Terminology is important ! Draught draught is unwanted cooling of the body caused by air movement, which depends on the air speed, air temperature, turbulence intensity, activity and clothing of the building occupants. The predicted percentage of people dissatisfied due to annoyance by draught (DR) is limited to:10% for Class A and 20% for Class B and C environments, All of which prescribe a mean air velocity within 0.13 to 0.22m/s for a local air temperature of 24oC Don’t nod off just yet notes • “Sister strategies” – focused air delivery & mixing air delivery. • Cooling & energy performance is intrinsically linked to air diffusion because ultimately air diffusion influences suction pressures. • Air rarely moves predictably • “Air diffusion first” can often reveal opportunities for saving energy Natspec is OK, right? Specification elements for Indoor Air Quality & Comfort • Potential Diffusion features: • Air Diffuser Performance Index (ADPI) • Temperature • CO2 concentration • • Furniture off gassing • VOCs • Sick Building Syndrome Why is this important ? VAV System – Mixed flow ADPI – Zone control critical Displacement System – Mixed flow for low ceilings – Individual occupant control – Pollutants rise to extract • Chilled Ceiling – 100% outdoor air @ 1.5/L/s per m2 – Zone control Fundamentals are affected • AS1668.2 (Fresh air) does not standardize how well the air is diffused. • ISO7730 (PMV) does not specify velocities. • The use of PMV in ASHRAE 55 is limited to velocity< 0.2m/s. • Hot Air rises. • ACE is strongly driven by air patterns, OA, TD • The higher the ADPI, the higher the % of occupants satisfied w/ thermal conditions. • Design is for heating & cooling extremes & everywhere inbetween The “New Normal” “The pace of change in the workplace is such that the mindset and disposition of the worker is the Number 1 CEO concern…” THE FUTURE OF WORK /ASPEN INSTITUTE New systems with user interaction Comfort ...affects our performance Comfort ...differs between gender Air movement ...is fundamental This is normal Boss sits here! Comfort & Well‐being Complaints incl: Choice Productivity “Do you think having control of air movement will enhance or hinder productivity?” Control Air Diffusion Performance Index ADPI is the % of measurements within an occupied volume where the (Eff Draft Temperature) is between -1.5 to +1C of setpoint with air velocity <0.35m/s. Strategies • Focused air delivery • Mixing air delivery Focussed Delivery – workstation air Focussed Delivery – Workstation air 3500 Focussed Delivery‐ UFAD / Displacement Focussed Delivery‐ Displacement Mixing Delivery ‐ Flexibility Mixing Delivery – Wide Temperatures Types of Variable Air Volume Systems • VAV System – – – – – RSH < 200 W/m2 Supply air > 12°C S/R air < 10 K Standard Induction diffusers < 500 L/s per diffuser Low Temp VAV System – – – – – RSH < 200 W/m2 Supply air > 8°C S/R air < 16 K High induction air diffusers < 500 L/s per diffuser Variable Airflow & Coil Control Cool KW = 55 Sens & 47KW Latent COP = 3.1 Comp Input = 32.9 KW Airflow = 5050L/s Fan Energy 7.7KW absorbed Cool KW = 79.5 Sens & 19.9KW Latent COP = 4.2 Comp Input = 23.8 KW Airflow = 5050L/s Fan Energy 7.7KW absorbed What are we playing for? Combining entrainment and swirl Is combining focus and mixing Sinusoidal air movement is real Below brief, above brief and compliant 3 minutes later Airflow variation = arm wrestling between AHUs Pressure sensors Common Atrium/ Open space Equilibrium Try “Air Diffusion First” If I had my time again... Scenario Focussed or Mixed Advantages Large atrium or mall Mixed Little duct required Focussed UFAD / Task Air Mixed LT VAV High turndown capability Flexibility of diffuser placement Commercial office – high churn expectations 3.5 flr to flr Both Retail tenancies Mixed Try “Focussed” strategies first – they are intrinsically lower energy and duty. Where it is impractical (large retail or warehouse spaces), try mixing strategies. Where VAV turndown is important, try mixing and possibly motorised diffusers. Summary • Air Diffusion is essential to thermal comfort and air quality delivering air where people are. • Style of air diffusion is related to coil and airflow decisions & thus energy • Air rarely moves predictably. • Try looking “Air diffusion first” for a change. • Air diffusion needs to be deliberate in design. • Our clients are searching for higher levels of comfort & IAQ without energy penalty.
© Copyright 2025 Paperzz