Small Packaged Products 1-1/2 to 5 Tons (50/60 Hz) Accessory Motormaster II Head Pressure Controller Cancels: IIK 555A-18-36 IIK 555A-18-37 6–02 Installation Instructions Part Numbers CPLOWAMB001A00, CPLOWAMB002A00 NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Installation, start-up and servicing of this equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.) Only trained, qualified installers and service technicians should install, start up, and service this equipment. When working on this equipment, observe precautions in the literature, tags, stickers, and labels attached to the equipment, and any other safety precautions that may apply. DESCRIPTION AND USAGE The Motormaster II head pressure controller is a cycle control device activated by a temperature sensor mounted on a header tube of the outdoor coil (see Fig. 1). It is designed to cycle the outdoor-fan motors to maintain the saturated condensing temperature within normal operating limits of approximately 130 to 110°F high, 70 to 50°F low (55–43°C high, 21 to 10°C low). The controller maintains working head pressure at low ambient temperatures down to –20°F when properly installed. INSTALLATION 1. Disconnect power to unit. Install lockout tag. 2. Remove unit access panel. 3. Disconnect outdoor-fan motor (OFM). (See Wiring Schematic, Fig. 8 or 9) Open all remote disconnects before servicing this equipment. Electrical shock could result in serious injury or death. INTRODUCTION These instructions cover the installation of the Motormaster II Controller head pressure control device. Refer to the Installation section for directions. Louvered panels are required for this installation; see Note 9 in the Installation section of this document and Tables 1 and 2 for more information. Table 1—Add Louvered Panels to These Units 48GS 48GX 50GS 50GX 50JS 50JX 582A 583A 701A 702A 601A 602A PY1P-B PY2P-B PA1P-B PA2P-B PH1P-B PH2P-B Table 2—Do NOT Add Louvered Panels to These Units 50SX 50HX 50ZP 50ZH 48GP* 50GL* 50JZ* 48JZ* 557A 657A 564A 664A 583B* 702B* 602B* 683B* PA1Z PH1Z 4. Remove OFM wires from unit control box. 5. Mount Motormaster II Controller on unit. Refer to Fig. 3–6. The controller must be mounted vertically with the leads at the bottom. Using the Mounting Template (Fig. 10) as a guide, drill mounting holes. To ensure electrical ground, insert star washers (supplied with the controller) under the heads of mounting screws. NOTE: Field-supplied conduit must be used between controller and access panel (or wire into unit entrance). 6. Determine sensor location by referring to Fig. 11–25. Route sensor wire through bottom of Motormaster II Controller (Fig. 1.) to sensor location specified. Prior to installation, apply conductive grease supplied with accessory to contact surface of sensor. Sensor assembly is delicate. Handle with care. 7. Attach sensor to top half of header tube as shown in Fig. 2. Installed sensor must be left uninsulated. 8. Power wiring must comply with all local and National Electrical Code (NEC) and International Electric Code (IEC) requirements. Refer to Fig. 8 and 9 for power wiring connections. Coil up all excess wire and secure. (Yellow and blue wires, from controller, must run to unit contactor and connect on the load side.) * Louvered panels are standard on these units. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 1 4 1 4 PC 101 Catalog No. 534–80118 Printed in U.S.A. Form 48/50–105SI Pg 1 6–02 Replaces: 48/50–101SI Tab 1a 6a 1b 6b 5a 5a Motormaster® II Controller Interior C00102 Fig. 1—Controller Interior SENSOR INTEGRAL WIRE TIE 3/8" HEADER TUBE CONDUCTIVE GREASE NOTE: INSTALLED SENSOR MUST BE LEFT UNINSULATED. Sensor Connection Details C00103 Fig. 2—Sensor Connection Details condensing temperature approximately 20°F higher than the standard operating mode. In this alternate mode, the outdoor fan begins cycling at higher outdoor ambient temperatures. This mode should only be used if the evaporator coil shows signs of frosting at low outdoor ambient temperatures. All wires must be secured so that they are not in contact with unit tubing. 9. To prevent wind cross-currents from causing abnormally low condensing temperatures, louvered panels are required on some models. See Table 1 and 2 for models requiring/not requiring louvered panels. To select the alternate operating mode, move the jumper wire on the Motormaster II control board from reset T1 to reset T2. Refer to Fig. 7 for thermistor resistance vs. temperature. 10. Reconnect power to the unit. The Motormaster II head pressure controller is equipped with an alternate operating mode. When this mode is selected, the controller shifts the fan cycle sequence to effectively raise the average 2 MOTORMASTER II WIRE LEADS BULKHEAD COMPRESSOR CONDENSER COIL MOTORMASTER II SLICE PLASTIC SERVICE CAP DN UNIT AND FEED LEADS 50ZP, ZH, 564A/664A, PA1Z/PH1Z UNITS C00108 Fig. 3—Mounting Locations 1 3/8” EVAP COIL ACCESS PANEL MOTORMASTER II CONTROLLER MOTORMASTER II CONTROLLER CONDUIT 6” FROM BOTTOM OF UNIT CONDUIT HOLE LOCATION FOR CONDUIT CONNECTION 50SX/ 557A 50HX/ 657A C00141 Fig. 4—Mounting Locations 3 BULKHEAD MOTORMASTER II MOTORMASTER II WIRE LEADS SLICE PLASTIC SERVICE CAP ON UNIT AND FEED LEADS COMPRESSOR 48/50GS, GX, JS, JX, GP, GL, JZ UNITS 582A/701A, 583A/702A, 601A, 602A, 583B, 702B, 602B,683B PY1P-B/PA1P-B, PY2P-B/PA2P-B, PH1P-B, PH2P-B SMALL CABINET C00109 Fig. 5—Mounting Locations-Small Cabinet BULKHEAD MOTORMASTER II MOTORMASTER II WIRE LEADS SLICE PLASTIC SERVICE CAP ON UNIT AND FEED LEADS COMPRESSOR 48/50GS, GX, JS, JX, GP, GL, JZ UNITS 582A/701A, 583A/702A, 601A, 602A, 583B, 702B, 602B, 683B PY1P-B/PA1P-B, PY2P-B/PA2P-B, PH1P-B, PH2P-B LARGE CABINET C00110 Fig. 6—Mounting Locations-Large Cabinet 4 Table 3—Sensor Mounting Locations MODEL NUMBER 50JX/602A/PH2P-B 024-048 50JX/602A/PH2P-B 060 and 50JS/601A/PH1P-B 018-030 50JS/601A/PH1P-B 036-060 48GS/582A/PY1P-B/50GS/701A/PA1P-B 018-036 and 48GX/583A/PY2P-B/50GX/702A/PA2P-B 024-030 48GS/582A/PY1P-B/50GS/701A/PA1P-B 042-060 and 48GX/583A/PY2P-B/50GX/702A/PA2P-B 036-060 48GP/50GL/583B/702B 024-048 and 50GL 024-048 48GP/50GL/583B/702B 060 48/50JZ/683B/602B 024–060 50ZP/564A/PA1Z 024–042 50ZP/564A/PA1Z 048–060 50ZH/664A/PH1Z 024–042 50ZH/664A/PH1Z 048–060 50SX/557A 024–060 50HX/657A 048–060 50HX/657A 024–042 FIGURE NUMBER Fig. 11 Fig. 12 Fig. 13 Fig. 14 Fig. 15 Fig. Fig. Fig. Fig. Fig. Fig. Fig. Fig. Fig. Fig. 16 17 18 19 20 21 22 23 24 25 50,000 RESISTANCE (OHMS) 40,000 30,000 20,000 10,000 0 20 40 60 80 100 120 140 TEMPERATURE (F) Thermistor Rsistance vs Temperature C00104 Fig. 7—Thermistor Resistance vs. Temperature Chart 5 OUTDOOR-FAN MOTOR SINGLE-PHASE UNITS 3-PHASE UNITS UNIT CONTROL BOX UNIT CONTROL BOX C BLK YEL C L1 T1 21 L2 21 BRN C BLK T2 23 BLK 23 THIS WIRE RELOCATED FROM BASE UNIT CONTACTOR YEL YEL 048.060 UNITS YEL YEL YEL VIEW A YEL BLU VIEW A 208/230-V UNITS ONLY MOTORMASTER II CONTROL BOX OFC BLK OF1 OF2 DR BLU ORANGE RED YEL BLK 460 L2 208 230 T2 LOW VOLTAGE CONTROL BOX* BLK OFC T1 L1 O C C TRAN (SEE NOTE #1) 460-V UNITS ONLY BLK A 24 RED BRN OFR 1 3 C GRN-YEL 3 R C C1 OFC C2 ORG COIL 4 1 (SEE NOTE #2) 5 BRN LOGIC BOARD BLU W1 LEGEND C DR OFC OFR TRAN T2 S2 YEL T1 S1 YEL RELOCATE JUMPER TO TERMINAL T2 FOR ALTERNATE OPERATION. Field supplied relay for all Heat pumps should be located in the control box of the unit. CONTROL THERMISTOR Contactor Defrost Relay Outdoor-Fan Contactor Outdoor-Fan Relay Transformer Field Wiring *In low voltage control box, “O” is orange and “C” is Brown (common). NOTES: 1. Motomaster® II transformer is wired for 460-v supply; it must be rewired for 208/230-v application. Be sure to insulate unused tap. 2. Relay, part no. HN61KB324, is field supplied and normally closed. 3. CPLOWAMB002A00 transformer only contains a 400-v. supply. C00106 Fig. 8—Wiring Schematic, Heat Pumps 6 OUTDOOR-FAN MOTOR SINGLE-PHASE UNITS 3-PHASE UNITS UNIT CONTROL BOX UNIT CONTROL BOX C L1 BLK C T1 21 C L2 BLU T2 23 BLU YEL THIS WIRE RELOCATED FROM BASE UNIT CONTACTOR YEL MOTOMASTER CONTROL BOX BLK SEE NOTE 460 230 OFC L2 ORANGE RED YEL 208 A BLK L1 T1 C C 24 RED BRN GRN-YEL C1 R T2 OFC OFC C2 C ORG BRN LOGIC BOARD W1 T2 S2 YEL T1 S1 YEL RELOCATE JUMPER TO TERMINAL T2 FOR ALTERNATE OPERATION CONTROL THERMISTOR LEGEND C - Contractor OFC - Outdoor- Fan Contactor TRAN - Transformer NOTE: 1. Motormaster® II is wired for 460-v supply; it must be rewired for 208/230-v application. Be sure to insulate unused tap. 2. CPLOWAMB002A00 Transformer only contains a 400V supply. C00140 Fig. 9—Wiring Schematic, AC and Gas PACs 7 MOUNTING TEMPLATE 5-3/8" REF [136.5] TOP CUT ALONG SOLID BORDER LINES TO REMOVE TEMPLATE DRILL 9/64" [3.6] DIAMETER HOLE 9" REF [228.6] TEMPLATE FOR MOTORMASTER® II CPLOWAMB001A00 NOTE: Dimensions in [ ] are in millimeters 5" [127] DRILL 9/64" [3.6] DIAMETER HOLE 2-3/8" REF [60.3] 1-1/8" REF [28.6] C00105 Fig. 10—Controller Mounting Template 8 SENSOR LOCATION SENSOR LOCATION 50 JX, 602A, PH2P-B 024 Left Back 50 JX, 602A, PH2P-B 042 Left Back SENSOR LOCATION SENSOR LOCATION 50 JX, 602A, PH2P-B 030/036 Left Back 50 JX, 602A, PH2P-B 048 Left Back C00111 Fig. 11—Sensor Mounting Location SENSOR LOCATION SENSOR LOCATION 50JX, 602A,PH2P-B 060 LEFT BACK 50JS, 601A,PH1P-B 024 LEFT BACK SENSOR LOCATION SENSOR LOCATION 50JS, 601A,PH1P-B 018 LEFT BACK 50JS, 601A,PH1P-B 030 LEFT BACK Fig. 12—Sensor Mounting Location 9 C00112 SENSOR LOCATION SENSOR LOCATION 50JS.601A.PHIP-B 036 50JS.601A.PHIP-B 048 LEFT BACK LEFT BACK SENSOR LOCATION SENSOR LOCATION 50JS.601A.PHIP-B 042 50JS.601A.PHIP-B 060 LEFT BACK LEFT BACK Fig. 13—Sensor Mounting Location 10 C00113 SENSOR LOCATION RETURN BEND END 48GS, 582A, PY1P-B, 50GS, 701A, PA1P-B, 018, 024, 030 & 036 48GX, 583A, PY2P-B, 024, 50GX, 702A, PA2P-B, 024 LEFT BACK SENSOR LOCATION RETURN BEND END 50/48GX030, 702A/583A030, PA2P/PY2P 030 (B SERIES) LEFT BACK C00114 Fig. 14—Sensor Mounting Location 11 SENSOR LOCATION SENSOR LOCATION 48GS.582A,PY1PB042 50GS,701A,PY2PB042 48GX,583A,PY2P-B 036 50GX,702A,PA2P-B 036 LEFT BACK 50/48GS048 701A/582A048 PA1P/PY1P048 (B SERIES) LEFT BACK RETURN BEND END RETURN BEND END SENSOR LOCATION SENSOR LOCATION 50/48GS/060 RETURN BEND END 701A/582A060 PA1P/PY1P060 48/50GX042&048 583A/702A042&048 PY2P/PA2P042&048 (B SERIES) LEFT BACK Fig. 15—Sensor Mounting Location 12 48/50GX060 RETURN BEND END 702A/582A/583A060 PA2P/PY1P/PY2P060 (B SERIES) LEFT BACK C00115 SENSOR LOCATION SENSOR LOCATION 48GP024/50GL024 583B024/702B024 LEFT BACK 48GP030/50GL030 583B030/702B030 LEFT BACK SENSOR LOCATION SENSOR LOCATION 48GP036/50GL036 583B036/702B036 LEFT BACK 48GP042, 048/50GL042, 048 583B042, 048/702B042, 048 LEFT BACK C00116 Fig. 16—Sensor Mounting Location 13 SENSOR LOCATION 48GP060/50GL060 583B060/702B060 LEFT BACK C00117 Fig. 17—Sensor Mounting Location SENSOR LOCATION SENSOR LOCATION 48/50JZ024 683B/602B024 LEFT BACK 48/50JZ030, 036 683B/602B030, 036 LEFT BACK SENSOR LOCATION SENSOR LOCATION 48/50JZ042, 048 683B/602B042, 048 LEFT BACK 48/50JZ060 683B/602B060 LEFT BACK C00118 Fig. 18—Sensor Mounting Location 14 SENSOR LOCATION SENSOR LOCATION 50ZP, 564A, PA1Z030 50ZP, 564A, PA1Z024 SENSOR LOCATION SENSOR LOCATION 50ZP, 564A, PA1Z036 50ZP, 564A, PA1Z042 C00119 Fig. 19—Sensor Mounting Location 15 SENSOR LOCATION SENSOR LOCATION 50ZP/564A/PA1Z048 50ZP/564A/PA1Z060 Fig. 20—Sensor Mounting Location C00120 SENSOR LOCATION SENSOR LOCATION 50ZH/664A/PH1Z030 50ZH/664A/PH1Z024 SENSOR LOCATION SENSOR LOCATION 50ZH/664A/PH1Z036 50ZH/664A/PH1Z042 C00121 Fig. 21—Sensor Mounting Location 16 SENSOR LOCATION 50ZH/664A/PH1Z060 SENSOR LOCATION 50ZH/664A/PH1Z048 C00122 Fig. 22—Sensor Mounting Location 17 SENSOR LOCATION SENSOR LOCATION 50SX/557A 024 50SX/557A 030/036 SENSOR LOCATION SENSOR LOCATION 50SX/557A 042/048 50SX/557A 060 C00123 Fig. 23—Sensor Mounting Location 18 Sensor Location Sensor Location 50HX/657A/060 50HX/657A/048 C00127 Fig. 24—Sensor Mounting Location Sensor Location Sensor Location 50HX/657A024 50HX/657A030 Sensor Location Sensor Location 50HX/657A042 50HX/657A036 C00128 Fig. 25—Sensor Mounting Location 19 Copyright 2002 Carrier Corporation 555a1837 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 1 4 1 4 PC 101 Catalog No. 534–80118 Printed in U.S.A. Form 48/50–105SI Pg 20 6–02 Replaces: 48/50–101SI Tab 1a 6a 1b 6b 5a 5a
© Copyright 2026 Paperzz