RS485 External Module for Data Logger Meteo-40 • • • • • • • M83550 Biasing resistors for RS485 bus (680Ω) (configurable with jumpers) RS485 bus termination (120Ω) (switchable with jumper) Overvoltage protection for all RS485 bus lines A stabilised and actively fused 5V / 110mA output for general purposes Protected with fuse T0.8A (time-lag) Housing dimensions (width x height x depth): 22.5 x 110 x 115mm Operating temperature: -40°C ... +75°C Pin Assignment 1 2 3 4 9 10 11 12 1: TxD − 110mm 5 6 7 8 9: RxD − 10: TxD + 2: TxD + 13 14 15 16 3: RxD + 11: RxD + 4: RxD − 12: TxD − 5: 5V Out 13: A − 6: GND 14: Supply 7: B + 15: B + 8: A − 16: GND Earth contact 22.5mm Metall foot catch Electrical Characteristics Parameter Supply voltage Quiescent current Min Type 9V 24V 7.5mA 18mA T0.8A (time-lag) (5 x 20mm) Fuse Output voltage Max 4.9V 5.0V Output current (ϑ = 25°C) 5.2V 110mA Bus termination 120Ω Biasing resistors 680Ω page 1/5 Ammonit Measurement GmbH Wrangelstrasse 100, D-10997 Berlin, Germany T: +49 30 6003188-0, E: [email protected] measuring wind power www.ammonit.com RS485 External Module for Data Logger Meteo-40 M83550 Principle of operation RS485-M (Master) •• Half duplex interface Supply The intention of the M83550 is to provide a universal interface to different types of RS485-sensors of different manufacturers. In order to have this flexibility, biasing resistors (680Ω) for the B+ line and the A- line are needed. The figure on the right side shows the half duplex interface for RS485 with M83550 working on the lines B+ and A-. 14 Internal 5V Meteo−40 JP1 Jumper: Pull−Up RS485 Sensor 680 Ohm 15 7 B+ TXD+/RXD+ JP2 Jumper: Termination 120 Ohm To have active biasing resistors, jumpers JP1 and JP3 are set by default. RS485 M Master 120 Ohm 8 13 TXD−/RXD− A− JP3 Jumper: Pull−Down if available Additionally a termination resistor of 120Ω may be set via jumper JP2. In conjunction with Meteo-40 it is not needed. Therefore, M83550 is shipped with an open jumper JP2. 680 Ohm M83550 6 / 16 Up to 8 sensors can be connected. Supply 14 Internal 5V Sensor 8 Sensor 2 Sensor 1 Meteo−40 JP1 Jumper: Pull−Up 680 Ohm TXD+/RXD+ 15 7 JP2 Termination B+ Jumper: Termination RS485 M 120 Ohm 120 Ohm Resistor Master 120 Ohm TXD−/RXD− 13 8 A− JP3 Jumper: Pull−Down 680 Ohm M83550 6 / 16 page 2/5 Ammonit Measurement GmbH Wrangelstrasse 100, D-10997 Berlin, Germany T: +49 30 6003188-0, E: [email protected] measuring wind power www.ammonit.com RS485 External Module for Data Logger Meteo-40 RS485-S (Slave) •• Full duplex interface •• SCADA M83550 Supply 14 The figure on this page shows the setup of a SCADA system. The Meteo-40 data logger is connected to the SCADA client via the full duplex interface (Slave). Internal 5V SCADA JP7 Meteo−40 Jumper: Pull−Up Client If biasing on the full duplex (Slave) interface is needed, the jumpers JP4, JP6, JP7 and JP9 have to be set additionally. 680 Ohm 2 10 TxD+ JP8 Up to eight sensors can be connected to the half duplex interface (Master) of the Meteo-40. Jumper: Termination 120 Ohm 1 12 TxD− JP9 Jumper: Pull−Down 680 Ohm RS485 S Master Slave JP4 Jumper: Pull−Up 680 Ohm 3 11 RxD+ JP5 Jumper: Termination 120 Ohm 4 9 RxD− JP6 Jumper: Pull−Down 680 Ohm Internal 5V RS485 Sensor 8 RS485 Sensor 2 JP1 RS485 Sensor 1 Jumper: Pull−Up 680 Ohm 15 7 JP2 Termination B+ Jumper: Termination 120 Ohm 120 Ohm Resistor RS485 M Master 120 Ohm 13 8 A− JP3 Jumper: Pull−Down 680 Ohm M83550 6/16 page 3/5 Ammonit Measurement GmbH Wrangelstrasse 100, D-10997 Berlin, Germany T: +49 30 6003188-0, E: [email protected] measuring wind power www.ammonit.com RS485 External Module for Data Logger Meteo-40 RS485-S (Slave) •• Half Duplex SCADA client M83550 SCADA Meteo−40 Converter Client The figure on this page shows a SCADA setup using a half duplex interface at the SCADA client. In order to connect the SCADA client to the Meteo-40 slave interface, an additional converter (e.g. Comm-Front RPT-485-422-2) has to be applied. B+ RX+ TxD+ RX− TxD− RX+ The converter can be supplied by the 5V output of the M83550 module (Pin 5). The master interface has the same setup as shown on page 3. RS485 S Master Slave A− TX+ 5VDC TX+ RxD+ TX− RxD− GND Supply 5 14 5V Out Internal 5V RS485 Sensor 8 RS485 Sensor 2 JP1 RS485 Sensor 1 Jumper: Pull−Up 680 Ohm 15 7 JP2 Termination B+ Jumper: Termination 120 Ohm 120 Ohm Resistor RS485 M Master 120 Ohm 13 8 A− JP3 Jumper: Pull−Down 680 Ohm M83550 6/16 page 4/5 Ammonit Measurement GmbH Wrangelstrasse 100, D-10997 Berlin, Germany T: +49 30 6003188-0, E: [email protected] measuring wind power www.ammonit.com RS485 External Module for Data Logger Meteo-40 M83550 Jumper settings Jumper Description RS485-M (Master) RS485-S (Slave) JP1 Pull-up B+ on JP2 Termination B+/A- off JP3 Pull-down A- on JP4 Pull-up RxD + off JP5 Termination RxD off JP6 Pull-down RxD - off JP7 Pull-up TxD + off JP8 Termination TxD off JP9 Pull-down TxD - off JP4 JP5 JP6 JP7 JP8 JP9 JP1 JP2 JP3 Fuse page 5/5 Ammonit Measurement GmbH Wrangelstrasse 100, D-10997 Berlin, Germany T: +49 30 6003188-0, E: [email protected] Last Modification: 09 August 2012 measuring wind power www.ammonit.com
© Copyright 2026 Paperzz