INSTALLATION INSTRUCTIONS FOR MARSHALL-DEKALB ELECTRIC COOPERATIVE MOBILE HOME OVERHEAD SERVICE 05-18-2004 WIRE GUIDELINES CHART-MOBILE HOMES DISCONNECT COPPER WIRE ALUMINUM WIRE CONDUIT SIZE 100 AMP #2 #2 1 1/4" 200 AMP 3/0 4/0 2" EQUIPMENT GROUND #6 MOBILE HOME CHECKLIST #4 MDEC DOES NOT ALLOW ANY TYPE OF METER BASE TO BE MOUNTED ON THE SIDE OF THE MOBILE HOME WEATHERHEAD IS THERE AN OUTSIDE DISCONNECT ADJACENT TO THE METER BASE RATED FOR MAIN BREAKER INSIDE MOBILE HOME MIN. 18" LEADS OUT OF WEATHERHEAD IS THERE A FOUR WIRE SERVICE FROM THE DISCONNECT INTO THE MOBILE HOME (EQUIPMENT GROUND) CLAMPS IS THE POLE AT LEAST 16 FEET TALL AND AT LEAST FIVE INCHES IN DIAMETER? OR, IS THE POLE 16 FEET AND AT LEAST SIX BY SIX PRESSURE TREATED? HUB WITH RAINTIGHT ADAPTER 12'-0" OR PVC MALE ADAPTER SERVICE ENTRANCE CABLE (GRAY INSULATION) IS THE POLE SET AT LEAST FOUR FEET OR STRANDED INSULATED CONDUCTORS IN SCHEDULE 40 PVC CONDUIT MOBILE HOME INTO THE GROUND? IS THE POLE SET SO THAT THE WIRES TO THE WEATHER HEAD DO NOT CROSS THE ROOF MAIN DISCONNECT/METER BASE AMPERAGE OF THE MOBILE HOME? EQUIVALENT TO SWITCH BOX INSIDE MOBILE HOME 5'-6" ARE THE METER BASE AND DISCONNECT MOUNTED ON PRESSURE TREATED MATERIAL? 16' TREATED CREOSOTE POLE No. 4 (Minimum) COPPER GROUNDWIRE FROM GROUND ROD INTO DISCONNECT MAIN PANEL ARE THE METER AND DISCONNECT INSIDE MOBILE HOME MOUNTED WITH TWO-INCH LAG BOLTS? ARE THE WIRES IN CONDUIT AT ALL POINTS SCHEDULE 40 PVC CONDUIT ALL THE WAY TO MAIN THAT THEY ARE ABOVE THE GROUND? INSIDE MOBILE HOME NOTE: DO NOT USE SHIELDED ENTRANCE CABLE IN CONDUIT (GRAY INSULATION) 30'-0" MAXIMUM DISTANCE FROM MOBILE HOME IS THE WIRE APPROVED FOR UNDERGROUND SERVICE? NOTE: DO NOT USE SHIELDED ENTRANCE CABLE GROUND LEVEL 4'-0" GROUND CLAMP FOR DIRECT BURIAL 24" EQUIPMENT GROUND MARKED WITH GREEN MINIMUM #6 COPPER OR #4 ALUMINUM GROUND ROD 5/8" x 8'-0" USE PENATROX OR OXYGUARD ON ALL ALUMINUM CONNECTIONS USE DIRECT BURIAL TYPE CABLE WITH 4th WIRE GROUND TYPICAL SERVICE MAST INSTALLATION 05-18-2004 100 AMP - #2 SINGLE INSULATED COPPER WEATHERHEAD OR #2 INSULATED ALUMINUM 200 AMP - 3/0 INSULATED COPPER OR 4/0 INSULATED ALUMINUM #4 BARE COPPER SHEET METAL FLASHING BOLTS THRU STUD 2" RIGID CONDUIT 12'-0" MIN. ABOVE GROUND ELECTRICAL PANEL SITE METER SOCKET BUILT STUCTURE CHECKLIST DOES THE CONDUIT FOR THE SERVICE EXTEND AT LEAST 18" ABOVE THE ROOF? IF THE CONDUIT EXTENDS CONTINUE ABOVE THE ROOF, IS IT CONDUIT TO GALVANIZED CONDUIT? SWITHCHBOX OR USE SHIELDED ENTRANCE CABLE GROUND WIRE (GRAY INSULATION) #4 BC IN CONTINUOUS LENGTH NOTE: IF THE CONDUIT DOES NOT 5'-6" UP TO WEATHERHEAD DO NOT INSTALL EXTEND ABOVE THE ROOF, HAS A EYEBOLT BEEN INSTALLED THROUGH A FRAMING MEMBER? IF THE CONDUIT RISER HAS A SPLICE, DOES THE SPLICE SHIELDED ENTRANCE CABLE OCCUR WITHIN FOUR FEET OF (GRAY INSULATION) IN CONDUIT THE METER BASE? GROUND ROD CLAMP GROUND LEVEL IS THE METER BASE INSTALLED SO THAT THE WIRES TO THE WEATHER HEAD DO NOT CROSS THE ROOF GROUND ROD, 5/8" X 8' GALV. IS THE METER BASE INSTALLED AT THE CORRECT HEIGHT - 5 1/2 FEET USE PENATROX OR OXYGUARD ON ALL ALUMINUM CONNECTIONS TEMPORARY SERVICE (240 VOLTS) RESIDENTIAL CONSTRUCTION WEATHERHEAD 100 AMP. No. 2 SINGLE CONDUCTOR INSULATED COPPER OR #2 ALUMINUM EQUIVALENT. 200 AMP. #3/0 SINGLE CONDUCTOR INSULATED COPPER OR #4/0 ALUMINUM EQUIVALENT. SE CABLE STRAPS TEMPORARY POLE CHECKLIST IS THE POLE AT LEAST 16 FEET TALL AND AT LEAST FIVE INCHES IN DIAMETER? OR, IS THE POLE 16 FEET AND AT LEAST SIX BY SIX PRESSURE TREATED? RE O YWI IS THE POLE SET AT LEAST FOUR FEET INTO THE GROUND? IS THE RECEPTACLE A GROUND FAULT INTERRUPT TYPE, OR IS IT FED BY A GROUND FAULT INTERRUPT BREAKER? IS THE RECEPTACLE IN A WEATHERPROOF BOX? SE CABLE " GU 12'-0" R BR ACE NOTE: OPTION IS 5' GAL. OR AL. CONDUIT WITH CONDUIT STRAPS CONTAINING WIRE FROM METER SOCKET TO WEATHERHEAD. 12'-0 ARE THE WIRES FROM THE RECEPTACLE TO THE DISCONNECT RUN IN CONDUIT? 6'-0" MAX. METER SOCKET AMPERAGE EQUIVALENT TO SWITCH BOX. SWITCH BOX (AMPERAGE DETERMINATION ACCORDING TO USE. MIN. 60 AMPS.) 5'-0" MIN. DUPLEX OUTLETS W/GFI 16' TREATED CREOSOTE POLE No. 4 (MIN.) COPPER GROUNDWIRE FOR 100 AMP SERVICE. No. 2 COPPER FOR 200 AMP. GROUND LEVEL GROUND CLAMP 4'-0" GROUND ROD 5/8" x 8'-0" IS THE POLE BRACED PROPERLY UNDERGROUND SERVICE TO MOBILE HOME CHECKLIST MDEC DOES NOT ALLOW ANY TYPE OF METER BASE TO BE MOUNTED ON THE SIDE OF THE MOBILE HOME IS THERE AN OUTSIDE DISCONNECT ADJACENT TO THE METER BASE RATED FOR MAIN BREAKER INSIDE MOBILE HOME 05-18-2004 UNDERGROUND PEDESTAL INSTALLATION FOR MOBILE HOMES MARSHALL-DEKALB ELECTRIC COOPERATIVE WIRE GUIDELINES CHART FOR MOBILE HOMES DISCONNECT #2 #2 1 1/4" 3/0 4/0 2" #6 #4 1/2" PLYWOOD UNDERGROUND METER BASE OR UNDERGROUND POWER PANEL DISCONNECT SIZE DEPENDS ON MAIN BREAKER INSIDE MOBILE HOME NOTE #2: 5'-6" #4 BARE COPPER GROUND WIRE 6" X 6" TREATED POST GROUND LEVEL NOTE #3 SHIELDED ENTRANCE CABLE (GRAY INSULATION) CAN NOT BE USED WITH CONDUIT AND CAN NOT BE DIRECT BURIED 24" CUSTOMER TO OPEN DITCH TO MDEC POLE MDEC WILL PROVIDE CONDUIT FROM POLE INTO METER BASE SEE MDEC FOR COST ESTIMATE 225' MAXIMUM LENGTH ARE THE METER BASE AND DISCONNECT MOUNTED ON PRESSURE TREATED MATERIAL? ARE THE METER AND DISCONNECT MOUNTED WITH TWO-INCH LAG BOLTS? ARE THE WIRES IN CONDUIT AT ALL POINTS THAT THEY ARE ABOVE THE GROUND? NOTE: DO NOT USE SHIELDED ENTRANCE CABLE IN CONDUIT (GRAY INSULATION) CONDUIT SIZE 200 AMP METER BASE/DISCONNECT CAN NOT BE MOUNTED ON THE SIDE OF MOBILE HOME CUSTOMER MUST PROVIDE SPACE FOR MDEC TO INSTALL CONDUIT IN LEFT HAND SIDE OF METER BASE ALUMINUM WIRE IS THE PEDESTAL SET SO THAT THE UNDERGROUND SERVICE IS IN A STRAIGHT LINE FROM THE MDEC POLE AND DOES NOT GO UNDERNEATH ANY PART OF MOBILE HOME IS THE WIRE APPROVED FOR UNDERGROUND SERVICE? NOTE: DO NOT USE SHIELDED ENTRANCE CABLE FOR DIRECT BURIAL 100 AMP EQUIPMENT GROUND NOTE #1: COPPER WIRE IS THERE A FOUR WIRE SERVICE FROM THE DISCONNECT INTO THE MOBILE HOME (EQUIPMENT GROUND) SCHEDULE 40 PVC CONDUIT ALL THE WAY TO MAIN INSIDE TRAILER 5/8" X 8 FT GROUND ROD & CLAMP GROUND LEVEL 30'-0" MAXIMUM DISTANCE FROM MOBILE HOME USE DIRECT BURIAL TYPE CABLE WITH 4th WIRE GROUND EQUIPMENT GROUND MARKED WITH GREEN MOBILE HOME MAIN INSIDE MOBILE HOME MARSHALL DeKALB WILL MAKE THESE CONNECTIONS 200 AMP UNDERGROUND METER BASE CONNECTIONS 05-18-2004 NOTE #1: USE PENATROX ON ALL ALUMINUM CONNECTIONS. HOT LEG CONNECTIONS INTO STUCTURE / DISCONNECT NOTE #2: DO NOT INSTALL SHIELDED ENTRANCE CABLE IN CONDUIT (GRAY INSULATION) CONDUIT W/WIRE OR SERVICE ENTRANCE CABLE W/CONNECTOR 4/0 ALUMINUM OR 3/0 COPPER NEUTRAL CONNECTION INTO STRUCTURE / DISCONNECT SAME SIZE OR 1/2 SIZE OF HOT LEG CONNECTIONS. 2" PVC MALE ADAPTER ( MDEC WILL PROVIDE ) MUST PROVIDE SPACE FOR MDEC TO INSTALL CONDUIT IN LEFT HAND SIDE OF METER BASE/POWER PANEL 2" PVC CONDUIT ( MDEC WILL PROVIDE ) #4 SOLID BARE COPPER TO GROUND ROD 200 AMP OVERHEAD INSTALLATION 05-18-2004 WIRE GUIDELINES CHART DISCONNECT NOTE #1: USE PENATROX ON ALL ALUMINUM CONNECTIONS. COPPER WIRE ALUMINUM WIRE CONDUIT SIZE 100 AMP #2 #2 1 1/4" 200 AMP NEUTRAL GROUND 3/0 4/0 2" 1/2 SIZE OF HOTLEG #4 BARE COPPER 1/2 SIZE OF HOTLEG 2" RIGID CONDUIT METALLIC NOTE #2: DO NOT INSTALL SHIELDED ENTRANCE CABLE IN CONDUIT (GRAY INSULATION) HOT LEG CONNECTIONS UP TO WEATHERHEAD #4 BARE COPPER IN CONTINUOUS LENGTH UP TO WEATHERHEAD NEUTRAL CONNECTION UP TO WEATHERHEAD NEUTRAL CONNECTION INTO HOUSE / DISCONNECT HOT LEG CONNECTIONS INTO HOUSE / DISCONNECT #4 BARE COPPER TO GROUND ROD UNBROKEN FROM GROUND ROD TO WEATHERHEAD MARSHALL-DeKALB ELECTRIC COOPERATIVE RESIDENTIAL UNDERGROUND SERVICE REQUIREMENTS 200 AMP 05-18-2004 NOTE #1: MAXIMUM LENGTH OF UNDERGROUND SERVICE IS 225 FEET. ANY SERVICE OVER THIS LENGTH WILL BE THE RESPONSIBILITY OF THE CUSTOMER TO INSTALL. ****MUST MEET MDEC SPECS**** SITE BUILT STRUCTURE CHECKLIST IF THE SERVICE IS GOING TO BE UNDERGROUND: IS THE METER BASE FROM MDEC? HAVE PORTIONS OF THE FOUNDATION BEYOND THE EXTERIOR WALL BEEN REMOVED? NOTE #2: DITCH OPENING TO BE CLEAR OF ROOTS AND OTHER OBSTRUCTIONS. CUSTOMER MUST OPEN DITCH 24 INCHES IN DEPTH CONDUIT W/WIRE OR SERVICE ENTRANCE CABLE W/CONNECTOR 4/0 ALUM. OR 3/0 COPPER IS DITCH CLEAR OF ALL OBSTUCTIONS, TREE ROOTS, ETC. 200 AMP METER BASE 5'-6" MDEC POLE #4 SOLID BARE COPPER 2" PVC CONDUIT MDEC WILL PROVIDE DEEP DITCH GROUND LEVEL 2'-0" GROUND LEVEL MAXIMUM LENGTH 225 FEET 2" SWEEP PVC ELL MDEC WILL PROVIDE 5/8" X 8'-0" GROUND ROD 6" MIN. DITCH WIDTH
© Copyright 2026 Paperzz