Data sheets - Sauter Controls

Product data sheet
67.440
RLP100F910, F916, F918: Dual-channel air-volume controller
How energy efficiency is improved
For demand-based volume flow control of dual-channel systems in offices
Features
• Optimum use of energy thanks to RLP100 2-channel controller in combination with room operating
units of the TSP, TSFP and TSSP series
• Compatible with practically all currently-available mixing boxes
• Suitable for explosion hazard zone 1 II 2 G T6
• Conformity tested as per EN 13463-1 and EN 1127-1 (ex zone 1 II 2 G T6)
• Controls constant, switchable or variable air volumes
• Accurate, static differential pressure sensor with large measuring range
• Front plate printed with circuit diagrams for easy identification of the controller functions
• Compressed-air connections with Rp⅛" female thread
• Special measuring connection for detecting the air volume
• Low-pressure connections with dual-diameter connector for soft plastic tubing (internal Ø 4 and
6 mm)
• 2 inputs
• Command variable
• Day/night change-over or heating/cooling signal
• 3 outputs
• Actual value, air volume
• Activates two damper actuators, heating and cooling
• 1 adjuster for setting the sensor measuring range
• 2 setpoint adjusters for maximum and minimum limitation of the air volume
Technical data
Parameters
Admissible pressure
RLP100F91*
RLP100F910, RLP100F916
RLP100F918
Low-pressure connections
3000 Pa
Supply pressure
1.3 bar ±0.1
Operating range Pstat
0...3000 Pa
Response sensitivity
0.1 Pa
Input for setpoint shift w1, w2;
20...100% m
0.2...1.0 bar
Measuring range ∆p (factory setting) 6.4...160 Pa,
can be reduced to 1...25 Pa
Ambient conditions
Admissible ambient temperature
0...55 °C
Setting range for setpoint
20...100% m
Output pressures
0.2...1.0 bar
Inputs/Outputs
Linearity and accuracy of root extrac- 2% of 100% m
tion
Construction
Housing material
Glass-fibre-reinforced thermoplastic
Fitting
To walls or top-hat rails
(EN 60715 rail)
Weight
0.6 kg
Type of protection
IP 30
Type
RLP100F910
RLP100F916
Properties
Constant-air-volume controller (PI)
for full-range actuators
Constant VAV controller (PI) for sequential actuators
Air capacity, connection 2, cooling
400 ln/h
100 ln/h
Standards and directives
Overview of types
Right of amendment reserved © 2015 Fr. Sauter AG
6.1
1/5
67.440
Product data sheet
Type
RLP100F910
RLP100F916
Air capacity, connection 7, heating
400 ln/h
18 ln/h
Air consumption
53 ln/h
60 ln/h
P-band (fixed)
100%
400%
Accessories
Type
Description
0297354000
Short screw-in connector R⅛", for soft plastic tubing Ø 4 mm (internal)
0297762001
Restrictor Ø 0.8 mm for damping turbulent low-pressure signals
0274571000
Restrictor Ø 0.5 mm for damping turbulent low-pressure signals
0297870001
Bracket for fixing to ceilings, floors or in panels
A
A
A
0297354000: 5 pieces required
0297762 001: Can be plugged into soft plastic hose, inner Ø 4 mm. If attenuation is insufficient, instead of the
Ø 0.8 mm restrictor, the Ø 0.5 mm restrictor can be used (accessory 0274571; this restrictor is not suitable for
RLP100F908, F914, F123).
0274571 000: Can be plugged into soft plastic hose, inner Ø 4 mm. Suitable for extreme cases when the Ø
0.8 mm restrictor (accessory 0297762) does not provide sufficient attenuation. Not suitable for volume flow
controllers (RLP100F914, F123) and transducers (RLP100F908) where the “+ and -” low pressure line is constantly supplied with a very small quantity of air, because the pressure signals in the lower measuring range
are falsified and the positioning time of 1...2 s (RLP100F123) is not achieved.
Additional information
Fitting instructions
RLP100F916
MV 505338
RLP100F918
MV 505262
RLP100F910
MV 505089
VAV technical manual
7 000 621 001
Description of operation
A square root transducer converts the pressure difference (6.4...160 Pa) produced at an orifice plate
or pitot tube into a standard signal (0.2...1.0 bar) that is linear to the flow. The pressure difference of
the setpoint range (E = 0.7...1.8) is set using the adjuster E. The integral controller compensates for
the control deviations with no persistent error.
RLP100F916:
The command variable w shifts the volume flow (e.g. TSP 80 B temperature controller). An external
setpoint signal can be supplied via connection 8 and limited with the adjusters mmin and mmax. When
the connection is open mmin is effective, and when it is closed mmax applies.
RLP100F918:
The command variables w1 (heating) and w2 (cooling) shift the volume flow (e.g. TSSP 80 temperature controller). The volume flows for heating and cooling can be individually limited using the mmin
and mmax adjusters and the internal adjuster mmax (int.).
RLP100F910:
The command variable w shifts the heating volume flow (e.g. TSP 80 B temperature controller). The
ratio of hot to cold air is fixed at 1:2. An external setpoint signal can be supplied via connection 8 and
limited with the adjusters mmin and mmax. When the connection is open mmin is effective, and when it is
closed mmax applies.
Intended use
This product is only suitable for the purpose intended by the manufacturer, as described in the “Description of operation” section.
All related product documents must also be adhered to. Changing or converting the product is not admissible.
Engineering and fitting notes
Crosswise mounting is not permitted.
2/5
6.1
Right of amendment reserved © 2015 Fr. Sauter AG
Product data sheet
67.440
To prevent turbulent flow causing vibrations that affect the low pressure signal, there must be a
smoothing sector in front of the cross meter for measuring the differential pressure.
Where there are unfavourable inflows – bends, elbows or branches immediately in front of the cross
meter – a restrictor (accessory 0297762 or 0274571) must be installed in the plastic hose of the + and
– connection to attenuate turbulent low pressure signals.
Disposal
When disposing of the product, observe the currently applicable local laws.
More information on materials can be found in the Declaration on materials and the environment for
this product.
Connection diagrams
RLP 100 F916
RLP 100 F918
E
1
1
E
DP
I
E
xi
1,3 bar
p1
PI
1
DP
1
E
xi
Controller
I
16 l/h
16 l/h
Controller
8
2
6
y2
DP
8
y1
DP
NC
0,2...1,0
y2
NC
0,2...1,0
V
M
RLP 100 F910
E
1,3 bar 1
p1
2
y1
0,2...0,6
V
DP
7
w2
T
NC
NC
0,6...1,0
6
w1
T
1,3 bar
Controller
7
w1
0,2...1 bar
1,3 bar
p1
xi
1
E
PI
1:2
Min
Controller
2
8
7
6
y2
w1
???
?????
DP
y1
p1
NC
0,2...1,0
NC
T
0,2...1
V
Right of amendment reserved © 2015 Fr. Sauter AG
6.1
3/5
67.440
Product data sheet
Dimension drawing
12
Ø6,8
Ø4,7
20
70
103
136
s11
8,5
5
8
7
2
110
1
23,5 23,5 23,5 23,5
6
88
Rp 1/8 (ISO 7/1)
Accessories
297870 001
150
6
10
135
M00568
s10
1,5
4,5
Ø5
(ISO 7/1)
R 1/8
297354
14
M09889
108
28
Application example for RLP100F918
VAV control facility for 2-duct installations with room temperature for heating and cooling
0,2...1,0 bar
NC
2
AK 31P
3
3
V
KL
V
non-pressursed room
FO
NC
4 T
AK 31P
2
NC
l < 0,3 m
1,3 bar
PD/F
1
M
6
8
I
5
P
2
7
TSSP 80
1 PD/F
1
2
1,3 bar
1
6
I
2
2
RLP 100 F001
RLP 100 F918
6
3
1:1
2
XRP 101
4/5
6.1
Right of amendment reserved © 2015 Fr. Sauter AG
AK 31P
0,2...1,0 bar
WL
Product data sheet
67.440
1 VAV controller
4 Room temperature controller
CA
2 Damper actuator
5 2-duct VAV controller
WA
Cold air
Warm air
3 Reducing box
6 Interface relay
EA
Exhaust air
NC
Normally closed
Fr. Sauter AG
Im Surinam 55
CH-4016 Basel
Tel. +41 61 - 695 55 55
www.sauter-controls.com
Right of amendment reserved © 2015 Fr. Sauter AG