Data sheets - Sauter Controls

Product data sheet
68.451
RUP: Differential pressure controller/transducer, centair
How energy efficiency is improved
Efficient duct pressure control for optimum system operation
Features
• Conversion of measured differential pressures into a pneumatic
standard signal 0.2...1.0 bar by a pressure sensor
• PI controller
• Easy to use, PI-controller not operational when used only as a transducer
• Differential pressure measuring range up to 500 Pa and 4000 Pa
• Front plate printed with circuit diagrams for easy identification of the controller functions
• Compressed-air connections with Rp⅛" female thread
• Nozzle-ball system
RUP1**F0001
PI
PD
Technical data
RUP105F001
Parameters
Controllers
Transducers
Supply pressure
1.3 bar ±0.1
Air capacity
100 ln/h
Air consumption
50 ln/h
Supply pressure1)
1.3 bar ±0.1
(via ext. restrictor Ø 0.2 mm)
Air consumption
33 ln/h
Air capacity
33 ln/h
Output pressure
0.2...1.0 bar
P-band (fixed)
400%
Setpoint
0...100%
Integral action time
0.5...3 s
Remote setpoint adjustment
0.2...1.0 bar
Linearity error
2%
Hysteresis
0.5%
Low-pressure connections
100 mbar (permissible pressure)
Admissible ambient temperature
0...55 °C
Housing material
Thermoplastic
Fitting
Wall/top-hat rail
Weight
0.15 kg
PD
RUP140F001
Ambient conditions
Construction
Overview of types
Type
Measuring range (Pa)
RUP105F001
0...500 Pa
RUP140F001
0...4000 Pa
Accessories
Type
Description
0297354000
Short screw-in connector R⅛", for soft plastic tubing Ø 4 mm (internal)
0296936000
Fixing brackets for rail: top-hat rail EN 60715, 35 × 7.5 mm and 35 × 15 mm
A
0297354000: 3 pieces required
Additional information
Fitting instructions
1)
MV 505658
Restrictors (Ø 0.2 mm) are installed at inputs 3 and 4 on the RCP and RPP 20 controllers; for regulations
concerning the quality of the air supply, particularly at low ambient temperatures, see www.sautercontrols.com/en/pneumatic_plants
Right of amendment reserved © 2015 Fr. Sauter AG
4.1
1/3
68.451
Product data sheet
Description of operation
Function as duct pressure controller
The pressure sensor converts the pressure difference to be measured into a standard signal
(0.2...1.0 bar). This actual value signal is compared to the setpoint XS. The PI controller compensates
for the control deviations with no persistent error. The setpoint XS can be adjusted externally via connection 6, with the set value becoming the minimum limitation.
Function as transducer
The pressure sensor converts the pressure difference to be measured into a standard signal
(0.2...1.0 bar). The output signal at connection 3 is proportional to the pressure difference. As the
pressure increases, so does the output pressure.
Intended use
This product is only suitable for the purpose intended by the manufacturer, as described in the “Description of operation” section.
All related product documents must also be adhered to. Changing or converting the product is not admissible.
Engineering and fitting notes
Upright mounting is not permitted.
Disposal
When disposing of the product, observe the currently applicable local laws.
More information on materials can be found in the Declaration on materials and the environment for
this product.
Connection diagram
RUP (controller)
?????
1,3 bar
p1
1
RUP (tranducer)
F
xi
P
A (B)
+ (-)
Tn
?????
PI
F
PI
P
- (+)
Controller
2
6
w
Dp
0.2...1 bar
16 l/h
3
Max
0.2...1 bar
Max
Xs
3
y
Dp
Ø 0,2 mm
1,3 bar
xi
2/3
4.1
RCP
xi
Right of amendment reserved © 2015 Fr. Sauter AG
68.451
Product data sheet
Dimension drawing
25
29,5
Ø4,7
Ø6,8
9
72
40
16
4
8
59
80
94
22
22
15
22
3
Rp 1/8
(ISO 7/1)
2
2
6
1
3
Accessories
32
30
4,5
40
4,5
5
13
18
25
12
5
0,
M00166
13
18
s10
10
M00568
Ø5
(ISO 7/1)
R 1/8
297354
Fr. Sauter AG
Im Surinam 55
CH-4016 Basel
Tel. +41 61 - 695 55 55
www.sauter-controls.com
Right of amendment reserved © 2015 Fr. Sauter AG
4.1
3/3