Operation and Service Instructions DC3100 Dust Collector Issue Date: Sept 2007 Silencer Control Panel Hopper Pail Pack Comco, Inc. 2151 N. Lincoln Street Burbank, California 91504 USA Phone: 818-841-5500 Fax: 818-955-8365 Web Site: www.COMCOinc.com Book P/N DC3115 File: DC3100man.doc DC3100 PRODUCTION DUST COLLECTOR SPECIFICATIONS Application: Dry blasting media Designed Air Flow: Maximum 1,600 CFM @ 7” external static pressure Filter Area: 570 square feet Air-to-Media Ratio: 2.5 : 1 Filter Cartridge Material: Ultra-Web® II NL Filter Quantity: 3 Standard Housing Unit is constructed of 12 gauge steel rated at -20" wg. Finish Exterior and interior surfaces are covered with an electro-statically applied powder coat TGIC polyester textured finish (2-mil dry film thickness). The finish passes a 350-hour salt spray corrosion performance test. The color is blue. Dust Laden Air Inlet Standard top inlet is 8 inches in diameter and creates a general downward airflow pattern in the filter section to optimize filter performance. Each filter column is protected from direct dust impingement by an internal baffle plate. Ultra-Web II NL Filters The media in each filter cartridge incorporates a durable outer layer of EON nanofibers that intercepts even the smallest particles at the surface of the media. Independent laboratory testing has determined that Ultra-Web II cartridges have start-up efficiencies of 99.9% on 0.2-2 micron dust particles, and operating efficiencies of 99.999% on 0.5-micron particulate. The tests were conducted using procedures defined in ASHRAE report #RP-531 and by BIA European Institute for Occupational Safety. The Ultra-Web II NL cartridge features an open design without outer liner to improve pulsecleaning effectiveness on very fine and agglomerative dusts. Each cartridge contains 190 square feet of media. Comco Inc. Page 1 Issue Date: Sept 2007 Filter Cleaning Periodic pulses of compressed air managed by high performance air control components clean the filter cartridges. Pulsed air back flushes in the opposite direction of normal airflow and into a patented venturi style cleaning system. The proprietary cleaning system delivers maximum cleaning energy and provides uniform pulse pressure for superior cleaning effectiveness. The cleaning system is fully enclosed for quiet operation. Cleaning Controls The proprietary solid-state Delta P Control Board, featuring a digital read-out display, controls the on-demand, continuous duty filter cleaning by measuring and controlling between high and low pressure set points. It provides filter restriction and cleaning control; starting and stopping the cleaning process at user selected set points. No battery backup required. For standard housing construction, control components are factory mounted internally to the collector, pre-wired, and are rated NEMA 12. Required Services The collector requires 6 scfm of maximum 60 psig, clean, dry compressed air based on a 10 second pulse interval. Timer requires 110 VAC. Compressed air to be supplied by customer. Discharge Hopper Discharge hopper is fabricated of 12-gauge steel and features a ledge-free internal design. Hopper angles are at 46° and 52° degrees. Top flange is rectangle and bottom discharge flange is a 7" square opening, which attaches to a 10 -gallon dust container with gate. Support Leg Structure Support leg structure provides 19” clearance between the hopper discharge flange and the base plate. Fan High performance backward inclined airfoil fan is mounted on the clean air side and at the base of the unit for maximum noise control. Fan wheel consists of fiberglass reinforced composite material. Motor starter is provided. Unit performance: 1,500 cfm @ 7” wg external static pressure with clean filters. Motor 5 Hp, 3,450RPM, 230/460 V, 60 Hz, 3 phase, TEFC Motor is directly coupled to fan and wired to control box located inside of clean air plenum. Cord /plug not included. Comco Inc. Page 2 Issue Date: Sept 2007 Exhaust Silencer Exhaust silencer is integral to unit and is supplied at all times for highest fan noise control. Damper Damper is of parallel blade construction with manual handle and locking quadrant, and is supplied at all times for maximum airflow control. Noise Level The standard 5 hp unlined fan plenum delivers an overall average sound pressure level of 80 dB (A) at an operator position of 1.5 m high and 1 m from source, which lowers to a hemispherical reading of 68 dB (A) at a 4 m radius from the source. Pulse cleaning accelerates noise level for short spikes to approximately 92 dB (A) at operator level. All sound measurements were taken in a hemianachoic chamber and under free field conditions and do not reflect the influences of actual operating environments. Shipping Weight 1,250 pounds (approximate). PLEASE NOTE: Collector will ship completely assembled. Some field assembly is required if accessories are purchased. Price does not include freight costs, unit installation, taxes, electrical connections, ducting or plumbing for the air supply. Comco Inc. Page 3 Issue Date: Sept 2007 NORMAL OPERATIONS Comco Inc. Page 4 Issue Date: Sept 2007 DC3100 DUST COLLECTOR INSTALLATION AND SETUP Introduction Your DC3100 Dust Collector has been setup in the following configuration: Blower Motor voltage as indicated on serial number plate ΔP Control Panel (pre-wired for 120V/60Hz) Front Panel Blower Control switches 5-Gallon Pail Pack without Gate After Shift Cleaner Installation Prior to installing your new DC3100 Dust Collector, thoroughly read the Installation and Operation Manual supplied with your dust collector. The dust collector must be installed in accordance with local building codes and precautions reviewed in the manual. All electrical wiring and connections must be made by a qualified electrician using the wiring and connection information found in the Installation and Operation Manual as a guide. If the dust collector is to be installed outside, protection from weather elements must be considered. Contact Comco Technical Support for additional information and suggestions. Air Supply Connections and Requirements: A compressed air supply must be connected to the dust collector for the pulse cleaning function. A clean, oil free supply of air at 60 psi, 2 scfm is required. A regulator and filter separator should be installed in the line in front of the dust collector. It is also recommend that a shut off gate or valve be installed in the line to facilitate servicing the unit. AIR PRESSURE REGULATOR SET AT 90 – 100 psi TO DUST COLLECTOR AIR INLET DIRECTION OF AIR FLOW AIR SHUT OFF FILTER/SEPARATOR Comco Inc. Page 5 Issue Date: Sept 2007 Setup Air Pressure Set the compressed air source connected to bottom of the collector at 60 psi. Electrical Power ELECTRICAL INTERLOCK SWITCH P CONTROL PANEL BLOWER CONTROL SWITCHES 1. Turn on Electrical power to the unit. Be sure the front panel electrical interlock switch is in its ON position. Note: The door must be closed and secured in order to turn the interlock switch. 2. Display on the Control Panel should light. Note: If the pressure differential displays a negative value, the pressure tubes from the Panel circuit board to the cabinet must be reversed. See reversing the pressure sensor tubes to the ΔP Control Panel. 3. Turn on the blower by depressing the Blower Start switch on the Control Panel. Comco Inc. Page 6 Issue Date: Sept 2007 ΔP Control Panel Settings The filters are monitored for media build up by measuring the pressure drop across the filters. The high and low set points determine at what point the pulse filter cleaning is to start and stop. When the pressure drop reaches the high point setting the air purge pulses will start and continue at the preset pulse duration and rate until the pressure drop reaches the low point setting. There are several factors to consider when setting these points. In general, setting points shown below will be suitable for most applications: Low Set: 1.5 High Set: 2.5 The ΔP Control also has a red alarm light that lights when a set alarm point is reached. This alarm indicates that the filters are not cleaning and maintenance of the filters is required or a system problem exits which is causing the filters to clog. A recommended set point for the alarm is: Alarm Set: 4.5 To set the points: 1) Turn ON the Dust Collector. 2) Press and hold one of the set point keys. 3) While holding down the key, use the UP and Down arrow keys to adjust that setting. 4) Repeat above procedure to adjust remaining settings. Note: If display indicates a negative differential pressure value, the pressure sensor tubes need to be reversed. See “Reversing the pressure sensor tubes to the ΔP Control Panel” below. Δ P Control Calibration When the unit is at rest the display should read 0.0. If not, the ΔP Control will need to be reset as follows: 1) Power the ΔP Control for a minimum of 30 minutes to stabilize the operating temperature. 2) Remove power from the Control so that the display shuts down. To turn off power rotate the interlock switch located on the control panel to the OFF position. 3) Press and hold the Low Set, High Set and Alarm Set keys while reapplying power to the Control. Continue to hold these keys while the Control goes Comco Inc. Page 7 Issue Date: Sept 2007 through a power-up routine. This is indicated by sequentially displaying “8” in each digit, and then displaying “0.0”. 4) Release all three keys. The new calibration automatically stores in memory. Downtime Clean The Downtime Clean function will require setting the cleaning cycle. This function is designed to cycle air pulses through the 3 filters for a set period of time after the dust collector is shut down. This cleaning process yields a very complete cleaning of the four filter elements at the end of the operating shift. Several factors determine the optimum cycle time. In general the set time shown below should be sufficient. DOWNTIME CLEANING: Setting - Small Selector Dial: Setting - Large Selector Dial: ON 6-60 min 1 = 1/10 of 60 min or 6 Min To turn ON and set cleaning cycle time: 1) Turn OFF dust collector blower. 2) Turn electrical interlock switch on front panel to the OFF position. 3) Unscrew the 2 socket screws on the right side of the front panel. 4) Open front panel and locate After Shift Clean controls. 5) Small selector dial – Set at 6-60 min range. 6) Large selector dial - Set at 1 (1/10 of 60 min). 7) Set Down Time Cleaning switch to ON*. 8) Close and secure front panel. 9) Turn ON dust collector blower. * It is recommended that the Down Time Cleaning be turned OFF for the first few months until the filter elements have a light powder build up on them. The filters will work better after they have been used or broken in. Comco Inc. Page 8 Issue Date: Sept 2007 Replacement Filters for the DC3100 Dust Collector Refer to the Torit Installation and Operation Manual* for filter replacement instructions. Filters: Comco Part No.: DC3120 Torit Part No.: P191889-461-436 For additional repair and service parts refer to the: Torit Replacement Parts List included in this binder For Technical Assistance Call: Comco Technical Support Comco’s Technical Support Department is available Monday through Friday from 6:30 am to 4:30pm, Pacific Time, to help you with any questions you may have with your Dust Collector or with any other micro-abrasive blasting issues. The telephone and fax numbers are: Phone: -or- 1-800-796-6626 1-818-841-5500 Fax: 1-818-955-8365 You may also e-mail your questions to: [email protected] Comco maintains an extensive library of technical bulletins that encompass a variety of micro-abrasive blasting subjects and application information. These are available by contacting Customer Service at one of the above numbers or by viewing our website – www.COMCOinc.com – to download an electronic copy. Comco Inc. Page 9 Issue Date: Sept 2007 THIS PAGE LEFT INTENTIONALY BLANK Comco Inc. Page 10 Issue Date: Sept 2007
© Copyright 2025 Paperzz