply fan thermal The supply air filter is dirty (air pressure difference 170 Pa) The supply fan current exceeds the limit of the fuse (6A). 14 Exhaust fan thermal The exhaust fan current exceeds the limit of the fuse (6A). 15 Cooler fans thermal The cooler fans current exceeds the limit of the fuse (1.3A) 16 Max. defrost time exceeded The outdoor cooler defrost exceeds the maximum defrost time (45min.) 17 Phase (sequence) incorrect The phase sequence relay is switched off. 18 Main pump heating system thermal The main pump current exceeds the limit of the fuse (6A). 19 Pump cooling system thermal The pump current exceeds the limit of the fuse (6A). Solution: Check the refrigerant level in the sight glass of the liquid line during operation. The sight glass has to be filled completely. Reset by reset button. Check the buffer stock vessel probe (maximum 45 ºC). (Check for closed screw/ball valves). Reset by reset button. Replace air filter. Installation blocked Yes Yes No Check the fan for mechanical blockage. Reset by reset button. Check the fan for mechanical blockage. Check the inverter in the technical room. Reset by reset button. Check the fan for mechanical blockage by ice. Reset by reset button. Check the cooler fins on ice. Check the defrost probes in the cooler body. Check the defrost valve. Reset by reset button. Check the electric field rotation (clockwise). The electric field rotation is changeable by the reverse main switch. Check the main power voltage and phases. Check the fuses before the phase relay. No No Yes No Yes Check the main pump for mechanical blockage (by unscrewing pump lid). Reset by reset button. Check the main pump for mechanical blockage (by unscrewing pump lid). Reset by reset button. No No 19 Fault name: Description: 20 Low temp. buffer stock heating The buffer stock temperature is critically low (-25 ºC). 21 Pump heat recovery thermal The pump current exceeds the limit of the fuse (6A). 22 Pump floor heating thermal The pump current exceeds the limit of the fuse (6A). 23 Low fluid pressure heating system The fluid (glycol mixture) pressure of the heating system is critically low. 24 Low fluid pressure heat recovery system The fluid (glycol mixture) pressure of the heating system is critically low. 25 Tracing water pipe thermal The tracing current exceeds the limit of the fuse (6A). 26 Frost danger water pipe High temperature technical room The water pipe temperature is critically low (2 ºC) The technical room temperature is critically high (45 ºC). Comm. fault expansion: Restart! The extension of the controller has lost communication with the plant controller. 27 28 Solution: Check the whole installation for malfunctions. Reset by reset button. Check the main pump for mechanical blockage (by unscrewing pump lid). Reset by reset button. Check the main pump for mechanical blockage (by unscrew pump lid). Reset by reset button. Check the installation for leakage. Refill only with Ethylene Glycol 40% / 60% water. Reset by reset button. Check the installation for leakage. Refill with Ethylene Glycol 40% / 60% water only. Reset by reset button. Check the water pipe tracing for mechanical damage. (Check the insulated end of the tracing line). Reset by reset button. Check the water pipe tracing. Reset by reset button. Check the cause of heating in the technical room. Reset by reset button. Restart the installation by switching the control power fuse. Installation blocked No No No No No No No No Yes It is possible that the touch screen shows a fault which has been solved already. E.g. the fault: Phase (sequence) incorrect. The installation has already restarted, but the fault has to be accepted in the screen. 20 Settings The settings of the components in the installation have been adjusted accurately. Below a table of the component settings. 1 2 3 4 5 Component: Phase sequence relay Main fuse outdoor cooler fans Thermostat heating cabinet Cooler drain tracing delay Netgear router 6 7 8 Module ID of controller extension Plant / Extension controller term Plant controller direct log in 9 10 11 12 13 14 15 16 17 18 19 LP / HP Fluid overpressure valve Heat recovery pump Main pump heating system Floor heating pump Control valve floor heating Control valve heating Control valve defrost Control valve bypass heating Compressor inverter ramp up speed Exhaust fan inverter 20 3-way valve heating 21 Filter differential pressure transmitter 22 2-way valve floor heating 23 Air velocity meter Value(s): 400V / 8 sec. / 10% 1.3A 20 ºC 5 min. IP-address: 192.168.1.1 Username: admin Password: password 1 Y IP-address: 10.255.255.254 Username: install Password: 1234 LP:1bar / Diff:1bar / HP:30bar 0.4 bar Speed 1 (slow) Speed 2 (middle) Speed 1 (slow) Position 1.8 Position 2.6 Position 3.0 Position 1.9 5.0 sec. 01: 0 Hz 02: 50 Hz 05: Al.AV 06: 0.43 A 07: 1435 rpm 08: 400 V 16: Volt 22: A Linear flow C-B DIP switch 1: ON DIP switch 2: OFF DIP switch 4: OFF DIP switch 6: OFF 100% – 0% <= 0 – 10V Jumper 15m/s Details: 7X2 5F3 20S17 12T7 12X3 Resistance 120 Ω 10X3 17X6-2 6M6 6M3 6M8 TA ½ TA ½ TA ¾ TA ½ AKD2800 18Y11 13R18 18Y13 13R13 / 13R15 21 60 4408 1246 600 880 2280 625 1136 560 760 Cable management up to ceiling Fume Cupboard Engine room flow cytometer Sink (FAScanto II 228x76x117 cm ca. 200 Kg) laminair cross flow kast Electrical box 1226 900 3508 80 5714 Heat exchanger Evaporator 500 700 962 Air sock Filter Air sock Connection Fume Cupboard Evaporator Air sock Heating Capacitor + Buffer-barrel Capacitor + Buffer-barrel Compressor Fume Cupboard Ventilator Heat exchanger Compressor Cable housing extra Sink Cable housing extra Cable housing extra pomp floor heating. Effluent Pomp floor heating. Effluent Client : Order / Project Project : Description Rothera dry lab container nr. 81 Form Drawn by Scale Checked by ----- Date 10-3-2011 Drawingnr. Sht. Evaporator Fire connection box Evaporator Internet & VOIP Cable housing extra Electric connextion Water & nitrogen Sewage Client : Order / Project Project : Description Rothera dry lab container nr. 81 Form Drawn by Scale Checked by ----- Date 10-3-2011 Drawingnr. Sht.
© Copyright 2026 Paperzz