Issue 6 - Sept 2005 Technical information for the Institute of Refrigeration Service Engineers’ Section Welcome to this issue of Service Matters Welcome to this issue of Service Matters in which we cover the mystery of superheat. For reliable and efficient refrigeration the correct degree of superheat must be achieved in the evaporator. Too much and you will have insufficient capacity, too little and you could carry liquid out of the evaporator into the compressor leading to mechanical failures. Subcooling is also important and will be covered in a future issue of Service Matters. Stephen Benton Superheat is the temperature of the vapour above its boiling point. Fig 1 As you can see by the diagram in Fig 1 water boils at 100°C. Any heat added to the steam above this temperature superheats it (and any temperature removed from the water below this temperature subcools it). Remember superheat does not mean ‘Hot’ it simply means above its boiling point. R134a boils at approx -26°C at atmospheric pressure, so whenever R134a is warmer than -26°C and at atmospheric pressure it is superheated. We calculate superheat by taking the difference between the actual exit temperature of the refrigerant from the evaporator (T2) and the saturated evaporating temperature (T1). It should be between 5 to 7K. Fig 2 shows us this. Superheated 100°C (Water boils) Subcooled Measuring Superheat This is very simple, all you need are the following tools: • A set of accurate gauges • An accurate electronic thermometer with a suitable touch/contact probe • A refrigerant comparator (comparators are available free of charge to all SES members) Fig 2 Service Matters is produced for the IOR Service Engineers’ Section by Cool Concerns Ltd Please contact Stephen Benton with any feedback at [email protected] For more details of Section membershipo see the web site at www.ior.org.uk Issue 6 - Sept 2005 Follow the steps below (also see Fig 3 & 4): 1. Put you gauges on the suction pipe as close to the evaporator outlet as possible. There is usually a connection if you look. 2. Take the suction pressure and using your comparator convert it into a saturated temperature (T1). Check you are using the ‘gauge scale’ and NOT the ‘Absolute’ scale. When measuring superheats of blends make sure you use the Dew or Vapour scale. 3. Take the actual temperature using your thermometer adjacent to the expansion device phial or sensing probe (T2). 4. Take the saturated evaporating temperature (comparator) from the measured evaporator outlet temperature, SH = T2 – T1. Fig 3 Fig 4 Example Superheat - Q • • • • R134a Evap pressure, 1.5 bar g Exit temp, 5°C Superheat? A superheat of between 5 and 7K will ensure that all the liquid refrigerant is boiled off in the evaporator and will not carry over to the compressor. 5°C Why is Superheat Important? •• Optimum Optimum evaporator evaporator performance performance • Zero liquid • Zero liquid return to return to compressor compressor Example Superheat - A • • • • • R134a Evap pressure, 1.5 bar g Evap temp, -4 °C Exit temp, 5°C Superheat, 5 –(-4) = 9K 5°C • Open or close valve to correct superheat (5K)? Answer: Open the valve to reduce the superheat – check with manufacturer’s instructions on valve and always re measure the actual superheat after every adjustment. Allow time for the valve to settle after adjustments.
© Copyright 2026 Paperzz