PUR-ORANGE high abrasion, coolant resistant, meter

PUR-ORANGE
high abrasion, coolant resistant, meter marking
A
Technical data
Cable structure
Properties
Ⴠ Special PVC/PUR control cable, adapted to
DINVDE0281,0282
Ⴠ Temperature range
flexing -5 °C to +80 °C
fixed installation -40 °C to +80 °C
Ⴠ Nominal voltage U0/U 300/500 V
Ⴠ Test voltage 3000 V
Ⴠ Breakdown voltage min. 6000 V
Ⴠ Insulation resistance
min. 20 MOhm x km
Ⴠ Minimum bending radius
flexing 7,5x cable ø
fixed installation 4x cable ø
Ⴠ Radiation resistance
up to 100x106 cJ/kg (up to 100 Mrad)
Ⴠ Bare copper conductor, fine wire stranded
to DINVDE0295 cl.5, BS6360 cl.5 and
IEC60228 cl.5
Ⴠ Special PVC core insulation TI2, according
toDINVDE0281 part1
Ⴠ Cores numbered or colored according to
DINVDE0293-308
Ⴠ For 2-cores cable without green-yellow
earth core, core colours brown, blue black
Ⴠ cores with continuous white
numberingand green-yellow earth core
(up to 7 cores) or
cores colour coded with green-yellow earth
core (up to 5 cores)
Ⴠ Cores stranded in layers with optimal
lay-length
Ⴠ PVC-inner jacketguarantees agood
insulation cut-back
Ⴠ PUR-outer jacket TMPU, to DIN EN
50363-10-2 Ⴠ Colour orange (RAL2003)
Ⴠ with meter marking, change-over in 2011
Ⴠ High flexibility at low temperature
Ⴠ High abrasion resistance
Ⴠ Resistant to
Oils and fats
Non-alcoholic fuels and kerosene
Atmospheric influences
UV-radiation, Oxygene and ozone
Microbes and rotting
Sea and waste water, vibrations
Ⴠ The materials used in manufacture are
cadmium-free and contain no silicone and
free from substances harmful to the
wetting properties of lacquers
Note
Ⴠ G = with green-yellow earth core;
x = without green-yellow earth core
(OZ/OB).
Ⴠ AWG sizes are approximate equivalent
values. The actual cross-section is in mm².
Application
Robust control cable with an outstanding resistance to oil and abrasion. Suitable for use in tool making and machine industries, steel works,
on building sites and in the oil and coal industries. The cable can also be used for portable tools etc. To be recommended if the cable comes
into contact with chemical agents.
= The product is conformed with the EC Low-Voltage Directive 2006/95/EG.
PUR-jacket orange, cores numbered OZ/JZ
Part no.
22001
22002
22003
22004
22005
22006
22007
22008
22009
22010
22015
22016
22017
22018
22019
22025
22026
22027
22028
22029
22033
22034
22035
22036
22037
22038
22039
22040
22041
22042
22043
No.cores x
cross-sec.
mm²
2x0,75
3G0,75
4G0,75
5G0,75
7G0,75
2x1
3G1
4G1
5G1
7G1
2x1,5
3G1,5
4G1,5
5G1,5
7G1,5
2x2,5
3G2,5
4G2,5
5G2,5
7G2,5
3G4
4G4
5G4
7G4
4G6
5G6
7G6
4G10
5G10
4G16
5G16
Outer Ø
Cop.
approx. mm weight
kg/km
6,4
14,4
6,8
21,6
7,3
28,8
8,2
36,0
9,2
50,0
7,2
19,2
7,6
29,0
8,0
38,0
8,8
48,0
10,0
67,0
7,8
29,0
8,3
43,0
9,0
58,0
9,7
72,0
11,2
101,0
9,2
48,0
9,6
72,0
11,0
96,0
12,0
120,0
13,7
168,0
11,8
115,0
13,2
154,0
14,8
192,0
16,4
269,0
15,4
230,0
17,0
288,0
20,8
403,0
20,8
384,0
22,6
480,0
23,0
614,0
27,4
768,0
Weight
approx.
kg/km
50,0
70,0
80,0
100,0
140,0
63,0
76,0
95,0
120,0
170,0
80,0
105,0
135,0
158,0
221,0
150,0
173,0
203,0
253,0
356,0
250,0
300,0
370,0
500,0
480,0
583,0
780,0
740,0
920,0
1100,0
1400,0
AWG-No.
18
18
18
18
18
17
17
17
17
17
16
16
16
16
16
14
14
14
14
14
12
12
12
12
10
10
10
8
8
6
6
PUR-jacket orange OB/JB, cores colour coded to DIN VDE 0293
Part no.
22250
22251
22252
22253
22254
22255
22256
22257
22258
22259
22260
22261
22262
22263
22264
22265
22266
22267
22268
22269
22270
22271
22272
22273
22044
22045
22046
No.cores x
cross-sec.
mm²
2x0,75
3G0,75
4G0,75
5G0,75
2x1
3G1
4G1
5G1
2x1,5
3G1,5
4G1,5
5G1,5
2x2,5
3G2,5
4G2,5
5G2,5
4G4
5G4
4G6
5G6
4G10
5G10
4G16
5G16
4G25
5G25
4G35
Outer Ø
Cop.
approx. mm weight
kg/km
6,4
14,4
6,8
21,6
7,3
28,8
8,2
36,0
7,2
19,2
7,6
29,0
8,0
38,0
8,8
48,0
7,8
29,0
8,3
43,0
9,0
58,0
9,7
72,0
9,2
48,0
9,6
72,0
11,0
96,0
12,0
120,0
13,2
154,0
14,8
192,0
15,4
230,0
17,0
288,0
20,8
384,0
22,6
480,0
23,0
614,0
27,4
768,0
30,0
960,0
32,2
1200,0
33,0
1344,0
Weight
approx.
kg/km
50,0
70,0
80,0
100,0
63,0
76,0
95,0
120,0
80,0
105,0
135,0
158,0
150,0
173,0
203,0
253,0
300,0
370,0
480,0
583,0
740,0
920,0
1100,0
1400,0
1600,0
2000,0
2100,0
AWG-No.
18
18
18
18
17
17
17
17
16
16
16
16
14
14
14
14
12
12
10
10
8
8
6
6
4
4
2
Dimensions and specifications may be changed without prior notice. (RA02)
A 46