JD Steam - Utica Boilers

JD Steam
There Are Some Things You Can Always Depend On...
JD Steam
Commercial Gas Fired Steam Boiler
Electronic Ignition Base
Standard Equipment:
Base
• Fire Door
• Burner Orifice
• Manifold
• Main and Pilot Burner
• Electronic Pilot Gas Valve
• Intermittent Pilot Module
• Complete Jacket Assembly
•
Steam Trim Package:
Low Water Cut-Off
Glass Gauge Set
• Safety Valve
• Steam Gauge
• Pressure Limit
• Drain Valve
•
•
JD Series Boiler Bases are pre-assembled at the factory with burner manifold,
burner orifices, gas valves and electronic ignition installed, ready for field installation
of the pre-tested sections and appropriate packages.
Plug ‘N Play Harness and Junction Box
Individual base and junction box controls are designed for easy installation with Plug ‘n Play harnesses.
The entire boiler links together in a “snap”. A color-coded factory supplied harness eliminates wiring errors.
CSD1 Option
JD boilers are available with a CSD1 option to comply with CSD1 standards where required by building code.
The CSD1 option provides the increased number of controls and safety devices required to meet CSD1 standards.
Utica JD Commercial Gas-Fired Steam Boiler
Model
Gross
Input
(1) Output
(Mbh)
(Mbh)
Net AHRI Ratings
Steam
(PPF) (2)
Base Size & Flue Outlet
Steam
Steam
(Sq. Ft.) (3) (Mbh) (2) 300 (8") 400 (10") 500 (12")
Chimney
Vent
Size (4)
Connector Size Therm. Eff.
I.D. x Ht. to Chimney (4)
Comb Eff
JD-300S
300
233
1.333
729
175
1
0
0
8" x 20'
8
77.5
80.4
JD-400S
400
310
1.333
971
233
0
1
0
10" x 20'
10
77.5
80.5
JD-500S
500
388
1.333
1213
291
0
0
1
12" x 20'
12
77.5
80.5
JD-600S
600
465
1.333
1454
349
2
0
0
12" x 20'
12
77.5
80.4
JD-700S
700
543
1.333
1696
407
1
1
0
12" x 20'
12
77.5
80.5
JD-800S
800
620
1.333
1938
465
0
2
0
14" x 20'
14
77.5
80.5
JD-900S
900
698
1.333
2183
524
0
1
1
14" x 20'
14
77.5
80.5
JD-1000S
1000
775
1.333
2421
581
0
0
2
14" x 20'
14
77.5
80.5
JD-1100S
1100
853
1.333
2667
640
1
2
0
16" x 20'
16
77.5
80.5
JD-1200S
1200
930
1.333
2908
698
0
3
0
16" x 20'
16
77.5
80.5
JD-1300S
1300
1008
1.333
3150
756
1
0
2
16" x 20'
16
77.5
80.5
JD-1400S
1400
1085
1.333
3392
814
0
1
2
18" x 20'
18
77.5
80.5
JD-1500S
1500
1163
1.333
3633
872
0
0
3
18" x 20'
18
77.5
80.5
JD-1600S
1600
1240
1.333
3875
930
0
4
0
18" x 20'
18
77.5
80.5
JD-1700S
1700
1318
1.327
4138
993
1
1
2
18" x 20'
18
77.5
80.5
JD-1800S
1800
1395
1.319
4408
1058
0
2
2
20" x 20'
20
77.5
80.5
JD-1900S
1900
1473
1.313
4675
1122
0
1
3
20" x 20'
20
77.5
80.5
JD-2000S
2000
1550
1.307
4942
1186
0
0
4
20" x 20'
20
77.5
80.5
JD-2100S
2100
1628
1.301
5213
1251
2
0
3
20" x 20'
20
77.5
80.5
JD-2200S
2200
1705
1.296
5483
1316
0
3
2
22" x 20'
22
77.5
80.5
JD-2300S
2300
1783
1.292
5750
1380
0
2
3
22" x 20'
22
77.5
80.5
JD-2400S
2400
1860
1.290
6008
1442
0
1
4
22" x 20'
22
77.5
80.5
JD-2500S
2500
1938
1.288
6271
1505
0
0
5
22" x 20'
22
77.5
80.5
JD-2600S
2600
2015
1.288
6517
1564
2
0
4
22" x 20'
22
77.5
80.5
JD-2700S
2700
2093
1.288
6771
1625
1
1
4
24" x 20'
24
77.5
80.5
JD-2800S
2800
2170
1.288
7021
1685
0
2
4
24" x 20'
24
77.5
80.5
JD-2900S
2900
2248
1.288
7271
1745
0
1
5
24" x 20'
24
77.5
80.5
JD-3000S
3000
2325
1.288
7521
1805
0
0
6
24" x 20'
24
77.5
80.5
Right & Left End Tappings Data
D
A
1. Ratings are at sea level to 2,000 feet. For altitudes above 2,000 feet, reduce all ratings 4% for each 1,000 feet above sea level.
2. Net steam ratings based on piping and pickup allowance of 1.333 (300-1600), 1.327 (1700), 1.319 (1800), 1.313 (1900),
1.307 (2000), 1.301 (2100), 1.296 (2200), 1.292 (2300), 1.290 (2400), and 1.288 (2500-3000). Contact Technical Support
before selecting boiler for installations having unusual piping and pick-up factors, such as intermittent system operations,
Supply and Return extensive piping systems, etc.
3. Ratings in square feet are computed at 240 Btuh/square foot for steam boilers.
Primary LWCO
4. Chimney sizes shown are one option based on a typical venting system as shown in Figure 6 of the Installation Manual, and
and Gauge
sized according to the National Fuel Gas Code, assuming Type B double wall vent and vent connectors, other venting system
Glass set
designs are acceptable as shown on Flue Connection And Venting section of the installation manual. For further chimney
Drain, Left End
design and sizing information, consult the National Fuel Gas Code, ANSI Z223.1/NFPA 54-latest revision, or ASHRAE HVAC
Systems and Equipment Handbook, Chimney, Gas Vent, and Fireplace Systems, or the Standard for Chimneys, Fireplaces,
Drain, Right End Vents, and Solid Fuel Burning Appliances. NFPA 211. Follow standard engineering practice.
Opening
Size
A
4”
B
1/2”
C
3/4”
C
3/4”
D
1/2”
Plugged
E
1”
Accessories
*F
1”
Safety Valve
G
3/4”
Plugged or
Electronic
(Probe Type)
LWCO
F
B
G
B
A
E
C
Steam
*If opening F is to be used for something other than the Safety Valve or
Pressure Relief Valve, or the Safety/Relief Valve is larger than 1”, the
Safety/Relief Valve must be installed in the Header Piping as near to the
boiler as possible.
Contractor
Assistance: 800.325.5479
Certifications
All ratings and specifications subject to change.
P.O. Box 4729
Utica, New York 13504
tel: 315.797.1310 • fax: 315.797.3762
www.uticaboilers.com
PN 240009442 Rev. 6/12