1C, Aluminium - General Cable

ENERGY CABLES
Electric Utility Cables
MV XLPE
6.35/11kV Aluminium XLPE
1C, Light Duty Screen
APPLICATION
Primary supply to urban networks.
STANDARD
PVC/HDPE suitable for installation direct
buried or unenclosed where subject to mechanical damage.
Suitable for glanding.
Light Duty Screen - A screen fault matching
the conductor fault up to a value of 2.6kA for
1 second, increasing thereafter with minimum screen coverage
requirements.
VOLTAGE
CONDUCTOR
INSULATION
SCREEN
SHEATH
MAX. OPERATING
TEMP.
ASNZS 1429.1
IEC 60502.2
6350/11000V
Compacted Aluminium
TR-XLPE
Annealed Copper Wire
Light Duty
PVC, 5V-90 or PVC, 5V-90 / HDPE
90 °C
TECHNICAL SPECIFICATIONS
CONDUCTOR
mm2
NO OF
STRANDS
NOMINAL
OVERALL
DIAMETER
mm
16
25
35
50
70
95
120
150
185
240
300
400
500
630
7
7
7
19
19
19
19
19
36
37
36
59
60
60
22.1
23.4
24.2
25.7
27.2
29.0
30.4
31.9
33.5
36.1
38.4
41.5
44.6
48.2
APPROX.
MASS
Kg/Km
BENDING RADIUS
MINIMUM
INSTALLED
mm
MINIMUM
DURING
INSTALLATION
mm
430
540
600
670
760
870
1000
1100
1250
1450
1650
1950
2350
2800
330
350
360
390
410
440
460
480
500
540
580
620
670
720
550
580
600
640
680
730
760
800
840
900
960
1040
1120
1210
New Zealand/Energy/Electric Utility Cables/MV XLPe/6.35-11kV/ Light Duty/1C, Aluminium │ VERSION:

Listed diameter, mass and bending radii are for
PVC/HDPE Composite Sheath.

Bending radius based on 25x OD (during
installation) and 15x OD (installed) for
PVC/HDPE sheath.

Bending radius may be lowered to 18x OD
(during installation) and 12x OD (installed) for
PVC sheath.

Lengths and packing can be supplied to
customer’s requirements.

For glanding details, contact your local
service centre.

NB: Stranding in compacted conductors may be
subject to minor variations.
TECHNICAL SPECIFICATIONS - Continued
CONDUCTOR
Nominal
Area
mm²
CURRENT RATING (A)
Unenclosed
Buried Direct
In Air
Buried In Ducts
(c)
A
ELECTRICAL CHARACTERISTICS
Max. DC
Max. AC
Equivalent
Resistance
Resistance
Star
@ 20°C
@ 90°C
Reactance
ohm/km
(trefoil
(trefoil
group) (d)
group) (d)
ohm/km
ohm/km
Star
Capacitance
µF/km
3 Phase
Voltage
Drop
mV/A.m
0.18
0.20
0.22
0.26
0.30
0.33
0.36
0.39
0.43
0.48
0.52
0.58
0.65
0.73
4.25
2.68
1.94
1.44
1.01
0.74
0.59
0.49
0.41
0.33
0.28
0.24
0.21
0.19
A
A
16
25
35
50
70
95
120
150
185
240
300
400
500
630
94
122
148
181
224
267
307
353
401
471
545
644
740
851
97
124
149
179
216
255
290
327
361
422
476
553
621
700
CONDUCTOR
ELECTRICAL CHARACTERISTICS
(CONT.)
NOM.
AREA
mm²
1 SEC FAULT RATING (b)
3 PHASE
SCREEN
SYMMETRICAL
kA
kA
MAX.
STRESS
kV/mm
16
25
35
50
70
95
120
150
185
240
300
400
500
630
1.5
2.4
3.3
4.7
6.6
9.0
11.3
14.2
17.5
22.7
28.4
37.8
47.2
59.5
2.4
2.2
2.1
2.0
1.9
1.9
1.8
1.8
1.7
1.7
1.6
1.6
1.6
1.6
1.5
2.4
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
94
119
142
173
207
243
276
311
347
399
449
517
581
653
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
2.45
1.54
1.11
0.822
0.568
0.411
0.325
0.265
0.211
0.161
0.130
0.102
0.0804
0.0639
0.151
0.141
0.132
0.126
0.119
0.112
0.108
0.106
0.103
0.0987
0.0959
0.0928
0.0897
0.0867
(a)
Based on 30°C ambient air temperature and where applicable,
burial depth of 0.8m, soil temperature of 15°C and thermal
resistivity of 1.2°Cm/W.
(b)
For fault durations other than one second, divide the
appropriate given value by the square root of the required time
(in seconds).
(c)
Based on a duct size of 100mm internal diameter.
(d)
Trefoil groups are bonded at both ends.

Screen fault ratings are based on an initial temperature of 80°C
and a final temperature of 250°C.

Conductor fault ratings are based on an initial temperature of
90°C and a final temperature of 250°C.
GENERAL CABLE NEW ZEALAND LIMITED
75 – 89 Main South Road
Riccarton, Christchurch
PO Box 8044, Riccarton, Christchurch, New Zealand
Phone:
0800 CABLES (0800 222 537)
FAX:
0800 242 267
EMAIL:
[email protected]
New Zealand/Energy/Electric Utility Cables/MV XLPe/6.35-11kV/Light Duty/1C, Aluminium │ VERSION: 1C Aluminium v050412
TECHNICAL SPECIFICATIONS - Continued
CONDUCTOR
SCREEN
NOMINAL
AREA
mm2
NOMINAL
DIAMETER
mm
MIN. AVERAGE
INSULATION
THICKNESS
mm
NOMINAL
DIAMETER OVER
INSULATION
SCREEN
mm
NUMBER &
DIAMETER
OF WIRES
PER CORE
NOMINAL
AREA
mm2
16
25
35
50
70
95
120
150
185
240
300
400
500
630
4.9
6.1
7.0
8.4
9.8
11.6
12.9
14.3
16.0
18.4
20.6
23.5
26.6
29.9
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
15.7
17.0
17.8
19.2
20.6
22.4
23.8
25.2
26.8
29.2
31.4
34.4
37.4
40.8
18 x 0.85
29 x 0.85
31 x 0.85
31 x 0.85
31 x 0.85
31 x 0.85
31 x 0.85
31 x 0.85
31 x 0.85
31 x 0.85
31 x 0.85
31 x 0.85
31 x 0.85
31 x 0.85
10.2
16.5
17.6
17.6
17.6
17.6
17.6
17.6
17.6
17.6
17.6
17.6
17.6
17.6
GENERAL CABLE NEW ZEALAND LIMITED
75 – 89 Main South Road
Riccarton, Christchurch
PO Box 8044, Riccarton, Christchurch, New Zealand
Phone:
0800 CABLES (0800 222 537)
FAX:
0800 242 267
EMAIL:
[email protected]
New Zealand/Energy/Electric Utility Cables/MV XLPe/6.35-11kV/Light Duty/1C, Aluminium │ VERSION: 1C Aluminium v050412