PG6AB-PG6AM - Structura Tunisie

• Core made of high density calcium sulphate and organic fibres, 30 mm thick, primed on
both upper and bottom surfaces (PG6A0).
• It is also available with aluminium foil 0.05 mm thick on bottom surface (PG6AM), or on
both upper and bottom surface (PG6AB0).
• Self-extinguishing and antisqueak ABS edge trim, 0.6 mm thick.
Panels
PG6AB-PG6AM
Covering: Various
Core: Inert Material
b Covering
a
600
c Calcium sulphate
600
Edge
core
e
a
Bottom surface
TECHNICAL DATA
Nominal dimension
(mm)
TOP SURFACE
Various
Weight
each
Fire reaction
Core building
material
Fire Resistance
Electrical
resistance
Acoustic: EN ISO 140
Conductivity λ
(core/cover)
a
b
c
e
kg
EN 13501-1
class
EN 13501-1
class
EN 13501-2
class
Ω
Dn,f,w(2)
Ln,f,w(2)
W/m °C
~30-32
~0.05-2
30
0.05
~16
Bfl-s1
A1
REI 30
≤ 2x10 ohm
dB 54
dB 40
0.41
9
(1) Value for panel with antistatic coverings. For conductive coverings consider 1.5x105 ÷ 1x107. For other coverings please ask Nesite staff.
(2) With finish; VM = 26 dB
MECHANICAL CHARACTERISTICS (Deflection ≤2.5 mm; Safety Factor ≥2)
SUBSTRUCTURE
Specification
DISTRIBUTED LOAD kN/m2 (3)
CONCENTRATED LOAD kN(2)
Working load(5)
MPS
2.80
MPL
3.20
MPM
3.50
MPH
3.80
BPC
4.20
Ultimate load kN(4)
4.50
5.50
6.50
8.00
9.00
EN 12825
1A2
1A2
2A2
3A2
4A2
MPS
20.00
MPL
22.00
MPM
25.00
MPH
30.00
BPC
32.00
(2) Load valid at any point of the system.
(3) Not provided by EN 12825.
(4) Ultimate load at the failure moment (tensile strenght).
(5) When the applied load is equivalent to to the working load the measured deflection must not exceed the value declared in accordance with the prospectus.
For Finished Floor Height FFH higher than 750 mm, please verify the real operating condition of the System.
MPS= without stringers, MPL= light stringers, MPM= medium stringers, MPH/BPC= high resistance special stringers
Prospectus 1
Legend standard EN 12825
Class
Ultimate load kN
1
2
3
4
5
6
≥4
≥6
≥8
≥9
≥ 10
≥ 12
DEFLECTION CLASS
SAFETY FACTOR
A=2.5 mm
2
B=3.0 mm
3
C=4.0 mm
FIELDS OF APPLICATION:
Offices, EDPs, control rooms, technical rooms with
medium/high load bearing requirements and any room
with particular fire resistance rate.
Transpack Group Service S.p.A. reserves the right to change technical data without notice
12
APPLICATION NOTES:
Suitable for homogeneous vinyl, rubber, linoleum, plastic
laminate, carpet and loose lay covering material (PG6A00PG6AB0).