sp-mbs-8-10kva-2 installation and user guide

SP-MBS-8-10KVA-2
INSTALLATION AND USER GUIDE
SP-MBS-8-10KVA-2
Installation Instructions for bypass panel
This is a bypass panel manufactured for Powervar. It is intended for use as a bypass switch for the UPS protecting
critical loads.
The power circuitry is enclosed in a forced air cooled metal enclosure. Visible from the front of the unit is the
bypass switch operating handle.
Access is through the front by use of a screwdriver to remove the front cover. Disconnect all sources of supply
(Utility power and UPS power) prior to working on electrical equipment including the bypass and any downstream
distribution or loads. It is recommended that a licensed electrician install and troubleshoot the equipment.
This unit is HEAVY, take necessary safety precautions to prevent injury. Locate the panel in a convenient location
within sight of the UPS. The unit should be installed within sight of the UPS. Be sure to keep the rear vents clear
of any obstructions, failure to do so will result in damage to the unit.
Conduit entry can be at the upper left or upper right side of the enclosure toward the front. Rear entry can be at
the lower right side. Bottom entry is available through an access plate (remove to punch and replace). Cover any
internal components when punching or drilling through enclosure walls.
Incoming and outgoing wires to be terminated at the terminal block located at the upper rear section of the unit.
Input from utility power (208VAC, 1PH, 60Hz, L+L+G), input from the UPS output (240/208/120, 1PH, 60Hz,
L+L+L+N+G), output to UPS input (208VAC, 1PH, 60Hz, L+L+G), and output to the load (240/208/120, 1PH,
60Hz, L+L+L+N+G) will be hardwired observing local NEC codes. Wiring to be rated for 60 amps. Utility input
protection by others. Refer to UPS operating and installation instructions for actual connections needed for the
application.
Check for tightness of all the connections inside the panel. Some wires might have worked themselves loose
during shipping and handling. Insure that all connections are tight before applying power to the panel.
Observe proper cable sizing per NEC or local codes. Observe proper phase sequence when hooking up the panel.
SP-MBS-8-10KVA-2
Installation Instructions for bypass
All hardwired inputs and outputs are to be made to the terminal block in the upper section of the backpanel. There are
individual terminals for all connections. Follow NEC or local code requirements for wire sizing.
UPS operation:
The bypass switch should be in the “Normal” position. Conditioned power is output from the UPS to the critical load.
TEST operation:
In the event that the UPS needs to be serviced or replaced, rotating the bypass switch to “Test” will reroute the utility
power around the UPS through the bypass contacts on the switch to power the load. It is recommended to place the
UPS in internal bypass prior to switch operation. Check the UPS installation manual to determine how to perform this
operation. This mode also provides power to the input of the UPS for test purposes.
BYPASS operation:
In the event that the UPS needs to be isolated for service or to be replaced, rotating the bypass switch to “Bypass” will
reroute the utility power around the UPS through the bypass contacts on the switch to power the load. The UPS will be
fully isolated from this panel in this mode. A qualified technician should use proper safety guidelines when working on
the UPS. Always confirm that power has actually been removed prior to working on any equipment.
General Specifications:
Utility Input: 208VAC, 1PH, 60Hz, hardwired
UPS Input: 208VAC, 1PH, 60Hz, hardwired
UPS Output: 240/208/120VAC, 1PH, 60Hz, hardwired
Output to Load: 240/208/120VAC, 1PH, 60Hz, hardwired
Ampacity rating: 60 amps
24.00in
REAR OF ENCLOSURE: SHOWN FROM THE REAR
SIDE VIEW
3.50in
5.50in
3.75in
BYPASS
SWITCH
15.75in
TERMINAL
STRIP
11.50in
TERMINAL STRIP
BACK OF ENCLOSURE IS OPEN FOR
VENTILATION
TEST
B
Y
P
A
S
S
FAN BARRIER SHELF
N80
U
P
S
Csii
TRANSFORMER
28.00in
FAN MOUNTED ON REAR OF
ENCLOSURE
2.00in
FRONT
ACCESS
WITH
COVER
1
19.00in
3.75in
5.88in
3.00in
6.00in
3.00in
4.00in
3.00in
12.75in
TRANSFORMER
1
4.50in
10.00in
BOTTOM ACCESS PANEL
WITH COVER
BOTTOM VIEW FROM INSIDE LOOKING DOWN
NOTES:
1
PART NUMBER
OPENINGS SHOWN WITH DASHED LINES, AND COVERS
OVER THE OPENINGS ARE IN RED
REV.
SP-MBS-8-10kVA-2
REV. A:
DRAWN BY: MFN
Phone: (800) 369-7179 or (847) 596-7000
Fax (847) 596-7100
1450 Lakeside Drive, Waukegan, IL 60085
www.powervar.com
APPROVAL :
D.U.
Changed desc. per customer
REV. C:
8-10KVA MBS WITH ISOLATION TRANSFORMER (60 AMP)
DATE: 08/05/10
08/25/10
REV. B:
Reference: BPT060-4P-N1-00
DESCRIPTION
DATE: DESC.:
DATE: 08/05/10
REV. D:
DRAWING NO:
BPT060-4P-N1-00-D-0810
APPR :
D.U.
INCOMING POWER 208 VOLTS AC, 1 PHASE,3 WIRE, 60Hz
INTERNAL CABLE: #4 AWG (85A)
PANEL RATED FOR 60A
BYPASS SWITCH
U TEST
P
S
TB2: UPS INPUT
TB1: UTILITY INPUT
2.
L1
L1
L1
L1
L2
L2
L2
L2
UPS
17 TEST 18
1L1
UPS
19 TEST 20
1L2
1
#4AWG BLK
TB3: UPS OUTPUT
X4
L1
L1
X4
X4
L2
L2
N
N
#4AWG BLK
TO DISTRIBUTION
OR COMPUTER LOAD
TB4: CRITICAL LOAD
#4AWG BLK
UNINTERRUPTIBLE
POWER SUPPLY
208 VOLTS
1 PHASE
B
Y
P
A
S
S
X2
X1
X1
UPS
1X4
4
X4
X4
N
7
UPS
120V
1N
8
208V
N
X2
X2
3
1X2
11 UPS 12
1X1
15 UPS 16
X2
120V
X2
X1
N
240V
X1
X1
GROUND
1
GROUND
GROUND
GROUND
#4AWG BLK
L2
TRANSFORMER
0V
L2
0V
0V
L1
L1
120V
120V
208V
208V
208V
240V
240V
1
BYP. 2
TEST
5
BYP.
6
TEST
9
BYP.
10
TEST
13
BYP.
14
TEST
240V
1
GROUND
F1: 8/10A
USE BUSSMAN
FNM 8/10 OR EQUAL
AUX. SWITCH
1
#8AWG GRN
4L2
1
BYP.
2
TEST
2
3
BYP.
4
TEST
3
FAN : 120VAC
#14AWG RED
NOTES:
1
2
PART NUMBER
SWITCH CONTACTS ARE "MAKE-BEFORE-BREAK"
CONTACTS MARKED "UPS" ARE CLOSED IN THE "UPS"
POSITION.
CONTACTS MARKED "TEST" ARE CLOSED IN THE "TEST"
POSITION.
CONTACTS MARKED "BYP" ARE CLOSED IN
THE "BYPASS" POSITION.
SP-MBS-8-10kVA-2
Reference: BPT060-4P-N1-00
MAIN DISCONNECT AND BRANCH CIRCUIT PROTECTION
PROVIDED BY OTHERS
DESCRIPTION
DRAWN BY: MFN
Phone: (800) 369-7179 or (847) 596-7000
Fax (847) 596-7100
1450 Lakeside Drive, Waukegan, IL 60085
www.powervar.com
REV.
REV. A:
08/05/10
APPROVAL :
D.U.
DATE:
08/25/10
Changed desc. per customer
REV. B:
REV. C:
8-10KVA MBS WITH ISOLATION TRANSFORMER (60 AMP)
DATE:
DATE: DESC.:
08/05/10
REV. D:
DRAWING NO:
BPT060-4P-N1-00-S-0810
APPR :
D.U.
SP-MBS-8-10KVA-2
RATING INFORMATION:
VOLTAGE: 240/208/120VAC, 60 HZ
PHASE: SINGLE PHASE
FULL LOAD CURRENT: 60 AMPS
INTERRUPT RATING: 5KAIC SYM @ 600VAC
TYPE 1 ENCLOSURE
CONTACT INFORMATION:
Powervar
1450 Lakeside Dr.
Waukegan, Il. 60085
(800) 369-7179 or
(847) 596-7000
Fax (847) 596-7100