ESL-1080 - Icynene Inc. - ICC-ES

Most Widely Accepted and Trusted
0
ICC-ES Listing Report
ICC-ES | (800) 423-6587 | (562) 699-0543 | www.icc-es.org
000
ESL-1080
Issued 09/2016
This listing is subject to renewal 09/2017.
DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION
SECTION: 07 21 00—THERMAL INSULATION
SECTION: 07 25 00—WATER-RESISTIVE BARRIERS/WEATHER BARRIERS
REPORT HOLDER:
ICYNENE INC.
6747 CAMPOBELLO ROAD
MISSISSAUGA, ONTARIO L5N 2L7
CANADA
EVALUATION SUBJECT:
ICYNENE PROSEAL ECO (MD-R-210) CLOSED-CELL SPRAY POLYURETHANE
FOAM INSULATION
Look for the trusted marks of Conformity!
“2014 Recipient of Prestigious Western States Seismic Policy Council
(WSSPC) Award in Excellence”
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not
specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a
recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved.
A Subsidiary of
ICC-ES Listing Report
ESL-1080
Issued September 2016
This listing is subject to renewal September 2017.
www.icc-es.org | (800) 423-6587 | (562) 699-0543
CSI:
A Subsidiary of the International Code Council
®
DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION
Section: 07 21 00—Thermal Insulation
Section: 07 25 00—Water-resistive Barriers/Weather Barriers
Product Certification System:
The ICC-ES product-certification system includes evaluating reports of tests of standard manufactured
product, prepared by accredited testing laboratories and provided by the listee, to verify compliance with
applicable codes and standards. The system also involves factory inspections, and assessment and
surveillance of the listee’s quality system.
Product:
ICYNENE PROSEAL ECO (MD-R-210) CLOSED-CELL SPRAY POLYURETHANE FOAM INSULATION
Listee:
ICYNENE INC.
6747 CAMPOBELLO ROAD
MISSISSAUGA, ONTARIO L5N 2L7
CANADA
(905) 363-4040
www.icynene.com
Evaluation:
The Icynene ProSeal Eco (MD-R-210) Closed-Cell Spray Polyurethane Foam Insulation was evaluated
based on a tested exterior non-load-bearing wall assembly consisting of building-material components
described in the Assembly Section, tested in accordance with the following standards:
 UL 263-11, UL 263-03 (with revisions through October 2007) and UL 263-03, Standard for Fire Tests of
Building Construction and Materials, Underwriters Laboratories, Inc.
 ASTM E119-2012A, ASTM E119-08a, ASTM E119-07 and ASTM E119-00, Standard Test Methods for
Fire Tests of Building Construction and Materials, ASTM International.
Assembly:
Exterior Face: Nominally 6-inch-deep, No. 18 gage galvanized steel studs, spaced 16 inches (406 mm) on
1
center, are fastened to No. 18 gage galvanized steel floor and ceiling tracks. One layer of /2-inch-thick
®
(12.7 mm) Georgia Pacific DensGlass Gold Exterior Sheathing is installed with the long edge parallel to
steel studs with vertical joints offset a minimum of 16 inches (406 mm) from the vertical joints of the interior
Type X gypsum board, and the horizontal joints offset a minimum of 24 inches (610 mm) from the horizontal
1
joints of the gypsum board. The sheathing is attached using 1 /4-inch- long (32 mm) self-drilling drywall
screws spaced 8 inches (203 mm) on center around the perimeter and in the field. Hohmann & Barnard
1
DW-10 brick ties, 6 inches (152 mm) long by 1 /2 inches (38 mm) wide, are spaced 16 inches (406 mm) on
5
center vertically on each steel stud, and secured using two 1 /8-inch-long (41 mm) self-drilling screws,
1
1
3
through 4-inch (102 mm) red clay brick [(3 /2 inches (89 mm) by 2 /4 inches (57 mm) by 7 /4 inches
(197 mm)], laid in a running bond pattern with Type S mortar, leaving a nominally 1-inch air gap between the
brick and the exterior sheathing. The stud cavity is filled with Icynene ProSeal Eco (MD-R-210) insulation to
a maximum nominal thickness of 6 inches.
5
Interior Face: Two layers of Type X gypsum board, /8 inch (15.9 mm) thick and complying with ASTM
C1396, are applied to the interior side with joints offset from each other a minimum of 16 inches (406 mm)
1
and with the long edge parallel to steel studs. The gypsum board is secured using 1 /4-inch-long (32 mm),
self-drilling drywall screws spaced 8 inches (203 mm) on center around the perimeter and 12 inches
(305 mm) on center in the field. The gypsum board joints must be treated with vinyl or casein, dry or
premixed joint compound applied in two coats to cover all exposed screw heads and gypsum board butt
joints. A minimum 2-inch-wide (51 mm) paper, plastic, or fiberglass tape is embedded in the first layer of
compound over butt joints of the gypsum board.
Listings are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an
endorsement of the subject of the listing or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to
any finding or other matter in this listing, or as to any product covered by the listing.
1000
Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved.
Page 1 of 2
ESL-1080 | Most Widely Accepted and Trusted
Findings:
Page 2 of 2
The assembly described in the Assembly Section, with the Icynene ProSeal Eco (MD-R-210) Closed-Cell
Spray Polyurethane Foam Insulation as a component of the assembly, is a three-hour fire-resistance-rated
exterior non-load-bearing wall assembly, based on testing in accordance with UL 263/ASTM E119, as
referenced in the applicable sections of the following code editions:
 2015, 2012, and 2009 International Building Code
Applicable Section: 703.2 and 705
®
®
 2006 International Building Code
Applicable Section: 703.2 and 704
 2015, 2012, 2009, and 2006 International Residential Code
Applicable Section: R302
®
Identification:
Containers of Icynene ProSeal Eco (MD-R-210) components are identified with a label bearing the Icynene
Inc. name and address; the product trade name [Icynene ProSeal Eco (MD-R-210)]; the lot number; the
flame spread and smoke developed indices; mixing instructions; density; the shelf life and the expiration
date; the evaluation report number (ESR-3493), the listing report number (ESL-1080), and when applicable,
the listing mark.
Installation:
The Icynene ProSeal Eco (MD-R-210) Closed-Cell Spray Polyurethane Foam Insulation shall be installed in
accordance with the Icynene Inc. published installation instructions and applicable codes.
Conditions of Listing:
1.
The listing report addresses only conformance with the standards and code sections noted above.
2.
Approval of the product’s use is the sole responsibility of the local code official.
3.
The listing report applies only to the materials tested and as submitted for review by ICC-ES.
4.
The Assembly Section describes the assembly using Icynene ProSeal Eco (MD-R-210) Closed-Cell
Spray Polyurethane Foam Insulation that is qualified for use in an exterior non-load-bearing wall fireresistance-rated assembly.