green power 2.0 and Delphys BC

green power 2.0 and Delphys BC
Modbus - TCP / Jbus serial link
Installation and operating manual
GB
Index
1.Foreword
4
2. Safety Requirement
4
2. 1.
Using conditions
2. 2.DELPHYS Green Power Operating Reference
3.Environment
3. 1.Recycling of electrical products and equipment
4.Introduction
4
4
4
5
4. 1.General purpose
5
4. 2.Modbus protocol
5
4. 3.Data decoding
5
5.Installation OF modbus rtu card
5. 1.
‘Com-Slots’ localisation
6
6
5. 2.Modbus serial interface plug in
6
5. 3.Modbus interface in parallel system configuration
6
5. 4.Connections and wiring
7
5. 5.Com2 Serial link default settings
8
5. 6.
8
How to change the “serial link 2” settings ? 6. installation of MODBUS TCP CARD
9
6. 1.
‘Com-Slots’ localisation
9
6. 2.
UPS Com2 Modbus Serial link default settings
9
6. 3.
default settings of the modbus tcp interface
7.Conventions
7. 1.Frame errors management
8.Modbus in Single UPS unit
8. 1.
How to read data
10
11
11
12
12
8. 2.Incoming data structure
12
8. 3.
13
Ups Identification
8. 4.Date & Hours
13
8. 5.
Ups Configuration
13
8. 6.
Unit Status
14
8. 7.
Unit Alarms
16
8. 8.
Unit Measurements tables
18
8. 9.
Unit Enabled Controls Table
20
8. 10.Controls Send To Ups
2
4
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
20
21
9. 1.Reminder
21
9. 2.Modbus table in modular parallel system
22
9. 3.
22
Ups Identification
9. 4.Date & Hours
22
9. 5.
Ups Configuration
22
9. 6.
Preliminary Remarks
22
9. 7.
Ups Status
23
9. 8.
Ups Alarms
24
9. 9.
Ups Measurements
25
9. 10. Ups Enabled Controls Table
26
9. 11.To Send Control To Ups
26
10.MODBUS IN PARALLEL SYSTEM with centralised bypass
27
10. 1.Reminder
27
10. 2.Modbus table in parallel system with centralised bypass
28
10. 3. Ups Identification
28
10. 4.Date & Hours
28
10. 5. Ups Configuration
28
10. 6. Preliminary Remarks
28
10. 7. Ups Status
29
10. 8. Ups Alarms
30
10. 9. Ups Measurements
31
10. 10. Ups Enabled Controls Table
32
10. 11.To Send Control To Ups
32
11. Bypass TABLE
33
11. 1.Bypass Status
33
11. 2.Bypass Alarms
35
11. 3.Bypass Measurements tables
37
12.Module TABLE
39
12. 1.Module Status
39
12. 2.Module Alarms
41
12. 3.Module Measurements tables
43
13.ANNEXE
45
13. 1.
45
setting of the interface using digi® device discovery
13. 2.MODBUS TCP IDA specification ENGLISH
9.MODBUS IN modular PARALLEL SYSTEM CONFIGURATION
47
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
3
1. Foreword
We thank you for the trust you have in our Uninterruptible Power Systems.
This equipment is fitted with up to date technology. Rectifier and inverter subsets are provided with power semiconductors (IGBT) including a digital micro-controller.
Our equipment complies with IEC EN 62040-2 standard.
CAUTION : “This is a product for restricted sales distribution to informed partners. Installation restrictions or additional measures may be needed to prevent disturbances”.
SOCOMEC UPS reserves the right to modify their specifications at any time as far as this contributes
to technical progress.
2. Safety Requirement
2. 1. Using conditions
Do read carefully these operation instructions before using the JBUS/MODBUS interface.
Whatever the repairs, they must be made only by authorised staffs, which have been suitably trained.
For an optimal operation, it is recommended to maintain the ambient temperature and humidity of the DELPHYS
Green Power environment below the values specified by the manufacturer.
2. 2. DELPHYS Green Power Operating Reference
Respect the safety requirements.
Do read carefully the operation instructions of DELPHYS Green Power.
This equipment meets the requirements of the European directives applied to this product. As a consequence it is
labelled as follows:
3. Environment
3. 1. Recycling of electrical products and equipment
Provision is made in European countries to break up and recycle materials making up the system. The various components must be disposed of in accordance with the legal provisions in force in the country where the system is
installed.
4
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
4. Introduction
4. 1. General purpose
This document provides required information of the MODBUS protocol serial link or Ethernet network.
Before connecting a supervision equipment or BMS system (Building management system) to the UPS, it is neces-
ENGLISH
sary to install and set up the serial interface or network configurations in the case of a network connection..
4. 2. Modbus protocol
This
document
does
not
explain
the
MODBUS
protocol
management.
Please
refer
on
www.modbus.org web site for more information.
The DELPHYS Green Power MODBUS uses the following functions :
–– function 3 for reading Input Registers (16 bits),
–– function 6 for writing single Registers (to control DELPHYS Green Power).
The data field is composed of 1 word, defined by a MSB (most significant byte) and a LSB (lowest significant byte),
and displayed in the following order on the serial link.
1 WORD DATA
b7
MSBb0
b7
LSBb0
b15b0
4. 3. Data decoding
Status and alarms Information
This information are coding in bit. This means that 1 word defines 16 information. If the related bit is set to 1, this
information is active or true.
Measurements and counters data
1 word defines a measurement or a counter. Some values are numeric decimal signed or unsigned (0 to 65535 or
from -32767 to 32767), or in hexadecimal (0x0000 to 0xFFFF).
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
5
5. Installation OF modbus rtu card
5. 1. ‘Com-Slots’ localisation
The « Com-Slots » integrates all communication interfaces and it is located on the right side.
2
1
Please, see on the manual of the concerned UPS to see the correct localisation of the «com slot 2»
5. 2. Modbus serial interface plug in
The serial interface should be plugged in the slot 2, and fixed with 2 crews.
5. 3. Modbus interface in parallel system configuration
There is only one MODBUS serial link interface for a parallel system configuration. One serial interface
is used for the whole installation. The access to the data of the UPS module or unit is managed by the
table addressing .
In a parallel installation with centralized bypass, it is recommended to install the serial card in slot 2
of the bypass.
6
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
Installation Inside UPS
5. 4. Connections and wiring
NOTE : there is only one connection per interface (RS232 or RS422 or RS485)
ENGLISH
5. 4.1. RS232 connection:
–– Standard PC connection
–– Sub-D 9 pins connector
–– Pin 2 :
Rx
–– Pin 3 :
Tx
–– Pin 5 :
GND
RTX + RTX -
5. 4.2. Isolated RS485 connection
–– 2 wires connection
–– « dip-switch 1 » allows connecting the terminal resistor
–– Insulation via “opto-coupler”
–– 2 polarization resistors could be removed easily (if needed).
the shield should be earthing at one point.
TX + TX 5. 4.3. Isolated RS422 connection
–– 4 wires connection
–– « dip-switch 1 and 2 » allows connecting the terminal
resistor
–– Insulation via “opto-coupler”
–– 4 polarization resistors could be removed easily (if needed).
RX + RX -
the shield should be earthing at one point.
Before making any connection, please check the cabling. A wrong connection or cabling can damage
the serial link interface.
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
7
Installation Inside UPS
5. 5. Com2 Serial link default settings
Baud rate: 9600 bauds
Parity: NONE
Data:
8 bits
Stop: 1 bit
Slave:1
The serial link settings can be set from the control panel.
5. 6. How to change the “serial link 2” settings ?
Available baud rate: 1200 - 2400 - 4800 - 9600 - 19200 bauds
Parity: EVEN - ODD - NONE
Slave number:
1 to 32
Please, see on the manual of the concerned UPS to see the correct localisation of the «com slot»
8
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
6. installation of MODBUS TCP CARD
6. 1. ‘Com-Slots’ localisation
ENGLISH
The « Com-Slots » integrates all communication interfaces and it is located on the right side.
2
1
Please, see on the manual of the concerned UPS to see the correct localisation of the «com slot 2»
6. 2. UPS Com2 Modbus Serial link default settings
Baud rate: 9600 bauds
Parity: NONE
Data:
8 bits
Stop: 1 bit
Slave:1
The serial link settings can be set from the control panel.
These settings are compulsory to make the Modbus TCP communication available
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
9
6. 3. default settings of the modbus tcp interface
DEFAULT SETTING
DHCP mode by default. No IP address set by default
Mode MODBUS TCP
Port TCP 502
CONFIGURATION SOFTWARE
Configuration tools are to be installed on a PC with WINDOWS. The setup programme is on the CD provided with
the interface. A
new programme group has been created.
SEARCHING UPS CONNECTED TO THE ETHERNET
The utility programme «Digi Device Discovery» is for viewing the IP and MAC addresses of each UPS.
ACCESSING HTTP PAGES
Data related to connection and module setting can be accessed using the web interface. The «home page» can be
opened either by means of the «Discovery» utility or the Internet browser by selecting the IP address indicated by
the «Discovery» utility..
Access to pages is protected by a «login» and a password.
Login by default: root
Password: dbps
DOWNLOADING FIRMWARE
By default, the module is programmed with the firmware for the MODBUS TCP function.
In case of «real port» mode, the firmware on the CD must first be downloaded.
For any other configurations, please refer to the DIGI® manual available on the CD.
10
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
7. Conventions
The table addresses are written in hexadecimal, beginning with ‘0x’.
Some PLC systems request a relative address starting from 400 (0x0190) or 40001 (0x9C41), on this address it’s
necessary to add the first address of the MODBUS table.
6. 4. Frame errors management
Error function code
Error code
80 + code function
1
Function error
80 + code function
2
Addresses error
80 + code function
3
Wrong data
80 + code function
6
busy
80 + code function
8
Write register error
ENGLISH
In case of wrong data request, the DELPHYS Green Power answers with the following frame error :
Cause
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
11
8. Modbus in Single UPS unit
TABLE
Start addresses Table length in words
MODBUS FUNCTION
UPS Identification
0x1100
32
3 READ
Date and hours
0x1360
4
3 READ
UPS Configurations
0x1200
16
3 READ
UNIT Status (64 bits)
0x1143
4
3 READ
UNIT Alarm (80 bits)
0x114A
5
3 READ
UNIT Measurements
0x1220
96
3 READ
Controls permission
0x1150
4
3 READ
UPS Controls
0x1190
4
6 WRITE
8. 1. How to read data
The identification, status and alarms tables should be read completely (this means the number of word to read is
equal to the table length).
The measurements table should be read word by word or per group, without exceed the length of the table. (from
0x1220 to 0x127F).
8. 2. Incoming data structure
Example of 6 words
1
2
3
4
5
6
7
8
9
10
11
12
MSB 0
LSB 0
MSB 1
LSB 1
MSB 2
LSB 2
MSB 3
LSB 3
MSB 4
LSB 4
MSB 5
LSB 5
WORD 0
WORD 1
WORD 2
WORD 3
WORD 4
WORD 5
b15b0
b15b0
b15b0
b15b0
b15b0
b15b0
S015S000
S031S016
S047S032
S063S048
S079S064
S095S080
A015A000 A031A016 A047A032
A063A048
M004
M005
M000
12
M001
M002
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
M003
Single unit ups
modbus tables
8. 3. Ups Identification: Address 0x1100, 32 Words
Description
Number
Address
Type
Remarks
I000
UPS identification
10 WORDS
0x1100
1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
I010
UPS Description
6 WORDS
0x110A
1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
I016
Location
6 WORDS
0x1110
1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
I022
Serial number
10 WORDS
0x1116
1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
ENGLISH
Code
8. 4. Date & Hours: Address 0x1360, 4 Words
Code
Description
Number
Address
Type
Remarks
D00
Minutes / seconds 1 WORDS
0x1360
Byte value
MSB = minutes, LSB = seconds
D01
Hours / day
0x1361
Byte value
MSB = day, LSB = hours
Month / day of
D02
week
D03
1 WORDS
MSB = month,
1 WORDS
0x1362
Byte value
LSB = day of the week
1=Monday...7=Sunday
Year
1 WORDS
0x1363
00 = 2000
8. 5. Ups Configuration: Address 0x1120, 16 Words
Code
Measurements
Unit
T000 Kind of equipment
Address
Remarks
0x1120
1= single unit, 3= parallel + centralised bypass
6 = modular parallel system
T001 UPS output power
kVA
0x1121
T002 Unit output power
kVA
0x1122
T003 Unit number
0x1123
1-8
T004 Number of Unit
0x1124
1-8
T005 UPS redundant
0x1125
0-1
T006 With battery
0x1126
0-1
T007 With flywheel
0x1127
0-1
T008
0x1128
T009 With genset
0x1129
T010
0x112A
T011
0x112B
T012
0x112C
T013 With rectifier input supply
0x112D
0-1
T014 Single
0x112E
0 = Tri, 1 = Single
T015 Measurements management
0x112F
0 = x 1, 1 = x 10
0-1
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
13
Single unit UPS Modbus Tables
8. 6. Unit Status: Address 0x1143, 4 Words
Code
Description
Address
0x1143
S048
Load on inverter
0
S049
Load on auto. Bypass
1
S050
Load on maintenance Bypass
2
S051
Load not supplied
3
S052
Unit is available
4
S053
Unit isolated from inst.
5
S054
Output switch Q2/3 closed
6
S055
Rectifier ON
7
S056
Battery charging
8
S057
Battery charged
9
S058
10
S059
Inverter ON
11
S060
Inverter switch/contactor closed
12
S061
Bypass switch activated
13
S062
14
S063
Servicing alert
15
S064
Rectifier input supply fault
0
S065
Bypass input supply out of tolerance
1
S066
Bypass input supply failure V/F 2
2
S067
Bypass input supply is synchro ref
3
S068
Ext. synchro ref (ACS on)
4
S069
Synchro forced on ACS
5
S070
“UPS general power off” input active
6
S071
Generator set active
7
S072
Unit in normal mode
8
S073
Unit in eco-mode
9
S074
S075
10
Unit in stand-by mode
11
S076
12
S077
13
S078
14
S079
14
Bit
Unit in servicing mode
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
15
0x1144
Remarks
Single unit UPS Modbus Tables
Description
Bit
Address
0x1145
S080
Unit Start procedure progress
0
S081
Unit maintenance bypass procedure progress
1
S082
Remarks
2
S083
Battery test interrupted
3
S084
Battery test in progress
4
S085
Battery test in stand-by
5
S086
6
S087
7
S088
8
S089
9
S090
10
S091
11
ENGLISH
Code
S092
Local maintenance bypass Q5 clos.
12
S093
Remote maintenance bypass closed
13
Only on parallel
S094
Q21 switch closed
14
Only on parallel
S095
Q22 switch closed
15
Only on parallel
S096
Auxiliary input 1 active
0
S097
Auxiliary input 2 active
1
S098
Auxiliary input 3 active
2
S099
Auxiliary input 4 active
3
S100
Auxiliary input 5 active
4
S101
Auxiliary input 6 active
5
S102
Auxiliary input 7 active
6
S103
Auxiliary input 8 active
7
S104
Auxiliary input 9 active
8
S105
Auxiliary input 10 active
9
S106
Auxiliary input 11 active
10
S107
Auxiliary input 12 active
11
S108
12
S109
13
S110
14
S111
Acknowledgement alarm request
0x1146
15
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
15
Single unit UPS Modbus Tables
8. 7. Unit Alarms: Address 0x114A, 4 Words
Code
A032
A033
A034
A035
A036
A037
A038
A039
A040
A041
A042
A043
A044
A045
A046
A047
A048
A049
A050
A051
A052
A053
A054
A055
A056
A057
A058
A059
A060
A061
A062
A063
A064
A065
A066
A067
A068
A069
A070
16
Description
Unit Imminent stop
Unit overload
Transfer blocked
Transfer impossible
Insufficient Resources
Rectifier critical
Inverter critical
Bypass critical
Common critical
FAN alarm
Back feed protection open
ACS synchro source fault
Operating on battery
Battery alarm
Battery room
Battery discharged
End of autonomy time
Battery test failure
Earth leakage fault
Battery circuit open
On battery with mains OK
DC voltage not OK
Rectifier preventive
Inverter preventive
Bypass preventive
Common preventive
Mimic panel
Ambient T° max
BHC general alarm
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
Bit
Address
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
0x114A
Remarks
Only on parallel
0x114B
0x114C
Single unit UPS Modbus Tables
A071
A072
A073
A074
A075
A076
A077
A078
A079
A080
A081
A082
A083
A084
A085
A086
A087
A088
A089
A090
A091
A092
A093
A094
A095
A096
A097
A098
A099
A100
A101
A102
A103
A104
A105
A106
A107
A108
A109
A110
A111
Description
Preventive maintenance
Maintenance bypass alarm
Rotation phase fault
Rectifier or Bypass Input supply not OK
Output since xx minutes on auto bypass
Unit General alarm
Fly Wheel disconnected
Fly Wheel Critical
Fly Wheel preventive
Aux. input alarm
kW - kVA configuration Error
Eco-mode configuration Error
Option board alarm
Bit
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Address
Remarks
ENGLISH
Code
0x114D
0x114E
If set
If set
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
17
Single unit UPS Modbus Tables
8. 8. Unit Measurements tables: Address 0x1220, 80 words
Code
M032
M033
M034
M035
M036
M037
M038
M039
M040
M041
M042
M043
M044
M045
M046
M047
M048
M049
M050
M051
M052
M053
M054
M055
M056
M057
M058
M059
M060
M061
M062
M063
M064
M065
M066
M067
M068
M069
M070
18
Description
Output voltage U12
Output voltage U23
Output voltage U31
Output voltage L1
Output voltage L2
Output voltage L3
Output current L1
Output current L2
Output current L3
Output frequency x10
Output Power factor L1
Output Power factor L2
Output Power factor L3
Output Active Power L1
Output Active Power L2
Output Active Power L3
Output Apparent Power L1
Output Apparent Power L2
Output Apparent Power L3
Output Crest Factor
Output load rate L1
Output load rate L2
Output load rate L3
Unit load rate
Unit Power S Output
Unit Power P Output
Rectifier input supply volt. U12
Rectifier input supply volt. U23
Rectifier input supply volt. U31
Rectifier V1
Rectifier V2
Rectifier V3
Rectifier input supply frequency x10
Rectifier input supply current L1
Rectifier input supply current L2
Rectifier input supply current L3
Inverter output voltage U12
Inverter output voltage U23
Inverter output voltage U31
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
Unit
Address
V
V
V
V
V
V
A
A
A
Hz
0x1220
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0x1230
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0x1240
1
2
3
4
5
6
kW
kW
kW
kVA
kVA
kVA
%
%
%
%
kVA
kW
V
V
V
V
V
V
Hz
A
A
A
V
V
V
Format
Format
T015=0
T015=1
###
###
###
###
###
###
# ###
# ###
# ###
##.#
+/- #.##
+/- #.##
+/- #.##
# ###
# ###
# ###
# ###
# ###
# ###
#.#
###
###
###
###
# ###
# ###
###
###
###
###
###
###
##.#
###.#
###.#
###.#
###
###
###
###
###
###
###
###
###
# ###.#
# ###.#
# ###.#
##.#
+/- #.##
+/- #.##
+/- #.##
# ###.#
# ###.#
# ###.#
# ###.#
# ###.#
# ###.#
#.#
###
###
###
###
# ###.#
# ###.#
###
###
###
###
###
###
##.#
###.#
###.#
###.#
###
###
###
Code
M071
M072
M073
M074
M075
M076
M077
M078
M079
M080
M081
M082
M083
M084
M085
M086
M087
M088
M089
M090
M091
M092
M093
M094
M095
M096
M097
M098
M099
M100
M101
M102
M103
M104
M105
M106
M107
M108
M109
M110
M111
Description
Format
T015=0
##.#
###
###
###
###
###
###
###.#
##.#
###
Format
T015=1
##.#
###
###
###
###
###
###
###.#
##.#
###
2
###
###.#
4
# ###
# ###.#
##.#
##.#
# ###
###
###
##.#
##.#
# ###.#
###
###
Unit
Address
Inverter frequency x10
Bypass input supply voltage U12
Bypass input supply voltage U23
Bypass input supply voltage U31
Bypass input supply voltage V1
Bypass input supply voltage V2
Bypass input supply voltage V3
Bypass input supply frequency x10
Ambient T°
Vdc +
Hz
V
V
V
V
V
V
Hz
°C
V
7
8
9
A
B
C
D
E
F
0x1250
Battery voltage string +
V
Battery current +
A
Battery T°
Average battery T°
Battery capacity
Battery capacity
Remaining backup time
°C
°C
Ah
%
mn
6
7
8
9
A
B
C
D
E
F
0x1260
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
ENGLISH
Single unit UPS Modbus Tables
19
Single unit UPS Modbus Tables
8. 9. Unit Enabled Controls Table: Address 0x1150; 1 Words
Code
V007
V008
V032
V033
V034
V035
V036
V037
V038
V039
V040
V041
V042
V043
V044
V045
Description
Eco-mode
Normal-mode
Unit Start procedure
Reserved
Make unit available
Switch load to inverter
Switch load to mains
Switch off unit output
Bit
7
8
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Rectifier on
Rectifier off
Inverter on
Inverter off
Battery test
Address
0x1150
Remarks
0x1152
8. 10. Controls Send To Ups: Address 0x1190, write 1 words
For a remote UPS control, it is necessary to set the serial interface in “remote” mode using ADICOM interface.
The control table below shows if the selected control is allowed or not. If the control sent to the UPS is not allowed,
the function will be ignored. Controls available by MODBUS connection:
Code
C007
C008
C032
C033
C034
C035
C036
C037
C038
C039
C040
C041
C042
C043
C044
C045
C046
C047
C048
20
Description
Eco-mode
Normal-mode
Unit Start procedure
Reserved
Make unit available
Switch load to inverter
Switch load to mains
Switch off unit output
Rectifier on
Rectifier off
Inverter on
Inverter off
Battery test
Bit To Write
7
8
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Address
0x1190
0
0x1193
Reset alarm
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
Remarks
0x1192
LOAD OFF IMMEDIATE!!
9. MODBUS IN modular PARALLEL SYSTEM CONFIGURATION
9. 1. Reminder
In UPS parallel system configuration, there is only one MODBUS interface. The addresses mapping gives the possibility to read data from each unit and system. There is no link between the MODBUS salve number and the unit
number.
ENGLISH
The interface is plugged in the UPS unit 1 “com slots 2” in case of modular system (see bellow).
1
2
3
MODBUS link setting
The setting of the link is made from the mimic panel unit where the board is plugged.
How to read data:
In the MODBUS table, one part is dedicated to UPS part; it means the data from the whole system.
This part is the same for each unit. Same data are present in the UPS fields addresses.
UNIT 1
UPS DATA
UNIT 1 DATA
UNIT 2
=
UPS DATA
UNIT 2 DATA
UNT 3
=
UPS DATA
UNIT 3 DATA
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
21
Modbus tables in modular parallel system configuration
9. 2. Modbus table in modular parallel system
Table
Start Addresses Table Length In Words
UPS Identification
0x0100
32
3 READ
Date and hours
0x0360
4
3 READ
UPS Configurations
0x0200
16
3 READ
UPS Status (48 bits)
0x0140
3
3 READ
UNIT Status (64 bits)
0xm143
4
3 READ
UPS Alarms (32 bits)
0x0148
2
3 READ
UNIT Alarm (80 bits)
0xm14A
5
3 READ
UPS Measurements
0x0200
32
3 READ
UNIT Measurements
0xm220
80
3 READ
Controls permission
0xm150
4
3 READ
UPS Controls
0xm190
4
6 WRITE
m = number of unit
Example:
0x3100 = ID of unit 3
0x3140 = UPS States
0x3143 = unit 3 states
9. 3. Ups Identification: Address 0x0100, 32 Words
See unit part
9. 4. Date & Hours: Address 0x0360, 4 Words
See unit part
9. 5. Ups Configuration: Address 0xm120, 16 Words
See unit part
9. 6. Preliminary Remarks
The UNIT data are the same as described for single unit.
Following tables describe only the UPS part (common for all units)
22
Modbus Function
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
Modbus tables in modular parallel system configuration
9. 7. Ups Status: Address 0x0140, 3 Words
Description
Bit
Address
0x0140
S000
Load supplied by inverter
0
S001
Load on automatic bypass
1
S002
Load on maintenance. Bypass
2
S003
Load not supplied
3
S004
Eco-mode
4
S005
Energy Saver
5
S006
UPS in normal mode
6
S007
UPS Starting procedure in progress
7
S008
UPS on maintenance bypass proc. in progress
8
S009
9
S010
10
S011
11
S012
UPS Bypass input supply absence
12
S013
UPS Rectifier input supply absence
13
S014
Remarks
ENGLISH
Code
Synthesis of all
units
14
S015
Remote control enabled
15
S016
Unit 1 operating
0
S017
Unit 2 operating
1
S018
Unit 3 operating
2
S019
Unit 4 operating
3
S020
Unit 5 operating
4
S021
Unit 6 operating
5
S022
Unit 7 operating
6
S023
Unit 8 operating
7
S024
8
S025
9
S026
10
S027
11
S028
12
S029
13
S030
14
S031
15
S032
Unit 1 available
0
S033
Unit 2 available
1
S034
Unit 3 available
2
S035
Unit 4 available
3
S036
Unit 5 available
4
S037
Unit 6 available
5
S038
Unit 7 available
6
S039
Unit 8 available
7
0x0141
0x0142
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
23
Modbus tables in modular parallel system configuration
9. 8. Ups Alarms: Address 0x0148, 2 Words
Code
24
Description
Bit
Address
0x0148
A000
UPS imminent stop
0
A001
UPS overload
1
A002
UPS transfer blocked
2
A003
UPS transfer impossible
3
A004
UPS insufficient Resource
4
A005
UPS Redundancy loss
5
A006
Parallel fault
6
A007
7
A008
8
A009
UPS: Battery alarm
9
A010
UPS on battery
10
A011
UPS: Battery discharge
11
A012
UPS: End of autonomy
12
A013
UPS: Temperature alarm
13
A014
14
A015
15
A016
Unit 1 general
0
A017
Unit 2 general
1
A018
Unit 3 general
2
A019
Unit 4 general
3
A020
Unit 5 general
4
A021
Unit 6 general
5
A022
Unit 7 general
6
A023
Unit 8 general
7
A024
8
A025
9
A026
10
A027
11
A028
12
A029
13
A030
14
A031
15
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
Remarks
synthesis of all unit
alarms
0x0149
Modbus tables in modular parallel system configuration
9. 9. Ups Measurements: Address 0x0200, 32 Words
Description
M000
Format
T015=0
Format
T015=1
Unit
Address
Output voltage U12
V
0x0200
###
###
M001
Output voltage U23
V
1
###
###
M002
Output voltage U31
V
2
###
###
M003
Output voltage L1
V
3
###
###
M004
Output voltage L2
V
4
###
###
M005
Output voltage L3
V
5
###
###
M006
Output current L1
A
6
# ###
# ###.#
M007
Output current L2
A
7
# ###
# ###.#
M008
Output current L3
A
8
# ###
# ###.#
M009
Output frequency x10
Hz
9
##.#
##.#
M010
Output Power factor L1
A
+/- #.##
+/- #.##
M011
Output Power factor L2
B
+/- #.##
+/- #.##
M012
Output Power factor L3
C
+/- #.##
+/- #.##
M013
Output Active Power L1
kW
D
# ###
# ###.#
M014
Output Active Power L2
kW
E
# ###
# ###.#
M015
Output Active Power L3
kW
F
# ###
# ###.#
M016
Output Apparent P. L1
kVA
0x210
# ###
# ###.#
M017
Output Apparent P. L2
kVA
1
# ###
# ###.#
M018
Output Apparent P. L3
kVA
2
# ###
# ###.#
M019
Output Crest Factor
3
#.#
#.#
M020
Output load rate L1
%
4
###
###
M021
Output load rate L2
%
5
###
###
M022
Output load rate L3
%
6
###
###
M023
UPS load rate
%
7
###
###
M024
UPS Output power
kVA
8
# ###
# ###.#
M025
9
M026
A
M027
B
M028
C
M029
D
M030
E
M031
F
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
ENGLISH
Code
25
Modbus tables in modular parallel system configuration
9. 10. Ups Enabled Controls Table: Address 0xm150, 2 Words
Code
Description
Bit
Address
UPS Start procedure
0
0xm150
Reserved
1
Transfer load to inverter
2
Transfer load to mains
3
UPS load off
4
Energy Saver ON
5
Energy Saver OFF
6
Eco-mode
7
Normal mode
8
Remarks
9
10
11
12
13
14
15
Remark: A bit set to 0 means that the control is disabled by the UPS. The control will be not executed.
9. 11. To Send Control To Ups: Address 0x15b0, Write 1 Words
For a remote UPS control, it is necessary to set the serial interface in “remote” mode using the Human Machine
Interface. Local controls are then locked.
The control table below shows if the selected control is allowed or not. If the control sent to the UPS is not allowed,
the function will be ignored.
Controls available by MODBUS connection:
Code
Control
Value to write
Address
UPS Start procedure
1
0xm190
Reserved
2
Transfer load to inverter
4
Transfer load to mains
8
UPS load off
16
Energy Saver ON
32
Energy Saver OFF
64
Eco-mode
128
Normal mode
256
512
26
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
Remarks
IMMEDIATE LOAD OFF !!
10.MODBUS IN PARALLEL SYSTEM with centralised bypass
10. 1. Reminder
In UPS parallel system configuration, there is only one MODBUS interface. The addresses mapping gives the possibility to read data from each unit and system. There is no link between the MODBUS salve number and the unit
number.
ENGLISH
The interface is plugged in the ‘com-slots 2’ of bypass cabinet.
By-pass
1
2
MODBUS link setting
The setting of the link is made from the mimic panel unit where the board is plugged.
How to read data:
In the MODBUS table, one part is dedicated to UPS part; it means the data from the whole system.
This part is the same for each unit. Same data are present in the UPS fields addresses.
BYPASS
UPS DATA
UNIT BYPASS (15)
UNIT 1
=
UPS DATA
UNIT 1 DATA
UNT 2
=
UPS DATA
UNIT 2 DATA
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
27
Modbus in parallel system with centralised bypass
10. 2. Modbus table in parallel system with centralised bypass
Table
Start Addresses Table Length In Words
UPS Identification
0x0100
32
3 READ
Date and hours
0x0360
4
3 READ
UPS Configurations
0x0200
16
3 READ
UPS Status (48 bits)
0x0140
3
3 READ
UNIT Status (64 bits)
0xm143
4
3 READ
UPS Alarms (32 bits)
0x0148
2
3 READ
UNIT Alarm (80 bits)
0xm14A
5
3 READ
UPS Measurements
0x0200
32
3 READ
UNIT Measurements
0xm220
80
3 READ
Controls permission
0xm150
4
3 READ
UPS Controls
0xm190
4
6 WRITE
m=1
- - - - number of module
m = 8
m = 15 Bypass data
Example:
0x3100 = ID of unit 3
0x3140 = UPS States
0xF143 = Bypass 3 states
10. 3. Ups Identification: Address 0x0100, 32 Words
See unit part
10. 4. Date & Hours: Address 0x0360, 4 Words
See unit part
10. 5. Ups Configuration: Address 0xm120, 16 Words
See unit part
10. 6. Preliminary Remarks
Following tables describe only the UPS part (common for all units)
28
Modbus Function
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
Modbus in parallel system with centralised bypass
10. 7. Ups Status: Address 0x0140, 3 Words
Description
Load supplied by inverter
Load on automatic bypass
Load on maintenance. Bypass
Load not supplied
Eco-mode
Energy Saver
UPS in normal mode
UPS Starting procedure in progress
UPS on maintenance bypass proc. in progress
UPS Bypass input supply absence
UPS Rectifier input supply absence
Remote control enabled
Module 1 operating
Module 2 operating
Module 3 operating
Module 4 operating
Module 5 operating
Module 6 operating
Module 7 operating
Module 8 operating
Bypass working
Module 1 available
Module 2 available
Module 3 available
Module 4 available
Module 5 available
Module 6 available
Module 7 available
Module 8 available
Bypass available
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
14
Address
0x0140
Remarks
ENGLISH
Code
S000
S001
S002
S003
S004
S005
S006
S007
S008
S009
S010
S011
S012
S013
S014
S015
S016
S017
S018
S019
S020
S021
S022
S023
S024
S025
S026
S027
S028
S029
S030
S031
S032
S033
S034
S035
S036
S037
S038
S039
S046
Synthesis of all
units
0x0141
0x0142
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
29
Modbus in parallel system with centralised bypass
10. 8. Ups Alarms: Address 0x0148, 2 Words
Code
Description
Address
0x0148
A000
UPS imminent stop
0
A001
UPS overload
1
A002
UPS transfer blocked
2
A003
UPS transfer impossible
3
A004
UPS insufficient Resource
4
A005
UPS Redundancy loss
5
A006
Parallel fault
6
A007
7
A008
8
A009
UPS: Battery alarm
9
A010
UPS on battery
10
A011
UPS: Battery discharge
11
A012
UPS: End of autonomy
12
A013
UPS: Temperature alarm
13
A014
14
A015
15
A016
Module 1 general
0
A017
Module 2 general
1
A018
Module 3 general
2
A019
Module 4 general
3
A020
Module 5 general
4
A021
Module 6 general
5
A022
Module 7 general
6
A023
Module 8 general
7
A024
8
A025
9
A026
10
A027
11
A028
12
A029
13
A030
Bypass alarm
A031
30
Bit
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
14
15
Remarks
synthesis of all unit
alarms
0x0149
Modbus in parallel system with centralised bypass
10. 9. Ups Measurements: Address 0x0200, 32 Words
Description
M000
Format
T015=0
Format
T015=1
Unit
Address
Output voltage U12
V
0x0200
###
###
M001
Output voltage U23
V
1
###
###
M002
Output voltage U31
V
2
###
###
M003
Output voltage L1
V
3
###
###
M004
Output voltage L2
V
4
###
###
M005
Output voltage L3
V
5
###
###
M006
Output current L1
A
6
# ###
# ###.#
M007
Output current L2
A
7
# ###
# ###.#
M008
Output current L3
A
8
# ###
# ###.#
M009
Output frequency x10
Hz
9
##.#
##.#
M010
Output Power factor L1
A
+/- #.##
+/- #.##
M011
Output Power factor L2
B
+/- #.##
+/- #.##
M012
Output Power factor L3
C
+/- #.##
+/- #.##
M013
Output Active Power L1
kW
D
# ###
# ###.#
M014
Output Active Power L2
kW
E
# ###
# ###.#
M015
Output Active Power L3
kW
F
# ###
# ###.#
M016
Output Apparent P. L1
kVA
0x0210
# ###
# ###.#
M017
Output Apparent P. L2
kVA
1
# ###
# ###.#
M018
Output Apparent P. L3
kVA
2
# ###
# ###.#
M019
Output Crest Factor
3
#.#
#.#
M020
Output load rate L1
%
4
###
###
M021
Output load rate L2
%
5
###
###
M022
Output load rate L3
%
6
###
###
M023
UPS load rate
%
7
###
###
M024
UPS Output power
kVA
8
# ###
# ###.#
M025
9
M026
A
M027
B
M028
C
M029
D
M030
E
M031
F
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
ENGLISH
Code
31
Modbus in parallel system with centralised bypass
10. 10.Ups Enabled Controls Table: Address 0xm150, 2 Words
Code
Description
Bit
Address
UPS Start procedure
0
0xm150
Reserved
1
Transfer load to inverter
2
Transfer load to mains
3
UPS load off
4
Energy Saver ON
5
Energy Saver OFF
6
Eco-mode
7
Normal mode
8
Remarks
9
10
11
12
13
14
15
Remark: A bit set to 0 means that the control is disabled by the UPS. The control will be not executed.
10. 11.To Send Control To Ups: Address 0x15b0, Write 1 Words
For a remote UPS control, it is necessary to set the serial interface in “remote” mode using the Human Machine
Interface. Local controls are then locked.
The control table below shows if the selected control is allowed or not. If the control sent to the UPS is not allowed,
the function will be ignored.
Controls available by MODBUS connection:
Code
Control
Value to write
Address
UPS Start procedure
1
0xm190
Reserved
2
Transfer load to inverter
4
Transfer load to mains
8
UPS load off
16
Energy Saver ON
32
Energy Saver OFF
64
Eco-mode
128
Normal mode
256
512
32
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
Remarks
IMMEDIATE LOAD OFF !!
11.Bypass TABLE
11. 1. Bypass Status: Address 0xF143, 4 Words
Description
Bit
Address
0xF143
S048
Load on inverter
0
S049
Load on auto. Bypass
1
S050
Load on maintenance Bypass
2
S051
Load not supplied
3
S052
4
S053
5
S054
Output switch 3 closed
6
S055
7
S056
8
S057
9
S058
10
S059
1
S060
12
S061
Bypass switch activated
S062
S063
13
14
Servicing alert
15
S064
0
S065
1
S066
2
S067
3
S068
4
S069
5
S070
6
S071
7
S072
Unit in normal mode
9
S074
10
S075
1
S076
12
S077
13
S078
14
Bypass in servicing mode
0xF144
8
S073
S079
Remarks
ENGLISH
Code
15
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
33
Bypass Tables
Code
Bit
Address
0xF145
S080
Starting
0
S081
Unit maintenance bypass procedure progress
1
S082
2
S083
3
S084
4
S085
5
S086
6
S087
7
S088
8
S089
9
S090
10
S091
Q4 closed
11
S092
Local maintenance bypass Q5 clos.
12
S093
Remote maintenance bypass closed
13
S094
14
S095
15
S096
Auxiliary input 1 active
0
S097
Auxiliary input 2 active
1
S098
Auxiliary input 3 active
2
S099
Auxiliary input 4 active
3
S100
Auxiliary input 5 active
4
S101
Auxiliary input 6 active
5
S102
Auxiliary input 7 active
6
S103
Auxiliary input 8 active
7
S104
Auxiliary input 9 active
8
S105
Auxiliary input 10 active
9
S106
Auxiliary input 11 active
10
S107
Auxiliary input 12 active
11
S108
12
S109
13
S110
14
S111
34
Description
Acknowledgement alarm request
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
15
0xF146
Remarks
Bypass Tables
11. 2. Bypass Alarms: Address 0xF14A, 4 Words
A032
A033
A034
A035
A036
A037
A038
A039
A040
A041
A042
A043
A044
A045
A046
A047
A048
A049
A050
A051
A052
A053
A054
A055
A056
A057
A058
A059
A060
A061
A062
A063
A064
A065
A066
A067
A068
A069
A070
Description
Unit Imminent stop
Unit overload
Transfer blocked
Transfer impossible
Insufficient Resources
Bypass critical
Common critical
FAN alarm
Back feed protection open
ACS synchro source fault
Bypass preventive
Bit
Address
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
0xF14A
Remarks
ENGLISH
Code
Only on parallel
0xF14B
0xF14C
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
35
Bypass Tables
Code
A071
A072
A073
A074
A075
A076
A077
A078
A079
A080
A081
A082
A083
A084
A085
A086
A087
A088
A089
A090
A091
A092
A093
A094
A095
A096
A097
A098
A099
A100
A101
A102
A103
A104
A105
A106
A107
A108
A109
A110
A111
36
Description
Preventive maintenance
Maintenance bypass alarm
Output since xx minutes on auto bypass
Bypass General alarm
Aux. input alarm
Option board alarm
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
Bit
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Address
Remarks
0xF14D
0xF14E
If set
Bypass Tables
11. 3. Bypass Measurements tables: Address 0xF220, 80 words
M032
M033
M034
M035
M036
M037
M038
M039
M040
M041
M042
M043
M044
M045
M046
M047
M048
M049
M050
M051
M052
M053
M054
M055
M056
M057
M058
M059
M060
M061
M062
M063
M064
M065
M066
M067
M068
M069
M070
Description
Output voltage U12
Output voltage U23
Output voltage U31
Output voltage L1
Output voltage L2
Output voltage L3
Output current L1
Output current L2
Output current L3
Output frequency x10
Output Power factor L1
Output Power factor L2
Output Power factor L3
Output Active Power L1
Output Active Power L2
Output Active Power L3
Output Apparent Power L1
Output Apparent Power L2
Output Apparent Power L3
Output Crest Factor
Output load rate L1
Output load rate L2
Output load rate L3
Unit load rate
Unit Power S Output
Unit Power P Output
Unit
Address
V
V
V
V
V
V
A
A
A
Hz
0xF220
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0xF230
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0xF240
1
2
3
4
5
6
kW
kW
kW
kVA
kVA
kVA
%
%
%
%
kVA
kW
Format
Format
T015=0
T015=1
###
###
###
###
###
###
# ###
# ###
# ###
##.#
+/- #.##
+/- #.##
+/- #.##
# ###
# ###
# ###
# ###
# ###
# ###
#.#
###
###
###
###
# ###
# ###
###
###
###
###
###
###
# ###.#
# ###.#
# ###.#
##.#
+/- #.##
+/- #.##
+/- #.##
# ###.#
# ###.#
# ###.#
# ###.#
# ###.#
# ###.#
#.#
###
###
###
###
# ###.#
# ###.#
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
ENGLISH
Code
37
Bypass Tables
Code
M071
M072
M073
M074
M075
M076
M077
M078
M079
M080
M081
M082
M083
M084
M085
M086
M087
M088
M089
M090
M091
M092
M093
M094
M095
M096
M097
M098
M099
M100
M101
M102
M103
M104
M105
M106
M107
M108
M109
M110
M111
38
Description
Bypass input supply voltage U12
Bypass input supply voltage U23
Bypass input supply voltage U31
Bypass input supply voltage V1
Bypass input supply voltage V2
Bypass input supply voltage V3
Bypass input supply frequency x10
Ambient T°
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
Unit
V
V
V
V
V
V
Hz
°C
Address
7
8
9
A
B
C
D
E
F
0xF250
1
2
3
4
6
7
8
9
A
B
C
D
E
F
0xF260
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Format
T015=0
###
###
###
###
###
###
###.#
##.#
Format
T015=1
###
###
###
###
###
###
###.#
##.#
12.Module TABLE
12. 1. Module Status: Address 0xm143, 4 Words
Code
S048
Description
Load on inverter
Bit
Address
0
0xm143
Remarks
1
S051
Load not supplied
3
S052
Module is available
4
S053
Module isolated from inst.
5
S054
Output switch 2 closed
6
S055
Rectifier ON
7
S056
Battery charging
8
S057
Battery charged
9
S058
10
S059
Inverter ON
11
S060
Inverter switch/contactor closed
12
S061
13
S062
14
S063
Servicing alert
15
S064
Rectifier input supply fault
0
S065
Bypass input supply out of tolerance
1
S066
S067
Bypass input supply is synchro ref
3
4
S069
5
S070
“UPS general power off” input active
6
S071
Generator set active
7
S072
Module in normal mode
8
S073
Module in eco-mode
9
S074
10
Module in stand-by mode
11
S076
12
S077
13
S078
14
S079
0xm144
2
S068
S075
ENGLISH
2
Module in servicing mode
15
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
39
Module Tables
Code
S080
Module Start procedure progress
Bit
Address
0
0xm145
S081
1
S082
2
S083
Battery test interrupted
3
S084
Battery test in progress
4
S085
Battery test in stand-by
5
S086
6
S087
7
S088
8
S089
9
S090
Q1 closed
10
S091
11
S092
12
S093
13
S094
Q21 switch closed
14
S095
Q22 switch closed
15
S096
Auxiliary input 1 active
0
S097
Auxiliary input 2 active
1
S098
Auxiliary input 3 active
2
S099
Auxiliary input 4 active
3
S100
Auxiliary input 5 active
4
S101
Auxiliary input 6 active
5
S102
Auxiliary input 7 active
6
S103
Auxiliary input 8 active
7
S104
Auxiliary input 9 active
8
S105
Auxiliary input 10 active
9
S106
Auxiliary input 11 active
10
S107
Auxiliary input 12 active
11
S108
12
S109
13
S110
14
S111
40
Description
Acknowledgement alarm request
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
15
0xm146
Remarks
Module Tables
12. 2. Module Alarms: Address 0xm14A, 4 Words
A032
A033
A034
A035
A036
A037
A038
A039
A040
A041
A042
A043
A044
A045
A046
A047
A048
A049
A050
A051
A052
A053
A054
A055
A056
A057
A058
A059
A060
A061
A062
A063
A064
A065
A066
A067
A068
A069
A070
Description
Unit Imminent stop
Module overload
Rectifier critical
Inverter critical
Common critical
FAN alarm
Back feed protection open
Operating on battery
Battery alarm
Battery room
Battery discharged
End of autonomy time
Battery test failure
Earth leakage fault
Battery circuit open
On battery with mains OK
DC voltage not OK
Rectifier preventive
Inverter preventive
Common preventive
Mimic panel
Ambient T° max
BHC general alarm
Bit
Address
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
0xm14A
Remarks
ENGLISH
Code
0xm14B
0xm14C
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
41
Module Tables
Code
A071
A072
A073
A074
A075
A076
A077
A078
A079
A080
A081
A082
A083
A084
A085
A086
A087
A088
A089
A090
A091
A092
A093
A094
A095
A096
A097
A098
A099
A100
A101
A102
A103
A104
A105
A106
A107
A108
A109
A110
A111
42
Description
Preventive maintenance
Rotation phase fault
Unit General alarm
Fly Wheel disconnected
Fly Wheel Critical
Fly Wheel preventive
Aux. input alarm
kW - kVA configuration Error
Eco-mode configuration Error
Option board alarm
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
Bit
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Address
Remarks
0xm14D
0xm14E
If set
If set
Module Tables
12. 3. Module Measurements tables: Address 0xm220, 80 words
M032
M033
M034
M035
M036
M037
M038
M039
M040
M041
M042
M043
M044
M045
M046
M047
M048
M049
M050
M051
M052
M053
M054
M055
M056
M057
M058
M059
M060
M061
M062
M063
M064
M065
M066
M067
M068
M069
M070
Description
Output voltage U12
Output voltage U23
Output voltage U31
Output voltage L1
Output voltage L2
Output voltage L3
Output current L1
Output current L2
Output current L3
Output frequency x10
Output Power factor L1
Output Power factor L2
Output Power factor L3
Output Active Power L1
Output Active Power L2
Output Active Power L3
Output Apparent Power L1
Output Apparent Power L2
Output Apparent Power L3
Output Crest Factor
Output load rate L1
Output load rate L2
Output load rate L3
Unit load rate
Unit Power S Output
Unit Power P Output
Rectifier input supply volt. U12
Rectifier input supply volt. U23
Rectifier input supply volt. U31
Rectifier V1
Rectifier V2
Rectifier V3
Rectifier input supply frequency x10
Rectifier input supply current L1
Rectifier input supply current L2
Rectifier input supply current L3
Inverter output voltage U12
Inverter output voltage U23
Inverter output voltage U31
Unit
Address
V
V
V
V
V
V
A
A
A
Hz
0xm220
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0xm230
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0xm240
1
2
3
4
5
6
kW
kW
kW
kVA
kVA
kVA
%
%
%
%
kVA
kW
V
V
V
V
V
V
Hz
A
A
A
V
V
V
Format
Format
T015=0
T015=1
###
###
###
###
###
###
# ###
# ###
# ###
##.#
+/- #.##
+/- #.##
+/- #.##
# ###
# ###
# ###
# ###
# ###
# ###
#.#
###
###
###
###
# ###
# ###
###
###
###
###
###
###
##.#
###.#
###.#
###.#
###
###
###
###
###
###
###
###
###
# ###.#
# ###.#
# ###.#
##.#
+/- #.##
+/- #.##
+/- #.##
# ###.#
# ###.#
# ###.#
# ###.#
# ###.#
# ###.#
#.#
###
###
###
###
# ###.#
# ###.#
###
###
###
###
###
###
##.#
###.#
###.#
###.#
###
###
###
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
ENGLISH
Code
43
Module Tables
Code
M071
M072
M073
M074
M075
M076
M077
M078
M079
M080
M081
M082
M083
M084
M085
M086
M087
M088
M089
M090
M091
M092
M093
M094
M095
M096
M097
M098
M099
M100
M101
M102
M103
M104
M105
M106
M107
M108
M109
M110
M111
44
Description
Format
T015=0
##.#
###
###
###
###
###
###
###.#
##.#
###
Format
T015=1
##.#
###
###
###
###
###
###
###.#
##.#
###
Unit
Address
Ambient T°
Vdc +
Hz
V
V
V
V
V
V
Hz
°C
V
7
8
9
A
B
C
D
E
F
0xm250
Battery voltage string +
V
2
###
###.#
Battery current +
A
4
# ###
# ###.#
##.#
##.#
# ###
###
###
##.#
##.#
# ###.#
###
###
Frequency inverter x10
Battery T°
Average battery T°
Battery capacity
Battery capacity
Remaining backup time
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
°C
°C
Ah
%
mn
6
7
8
9
A
B
C
D
E
F
0xm260
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
13.ANNEXE
13. 1.
4.5-1
setting of the interface using digi® device discovery
Search window for UPSs connected to the network
ENGLISH
Access to WEB pages
Network setting
4.5-2
Network settings
To set a specific
IP address
4.5-3
Access to HTTP pages
Login:root
Password:dbps
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
45
ANNEXE
4.5-4
Home Page
4.5-5
Updating of the firmware
Indicate directory of binary file
to be downloaded
Version of firmware:
MODBUS TCP:
82001164.bin
REAL PORT:
82000856_F5.bin
Click on
opens an on-line help window and a link to DIGI site if necessary.
After completing the downloading process, click on Reboot.
Wait for at least 1 minute before trying to access the interface.
46
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
ANNEXE
Problem during downloading process:
If the following screen appears during downloading, it is necessary to download the POST version of the firmware (available on the CD)
as well as the firmware.
Updating of the firmware
ENGLISH
4.5-6
13. 2. MODBUS TCP IDA specification
The JBUS frames below are only examples:
REQUEST BY MASTER IN MODE JBUS/MODBUS RTU
Original frame:
01 03 1034 0003 40C5
Encapsulated frame:
0046 0000 0006 01 03 1034 0003
where:
0046
corresponds to the transaction number
0000
corresponds to the protocol identifier
0006
corresponds to the number of bytes (length of the message)
Note:
The CRC is suppressed in the encapsulated MODBUS frame.
REPLY OF THE UPS IN MODE JBUS/MODBUS RTU:
Original frame:
01 03 06 0002 0184 0000 1960
Encapsulated frame:
0046 0000 0009 01 03 06 0002 0184 0000
where:
0046
corresponds to the transaction number
0000
corresponds to the protocol identifier
0006
corresponds to the number of bytes (length of the message)
Note: The CRC is suppressed in the encapsulated MODBUS frame.
DELPHYS GREEN POWER - Ref.: IOMDGPJB0910-GB_09
47
Socomec worldwide
HITCHIN HERTFORDSHIRE
CIRENCESTER
LONDON
Power Control & Energy Efficiency
Knowl Piece - Wilbury Way
Hitchin Hertfordshire SG4 0TY
Tel. 01462 440033
Fax 01462 431143
[email protected]
UPS
Units 7A-9A Lakeside Business Park
Broadway Lane - South Cerney
Cirencester - GL7 5XL
Tel. 01285 863300
[email protected]
UPS
Central Court
25 Southampton Buildings
London - WC2A 1AL
Tel. 020 3427 5107
[email protected]
in eUroPe
in asia PaciFic
in MiDDle easT
BELGIUM
PORTUGAL
AUSTRALIA
UNITED ARAB EMIRATES
UPS / Power Control & Energy Efficiency /
Solar
[email protected]
UPS / Solar
[email protected]
UPS
[email protected]
FRANCE
ROMANIA
CHINA
UPS / Power Control & Energy Efficiency /
Solar
[email protected]
UPS / Power Control & Energy Efficiency /
Solar
[email protected]
UPS / Power Control & Energy Efficiency
[email protected]
RUSSIA
Power Control & Energy Efficiency
[email protected]
Solar
[email protected]
UPS
[email protected]
UPS / Power Control & Energy Efficiency /
Solar
[email protected]
GERMANY
Power Control & Energy Efficiency
[email protected]
UPS
[email protected]
ITALY
Power Control & Energy Efficiency
[email protected]
Solar
[email protected]
UPS
[email protected]
NETHERLANDS
UPS / Power Control & Energy Efficiency /
Solar
[email protected]
UPS / Power Control & Energy Efficiency /
Solar
[email protected]
SLOVENIA
UPS / Power Control & Energy Efficiency /
Solar
[email protected]
SPAIN
INDIA
SINGAPORE
UPS / Power Control & Energy Efficiency
[email protected]
UPS / Power Control & Energy Efficiency /
Solar
[email protected]
THAILAND
TURKEY
VIETNAM
UPS / Power Control & Energy Efficiency /
Solar
[email protected]
UPS
[email protected]
UPS
[email protected]
S.A. SOCOMEC capital 10 816 800€
R.C.S. Strasbourg B 548 500 149
B.P. 60010 - 1, rue de Westhouse
F-67235 Benfeld Cedex - FRANCE
Tel. +33 3 88 57 41 41
Fax +33 3 88 74 08 00
[email protected]
www.socomec.co.uk
Power Control & Energy Efficiency
[email protected]
oTher coUnTries
NORTH AFRICA
Algeria / Morocco / Tunisia
[email protected]
AFRICA
Other countries
[email protected]
SOUTH EUROPE
Cyprus / Greece / Israel / Malta
[email protected]
[email protected]
MORE DETAILS
Power Control & Energy Efficiency
[email protected]