September 18, 0430 hrs following switching of Cumberland-Marshall 500 kV line (Jville - Gleeson out) Cumberland Fossil Plant TVA's largest coal plant, completed in 1973 Plant can output 2,700 MW Two cross-compound units- four 722 MVA generators Unit 1 - original Unitrol B analog exciter, SCRX model Unit 2 - exciter upgraded to Unitrol P in 2003, ESST1A model first applied in Sept 2006. Instability Plant operated under Operating Guide Previous event Nov 4 2000, + 600 MW oscillation, following switching of Cumberland-Davidson, pre-outages of CumberlandMarshall, Weakley-Shelby, Maury-Davidson, Jville bank. Not recorded, not reproduced by PSS/E Event of Monday Sep 18, 2006 Plant at full output (>2,600 MW) Pre-outage of Jville-Gleason Oscillation followed switching of Cumberland-Marshall for maintenance Operator reclosed line after ~3 minutes 500 kV Transmission System Around Cumberland Fossil Plant Cumberland 500 kV Line Outages During Sept 18, 2006 Oscillations Switched line which triggered oscillations WBN out and Bus split First record - Dataware system 3 seconds per sample Why did the plant oscillate? Typical of an exciter-driven event Not shown by PSS/E study with recorded settings oscillation only with large change in gain settings (later) Possibilities: - exciter setting incorrectly applied - exciter settings or models incorrect - circuit error - inadequate modeling - other? (evil spirits?) Powerflows at Cumberland 500 kV Switchyard prior to Sept 18 event. Davidson FP 500 kV 1350 MW, -106 MVAR 1321 MW, -67 MVAR Johnsonville FP 500 kV -217 MW, 41 MVAR 1332 MW, 178 MVAR 1279 MW, 149 MVAR Marshall 500 kV ~200 MW initial Magnitude Swing ~680 MW max Magnitude Swing PMU record 30 samples per second First Attempt: Simulation of Sept 18 Cumberland switching event <70 MW Magnitude Swing This simulation shows no damping problems. Cumberland with Exciter gain set too high Unit 1 K= 1000 (from 100) Unit 2 Ka=1000 (from 450) Oscillates @ ~1.25 Hz 400 MW Magnitude Swing This simulation shows that incorrect Exciter settings could have caused the oscillations. The decision was made to do testing on Cumberland’s exciters. TVA Investigation of Cumberland Generator Data Investigation of Generator data. Manufacturer’s data did not provide values for T’q0 and T’’q0 This data was marked “typical data” and did not indicate where the values came from. T’q0 and T’’q0 immediately became suspect values. We needed to determine if these values were out of normal ranges. How might we accomplish this? Investigation of Generator data. To accomplish this we looked at all similar generators in MMWG dynamics case Similar values based on MVA Base, reactances, and direct axis time constants. Investigation of Generator data. Conclusion: T’’q0 appears to be within normal ranges while T’q0 is below the expected range. Simulations indicate that raising T’q0 lessens damping at Cumberland Fossil Plant,Leonardo but as long as ranges are within reason the oscillations still damp out for the Sept 18 switching event. Epilogue Long-term undetected error in generator model Instability still not exactly reproducible - criteria issue PSS installed on both generators of one unit Limited support from manufacturer
© Copyright 2026 Paperzz