ERIFLEX FLEXIBAR, Tinned Copper

ERIFLEX FLEXIBAR, Tinned Copper
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Thin layers of tinned electrolytic copper formed into a stack
Insulated by high-resistance, self-extinguishing PVC with less than 20% contact with conductor for high flexibility
Easily bent, folded, and twisted, improving assembly flexibility, shortening connections, and decreasing footprint
Dramatically smaller and more flexible than comparable cable based on ampacity
Better power density than cable with lower skin effect ratio
Connections made by punching and bolting directly through the copper laminates, clamping onto the end of the ERIFLEX
FLEXIBAR, or welding using ERICO CADWELD
No lugs needed, reducing installation time and improving resistance to vibration
Weight savings and material savings compared to wire alternatives
Reduces total installation cost
Traceability codes and designation part numbers printed on insulation
100% production dielectric tested
UL 758 Appliance Wiring Material requirements for Cold Bend testing at -40°C and -50°C (-40°F and -58°F)
GOST compliant
RoHS compliant
L
B
A
N
Finish: Tinned
Material: Copper, Polyvinylchloride
Dielectric Strength: 20 kV/mm
Flammability Rating: UL® 94V-0
Insulation Elongation: 370 %
Insulation Thickness: 0.08"
Nominal Voltage, UL/IEC: 1,000 VAC, 1,500 VDC
Operating Temperature: -58 to 221 °F
Forming Temperature: 32 – 131 °F
Complies With: IEC® 60439.1, IEC® 61439.1, IEC® 61439.1 Class II
Part Number
Article
Number
L
(')
∆T 30 K
(A)
∆T 45 K
(A)
∆T 60 K
(A)
N
A
(")
B
(")
Cross
Section
(kcmil)
2 Bar
Current
Coefficient
3 Bar
Current
Coefficient
Typical Application Current Rating: 125 A – Certification Details: UL® 67, UL® 758
FLEX2MTC3X9X0-8
505051
6.56
126
158
185
3
0.354
0.031
42.63
1.72
2.25
FLEX2MTC3X13
505053
6.56
128
160
187
3
0.512
0.020
38.48
1.72
2.25
FLEX2MTC2X15-5
505059
6.56
152
190
222
2
0.610
0.031
48.94
1.72
2.25
FLEX2MTC6X13
505054
6.56
188
235
275
6
0.512
0.020
77.00
1.72
2.25
FLEX2MTC6X9X0-8
505052
6.56
192
241
281
6
0.354
0.031
85.26
1.72
2.25
Part Number
Article
Number
L
(')
∆T 30 K
(A)
∆T 45 K
(A)
∆T 60 K
(A)
N
A
(")
B
(")
Cross
Section
(kcmil)
2 Bar
Current
Coefficient
3 Bar
Current
Coefficient
Typical Application Current Rating: 250 A – Certification Details: UL® 67, UL® 758
FLEX2MTC4X16
505055
6.56
223
279
326
4
0.610
0.031
97.89
1.72
2.25
FLEX2MTC6X16
505056
6.56
282
353
412
6
0.610
0.031
146.83
1.72
2.25
FLEX3MTC2X20X1
505501
9.84
211
263
307
2
0.787
0.039
78.94
1.72
2.25
FLEX3MTC2X24X1
505506
9.84
244
305
357
2
0.945
0.039
94.73
1.72
2.25
FLEX3MTC3X20X1
505502
9.84
263
328
383
3
0.787
0.039
118.41
1.72
2.25
FLEX3MTC3X24X1
505507
9.84
304
379
443
3
0.945
0.039
142.10
1.72
2.25
FLEX3MTC4X20X1
505503
9.84
308
385
450
4
0.787
0.039
157.88
1.72
2.25
FLEX3MTC2X32X1
505513
9.84
311
385
454
2
1.260
0.039
126.30
1.72
2.25
Typical Application Current Rating: 400 A – Certification Details: UL® 67, UL® 758
FLEX3MTC5X20X1
505504
9.84
351
438
512
5
0.787
0.039
197.35
1.72
2.25
FLEX3MTC4X24X1
505508
9.84
356
445
520
4
0.945
0.039
189.46
1.72
2.25
FLEX3MTC3X32X1
505514
9.84
385
481
562
3
1.260
0.039
189.46
1.72
2.25
FLEX3MTC6X20X1
505505
9.84
390
487
569
6
0.787
0.039
236.80
1.72
2.25
FLEX3MTC5X24X1
505509
9.84
403
504
589
5
0.945
0.039
236.80
1.72
2.25
FLEX3MTC6X24X1
505510
9.84
448
559
653
6
0.945
0.039
284.19
1.72
2.25
FLEX3MTC4X32X1
505515
9.84
449
561
665
4
1.260
0.039
252.60
1.72
2.25
FLEX3MTC3X40X1
505521
9.84
464
580
677
3
1.575
0.039
236.80
1.72
2.25
FLEX3MTC5X32X1
505516
9.84
507
633
740
5
1.260
0.039
315.70
1.72
2.25
FLEX3MTC8X24X1
505511
9.84
531
663
775
8
0.945
0.039
378.90
1.72
2.25
FLEX3MTC4X40X1
505522
9.84
541
675
789
4
1.575
0.039
315.70
1.72
2.25
FLEX3MTC6X32X1
505517
9.84
561
701
819
6
1.260
0.039
378.90
1.72
2.25
FLEX3MTC3X50X1
505527
9.84
562
702
820
3
1.969
0.039
296.03
1.72
2.25
FLEX3MTC10X24X1
505512
9.84
606
757
885
10
0.945
0.039
473.65
1.72
2.25
FLEX3MTC5X40X1
505523
9.84
608
759
887
5
1.575
0.039
394.70
1.72
2.25
Typical Application Current Rating: 800 A – Certification Details: UL 67, UL 758
®
®
FLEX3MTC4X50X1
505528
9.84
651
813
950
4
1.969
0.039
394.70
1.72
2.25
FLEX3MTC8X32X1
505518
9.84
657
821
959
8
1.260
0.039
505.22
1.72
2.25
FLEX3MTC6X40X1
505524
9.84
669
835
976
6
1.575
0.039
473.65
1.72
2.25
FLEX3MTC3X63X1
505533
9.84
687
857
1,002
3
2.480
0.039
373.00
1.65
2.12
FLEX3MTC5X50X1
505529
9.84
730
911
1,065
5
1.969
0.039
493.38
1.72
2.25
FLEX3MTC6X45X1
505551
9.84
736
919
1,074
6
1.772
0.039
532.85
1.72
2.25
FLEX3MTC10X32X1
505519
9.84
745
931
1,088
10
1.260
0.039
631.50
1.72
2.25
FLEX3MTC8X40X1
505525
9.84
786
981
1,146
8
1.575
0.039
631.50
1.72
2.25
FLEX3MTC4X63X1
505534
9.84
792
988
1,155
4
2.480
0.039
497.33
1.65
2.12
FLEX3MTC6X50X1
505530
9.84
802
1,002
1,171
6
1.969
0.039
592.06
1.72
2.25
FLEX3MTC10X40X1
505526
9.84
879
1,097
1,282
10
1.575
0.039
789.41
1.72
2.25
FLEX3MTC5X63X1
505535
9.84
883
1,102
1,288
5
2.480
0.039
621.66
1.65
2.12
FLEX3MTC8X50X1
505531
9.84
927
1,157
1,352
8
1.969
0.039
789.41
1.72
2.25
Typical Application Current Rating: 1,200 A – Certification Details: UL® 67, UL® 758
FLEX3MTC6X63X1
505536
9.84
966
1,205
1,408
6
2.480
0.039
746.00
1.65
2.12
FLEX3MTC4X80X1
505540
9.84
970
1,211
1,415
4
3.150
0.039
631.50
1.65
2.12
FLEX3MTC10X50X1
505532
9.84
1,040
1,298
1,517
10
1.969
0.039
986.76
1.72
2.25
FLEX3MTC5X80X1
505541
9.84
1,077
1,344
1,570
5
3.150
0.039
789.41
1.65
2.12
FLEX3MTC8X63X1
505537
9.84
1,108
1,383
1,616
8
2.480
0.039
994.66
1.65
2.12
FLEX3MTC6X80X1
505542
9.84
1,172
1,463
1,709
6
3.150
0.039
947.30
1.65
2.12
FLEX3MTC10X63X1
505538
9.84
1,232
1,538
1,797
10
2.480
0.039
1,243.30
1.65
2.12
Part Number
Article
Number
L
(')
∆T 30 K
(A)
∆T 45 K
(A)
∆T 60 K
(A)
N
A
(")
B
(")
Cross
Section
(kcmil)
2 Bar
Current
Coefficient
3 Bar
Current
Coefficient
Typical Application Current Rating: 1,600 A – Certification Details: UL® 67, UL® 758
FLEX3MTC5X100X1
505546
9.84
1,301
1,624
1,898
5
3.937
0.039
986.76
1.60
2.02
FLEX3MTC8X80X1
505543
9.84
1,341
1,674
1,956
8
3.150
0.039
1,263.06
1.65
2.12
FLEX3MTC6X100X1
505547
9.84
1,414
1,765
2,062
6
3.937
0.039
1,184.12
1.60
2.02
FLEX3MTC10X80X1
505544
9.84
1,484
1,851
2,164
10
3.150
0.039
1,578.80
1.65
2.12
FLEX3MTC8X100X1
505548
9.84
1,598
1,994
2,330
8
3.937
0.039
1,578.80
1.60
2.02
2,800
12
3.937
0.039
2,368.23
1.60
2.02
10
3.937
0.039
1,973.52
1.60
2.02
Typical Application Current Rating: 2,000 A – Certification Details: UL 67
®
FLEX3MTC12X100
505550
9.84
1,920
2,396
Typical Application Current Rating: 2,000 A – Certification Details: UL 67, UL 758
®
FLEX3MTC10X100
505549
9.84
1,765
2,203
®
2,574
ADMISSIBLE CURRENTS: This table indicates the temperature rise produced by chosen current in the given section. This calculation does not take into account the heat dissipation
from the switch gear.
∆T = Temperature of conductors – Internal temperature of panel.
Refer to technical documentation for additional ampacity ratings.
ABS is a registered certification mark of American Bureau of Shipping. CSA, CSA-US and C-CSA-US are registered trademarks of Canadian Standards Association. IEC is a registered
trademark of the International Electrotechnical Commission. UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.
WARNING
Pentair products shall be installed and used only as indicated in Pentair’s product instruction sheets and training materials. Instruction sheets are available at erico.pentair.com and
from your Pentair customer service representative. Improper installation, misuse, misapplication or other failure to completely follow Pentair’s instructions and warnings may cause
product malfunction, property damage, serious bodily injury and death and/or void your warranty.
© 2016 Pentair All rights reserved
Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates.
All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.