Electrical Wiring Instructional Materials Service Texas A&M University Introduction • Well-planned wiring system must be safe, economical, adequate, & expandable. • Install according to the National Electric Code (NEC) which insures safety • An economical system is safe, adequate, and efficient and can be acquired at a minimum cost. • NEC requirements state that electrical systems should be of sufficient capacity to operate all appliance, lighting, and heating circuits with a voltage drop not to exceed 2%. • An adequate number of outlets and switches of proper type and rating should be included in the system • Anticipated future electrical needs should be considered & allowances made for their installation. Wiring Materials • Wire Size: – Size of conductor is VERY important – Larger wire will safely carry more amperage – Inefficient operation of electrical devices caused by attempting to force too much current through a small wire • Increases resistance • Decreases available voltage – Conductors are numbered to indicate size (gauge) according to the American Wire Gauge (AWG) Standards • Small number = large wires • Large number = small wires • Kinds of Wire: – Solid or stranded – Stranded: • Made up of several small wires wrapped together • Provides more flexibility, particularly the larger sizes • Indoor wire larger than a No. 8 is generally stranded. • No. 6 stranded conductor is made up of 7 smaller wires with a total cross-sectional area the same as that of a No. 6 solid conductor • Diameter of electrical conductors measured in thousands of circular mils (kcmil) • Circular mil = area of a circle with a diameter of one onethousandth of an inch – Copper (CU) or Aluminum (AL) – Copper: • Most common conductor used in residential & commercial wiring – Aluminum: • Lighter in weight • Requires approximately one size larger than copper to carry the same load in amperes • Aluminum conductors generally used in overhead applications • Types of Wires: – Outdoor: • Used for wiring between buildings • Usually covered with neoprene or polyethylene • Common three-conductor self-supporting service drop – Two insulated wires wrapped around a bare stranded wire used as the ground & supporting wire • Underground conductors (USE) have increased significantly over the years – Eliminates ice & wind damage – Adds to attractiveness of farm, home, or business – Generally required in new subdivisions for electric & communications service Outdoor Wire Type Designation UF USE SE/SEU ASE Meaning Use Underground feeder Underground service – direct burial in soil, not concrete Underground entrance Mechanical protection required where wires enter and leave ground, moisture-resistant service Service entrance/unarmored To bring service into building – flameretardant & moistureresistant Armored entrance To bring service into building service – Indoor: • Designed for use inside buildings • Some types can be used both inside and outside • Special coatings have been developed for wires used inside buildings having excessive moisture • Most of the insulators used on inside conductors are made of fire & moisture resistant materials. Indoor Wire Type Designation Meaning Use Thermoplastic Indoor use – dry locations Moisture resistant thermoplastic Dry or wet locations THHN Heat-resistant thermoplastic (nylon jacket) Dry locations with high temperature THW/THWN Moisture- and heat-resistant thermoplastic (nylon jacket) Wet locations with high temperature Rubber, heat resistant Carries higher voltage than T or TW – dry and damp locations Rubber, heat & moisture resistant Service entrance or larger appliance- dry and wet locations Moisture-resistant and flameretardant thermoplastic High moisture and high temperature T TW RH RHW XHHW – Most residential wiring is non-metallic (NM) sheathed cable, commonly called RomexTM. • Plastic sheath that encloses a white conductor, a black conductor & a bare conductor • Bare conductor is wrapped in paper • Sheath is lined with paper – Manufacturer, type of covering, size & number of conductors, presence or absence of a ground wire, and max voltage rating are stamped on sheath – In accordance with the NEC: • Black conductor = current carrier • White conductor = neutral carrier • Bare conductor = ground – Bare ground conductor may not always be the same gauge as the current carriers • Conduit: – Wiring requiring mechanical protection necessitates the use of conduit – Other advantages: • Greater choice of wiring colors • Use of additional conductors • Added safety if the conduit is properly grounded – Available as: • Flexible or nonflexible • Metallic or non-metallic • Nonflexible Metallic: – Can be rigid or thin wall (EMT) – Rigid: » threaded ends » approx. 1/8” thick » bent with a special type of bender – EMT: » Thinner » Type most often used for agricultural & residential applications » Easily bent » Available in 10-ft. lengths » Can be mounted to steel boxes » May be cut with a 32-tooth hacksaw • Rigid non-metallic tubing (ENT): – – – – – – – – – Schedule 40 or Schedule 80 PVC pipe Either gray or white in color Somewhat flexible Pre-manufactured bends used for 45o & 90o bends Cut & assembled in same manner as other PVC pipe products Schedule 80 PVC has a smaller inside diameter (ID) than Schedule 40 & can carry fewer conductors NEC handbook addresses the number & rating of conductors that can be placed in various sizes of ENT Outside diameter (OD) of PVC is same for all schedules PVC conduit identified as DZYR in NEC Handbook – Conduit is supported & kept in place with metal conduit straps – EMT is fastened to the boxes with metal connectors & screw locks – DO NOT damage or reduce the internal diameter when bending conduit – Bends that reduce the internal crosssectional area of conduit are not allowed in the NEC Outlet, Junction, & Switch Boxes • Installed at every switch, light, splice, or junction point where wires are attached or spliced, with the exception of some outside wiring • Outlet Boxes: – Usually octagonal or square – Octagon & square boxes are about the same size & measure 4” in diameter & 1½” deep • Switch Boxes: – Made for flush or surface mounting – Flush Mounting: • Used in walls where wire is concealed • Most commonly used box has beveled corners with clamps for nonmetallic cable • Sides are removable in order that boxes can be ganged together to provide for a series of switches or receptacles at one location – Surface Mounting: • Made to fasten to an exposed surface • Widely used in barns & outbuildings • Corners are round • Do not have clamps for nonmetallic cable • Can be used for conduit or cable wiring • If NM cable is used, they should have a bare ground. – To prevent possible damage to the wires, the NEC specifies the number of wires of various sizes permitted in boxes. MAXIMUM NUMBER OF CONDUCTORS PERMITTED IN OUTLET, SWITCH, AND JUNCTION BOXES1 Trade Size of Box Maximum Number of Conductors #14 #12 #10 #8 4” octagon box, 1½” deep 7 6 6 5 4” square box, 1½” deep 10 9 8 7 Switch or handy box, 2” deep 5 4 4 3 Switch or handy box, 2½” deep 6 6 5 4 Switch or handy box, 3” deep 7 7 6 1These numbers of wires apply if no cable clamps, fixture studs, switches, or receptacles are contained in the box. If the box contains cable clamps or fixture studs, the number of wires shall be reduced by one, with a further reduction of one wire if flush switches or receptacles are contained in the box. Each wire running through the box without splice is counted as one. Each wire terminating in the box is counted as one. Receptacles Switches • Three common types: – Single-pole: • Have two terminal screws • Control lights from one location – Three-way: • Three terminals • Control lights from two locations – Four-way: • Four terminals • Used in combination with three-way switches to control lights from three or more locations Blank Covers • Used to cover surface mounted boxes that serve as junction boxes for splices or future receptacle installations Wall Plates • Available in bakelite, metal, glass & other materials Connectors • Connect cables to boxes that do not have built-in cable clamps • Available to fit different sizes of knockouts in boxes • Pressure-type, split bolt connector used to connect outside wires to entrance wires • When connecting aluminum to copper wires, a spacer should be placed between the two to prevent corrosion. • Solderless connectors: join wires inside junction boxes Grounding Screws, Clips, & Clamps • Screws & Clips: – May be used to ground conductors to boxes – Boxes having tapped holes use the screw and pigtail – Boxes without tapped holes may use the grounding clip • Clamps: – Two types: • One is for use with a ground rod • The other is for grounding the system to deeply buried water pipes – Grounding rods should be at least 8’ long Grounding Clip Grounding Wire Grounding Clamp for Rod Grounding Clamp Insulators & Entrance Elbows • Insulators: – Support outdoor wires – With screw knobs: placed in areas having a moderate amount of tension – Wrap-around clamps: used in metal structures – Racks of insulators are used for long spans of multiple conductors • Entrance Elbows: – Use where conduit or SE cable enters the building – Removable cover on elbow aids in installing the wires Entrance Cap or Weatherhead • Protects the entrance cable connection Common Splices & Connections • Western Union: – Used when strength is require – Remove enough insulation from wires to allow 5-6 turns of the wire – If using a knife, cut insulation at a slant – Combination wire cutters/strippers • Adjust to correct wire gauge – To begin splice: • Bend each wire into a 90o angle about 1” from the insulation • Cross the wires and wrap each wire around the other wire • Pliers can be used to smooth sharp edges – To tape a splice: • Extend electrical tape about ¾ of an inch over insulation on one end • Extend each lap ½ the distance of the previous wrap • Keep tape tight • Wrap about ¾ of an inch on opposite end • Two complete wrappings results in four thicknesses of tape sufficient for proper insulation • Center Tap: – Used to branch off a wire & go in another direction – Has very little strength – Procedure: • Remove about 2½” of insulation • Bend tap wire into a 90o about 1” from insulation • Place tap wire around center of main wire & make 7-8 wraps • Tape – Split bolt connectors used with center tap splices on larger conductors • Rat Tail: – – – – Use to clamp conductors inside junction boxes Has very little strength Use electricians pliers to twist this splice tight Insulate with a solderless connector • Other connections: – When making connections to terminals on switches, outlets, etc., attach the wire loop to the terminal in the direction in which the screw tightens Types of Switches & Circuit Diagrams • Simple Switches: – Single pole-single throw (SPST) – Controls a circuit from one location – Types: • Toggle • Mercury (thermostat & humidistat) • Silent • Rocker button • Push button – NEVER install switches in a neutral line • Three-Way Switches: – Single pole-double throw (SPDT) – Use to control a circuit from two locations – Have three terminals • 1 common terminal & 2 traveler terminals • Four-way Switches: – Used between three-way switches to provide additional points of control – Have four terminals Installing Lighting & Outlet Circuits • • • • • • • Use No. 14 wire on demonstration board In actual wiring the NEC requires No. 12 wire Outlet & lighting circuit: No. 14-2 WG Three-way switches: No. 14-3 WG Use black tape to mark white wires used as hot Use solderless connectors to make splices Use romex clamps to secure cables to boxes • Outlet Circuit: – Strip romex and remove insulation from wires – Place romex in breaker box – Connect black to breaker terminal – Connect white & bare to neutral bar – Place other end of romex through 1st outlet box, strip & remove insulation – Connect black wire to brass screw (small slot side of outlet) – Connect white wire to silver screw (large slot side of outlet) – Connect bare wire to safety-ground (green) screws – Use same color code & connect 1st outlet to 2nd outlet with another length of romex – Jumper wires may be used from receptacles to main wires in order to maintain continuous neutral & ground conductors – Install outlets & place covers on outlet boxes • Lighting Circuit: – Place No. 14-2 WG into breaker box – Strip romex and remove insulation – Connect black wire to breaker terminal – Connect white & ground wires to neutral bar – Push other end of romex into first junction box, then strip & remove insulation – Place one end of another length of No. 14-2 WG into junction box and the other end into 1st switch box – Strip & remove insulation – Install another No. 14-2 WG from 1st junction box to 2nd junction box – Strip & remove proper amount of insulation – Now make these connections • 1st Junction box: – Black wire from breaker box to white (marked with black tape) from 1st switch box and to black going to 2nd junction box – Black from switch box and black lead of light – White from breaker box to white lead of light and to white wire going to 2nd junction box – Safety ground from breaker box, switch box & 2nd junction box should be attached to a clip – Place porcelain light fixture on junction box & install • 1st Switch Box: – Connect black to one switch terminal – Connect white (marked with black tape) to other terminal – Attach safety ground to switch box using a grounding clip – Attach bare safety ground to each switch box using grounding clips (No need for clips if there is a grounding terminal) • 3-Way Switch Boxes: – Connect black to common terminal – Connect red & white to traveler terminals of the 3-way switches – Use clips to attach ground wire to each switch box • 2nd Junction Box Splice: – Black from 1st junction box and black from one three-way switch – Black lead of light & black from 2nd 3-way switch – Red traveler wires – White traveler (marked with black tape) – White from 1st junction box & white lead of light – Ground from 1st junction box & from each 3way switch should be attached to a ground clip – Mount porcelain light fixture on junction box & install three-way switches & cover plates – Energize fuse box & check circuits and switches to determine if functioning properly – Circuit should be polarized when energized – Polarizing: neutral wire from power source is connected to neutral wire of demonstration board Planning the Wiring System • The Wiring System – Includes both exterior & interior wiring – Extends from the point of supply to various outlets located inside & outside of buildings • Well-planned Wiring System – Can pay dividends by reducing: • Size of wire • Size of electrical equipment needed • Amount of wire used • Installation labor • Amount of electricity used • Suggested Planning Procedure: – Prepare a plan with building & layout plans to scale – Determine number of circuits needed in each building and locate the outlets • General Purpose Outlets: at least one outlet for every 12 ft of wall space (in a residence) – Provides a circuit for any appliance having a cord 6 ft. long – Max of eight convenience or light outlets on any one circuit (less in kitchen) – Number & size of light fixtures determined by amount of floor space in a given area & candle-power of fixtures – At least two general-purpose circuits in kitchen for high-wattage appliances – No. 12 wire is used for general purpose circuits & should be protected with 15 or 20 ampere fuses, circuit breakers, or ground fault circuit interrupters • Special Purpose Circuits: – Needed for the range, water heater, air conditioner(s), food freezer, water system & clothes dryer – Wire size and circuit protection based on safe ampere capacity & permissible voltage drop – Place electrical symbols on building floor plans to indicate outlets • Service Entrance and Distribution Panel: – Requirements can be determined from plans and by consulting with the power supplier – Service entrance cables & service equipment are capacity rated and should have a rating adequate to handle the electrical load safely – Modern home may require equipment with a capacity to handle a minimum of 200 amperes – Distribution panel with 36-37 branch circuit positions recommended for the home Calculating Voltage Drop • Voltage drop causes problems such as less efficient heaters, dimmer lights, and inefficient electric motors. • Voltage at load or outlet may be significantly lower than transformer voltage due to distance or use of improperly-sized conductors • Running equipment or appliances on low voltage can cause damage • Use a multi-meter to determine voltage at a wall outlet • Allowing for a 3% voltage drop, the lowest acceptable reading on a multi-meter should be at least 116 volts • 120 volts x 3% voltage drop = 3.6 120 – 3.6 = 116.4 Round down to 116 OR 120 volts x 97% voltage = 116.4 Round down to 116 • When working with voltage drop calculations, always round down to next lowest whole number – Provides extra safety factor in calculations • EXAMPLE: – Nameplate on the motor of a 4’ floor fan: • “1/3 hp, 1725 rpm, 115V, 6.3 A” – Fan operates on a 10’ cord from a wall receptacle – Multi-meter reads 110 volts at receptacle – Question: Will the floor fan be operating within an allowable voltage drop of 4%? • Ed = I x R – Used when trouble-shooting electrical circuits with a multi-meter – Ed: voltage drop – I: circuit amperage – R: resistance of the conductors in ohms – Based on Ohm’s Law • EXAMPLE: – Voltage in a 240V motor circuit was checked at the load with a multi-meter and had a reading of 232 volts – Conductors rated resistance: 0.16 ohms – Motor rated at 50 amperes – Using the formula: • Ed = 50 x 0.16 • Ed = 8 volts – Predicted voltage drop = Ed = 8 volts – Difference between 240V & 232V is also 8V – Calculation agrees with test reading – 240 volts x 5% max voltage drop = 12 volts – 8 volts reading is less than 12 volts predicted with a 5% voltage drop – Motor circuit will operate efficiently within voltage drop limitation – If measured voltage drop is greater than 5%, conductor size must be increased for motor to operate efficiently Acknowledgements Developed by Kristie Weller, Undergraduate Technician, Instructional Materials Service, developed this PowerPoint presentation. Kirk Edney, Curriculum Specialist, Instructional Materials Service, reviewed this PowerPoint presentation. Vickie Marriott, Office Software Associate, Instructional Materials Service, assisted in the development of this PowerPoint presentation. ALL RIGHTS RESERVED Reproduction or redistribution of all, or part, of this presentation without written permission is prohibited. Instructional Materials Service Texas A&M University 2588 TAMU College Station, Texas 77843-2588 http://www-ims.tamu.edu 2006
© Copyright 2026 Paperzz