DG12-260 (12V260Ah)

DG12-260
Specification
(12V260Ah)
DG (Deep Cycle GEL , 12 Volts ) series is pure GEL battery with 12 years
floating design life , it is ideal for standby or frequent cyclic discharge
applications under extreme environments. By using strong grids, high
purity lead and patented Gel electrolyte, the DG series offers excellent
recovery after deep discharge under frequent cyclic discharge use, and
can deliver 400 cycles at 100% DOD. Suitable for solar, CATV, marine , RV
and deep discharge UPS, communication , and telecommunication , etc.
Cells Per Unit
6
Voltage Per Unit
12
Capacity
260Ah@20hr-rate to 1.75V per cell @25 C
Weight
Approx. 74.0 Kg(Tolerance±1.5%)
Max. Discharge Current
2600 A (5 sec)
Internal Resistance
Approx. 5.0 mΩ
Operating Temperature Range
Discharge: -40 C~60 C
o
o
Charge:-20 C~50 C
o
Storage: -40 C~60oC
Normal Operating Temperature Range
25oC±5 oC
Float charging Voltage
13.6 to 13.8 VDC/unit Average at 25 C
Recommended Maximum Charging
Current
52A
Equalization and Cycle Service
14.2 to 14.4VDC/unit Average at 25 C
Self Discharge
RITAR Valve Regulated Lead Acid (VRLA) batteries can be stored
o
for more than 6 months at 25 C. Self-discharge ratio less than 3%
o
per month at 25 C. Please charge batteries before using.
Terminal
Terminal F14
Container Material
A.B.S. UL94-HB, UL94-V0 Optional.
o
o
o
o
o
Dimensions
Unit: mm
Dimension: 520(L)×269(W)×224(H)
Terminal F14
o
Constant Current Discharge Characteristics: A (25 C)(The capacity reaches the peak value after 5-20 cycles.)
F.V/Time
9.60V
10.0V
10.2V
10.5V
10.8V
11.1V
5MIN
619.3
601.4
583.5
530.2
484.1
418.1
10MIN 15MIN
443.2 355.7
421.7 348.4
406.8 343.0
379.8 330.4
350.4 308.1
316.8 279.5
30MIN
238.4
236.3
234.9
231.2
223.2
211.1
1HR
151.6
150.9
149.5
148.1
143.1
135.9
2HR
91.26
90.58
89.89
89.20
87.60
83.71
3HR
66.02
65.77
65.26
65.01
63.24
60.46
4HR
52.70
52.46
52.21
51.73
50.51
48.07
5HR
44.75
44.48
44.22
43.69
42.62
40.79
8HR
30.31
30.06
29.82
29.57
28.39
27.19
10HR
25.16
24.92
24.68
24.44
23.66
22.96
20HR
13.79
13.54
13.29
13.00
12.34
11.62
Constant Power Discharge Characteristics: W (25 oC)(The capacity reaches the peak value after 5-20 cycles.)
F.V/Time
9.60V
10.0V
10.2V
10.5V
10.8V
11.1V
5MIN
6405
6279
6207
5717
5268
4680
10MIN 15MIN
4720
3913
4575
3850
4454
3807
4197
3674
3914
3435
3580
3128
All mentioned values are average values
30MIN
2718
2708
2694
2657
2571
2438
1HR
1752
1747
1734
1718
1669
1597
( Tolerance ±2%) .
2HR
1076
1070
1064
1056
1042
1004
3HR
787.6
785.9
782.5
779.5
758.2
725.5
4HR
628.2
627.4
626.0
620.2
606.1
576.8
5HR
533.8
532.5
530.6
524.3
511.5
489.5
8HR
361.9
360.1
357.8
354.8
340.7
326.3
10HR
300.7
298.8
296.1
293.2
284.0
275.5
20HR
165.4
162.5
159.5
156.5
148.1
139.4
DG12-260
12V260Ah
Storage characteristic
Life characteristics of cyclic use
100
120
Supplementary charge required
(Carry out supplementary charge
before use if 100% capacity is
requires)
0℃
Capacity (%)
Capacity(%)
100
80
60
100%
D.O.D
80%
D.O.D
50%
D.O.D
30%
D.O.D
15%
D.O.D
40
80
10℃
Supplementary charge required
before use.
This supplementary charge will help
to recover the capacity and should
be made as early as possible.
60
20℃
40
30℃
40℃
Supplementary charge may often
fail to recover the capacity.
The battery should never be left
standing till this state is reached
20
20
0
400
0
800
1200
1600
2000
4
2
2400
6
Storage Time (months)
Number of Cycle(Times)
Charge characteristic curve for cyclic use
Discharge characteristic curve
15 7.5 5.0
120
0.24
Charge Volume
80
① Discharge
100%(0.05CA×20h)
50%(0.05CA×10h)
② Charge
Charge Voltage2.275V/C
Charge Current0.1CA
③ Temperature 25℃
12 6.0 4.0
11 5.5 3.7
60
40
0.16
0.12
0.08
T erm inal V oltage (V )
13 6.5 4.3
13
6.5
4.3
12
6.0
4.0
11
5.5
3.7
0.20
C h a rg e C u rre n t (C A )
100
Charge Voltage
C h a rg e V o lu m e (% )
C h a rg e V o lta g e ( V )
14 7.0 4.7
Supplementary charge and storage
guidelines
8 10 12 14 16 18 20 22 24
0.05C
10
5.0
3.3
9
4.5
3.0
0.16C 0.093C
0.35C
0.62C
3C
10 5.0 3.3
20
0.04
0
0
1C
Charge Current
9
4.5 3.0
0
4
2
6
8
0.6
1.2
3
6
12
30
1
2
10 12 14 16 18 20 24 28
5
10
20
24
Hr
min
Discharge Time
Charge Time(h)
Capacity Factors With Different Temperature
Battery Type
-20℃
-10℃
0℃
5℃
10℃
20℃
25℃
30℃
40℃
45℃
GEL
Battery
6V&12V
50%
70%
83%
85%
90%
98%
100%
102%
104%
105%
2V
60%
75%
85%
88%
92%
99%
100%
103%
105%
106%
AGM
Battery
6V&12V
46%
66%
76%
83%
90%
98%
100%
103%
107%
109%
2V
55%
70%
80%
85%
92%
99%
100%
104%
108%
110%
Discharge Current VS. Discharge Voltage
Final Discharge
Vo ltage V /cell
1.75V
Discharge
Current (A)
(A) ≤0.2C
Maintenance & Cautions
1.60V
1.70V
Cycle service
0.2C< (A) <1.0C
(A) ≥1.0C
※ Avoid battery over discharge, especially battery sereis connection use.
Charge the batteries at least once every six months,
o
if they are stored at 25 C.
※ Charged with recommend voltage, ensure battery can be full recharged.
In general, recharge capacity should be 1.1-1.15 times discharge capacity.
Charging Method:
Constant Voltage
-0.2Cx2h+2.4-2.45V/cellx24h,Max. Current 0.2C
Constant Current
-0.2Cx2h+0.1Cx12h
Fast
-0.2Cx2h+0.2Cx6h
※ Effect of temperature on cycle charge voltage: -4mV/℃/Cell.
※ There are a number of factors that will affect the length of cyclic service.
The most significant are depth of discharge, ambient temperature,
Bolt
M5
M6
M8
Terminal
F3 F4 F13 F18 T25 T26
F8 F11 F12-1 F15
F5 F9 F10 F12 F14 F16
Torque
6~7N-m
8~10N-m
10~12N-m
SHEN ZHEN RITAR POWER CO.,LTD.
URL:www.ritarpower.com
discharge rate, and the manner in which the battery is recharged.
Generally specking, the most important factors is depth of discharge.
Address: Rm405,Tower C, Huahan Building,Langshan Rd16, Nanshan District, ShenZhen, 518057, China
Tel:+86-755-33981668 Fax:86-755-8347-5180
2014 - Version 1