Performance Specifications—Air Cooled

Contents
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Optional Microprocessor Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Performance Specifications—Air Cooled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Performance Specifications—Water Cooled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Performance Specifications—Glycol Cooled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Performance Specifications—Chilled Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Air-Cooled Condensers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Fluid Coolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Remote Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Pump Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Guidelines for Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
CM
Capacity
(kW)
CM
003
005
007
R= Air Cooled with
Remote Condensing
FC=277/1/60
010
W= Water Cooled
KA= 480/3/60
014
F= Water Cooled with
Multicool
017
Configuration
Voltage
Air Pattern
A= Air Cooled
BC=208-230/1/60
S=Spot Cooled
E= Air Cooled with
Multicool
BA= 208-230/3/60
D=Ducted
G=Glycol Cooled
B= Glycol Cooled with
Multicool
P= Glycol Cooled with
Economizer
C= Chilled Water
CM
XXX
X
APC NetworkAIR™ CM
XX
X
i
ii
APC NetworkAIR™ CM
Overview
The APC NetworkAIR CM computer room air conditioning system
offers an increasingly compact,
modular, and reliable system solution without consuming valuable
floor space.
Precision environmental requirements now reach far beyond the
confines of the traditional data center or computer room to encompass
a larger suite of applications,
referred to as technology rooms.
Critical environment applications
include:
• Computer rooms
• Telecommunication facilities
• Clean rooms
• Power equipment
Room Air Distribution
The spot-cooled configuration is
supplied with a 2’ x 4’ (610mm x
1220mm) supply/return air filter
assembly. The filter assembly
includes one-way supply and return
air grilles. Available on 3-10kW (13 ton) units only.
Standard Features
• Scroll & Hermetic Reciprocating
Compressors
• Centrifugal Blower Assembly
• Heavy Gauge Steel Frame
• Thermostat/Humidistat Controller
Optional Features
The duct configuration is supplied
with a 1” (25mm) duct flange on the
supply and return air openings.
• 2 or 3 Way Fluid Regulating
Valves (Glycol/Water/
Economizer)
• Chilled Water Control Valve
Configuration
• Tube in tube coaxial condenser (310kW (1-3 ton) Glycol/Water)
• Glycol Cooled
• Glycol Cooled with Economizer
• Glycol Cooled with MultiCool
(Chilled Water Coil)
• Water Cooled
• Brazed plate condenser (14-17kW
(4-5 ton) Glycol/Water)
• Microprocessor w/Remote Display
• Remote Sensor
• Water Cooled with MultiCool
(Chilled Water Coil)
• Redundant Group Control
• Medical equipment rooms
• Archives
• Air Cooled
• Pure Steam Canister Humidifier
• LAN/WAN environments
• Air Cooled with MultiCool
(Chilled Water Coil)
• 30%, 1” Deep Filters
• Air Cooled with Remote
Condensing
• Hot Water Reheat
A worldwide network of APC representatives is fully qualified to
provide engineering, sales, installation and service for our products.
APC warrants all parts for 12
months from shipment. Extended
warranties are available.
Capacity
CM is available from 3-17 kW (1-5
ton) in direct expansion and chilled
water.
• Chilled Water
• Programmable Thermostat
• Electric Reheat
• Hot Gas Reheat (Water/Glycol)
• Hot Gas Bypass (N/A on Chilled
Water systems)
Compliance Approval
• ETL/CETL
• UL Listed to UL 1995 and CSA
C22.2 No. 236
• MEA #256-94-E (5, 7, 10, 17 kW),
#177-01-E (3, 14 kW) (City of
New York)
•
•
•
•
Ship Loose Spot Water Detector
Ship Loose Firestat
Ship Loose Smoke Detector
Ship Loose Condensate Pump
• Reheat/Humidity Lockout
• Environmental Monitoring
• Remote Relay Shutdown
• OHE Disconnect
• ModBus/JBus Gateway
• Fused Ship-Loose Disconnect
C
APC NetworkAIR™ CM
US
• Optional HP Motor
1
Standard Features
Cabinet
The frame is constructed of heavy
gauge steel for maximum strength.
Hanger mounting brackets shall be
part of the chassis and shock
mounts are provided for vibration
isolation. The unit offers service
access to all components through
removable access panels lined with
1/2” thick insulation. Please allow
36” (914mm) on all sides for
accessibility.
Fan/Motor Section
The air distribution system for the
3-10kW (1-3 ton) units is comprised of a direct-drive fan motor
with a double-inlet blower and permanently sealed ball-bearing type
blower bearings. The air distribution system for the 14-17kW (4-5
ton) units has a belt drive fan motor
with a double-inlet blower and permanently sealed ball-bearing type
blower bearings.
Evaporator Coil & Drain Pan
The evaporator coil is constructed
of copper tubes and aluminum fins
and is mounted in a stainless steel
condensate drain pan. The condensate drain pan is equipped with dual
condensate overflow switches that
will automatically shut-down the
equipment if the condensate drain
becomes clogged.
2
Chilled Water Coil
The cooling coil is constructed of
copper tubes and aluminum fins and
is mounted over a stainless steel
condensate drain pan. The coil circuiting ensures water distribution
over the entire coil face area.
Electrical Panel
The electrical panel contains the
contactors, starters, overload protection devices, and input power
disconnects. Each wire (except
jumpers) is numbered every 3”
(80mm), or color coded to facilitate
circuit tracing when installing and
servicing the unit. Each AC power
circuit is individually branch circuit
fused on all three phases. All compressor and motor devices are
thermally and short circuit protected. The electrical panel is easily
accessible from the front of the unit.
All electrical components are ULlisted and -recognized and all wiring conforms to NFPA 70 (NEC)
and UL 1995 requirements.
APC NetworkAIR™ CM
Refrigeration System and
Compressor
The refrigeration system consists of
a single hermetic compressor, externally equalized expansion valve,
filter-dryer, high pressure switch,
refrigerant sight glass, and moisture
indicator.
Thermostat Controller
The unit control provides two separate heat and cool temperature
setpoints with a minimum 2 degree
spacing between them. The controller shall activate heating or cooling
functions automatically in regard to
setpoint versus measured conditions. The control setpoint range
shall be 60-80°F (15-27°C). Units
requiring humidity control have
separate humidity and dehumidity
setpoints with a minimum 4% RH
spacing between them. The controller activates humidifying or
dehumidifying cycles as a function
of setpoint versus measured return
air conditions. The humidity setpoint range shall be 20% RH or
80% RH. As an option, the control
shall also allow daily or 5 day/2 day
program scheduling at a maximum
of two programs per day.
Optional Features
Air Filter
The filtration of conditioned air is
extremely vital to maintaining the
clean, particle-free environment
required by electrical equipment.
The CM system uses 30% efficient,
1” deep filters, with full depth filter
pleats. Filters are easily replaced on
all CM model configurations.
Humidifier
The humidifier utilizes a pure steam
generator specifically designed for
hi-tech area environmental control.
The pure steam eliminates contaminating mineral deposits, bacteria,
white dust and excessive humidity.
The humidifier requires little or no
scheduled maintenance. Automatic
flushing combined with an indicator
that signals when the canister is to
be changed, ensure maintenance
free operation.
Electric Reheat
The electrical resistance heater is
sized to offset the sensible cooling
capacity in the dehumidification
mode. The reheat elements are low
watt density finned tubular on the 35kW (1-1.5 ton) systems. Open coil
resistance type are used on the 717kW (2-5 ton) systems. Reheat
elements are electrically and thermally protected.
Condenser
The 3-10kW (1-3 ton) water- and
glycol-cooled systems employ a
coaxial style condenser that uses
efficient tube within a tube counterflow heat transfer to remove the
heat of compression. Water flows
through the inner tube while refrigerant flows in the cavity between
the inner copper tube and outer steel
tube. The convoluted tubes enhance
thermal performance while inhibiting the accumulation of deposits.
Water-Regulating Valve
Water and Glycol systems maintain
proper performance by sensing
refrigerant discharge pressure and
regulating the among of water or
glycol supplied to the condenser. A
two-way or three-way valve is
available. The standard valve pressure rating is 150 psi (1030kPa).
Valves with a pressure rating of 350
psi (2413 kPa) ship loose for field
installation. Space restrictions
within the cabinet prevent the
valves from being factory installed
when reheat and humidity are
selected.
Redundant Group Control
Allows up to six NetworkAIR units
the ability to communicate with
each other to automatically switch
upon alarm condition, or timed
rotation. Can also allow standby
units the ability to assist the running
system.
Chilled Water Control Valve
Cooling capacity shall be controlled
with a slow-close, 2-way, motorized
valve rated for 125 psi (862 kPa).
Hot Gas Reheat
Hot gas reheat is optional on waterand glycol-cooled systems. The
copper tube, aluminum fin hot gas
reheat coil maintains the leaving
dry bulb temperature when the system is in dehumidification mode.
The coil is controlled by the processor through a factory piped and
wired three-way heat reclaim regulator and check valve.
Remote Relay Shutdown
Shutdown of the NetworkAIR system can be done remotely by a
factory installed relay. The relay
can be ordered with a 24V, 120V, or
240V coil. The relay must be powered by others to disable the
NetworkAIR system.
Reheat/Humidity Lockout
When facilities have limited backup
power capacity, this lockout prevents the operation of electrical
loads that are not essential for continued site operation.
Programmable Thermostat
A wall-mount programmable thermostat with LCD display, sevenday programming, and battery
back-up will provide temperature
control. When equipped with a
humidifier and/or reheat, a hair element humidistat/dehumidistat
supplies humidification and or
dehumidification control.
APC NetworkAIR™ CM
Remote Sensor(s)
Environmental sensor(s) can be
strategically placed, up to 50ft.
from the unit to better meet the
site’s cooling needs. The sensor
must be positioned to permit air
movement across the sensors.
Hot Water Reheat (Modulating)
A modulating control valve controls
hot water reheat. The system is supplied with a factory-installed copper
tube and an aluminum fin hot water
coil. Option not available on MultiCool models.
Hot Water Reheat (2-Way On/
Off)
An on/off solenoid valve maintains
the dry bulb temperature when the
system is in dehumidification and
reheat mode. Completely factory
pre-piped, the system includes a
copper tube, aluminum fin reheat
coil, float, and thermostatic steam
trap.
3
Optional Features
Optional Blower/Motor HP
An optional 5HP motor can be used
for increased CFM or to accommodate special air filters, high external
static pressure, etc. while maintaining the standard CFM rating.
Ship Loose Condensate Pump
The condensate pump, shipped
loose, will pump 36 gal/h (0.06 L/s)
at 15 ft. (4.6 m) head. Condensate
pump must be mounted to the outside of the unit.
ModBus/JBus Gateway
The Gateway translates transmission protocol from the system’s
network into ModBus/JBus communication protocol. One gateway
can support up to 16 units.
Fused Disconnect
A Nema 1 fused disconnect, complete with fuses, will ship loose for
field installation, thus allowing the
disconnect to be unit-mounted or
remotely located.
Ship Loose Smoke Detector
The smoke detector is designed to
sense smoke in the return air
stream. Upon detection of smoke,
an audible and visual alarm on the
microprocessor will be activated
and the unit will be immediately
shutdown. Smoke detector ships
loose for field installation. Smoke
detector must be mounted externally, near the return air grille on
spot cooled units and in the duct
work in ducted configurations.
OHE Disconnect
A non-fused disconnect switch may
be wired to an outdoor heat
exchanger to disconnect high voltage power if necessary.
Hot Gas Bypass
An auxiliary side-port hot gas
bypass circuit maintains the evaporator coil temperature during low
load conditions. This optional feature will offer longer compressor
run times and minimize compressor
cycling and temperature
fluctuations.
Ship Loose Spot Water
Detector(s)
The solid-state spot water detector
activates an audible alarm on the
controller when moisture is
detected. A maximum of four
detectors may be installed. Spot
water detector ships loose for field
installation. Spot water detector
must be mounted externally.
Ship Loose Firestat
A firestat ships loose for field
installation in the air stream of the
unit. If the return air temperature
reaches 125°F (52°C), an audible
and visual alarm on the microprocessor will be activated and the unit
will immediately shutdown. Firestat
must be mounted externally, near
the return air grille on spot cooled
units and in the duct work in ducted
configurations.
4
MultiCool
MultiCool systems contain a chilled
water coil and direct expansion coil
within the same cabinet. Either
cooling coil can be used as a backup
to the other. These systems provide
cooling using either building chilled
water and/or the direct expansion
system.
Economizer
Glycol and water cooled systems
may be optionally configured with
an economizer coil. During cold
ambient conditions, the compressorized system will shut-down and
utilize the cold outdoor air to cool
the glycol system, rerouting it from
the heat exchanger to the economizer coil for efficient operation.
APC NetworkAIR™ CM
Environmental Monitoring Unit
A stand-alone unit performs contact
monitoring and continuous temperature and humidity sensing through
two probes (one included). The unit
is controlled by available web, control console, or SNMP interface
with a network connection. In the
event of an environmental anomaly,
notification is sent via e-mail or
SNMP. The unit is 18.25” x 9” x
2.75” (464mm x 229mm x 70mm).
The probes extend up to 12’
(3.66m) from the unit.
Environmental Management
System
A browser-accessible, 1U, rackmountable appliance allows monitoring of environmental conditions.
Monitoring of one temperature, one
humidity, and one vibration sensor
ship standard. When conditions
change, notifications are sent via
email to appropriate personnel. The
EMS provides 8 input contacts, 2
output relays, and controllable
power outlets for defining actions
remotely should conditions warrant
it.
Optional Microprocessor Controller
Microprocessor Controller
The microprocessor controller is
standard on the main module of
each system. The controller provides precision control for the
demanding requirements of:
• Data centers
• Control rooms
• Clean rooms
• Switch rooms
• UPS rooms
The easy-to-use display allows the
operator to select options from the
device’s menu-driven interface to
control and monitor the connected
air conditioning system.
Status
Complete status monitoring is provided within the status menu of the
microprocessor controller. Available information includes:
• Current Temperature/Humidity
• Temperature/Humidity Setpoint
Automatic setpoint crossover protection will prevent the setting of
the heat setpoint above the cool setpoint and the humidification
setpoint above the dehumidification
setpoint. Setpoint adjustment can be
restricted to only operators with
knowledge of the security codes set
within the security menu structure.
Configuration
Flexibility is offered through the
use of the configuration menu.
Operating requirements are satisfied by changing the configuration
settings. New configurations are
stored in EEPROM and protected
from unauthorized tampering by the
four-digit security password,
selected in the security menu. Configuration options include:
• Fahrenheit or celsius display
• Compressor minimum on/off time
• Power loss restart time delay
• Redundant unit grouping
• Cooling/Heating Status
• Alarm input polarity
• Humidification/Dehumidification
Status
• Alarm enable
Alarms
Quick access to any alarm condition
is facilitated through the menu
structure. The alarm key acts as a
hot key providing immediate access
to the alarm display menu. Presence
of a new alarm will sound the audible alarm. The red alarm LED on
the display panel will remain illuminated until all alarms have been
cleared. The temperature and
humidity alarm setpoints are adjustable. Alarm annunciations include:
• Loss of airflow
• Clogged filter
• High head pressure
• Low suction pressure
• High/Low temperature
• Temperature/Humidity deadbands
• Small room delay
Common Alarm Contact
A common alarm relay is installed
on every microprocessor. In the
event of an alarm condition, the
relay will change state. The user
can select which alarms change the
state of the relay. This feature
allows for remote enunciation of
alarm status.
Run Times
The major components within the
unit have independent run timers
that monitor and store accumulated
run hours on the components. The
run timers are provided with operator adjustable run time alarms.
Security
Multiple security levels prevent
unauthorized adjustment of important system parameters. The user
may select a four-digit password for
setpoint and configuration changes.
Should the password be forgotten,
APC can provide temporary access.
Monitoring
With the addition of a supervisory
network communications card the
microprocessor may interface with
the locally installed APC remote
monitoring and control system.
Gateways are available for interfacing with building management
systems. Please check with APC for
compatibility with your building
management system.
Cool Inhibit
Prevents the unit from over-cooling
during the dehumidification cycle.
If the space temperature falls below
a user adjustable setpoint, cooling
will become inhibited until the
space temperature returns to
setpoint.
Cool Override
A manual toggle switch will allow
the compressor to operate in the
event of a microprocessor failure.
The cool override can be field wired
to a snap acting thermostat for cooling control.
Remote Shutdown
Events external to the unit, such as
activation of a fire suppression system may require the unit to shut
down remotely. Additionally this
feature may be tied into a BMS that
would allow remote control of the
units on/off status.
• High/Low humidity
APC NetworkAIR™ CM
5
Performance Specifications—Air Cooled
NET COOLING CAPACITY - BTU/HR (kW)
3kW (1 ton) 5kW (1.5ton) 7kW (2 ton) 10kW (3 ton)
80F DB, 67F WB (26.7C DB, 19.4C WB) 50% RH
Total
15,000 (4.3) 18,000 (5.3) 24,000 (7.0) 34,000 (9.9)
Sensible
13,000 (3.9) 15,000 (4.3) 19,000 (5.6) 26,000 (7.6)
75F DB, 62.5F WB (23.9C DB, 16.9C WB) 50% RH
Total
14,000 (4.0) 17,000 (4.9) 21,000 (6.3) 32,000 (9.3)
Sensible
12,000 (3.6) 14,000 (4.0) 19,000 (5.6) 26,000 (7.6)
75F DB, 61F WB (23.9C DB, 16.1C WB) 45% RH
Total
13,000 (3.9) 16,000 (4.6) 22,000 (6.6) 31,000 (9.0)
Sensible
13,000 (3.9) 16,000 (4.6) 21,000 (6.3) 28,000 (8.0)
72F DB, 60F WB (22.2C DB, 15.5C WB) 50% RH
Total
13,000 (3.9) 16,000 (4.6) 21,000 (6.3) 30,000 (8.9)
Sensible
12,000 (3.6) 14,000 (4.0) 19,000 (5.6) 25,000 (7.3)
72F DB, 58.6 WB (22.2D DB, 14.8C WB) 45% RH
Total
13,000 (3.9) 16,000 (4.6) 21,000 (6.3) 30,000 (8.9)
Sensible
13,000 (3.9) 15,000 (4.3) 20,000 (5.9) 27,000 (7.9)
70F DB, 58.5F WB (21.1C DB, 14.8C WB) 50% RH
Total
12,000 (3.6) 15,000 (4.3) 21,000 (6.3) 29,000 (8.6)
Sensible
12,000 (3.6) 14,000 (4.0) 18,000 (5.3) 25,000 (7.3)
70F DB, 57.2F WB (21.1C DB, 14.0C WB) 45% RH
Total
12,000 (3.6) 15,000 (4.3) 20,000 (6.0) 29,000 (8.6)
Sensible
12,000 (3.6) 15,000 (4.3) 20,000 (6.0) 27,000 (8.0)
MULTICOOL -- COOLING CAPACITY DATA -- BTU/HR (kW) - 45F (7.2C) EWT
80F DB, 67F WB (26.7C DB, 19.4C WB) 50% RH
Total - BTU/HR (kW)
20,000 (5.9) 22,000 (6.6) 37,000 (10.9) 46,000 (13.6)
Sensible - BTU/HR (kW)
15,000 (4.3) 17,000 (4.9) 26,000 (7.6) 33,000 (9.6)
Flow Rate - GPM (L/s)
4.1 (0.3)
4.4 (0.3)
10.7 (0.7)
9.4 (0.6)
Pressure Drop - psig (kPa)
5.6 (38.6)
6.5 (44.8)
7.5 (51.7)
8.6 (59.3)
75F DB, 62.5F WB (23.9C DB, 16.9C WB) 50% RH
Total - BTU/HR (kW)
15,000 (4.3) 16,000 (4.6) 27,000 (8.0) 34,000 (9.9)
Sensible - BTU/HR (kW)
14,000 (4.0) 15,000 (4.3) 23,000 (6.9) 29,000 (8.6)
Flow Rate - GPM (L/s)
3.0 (0.2)
3.3 (0.2)
5.5 (0.3)
6.9 (0.4)
Pressure Drop - psig (kPa)
3.1 (21.4)
3.7 (25.5)
4.2 (29.0)
4.8 (33.1)
75F DB, 61F WB (23.9C DB, 16.1C WB) 45% RH
Total - BTU/HR (kW)
14,000 (4.0) 16,000 (4.6) 26,000 (7.6) 33,000 (9.6)
Sensible - BTU/HR (kW)
14,000 (4.0) 16,000 (4.6) 24,000 (7.0) 31,000 (9.0)
Flow Rate - GPM (L/s)
2.9 (0.2)
3.2 (0.2)
5.2 (0.3)
6.6 (0.4)
Pressure Drop - psig (kPa)
3.0 (20.7)
3.6 (24.8)
3.7 (25.5)
4.4 (30.3)
72F DB, 60F WB (22.2C DB, 15.5C WB) 50% RH
Total - BTU/HR (kW)
13,000 (3.9) 14,000 (4.0) 23,000 (6.9) 29,000 (8.6)
Sensible - BTU/HR (kW)
13,000 (3.9) 13,000 (3.9) 21,000 (6.3) 27,000 (7.9)
Flow Rate - GPM (L/s)
2.5 (0.2)
2.8 (0.2)
4.6 (0.3)
5.8 (0.4)
Pressure Drop - psig (kPa)
2.3 (15.9)
2.7 (18.6)
3.0 (20.7)
3.6 (24.8)
72F DB, 58.6 WB (22.2D DB, 14.8C WB) 45% RH
Total - BTU/HR (kW)
13,000 (3.9) 14,000 (4.0) 22,000 (6.6) 28,000 (8.3)
Sensible - BTU/HR (kW)
13,000 (3.9) 14,000 (4.0) 21,000 (6.3) 27,000 (7.9)
Flow Rate - GPM (L/s)
2.5 (0.2)
2.8 (0.2)
4.4 (0.3)
5.6 (0.4)
Pressure Drop - psig (kPa)
2.3 (15.9)
2.7 (18.6)
2.7 (18.6)
3.3 (22.8)
70F DB, 58.5F WB (21.1C DB, 14.8C WB) 50% RH
Total - BTU/HR (kW)
11,000 (3.3) 12,000 (3.6) 20,000 (6.0) 26,000 (7.6)
Sensible - BTU/HR (kW)
11,000 (3.3) 12,000 (3.6) 19,000 (5.6) 25,000 (7.3)
Flow Rate - GPM (L/s)
2.3 (0.1)
2.5 (0.2)
4.1 (0.3)
5.2 (0.3)
Pressure Drop - psig (kPa)
1.9 (13.1)
2.2 (15.2)
2.4 (16.5)
2.9 (20.0)
70F DB, 57.2F WB (21.1C DB, 14.0C WB) 45% RH
Total - BTU/HR (kW)
12,000 (3.6) 12,000 (3.6) 20,000 (6.0) 25,000 (7.3)
Sensible - BTU/HR (kW)
12,000 (3.6) 12,000 (3.6) 20,000 (6.0) 25,000 (7.3)
Flow Rate - GPM (L/s)
2.3 (0.1)
2.5 (0.2)
4.0 (0.3)
5.1 (0.3)
Pressure Drop - psig (kPa)
1.9 (13.1)
2.2 (15.2)
2.3 (15.9)
2.7 (18.6)
AIR SYSTEM -- BELT DRIVE CENTRIFUGAL
Air Volume -- CFM (L/s)
625 (295)
700 (330)
900 (425)
1,200 (566)
Blower Motor -- HP (kW)
0.25 (0.2)
0.25 (0.2)
0.25 (0.2)
0.50 (0.4)
External Static Pressure -- inches of water (Pa)
0.3 (75)
0.3 (75)
0.3 (75)
0.3 (75)
Number of Blowers
1
1
1
1
COMPRESSOR
EER
7.9
12.5
12.9
13.7
Quantity
1
1
1
1
Nominal HP (kW)
1.0 (0.75)
1.5 (1.13)
2.0 (1.50)
3.0 (2.26)
6
APC NetworkAIR™ CM
14kW (4 ton) 17kW (5 ton)
49,000 (14.3) 56,000 (16.6)
41,000 (11.9) 47,000 (13.9)
45,000 (13.3) 52,000 (15.3)
41,000 (11.9) 47,000 (13.9)
45,000 (13.3) 55,000 (16.3)
44,000 (13.0) 52,000 (15.3)
43,000 (12.6) 50,000 (14.6)
40,000 (11.6) 45,000 (13.3)
45,000 (13.3) 50,000 (14.6)
45,000 (13.3) 49,000 (14.3)
44,000 (13.0) 49,000 (14.3)
42,000 (12.3) 45,000 (13.3)
44,000 (13.0) 48,000 (14.0)
44,000 (13.0) 47,000 (13.9)
75,000 (21.9) 82,000 (23.9)
54,000 (15.9) 60,000 (17.6)
15.0 (0.9)
16.5 (1.0)
10.1 (69.6)
12.1 (83.4)
55,000 (16.3) 60,000 (17.6)
47,000 (13.9) 53,000 (15.6)
11.0 (0.7)
12.2 (0.8)
5.6 (38.6)
6.8 (46.9)
52,000 (15.3) 58,000 (17.0)
49,000 (14.3) 55,000 (16.3)
10.6 (0.7)
11.8 (0.7)
5.2 (35.9)
6.4 (44.1)
46,000 (13.6) 51,000 (14.9)
43,000 (12.6) 48,000 (14.0)
9.2 (0.6)
10.3 (0.6)
4.0 (17.6)
4.9 (33.8)
44,000 (12.9) 49,000 (14.3)
43,000 (12.6) 49,000 (14.3)
8.9 (0.6)
9.9 (0.6)
3.7 (25.5)
4.6 (31.7)
41,000 (11.9) 44,000 (12.9)
39,000 (11.3) 43,000 (12.6)
8.2 (0.5)
8.9 (0.6)
3.2 (22.1)
3.7 (25.5)
39,000 (11.3) 44,000 (12.9)
39,000 (11.3) 44,000 (12.9)
7.9 (0.5)
8.9 (0.6)
3.0 (20.7)
3.7 (25.5)
2,000 (944)
1.50 (1.1)
0.5 (125)
1
2,300 (1,086)
1.50 (1.1)
0.5 (125)
1
13.8
1
4.0 (3.01)
13.9
1
5.0 (3.76)
Performance Specifications—Air Cooled
Performance Specifications - Air Cooled
CM (kW-tons)
EVAPORATOR COIL -- SLAB
3kW (1 ton) 5kW (1.5ton) 7kW (2 ton) 10kW (3 ton) 14kW (4 ton) 17kW (5 ton)
Face Area -- ft2 (m2)
Rows Deep
Face Velocity -- FPM (m/s)
HUMIDIFICATION --- SOLID STATE ELECTRODE CANISTER
Flush Cycle
Capacity -- Lbs/hr (Kg/hr)
kW
FILTERS
Quantity
Size -- Inches (mm)
1.9 (0.17)
3
338 (1.72)
1.9 (0.17)
3
378 (1.92)
2.9 (0.27)
3
310 (1.57)
2.9 (0.27)
3
414 (2.10)
5.2 (0.48)
4
385 (1.96)
5.2 (0.48)
4
442 (2.25)
automatic
5 (2.3)
1.7
automatic
5 (2.3)
1.7
automatic
5 (2.3)
1.7
automatic
5 (2.3)
1.7
automatic
10 (4.5)
3.4
automatic
10 (4.5)
3.4
1
20 x 20
(508 x 508)
1 (25)
1
20 x 20
(508 x 508)
1 (25)
1
20 x 20
(508 x 508)
1 (25)
1
20 x 20
(508 x 508)
1 (25)
2
16 x 25
(406 x 635)
1 (25)
2
16 x 25
(406 x 635)
1 (25)
10,000 (3.0)
1
19,000 (5.6)
1
20,000 (6.0)
1
26,000 (7.6)
1.5 (0.09)
0.7 (4.8)
31,000 (9.0)
2.0 (0.13)
1.2 (8.3)
39,000 (11.3) 50,000 (14.6) 55,000 (16.3)
3.0 (0.19)
3.0 (0.19)
3.5 (0.22)
2.4 (16.6)
2.4 (16.6)
3.1 (21.4)
280 (127)
18.0 (465)
49.0 (1245)
26.0 (673)
355 (161)
26.0 (673)
51.0 (1295)
26.0 (673)
380 (172)
26.0 (673)
51.0 (1295)
26.0 (673)
585 (265)
26.0 (673)
60.0 (1524)
38.0 (958)
585 (265)
26.0 (673)
60.0 (1524)
38.0 (958)
3/8
5/8
1/2
5/8
1/2
5/8
1/2
7/8
5/8
7/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
1/4
1/4
1/4
1/4
1/4
7/8
7/8
7/8
7/8
7/8
1/2
1/2
7/8
7/8
7/8
7/8
1-3/8
1-3/8
1-3/8
1-3/8
Depth -- Inches (mm)
REHEAT
Electric -- Equally Loaded on each phase, rated at 230V/1 and 203/3
Capacity -BTU/HR (kW) Includes Motor Heat
10,000 (3.0)
Stages
1
Hot Water -- 180F (82.2C) EWT, 140F (63.9C) LWT
Capacity - BTU/HR (kW) Includes Motor Heat
23,000 (6.9)
GPM (L/s)
1.0 (0.06)
Pressure Drop -- PSI (kPA)
0.3 (2.1)
PHYSICAL DATA
Weight -- lbs (kg)
280 (127)
Height -- Inches (mm)
18.0 (465)
Length -- Inches (mm)
49.0 (1245)
Depth -- Inches (mm)
26.0 (673)
CONNECTION SIZES*
Air
Liquid Line -- inches OD
3/8
Discharge Line -- inches OD
5/8
Hot Water
Supply Line -- inches OD
5/8
Return Line -- inches OD
5/8
Humidifier
Supply Line -- inches OD
1/4
Condensate Drain
Drain Line -- inches ID
7/8
MultiCool
Supply Line -- inches OD
1/2
Return Line -- inches OD
1/2
*Connection sizes, not recommended piping sizes
APC NetworkAIR™ CM
39,000 (11.3) 39,000 (11.3)
2
2
7
Performance Specifications—Water Cooled
NET COOLING CAPACITY - BTU/HR (kW)
3kW (1 ton) 5kW (1.5ton) 7kW (2 ton) 10kW (3 ton)
80F DB, 67F WB (26.7C DB, 19.4C WB) 50% RH
Total
16,000 (4.6) 21,000 (6.3) 26,000 (7.6) 43,000 (12.6)
Sensible
13,000 (3.9) 16,000 (4.6) 20,000 (6.0) 37,000 (10.6)
75F DB, 62.5F WB (23.9C DB, 16.9C WB) 50% RH
Total
15,000 (4.3) 20,000 (6.0) 24,000 (7.0) 34,000 (9.9)
Sensible
13,000 (3.9) 16,000 (4.6) 20,000 (6.0) 27,000 (8.0)
75F DB, 61F WB (23.9C DB, 16.1C WB) 45% RH
Total
15,000 (4.3) 19,000 (5.6) 23,000 (6.9) 33,000 (9.6)
Sensible
14,000 (4.0) 17,000 (4.9) 21,000 (6.3) 29,000 (8.6)
72F DB, 60F WB (22.2C DB, 15.5C WB) 50% RH
Total
14,000 (4.0) 19,000 (5.6) 23,000 (6.9) 33,000 (9.6)
Sensible
13,000 (3.9) 16,000 (4.6) 19,000 (5.6) 27,000 (8.0)
72F DB, 58.6 WB (22.2D DB, 14.8C WB) 45% RH
Total
14,000 (4.0) 19,000 (5.6) 22,000 (6.6) 32,000 (9.3)
Sensible
14,000 (4.0) 17,000 (4.9) 21,000 (6.3) 29,000 (8.6)
70F DB, 58.5F WB (21.1C DB, 14.8C WB) 50% RH
Total
14,000 (4.0) 18,000 (5.3) 22,000 (6.6) 32,000 (9.3)
Sensible
12,000 (3.6) 15,000 (4.3) 19,000 (5.6) 26,000 (7.6)
70F DB, 57.2F WB (21.1C DB, 14.0C WB) 45% RH
Total
14,000 (4.0) 18,000 (5.3) 22,000 (6.6) 31,000 (9.0)
Sensible
13,000 (3.9) 16,000 (4.6) 20,000 (6.0) 28,000 (8.3)
MULTICOOL -- COOLING CAPACITY DATA -- BTU/HR (kW) - 45 F (7.2 C) EWT
80F DB, 67F WB (26.7C DB, 19.4C WB) 50% RH
Total - BTU/HR (kW)
20,000 (5.9) 22,000 (6.6) 37,000 (10.9) 46,000 (13.6)
Sensible - BTU/HR (kW)
15,000 (4.3) 17,000 (4.9) 26,000 (7.6) 33,000 (9.6)
Flow Rate - GPM (L/s)
4.1 (0.3)
4.4 (0.3)
10.7 (0.7)
9.4 (0.6)
Pressure Drop - psig (kPa)
5.6 (38.6)
6.5 (44.8)
7.5 (51.7)
8.6 (59.3)
75F DB, 62.5F WB (23.9C DB, 16.9C WB) 50% RH
Total - BTU/HR (kW)
15,000 (4.3) 16,000 (4.6) 27,000 (8.0) 34,000 (9.9)
Sensible - BTU/HR (kW)
14,000 (4.0) 15,000 (4.3) 23,000 (6.9) 29,000 (8.6)
Flow Rate - GPM (L/s)
3.0 (0.2)
3.3 (0.2)
5.5 (0.3)
6.9 (0.4)
Pressure Drop - psig (kPa)
3.1 (21.4)
3.7 (25.5)
4.2 (29.0)
4.8 (33.1)
75F DB, 61F WB (23.9C DB, 16.1C WB) 45% RH
Total - BTU/HR (kW)
14,000 (4.0) 16,000 (4.6) 26,000 (7.6) 33,000 (9.6)
Sensible - BTU/HR (kW)
14,000 (4.0) 16,000 (4.6) 24,000 (7.0) 31,000 (9.0)
Flow Rate - GPM (L/s)
2.9 (0.2)
3.2 (0.2)
5.2 (0.3)
6.6 (0.4)
Pressure Drop - psig (kPa)
3.0 (20.7)
3.6 (24.8)
3.7 (25.5)
4.4 (30.3)
72F DB, 60F WB (22.2C DB, 15.5C WB) 50% RH
Total - BTU/HR (kW)
13,000 (3.9) 14,000 (4.0) 23,000 (6.9) 29,000 (8.6)
Sensible - BTU/HR (kW)
13,000 (3.9) 13,000 (3.9) 21,000 (6.3) 27,000 (7.9)
Flow Rate - GPM (L/s)
2.5 (0.2)
2.8 (0.2)
4.6 (0.3)
5.8 (0.4)
Pressure Drop - psig (kPa)
2.3 (15.9)
2.7 (18.6)
3.0 (20.7)
3.6 (24.8)
72F DB, 58.6 WB (22.2D DB, 14.8C WB) 45% RH
Total - BTU/HR (kW)
13,000 (3.9) 14,000 (4.0) 22,000 (6.6) 28,000 (8.3)
Sensible - BTU/HR (kW)
13,000 (3.9) 14,000 (4.0) 21,000 (6.3) 27,000 (7.9)
Flow Rate - GPM (L/s)
2.5 (0.2)
2.8 (0.2)
4.4 (0.3)
5.6 (0.4)
Pressure Drop - psig (kPa)
2.3 (15.9)
2.7 (18.6)
2.7 (18.6)
3.3 (22.8)
70F DB, 58.5F WB (21.1C DB, 14.8C WB) 50% RH
Total - BTU/HR (kW)
11,000 (3.3) 12,000 (3.6) 20,000 (6.0) 26,000 (7.6)
Sensible - BTU/HR (kW)
11,000 (3.3) 12,000 (3.6) 19,000 (5.6) 25,000 (7.3)
Flow Rate - GPM (L/s)
2.3 (0.1)
2.5 (0.2)
4.1 (0.3)
5.2 (0.3)
Pressure Drop - psig (kPa)
1.9 (13.1)
2.2 (15.2)
2.4 (16.5)
2.9 (20.0)
70F DB, 57.2F WB (21.1C DB, 14.0C WB) 45% RH
Total - BTU/HR (kW)
12,000 (3.6) 12,000 (3.6) 20,000 (6.0) 25,000 (7.3)
Sensible - BTU/HR (kW)
12,000 (3.6) 12,000 (3.6) 20,000 (6.0) 25,000 (7.3)
Flow Rate - GPM (L/s)
2.3 (0.1)
2.5 (0.2)
4.0 (0.3)
5.1 (0.3)
Pressure Drop - psig (kPa)
1.9 (13.1)
2.2 (15.2)
2.3 (15.9)
2.7 (18.6)
COOLANT REQUIREMENTS
THR -- MBH (kW)
23,000 (6.9) 28,000 (8.3) 34,000 (9.9) 49,000 (14.3)
65 F (18.3 C) Water In -- GPM (L/s)
1.0 (0.06)
1.3 (0.08)
1.8 (0.11)
2.3 (0.15)
Pressure Drop -- psig (kPa)
1.9 (13.1)
1.6 (11.0)
1.6 (11.0)
1.8 (12.4)
75 F (23.9 C) Water In -- GPM (L/s)
1.5 (0.09)
1.9 (0.12)
2.8 (0.18)
3.6 (0.23)
Pressure Drop -- psig (kPa)
3.3 (22.8)
1.9 (13.1)
2.6 (17.9)
2.3 (15.9)
85 F (29.4 C) Water In -- GPM (L/s)
2.9 (0.18)
3.9 (0.24)
6.4 (0.40)
8.4 (0.53)
Pressure Drop -- psig (kPa)
2.8 (19.3)
5.2 (35.9)
3.7 (25.5)
9.3 (64.1)
8
APC NetworkAIR™ CM
14kW (4 ton) 17kW (5 ton)
55,000 (16.3) 63,000 (18.3)
44,000 (13.0) 50,000 (14.6)
51,000 (14.9) 58,000 (17.0)
43,000 (12.6) 49,000 (14.3)
50,000 (14.6) 57,000 (16.9)
46,000 (13.6) 53,000 (15.6)
49,000 (14.3) 56,000 (16.6)
42,000 (12.3) 48,000 (14.0)
50,000 (14.6) 55,000 (16.3)
49,000 (14.3) 52,000 (15.3)
49,000 (14.3) 54,000 (15.9)
45,000 (13.3) 47,000 (13.9)
48,000 (14.0) 54,000 (15.9)
47,000 (13.9) 51,000 (14.9)
75,000 (21.9) 82,000 (23.9)
54,000 (15.9) 60,000 (17.6)
15.0 (0.9)
16.5 (1.0)
10.1 (69.6)
12.1 (83.4)
55,000 (16.3) 60,000 (17.6)
47,000 (13.9) 53,000 (15.6)
11.0 (0.7)
12.2 (0.8)
5.6 (38.6)
6.8 (46.9)
52,000 (15.3) 58,000 (17.0)
49,000 (14.3) 55,000 (16.3)
10.6 (0.7)
11.8 (0.7)
5.2 (35.9)
6.4 (44.1)
46,000 (13.6) 51,000 (14.9)
43,000 (12.6) 48,000 (14.0)
9.2 (0.6)
10.3 (0.6)
4.0 (17.6)
4.9 (33.8)
44,000 (12.9) 49,000 (14.3)
43,000 (12.6) 49,000 (14.3)
8.9 (0.6)
9.9 (0.6)
3.7 (25.5)
4.6 (31.7)
41,000 (11.9) 44,000 (12.9)
39,000 (11.3) 43,000 (12.6)
8.2 (0.5)
8.9 (0.6)
3.2 (22.1)
3.7 (25.5)
39,000 (11.3) 44,000 (12.9)
39,000 (11.3) 44,000 (12.9)
7.9 (0.5)
8.9 (0.6)
3.0 (20.7)
3.7 (25.5)
71,000 (20.9) 81,000 (23.6)
3.8 (0.24)
4.4 (0.28)
2.3 (15.9)
2.8 (19.3)
5.5 (0.35)
6.5 (0.41)
2.9 (20.0)
3.4 (23.4)
10.8 (0.68)
14.0 (0.88)
9.1 (62.7)
11.1 (76.5)
Performance Specifications—Water Cooled
Performance Specifications—Water Cooled
CM (kW-tons)
WATER REGULATING VALVES
Size -- 2 Way Ball Valve -- Inches, NPT (Cv)*
AIR SYSTEM -- BELT DRIVE CENTRIFUGAL
Air Volume -- CFM (L/s)
Blower Motor -- HP (kW)
External Static Pressure -- inches of water (Pa)
Number of Blowers
COMPRESSOR
EER
Quantity
Nominal HP (kW)
EVAPORATOR COIL -- SLAB
Face Area -- ft2 (m2)
Rows Deep
Face Velocity -- FPM (m/s)
HUMIDIFICATION --- SOLID STATE ELECTRODE CANISTER
Flush Cycle
Capacity -- Lbs/hr (Kg/hr)
kW
FILTERS
Quantity
Size -- Inches (mm)
3kW (1 ton) 5kW (1.5ton) 7kW (2 ton) 10kW (3 ton) 14kW (4 ton) 17kW (5 ton)
1/2 (7)
1/2 (7)
1/2 (7)
3/4 (10)
1 (12)
1 (12)
625 (295)
0.25 (0.2)
0.3 (75)
1
700 (330)
0.25 (0.2)
0.3 (75)
1
900 (425)
0.25 (0.2)
0.3 (75)
1
1,200 (566)
0.50 (0.4)
0.3 (75)
1
2,000 (944)
1.50 (1.1)
0.5 (125)
1
2,300 (1,086)
1.50 (1.1)
0.5 (125)
1
9.7
1
1.0 (0.75)
16.1
1
1.5 (1.13)
16.5
1
2.0 (1.50)
18.0
1
3.0 (2.26)
18.0
1
4.0 (3.01)
18.0
1
5.0 (3.76)
1.9 (0.17)
3
338 (1.72)
1.9 (0.17)
3
378 (1.92)
2.9 (0.27)
3
310 (1.57)
2.9 (0.27)
3
414 (2.10)
5.2 (0.48)
4
385 (1.96)
5.2 (0.48)
4
442 (2.25)
automatic
5 (2.3)
1.7
automatic
5 (2.3)
1.7
automatic
5 (2.3)
1.7
automatic
5 (2.3)
1.7
automatic
10 (4.5)
3.4
automatic
10 (4.5)
3.4
1
20 x 20
(508 x 508)
1 (25)
1
20 x 20
(508 x 508)
1 (25)
1
20 x 20
(508 x 508)
1 (25)
1
20 x 20
(508 x 508)
1 (25)
2
16 x 25
(406 x 635)
1 (25)
2
16 x 25
(406 x 635)
1 (25)
10,000 (3.0)
1
19,000 (5.6)
1
20,000 (6.0)
1
26,000 (7.6)
1.5 (0.09)
0.7 (4.8)
31,000 (9.0)
2.0 (0.13)
1.2 (8.3)
39,000 (11.3) 50,000 (14.6) 55,000 (16.3)
3.0 (0.19)
3.0 (0.19)
3.5 (0.22)
2.4 (16.6)
2.4 (16.6)
3.1 (21.4)
14,000 (4.0)
16,000 (4.6)
20,000 (6.0)
26,000 (7.6)
27,000 (7.9)
280 (127)
18.0 (465)
49.0 (1245)
26.0 (673)
355 (161)
26.0 (673)
51.0 (1295)
26.0 (673)
380 (172)
26.0 (673)
51.0 (1295)
26.0 (673)
585 (265)
26.0 (673)
60.0 (1524)
38.0 (958)
585 (265)
26.0 (673)
60.0 (1524)
38.0 (958)
5/8
3/4
7/8
1-3/8
1-3/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
1/4
1/4
1/4
1/4
1/4
7/8
7/8
7/8
7/8
7/8
1/2
1/2
7/8
7/8
7/8
7/8
1-3/8
1-3/8
1-3/8
1-3/8
Depth -- Inches (mm)
REHEAT
Electric -- Equally Loaded on each phase, rated at 230V/1 and 203/3
Capacity -BTU/HR (kW) Includes Motor Heat
10,000 (3.0)
Stages
1
Hot Water -- 180F (82.2C) EWT, 140F (63.9C) LWT
Capacity - BTU/HR (kW) Includes Motor Heat
23,000 (6.9)
GPM (L/s)
1.0 (0.06)
Pressure Drop -- PSI (kPA)
0.3 (2.1)
Hot Gas Reheat
Capacity -- BTU/HR (kW) Includes Motor Heat
13,000 (3.9)
PHYSICAL DATA
Weight -- lbs (kg)
280 (127)
Height -- Inches (mm)
18.0 (465)
Length -- Inches (mm)
49.0 (1245)
Depth -- Inches (mm)
26.0 (673)
CONNECTION SIZES**
Water In/Out -- Inches OD
5/8
Hot Water
Supply Line -- Inches OD
5/8
Return Line -- Inches OD
5/8
Humidifier
Supply Line -- Inches OD
1/4
Condensate Drain
Drain Line -- Inches ID
7/8
MultiCool
Supply Line -- Inches OD
1/2
Return Line -- Inches OD
1/2
*2-Way Single Seated, 400 psig W.W.P. max
**Connection sizes, not recommended piping sizes
APC NetworkAIR™ CM
39,000 (11.3) 39,000 (11.3)
2
2
9
Performance Specifications—Glycol Cooled
NET COOLING CAPACITY - BTU/HR (kW)
3kW (1 ton) 5kW (1.5ton) 7kW (2 ton) 10kW (3 ton)
80F DB, 67F WB (26.7C DB, 19.4C WB) 50% RH
Total
14,000 (4.0) 17,000 (4.9) 23,000 (6.9) 32,000 (9.3)
Sensible
12,000 (3.6) 14,000 (4.0) 19,000 (5.6) 26,000 (7.6)
75F DB, 62.5F WB (23.9C DB, 16.9C WB) 50% RH
Total
13,000 (3.9) 16,000 (4.6) 22,000 (6.6) 31,000 (9.0)
Sensible
12,000 (3.6) 14,000 (4.0) 19,000 (5.6) 26,000 (7.6)
75F DB, 61F WB (23.9C DB, 16.1C WB) 45% RH
Total
13,000 (3.9) 16,000 (4.6) 21,000 (6.3) 30,000 (8.9)
Sensible
13,000 (3.9) 15,000 (4.3) 20,000 (6.0) 27,000 (7.9)
72F DB, 60F WB (22.2C DB, 15.5C WB) 50% RH
Total
12,000 (3.6) 15,000 (4.3) 21,000 (6.3) 29,000 (8.6)
Sensible
12,000 (3.6) 14,000 (4.0) 18,000 (5.3) 25,000 (7.3)
72F DB, 58.6 WB (22.2D DB, 14.8C WB) 45% RH
Total
12,000 (3.6) 15,000 (4.3) 20,000 (6.0) 29,000 (8.6)
Sensible
12,000 (3.6) 15,000 (4.3) 20,000 (6.0) 28,000 (8.3)
70F DB, 58.5F WB (21.1C DB, 14.8C WB) 50% RH
Total
12,000 (3.6) 15,000 (4.3) 20,000 (6.0) 29,000 (8.6)
Sensible
12,000 (3.6) 13,000 (3.9) 18,000 (5.3) 25,000 (7.3)
70F DB, 57.2F WB (21.1C DB, 14.0C WB) 45% RH
Total
12,000 (3.6) 15,000 (4.3) 22,000 (6.6) 28,000 (8.3)
Sensible
12,000 (3.6) 14,000 (4.0) 20,000 (6.0) 26,000 (7.6)
MULTICOOL -- COOLING CAPACITY DATA -- BTU/HR (kW) - 45F (7.2C) EWT
80F DB, 67F WB (26.7C DB, 19.4C WB) 50% RH
Total - BTU/HR (kW)
20,000 (5.9) 22,000 (6.6) 37,000 (10.9) 46,000 (13.6)
Sensible - BTU/HR (kW)
15,000 (4.3) 17,000 (4.9) 26,000 (7.6) 33,000 (9.6)
Flow Rate - GPM (L/s)
4.1 (0.3)
4.4 (0.3)
10.7 (0.7)
9.4 (0.6)
Pressure Drop - psig (kPa)
5.6 (38.6)
6.5 (44.8)
7.5 (51.7)
8.6 (59.3)
75F DB, 62.5F WB (23.9C DB, 16.9C WB) 50% RH
Total - BTU/HR (kW)
15,000 (4.3) 16,000 (4.6) 27,000 (8.0) 34,000 (9.9)
Sensible - BTU/HR (kW)
14,000 (4.0) 15,000 (4.3) 23,000 (6.9) 29,000 (8.6)
Flow Rate - GPM (L/s)
3.0 (0.2)
3.3 (0.2)
5.5 (0.3)
6.9 (0.4)
Pressure Drop - psig (kPa)
3.1 (21.4)
3.7 (25.5)
4.2 (29.0)
4.8 (33.1)
75F DB, 61F WB (23.9C DB, 16.1C WB) 45% RH
Total - BTU/HR (kW)
14,000 (4.0) 16,000 (4.6) 26,000 (7.6) 33,000 (9.6)
Sensible - BTU/HR (kW)
14,000 (4.0) 16,000 (4.6) 24,000 (7.0) 31,000 (9.0)
Flow Rate - GPM (L/s)
2.9 (0.2)
3.2 (0.2)
5.2 (0.3)
6.6 (0.4)
Pressure Drop - psig (kPa)
3.0 (20.7)
3.6 (24.8)
3.7 (25.5)
4.4 (30.3)
72F DB, 60F WB (22.2C DB, 15.5C WB) 50% RH
Total - BTU/HR (kW)
13,000 (3.9) 14,000 (4.0) 23,000 (6.9) 29,000 (8.6)
Sensible - BTU/HR (kW)
13,000 (3.9) 13,000 (3.9) 21,000 (6.3) 27,000 (7.9)
Flow Rate - GPM (L/s)
2.5 (0.2)
2.8 (0.2)
4.6 (0.3)
5.8 (0.4)
Pressure Drop - psig (kPa)
2.3 (15.9)
2.7 (18.6)
3.0 (20.7)
3.6 (24.8)
72F DB, 58.6 WB (22.2D DB, 14.8C WB) 45% RH
Total - BTU/HR (kW)
13,000 (3.9) 14,000 (4.0) 22,000 (6.6) 28,000 (8.3)
Sensible - BTU/HR (kW)
13,000 (3.9) 14,000 (4.0) 21,000 (6.3) 27,000 (7.9)
Flow Rate - GPM (L/s)
2.5 (0.2)
2.8 (0.2)
4.4 (0.3)
5.6 (0.4)
Pressure Drop - psig (kPa)
2.3 (15.9)
2.7 (18.6)
2.7 (18.6)
3.3 (22.8)
70F DB, 58.5F WB (21.1C DB, 14.8C WB) 50% RH
Total - BTU/HR (kW)
11,000 (3.3) 12,000 (3.6) 20,000 (6.0) 26,000 (7.6)
Sensible - BTU/HR (kW)
11,000 (3.3) 12,000 (3.6) 19,000 (5.6) 25,000 (7.3)
Flow Rate - GPM (L/s)
2.3 (0.1)
2.5 (0.2)
4.1 (0.3)
5.2 (0.3)
Pressure Drop - psig (kPa)
1.9 (13.1)
2.2 (15.2)
2.4 (16.5)
2.9 (20.0)
70F DB, 57.2F WB (21.1C DB, 14.0C WB) 45% RH
Total - BTU/HR (kW)
12,000 (3.6) 12,000 (3.6) 20,000 (6.0) 25,000 (7.3)
Sensible - BTU/HR (kW)
12,000 (3.6) 12,000 (3.6) 20,000 (6.0) 25,000 (7.3)
Flow Rate - GPM (L/s)
2.3 (0.1)
2.5 (0.2)
4.0 (0.3)
5.1 (0.3)
Pressure Drop - psig (kPa)
1.9 (13.1)
2.2 (15.2)
2.3 (15.9)
2.7 (18.6)
10
APC NetworkAIR™ CM
14kW (4 ton) 17kW (5 ton)
47,000 (13.9) 55,000 (16.3)
40,000 (11.6) 46,000 (13.6)
44,000 (13.0) 51,000 (14.9)
40,000 (11.6) 46,000 (13.6)
44,000 (13.0) 51,000 (14.9)
43,000 (12.6) 49,000 (14.3)
42,000 (12.3) 49,000 (14.3)
39,000 (11.3) 45,000 (13.3)
44,000 (13.0) 49,000 (14.3)
44,000 (13.0) 48,000 (14.0)
42,000 (12.3) 48,000 (14.0)
41,000 (11.9) 44,000 (13.0)
43,000 (12.6) 47,000 (13.9)
43,000 (12.6) 47,000 (13.9)
75,000 (21.9) 82,000 (23.9)
54,000 (15.9) 60,000 (17.6)
15.0 (0.9)
16.5 (1.0)
10.1 (69.6)
12.1 (83.4)
55,000 (16.3) 60,000 (17.6)
47,000 (13.9) 53,000 (15.6)
11.0 (0.7)
12.2 (0.8)
5.6 (38.6)
6.8 (46.9)
52,000 (15.3) 58,000 (17.0)
49,000 (14.3) 55,000 (16.3)
10.6 (0.7)
11.8 (0.7)
5.2 (35.9)
6.4 (44.1)
46,000 (13.6) 51,000 (14.9)
43,000 (12.6) 48,000 (14.0)
9.2 (0.6)
10.3 (0.6)
4.0 (17.6)
4.9 (33.8)
44,000 (12.9) 49,000 (14.3)
43,000 (12.6) 49,000 (14.3)
8.9 (0.6)
9.9 (0.6)
3.7 (25.5)
4.6 (31.7)
41,000 (11.9) 44,000 (12.9)
39,000 (11.3) 43,000 (12.6)
8.2 (0.5)
8.9 (0.6)
3.2 (22.1)
3.7 (25.5)
39,000 (11.3) 44,000 (12.9)
39,000 (11.3) 44,000 (12.9)
7.9 (0.5)
8.9 (0.6)
3.0 (20.7)
3.7 (25.5)
Performance Specifications—Glycol Cooled
Performance Specifications—Glycol Cooled
CM (kW-tons)
3kW (1 ton) 5kW (1.5ton) 7kW (2 ton) 10kW (3 ton) 14kW (4 ton) 17kW (5 ton)
ECONOMIZER -- NET COOLING CAPACITY DATA -- BTU/HR (kW)
80F DB, 67F WB (26.7C DB, 19.4C WB) 50% RH
Total
15,000 (4.3) 17,000 (4.9) 28,000 (8.3) 36,000 (10.3) 56,000 (16.6) 63,000 (18.3)
Sensible
13,000 (3.9) 15,000 (4.3) 22,000 (6.6) 29,000 (8.6) 46,000 (13.6) 52,000 (15.3)
75F DB, 62.5F WB (23.9C DB, 16.9C WB) 50% RH
Total
11,000 (3.3) 12,000 (3.6) 20,000 (6.0) 26,000 (7.6) 38,000 (10.9) 43,000 (12.6)
Sensible
11,000 (3.3) 12,000 (3.6) 19,000 (5.6) 25,000 (7.3) 38,000 (10.9) 43,000 (12.6)
75F DB, 61F WB (23.9C DB, 16.1C WB) 45% RH
Total
11,000 (3.3) 12,000 (3.6) 20,000 (6.0) 25,000 (7.3) 38,000 (10.9) 43,000 (12.6)
Sensible
11,000 (3.3) 12,000 (3.6) 20,000 (6.0) 25,000 (7.3) 38,000 (10.9) 43,000 (12.6)
72F DB, 60F WB (22.2C DB, 15.5C WB) 50% RH
Total
9,000 (2.6)
10,000 (2.9) 17,000 (4.9) 21,000 (6.3) 30,000 (8.9) 34,000 (9.9)
Sensible
9,000 (2.6)
10,000 (2.9) 17,000 (4.9) 21,000 (6.3) 30,000 (8.9) 34,000 (9.9)
72F DB, 58.6 WB (22.2D DB, 14.8C WB) 45% RH
Total
9,000 (2.6)
10,000 (2.9) 17,000 (4.9) 21,000 (6.3) 30,000 (8.9) 34,000 (9.9)
Sensible
9,000 (2.6)
10,000 (2.9) 17,000 (4.9) 21,000 (6.3) 30,000 (8.9) 34,000 (9.9)
70F DB, 58.5F WB (21.1C DB, 14.8C WB) 50% RH
Total
8,000 (2.3)
9,000 (2.6)
16,000 (4.6) 19,000 (5.6) 26,000 (7.6) 28,000 (8.3)
Sensible
8,000 (2.3)
9,000 (2.6)
16,000 (4.6) 19,000 (5.6) 26,000 (7.6) 28,000 (8.3)
70F DB, 57.2F WB (21.1C DB, 14.0C WB) 45% RH
Total
8,000 (2.3)
9,000 (2.6)
16,000 (4.6) 19,000 (5.6) 26,000 (7.6) 28,000 (8.3)
Sensible
8,000 (2.3)
9,000 (2.6)
16,000 (4.6) 19,000 (5.6) 26,000 (7.6) 28,000 (8.3)
COOLANT REQUIREMENTS
THR -- MBH (kW)
21,000 (6.3) 25,000 (7.3) 33,000 (9.6) 48,000 (14.0) 68,000 (20.0) 78,000 (23.0)
105 F (40.6 C) Glycol In -- GPM (L/s)
2.7 (0.17)
3.8 (0.24)
5.7 (0.36)
7.2 (0.45)
10.8 (0.68)
14.0 (0.88)
Pressure Drop w/HX -- psig (kPa)
3.2 (22.1)
3.9 (26.9)
4.9 (33.8)
8.3 (57.2)
8.0 (55.2)
9.1 (62.7)
Internal Glycol Volume -- gal (L)
2 (7.6)
2 (7.6)
2 (7.6)
2 (7.6)
2 (7.6)
2 (7.6)
Internal Glycol w/Economizer Volume -- gal (L)
4 (15.1)
4 (15.1)
4 (15.1)
4 (15.1)
4 (15.1)
4 (15.1)
WATER REGULATING VALVES
Size -- 2 Way Ball Valve -- Inches, NPT (Cv)*
1/2 (7)
1/2 (7)
1/2 (7)
3/4 (10)
1 (12)
1 (12)
AIR SYSTEM -- BELT DRIVE CENTRIFUGAL
Air Volume -- CFM (L/s)
625 (295)
700 (330)
900 (425)
1,200 (566)
2,000 (944) 2,300 (1,086)
Blower Motor -- HP (kW)
0.25 (0.2)
0.25 (0.2)
0.25 (0.2)
0.50 (0.4)
1.50 (1.1)
1.50 (1.1)
External Static Pressure -- inches of water (Pa)
0.3 (75)
0.3 (75)
0.3 (75)
0.3 (75)
0.5 (125)
0.5 (125)
Number of Blowers
1
1
1
1
1
1
COMPRESSOR
EER
7.3
11.6
11.9
12.5
12.6
12.7
Quantity
1
1
1
1
1
1
Nominal HP (kW)
1.0 (0.75)
1.5 (1.13)
2.0 (1.50)
3.0 (2.26)
4.0 (3.01)
5.0 (3.76)
EVAPORATOR COIL -- SLAB
1.9 (0.17)
1.9 (0.17)
2.9 (0.27)
2.9 (0.27)
5.2 (0.48)
5.2 (0.48)
Face Area -- ft2 (m2)
Rows Deep
3
3
3
3
4
4
Face Velocity -- FPM (m/s)
338 (1.72)
378 (1.92)
310 (1.57)
414 (2.10)
385 (1.96)
442 (2.25)
HUMIDIFICATION --- SOLID STATE ELECTRODE CANISTER
Flush Cycle
automatic
automatic
automatic
automatic
automatic
automatic
Capacity -- Lbs/hr (Kg/hr)
5 (2.3)
5 (2.3)
5 (2.3)
5 (2.3)
10 (4.5)
10 (4.5)
kW
1.7
1.7
1.7
1.7
3.4
3.4
FILTERS
Quantity
1
1
1
1
2
2
20
x
20
20
x
20
20
x
20
20
x
20
16
x
25
16
x 25
Size -- Inches (mm)
(508 x 508)
(508 x 508)
(508 x 508)
(508 x 508)
(406 x 635)
(406 x 635)
Depth -- Inches (mm)
1 (25)
1 (25)
1 (25)
1 (25)
1 (25)
1 (25)
REHEAT
Electric -- Equally Loaded on each phase, rated at 230V/1 and 203/3
Capacity -BTU/HR (kW) Includes Motor Heat
10,000 (3.0) 10,000 (3.0) 19,000 (5.6) 20,000 (6.0) 39,000 (11.3) 39,000 (11.3)
Stages
1
1
1
1
2
2
Hot Water -- 180F (82.2C) EWT, 140F (63.9C) LWT
Capacity - BTU/HR (kW) Includes Motor Heat
23,000 (6.9) 26,000 (7.6) 31,000 (9.0) 39,000 (11.3) 50,000 (14.6) 55,000 (16.3)
GPM (L/s)
1.0 (0.06)
1.5 (0.09)
2.0 (0.13)
3.0 (0.19)
3.0 (0.19)
3.5 (0.22)
Pressure Drop -- PSI (kPA)
0.3 (2.1)
0.7 (4.8)
1.2 (8.3)
2.4 (16.6)
2.4 (16.6)
3.1 (21.4)
Hot Gas Reheat
Capacity -- BTU/HR (kW) Includes Motor Heat
13,000 (3.9) 14,000 (4.0) 16,000 (4.6) 20,000 (6.0) 26,000 (7.6) 27,000 (7.9)
PHYSICAL DATA
Weight -- lbs (kg)
280 (127)
280 (127)
355 (161)
380 (172)
585 (265)
585 (265)
Height -- Inches (mm)
18.0 (465)
18.0 (465)
26.0 (673)
26.0 (673)
26.0 (673)
26.0 (673)
Length -- Inches (mm)
49.0 (1245)
49.0 (1245)
51.0 (1295)
51.0 (1295)
60.0 (1524)
60.0 (1524)
Depth -- Inches (mm)
26.0 (673)
26.0 (673)
26.0 (673)
26.0 (673)
38.0 (958)
38.0 (958)
APC NetworkAIR™ CM
11
Performance Specifications—Glycol Cooled
Performance Specifications—Glycol Cooled
CM (kW-tons)
CONNECTION SIZES**
Glycol In/Out -- Inches OD
Hot Water
Supply Line -- Inches OD
Return Line -- Inches OD
Humidifier
Supply Line -- Inches OD
Condensate Drain
Drain Line -- Inches ID
MultiCool
Supply Line -- Inches OD
Return Line -- Inches OD
*2-Way Single Seated, 400 psig W.W.P. max
**Connection sizes, not recommended piping sizes
12
3kW (1 ton) 5kW (1.5ton) 7kW (2 ton) 10kW (3 ton) 14kW (4 ton) 17kW (5 ton)
5/8
5/8
3/4
7/8
1-3/8
1-3/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
1/4
1/4
1/4
1/4
1/4
1/4
7/8
7/8
7/8
7/8
7/8
7/8
1/2
1/2
1/2
1/2
7/8
7/8
7/8
7/8
1-3/8
1-3/8
1-3/8
1-3/8
APC NetworkAIR™ CM
Performance Specifications—Chilled Water
COOLING CAPACITY - BTU/HR (kW) 45F (7.2C) --- EWT
80F DB, 67F WB (26.7C DB, 19.4C WB) 50% RH
Total - BTU/HR (kW)
Sensible - BTU/HR (kW)
Flow Rate - GPM (L/s)
Pressure Drop - psig (kPa)
75F DB, 62.5F WB (23.9C DB, 16.9C WB) 50% RH
Total - BTU/HR (kW)
Sensible - BTU/HR (kW)
Flow Rate - GPM (L/s)
Pressure Drop - psig (kPa)
75F DB, 61F WB (23.9C DB, 16.1C WB) 45% RH
Total - BTU/HR (kW)
Sensible - BTU/HR (kW)
Flow Rate - GPM (L/s)
Pressure Drop - psig (kPa)
72F DB, 60F WB (22.2C DB, 15.5C WB) 50% RH
Total - BTU/HR (kW)
Sensible - BTU/HR (kW)
Flow Rate - GPM (L/s)
Pressure Drop - psig (kPa)
72F DB, 58.6 WB (22.2D DB, 14.8C WB) 45% RH
Total - BTU/HR (kW)
Sensible - BTU/HR (kW)
Flow Rate - GPM (L/s)
Pressure Drop - psig (kPa)
70F DB, 58.5F WB (21.1C DB, 14.8C WB) 50% RH
Total - BTU/HR (kW)
Sensible - BTU/HR (kW)
Flow Rate - GPM (L/s)
Pressure Drop - psig (kPa)
70F DB, 57.2F WB (21.1C DB, 14.0C WB) 45% RH
Total - BTU/HR (kW)
Sensible - BTU/HR (kW)
Flow Rate - GPM (L/s)
Pressure Drop - psig (kPa)
WATER REGULATING VALVES
Size -- 2 Way Ball Valve -- Inches, NPT (Cv)*
AIR SYSTEM -- BELT DRIVE CENTRIFUGAL
Air Volume -- CFM (L/s)
Blower Motor -- HP (kW)
External Static Pressure -- inches of water (Pa)
Number of Blowers
COOLING COIL -- SLAB
3kW (1 ton) 5kW (1.5ton) 7kW (2 ton) 10kW (3 ton) 14kW (4 ton) 17kW (5 ton)
20,000 (5.9)
15,000 (4.3)
4.1 (0.3)
5.6 (38.6)
22,000 (6.6)
17,000 (4.9)
4.4 (0.3)
6.5 (44.8)
37,000 (10.9) 46,000 (13.6) 75,000 (21.9) 82,000 (23.9)
26,000 (7.6) 33,000 (9.6) 54,000 (15.9) 60,000 (17.6)
10.7 (0.7)
9.4 (0.6)
15.0 (0.9)
16.5 (1.0)
7.5 (51.7)
8.6 (59.3)
10.1 (69.6)
12.1 (83.4)
15,000 (4.3)
14,000 (4.0)
3.0 (0.2)
3.1 (21.4)
16,000 (4.6)
15,000 (4.3)
3.3 (0.2)
3.7 (25.5)
27,000 (8.0)
23,000 (6.9)
5.5 (0.3)
4.2 (29.0)
34,000 (9.9)
29,000 (8.6)
6.9 (0.4)
4.8 (33.1)
55,000 (16.3) 60,000 (17.6)
47,000 (13.9) 53,000 (15.6)
11.0 (0.7)
12.2 (0.8)
5.6 (38.6)
6.8 (46.9)
14,000 (4.0)
14,000 (4.0)
2.9 (0.2)
3.0 (20.7)
16,000 (4.6)
16,000 (4.6)
3.2 (0.2)
3.6 (24.8)
26,000 (7.6)
24,000 (7.0)
5.2 (0.3)
3.7 (25.5)
33,000 (9.6)
31,000 (9.0)
6.6 (0.4)
4.4 (30.3)
52,000 (15.3) 58,000 (17.0)
49,000 (14.3) 55,000 (16.3)
10.6 (0.7)
11.8 (0.7)
5.2 (35.9)
6.4 (44.1)
13,000 (3.9)
13,000 (3.9)
2.5 (0.2)
2.3 (15.9)
14,000 (4.0)
13,000 (3.9)
2.8 (0.2)
2.7 (18.6)
23,000 (6.9)
21,000 (6.3)
4.6 (0.3)
3.0 (20.7)
29,000 (8.6)
27,000 (7.9)
5.8 (0.4)
3.6 (24.8)
46,000 (13.6) 51,000 (14.9)
43,000 (12.6) 48,000 (14.0)
9.2 (0.6)
10.3 (0.6)
4.0 (17.6)
4.9 (33.8)
13,000 (3.9)
13,000 (3.9)
2.5 (0.2)
2.3 (15.9)
14,000 (4.0)
14,000 (4.0)
2.8 (0.2)
2.7 (18.6)
22,000 (6.6)
21,000 (6.3)
4.4 (0.3)
2.7 (18.6)
28,000 (8.3)
27,000 (7.9)
5.6 (0.4)
3.3 (22.8)
44,000 (12.9) 49,000 (14.3)
43,000 (12.6) 49,000 (14.3)
8.9 (0.6)
9.9 (0.6)
3.7 (25.5)
4.6 (31.7)
11,000 (3.3)
11,000 (3.3)
2.3 (0.1)
1.9 (13.1)
12,000 (3.6)
12,000 (3.6)
2.5 (0.2)
2.2 (15.2)
20,000 (6.0)
19,000 (5.6)
4.1 (0.3)
2.4 (16.5)
26,000 (7.6)
25,000 (7.3)
5.2 (0.3)
2.9 (20.0)
41,000 (11.9) 44,000 (12.9)
39,000 (11.3) 43,000 (12.6)
8.2 (0.5)
8.9 (0.6)
3.2 (22.1)
3.7 (25.5)
12,000 (3.6)
12,000 (3.6)
2.3 (0.1)
1.9 (13.1)
12,000 (3.6)
12,000 (3.6)
2.5 (0.2)
2.2 (15.2)
20,000 (6.0)
20,000 (6.0)
4.0 (0.3)
2.3 (15.9)
25,000 (7.3)
25,000 (7.3)
5.1 (0.3)
2.7 (18.6)
39,000 (11.3) 44,000 (12.9)
39,000 (11.3) 44,000 (12.9)
7.9 (0.5)
8.9 (0.6)
3.0 (20.7)
3.7 (25.5)
1/2 (7)
1/2 (7)
1/2 (7)
3/4 (10)
1 (12)
1 (12)
625 (295)
0.25 (0.2)
0.3 (75)
1
700 (330)
0.25 (0.2)
0.3 (75)
1
900 (425)
0.25 (0.2)
0.3 (75)
1
1,200 (566)
0.50 (0.4)
0.3 (75)
1
2,000 (944)
1.50 (1.1)
0.5 (125)
1
2,300 (1,086)
1.50 (1.1)
0.5 (125)
1
1.9 (0.17)
3
378 (1.92)
2.9 (0.27)
3
310 (1.57)
2.9 (0.27)
3
414 (2.10)
5.2 (0.48)
4
385 (1.96)
5.2 (0.48)
4
442 (2.25)
automatic
5 (2.3)
1.7
automatic
5 (2.3)
1.7
automatic
5 (2.3)
1.7
automatic
10 (4.5)
3.4
automatic
10 (4.5)
3.4
10,000 (3.0)
1
19,000 (5.6)
1
20,000 (6.0)
1
26,000 (7.6)
1.5 (0.09)
0.7 (4.8)
31,000 (9.0)
2.0 (0.13)
1.2 (8.3)
39,000 (11.3) 50,000 (14.6) 55,000 (16.3)
3.0 (0.19)
3.0 (0.19)
3.5 (0.22)
2.4 (16.6)
2.4 (16.6)
3.1 (21.4)
1
20 x 20
(508 x 508)
1 (25)
1
20 x 20
(508 x 508)
1 (25)
1.9 (0.17)
Face Area -- ft2 (m2)
Rows Deep
3
Face Velocity -- FPM (m/s)
338 (1.72)
HUMIDIFICATION --- SOLID STATE ELECTRODE CANISTER
Flush Cycle
automatic
Capacity -- Lbs/hr (Kg/hr)
5 (2.3)
kW
1.7
REHEAT
Electric -- Equally Loaded on each phase, rated at 230V/1 and 203/3
Capacity -BTU/HR (kW) Includes Motor Heat
10,000 (3.0)
Stages
1
Hot Water -- 180F (82.2C) EWT, 140F (63.9C) LWT
Capacity - BTU/HR (kW) Includes Motor Heat
23,000 (6.9)
GPM (L/s)
1.0 (0.06)
Pressure Drop -- PSI (kPA)
0.3 (2.1)
FILTERS
Quantity
1
20 x 20
Size -- Inches (mm)
(508 x 508)
Depth -- Inches (mm)
1 (25)
APC NetworkAIR™ CM
1
20 x 20
(508 x 508)
1 (25)
39,000 (11.3) 39,000 (11.3)
2
2
2
16 x 25
(406 x 635)
1 (25)
2
16 x 25
(406 x 635)
1 (25)
13
Performance Specifications—Chilled Water
Performance Specifications - Chilled Water
CM (kW-tons)
PHYSICAL DATA
Weight -- lbs (kg)
Height -- Inches (mm)
Length -- Inches (mm)
Depth -- Inches (mm)
CONNECTION SIZES**
Water In/Out -- Inches OD
Hot Water
Supply Line -- Inches OD
Return Line -- Inches OD
Humidifier
Supply Line -- Inches OD
Condensate Drain
Return Line -- Inches ID
*2-Way Single Seated, 400 psig W.W.P. max
**Connection sizes, not recommended piping sizes
14
3kW (1 ton) 5kW (1.5ton) 7kW (2 ton) 10kW (3 ton) 14kW (4 ton) 17kW (5 ton)
280 (127)
18.0 (465)
49.0 (1245)
26.0 (673)
280 (127)
18.0 (465)
49.0 (1245)
26.0 (673)
355 (161)
26.0 (673)
51.0 (1295)
26.0 (673)
380 (172)
26.0 (673)
51.0 (1295)
26.0 (673)
585 (265)
26.0 (673)
60.0 (1524)
38.0 (958)
585 (265)
26.0 (673)
60.0 (1524)
38.0 (958)
1/2
1/2
7/8
7/8
7/8
7/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
1/4
1/4
1/4
1/4
1/4
1/4
7/8
7/8
7/8
7/8
7/8
7/8
APC NetworkAIR™ CM
Electrical Data
AIR COOLED - SELF CONTAINED
REHEAT
Electric
HUMID
Electrode Canister - Steam
VOLTAGE 208 230 277 208 230 480
PHASE
1
1
1
3
3
3
3 kW (1 ton)
FLA 24.1 25.1 22.7 N/A N/A N/A
WSA 27.0 28.0 25.1 N/A N/A N/A
MOP 30.0 35.0 30.0 N/A N/A N/A
5 kW (1.5 ton)
FLA 24.0 25.0 22.6 N/A N/A N/A
WSA 29.4 30.4 27.1 N/A N/A N/A
MOP 35.0 35.0 35.0 N/A N/A N/A
7 kW (2 ton)
FLA 35.3 37.4 29.7 24.4 25.6 11.5
WSA 41.7 43.8 35.0 28.7 29.9 13.6
MOP 50.0 50.0 40.0 35.0 35.0 15.0
10 kW (3 ton)
FLA 43.4 45.5 35.9 30.5 25.9 13.2
WSA 52.6 54.7 43.5 35.9 37.1 15.8
MOP 70.0 70.0 50.0 45.0 45.0 20.0
14 kW (4 ton)
FLA N/A N/A N/A 50.0 52.0 25.3
WSA N/A N/A N/A 64.8 67.5 31.7
MOP N/A N/A N/A 70.0 70.0 35.0
17 kW (5 ton)
FLA N/A N/A N/A 51.2 53.2 25.3
WSA N/A N/A N/A 68.4 71.1 34.4
MOP N/A N/A N/A 80.0 80.0 40.0
AIR COOLED
REHEAT
Electric
HUMID
Electrode Canister - Steam
VOLTAGE 208 230 277 208 230 480
PHASE
1
1
1
3
3
3
3 kW (1 ton)
FLA 21.0 22.0 20.1 N/A N/A N/A
WSA 23.9 25.0 22.2 N/A N/A N/A
MOP 30.0 30.0 25.0 N/A N/A N/A
5 kW (1.5 ton)
FLA 20.9 21.9 14.5 N/A N/A N/A
WSA 26.3 27.3 19.0 N/A N/A N/A
MOP 35.0 35.0 25.0 N/A N/A N/A
7 kW (2 ton)
FLA 31.0 33.1 26.1 20.1 21.3 9.4
WSA 37.4 39.5 31.4 24.4 25.6 11.5
MOP 45.0 50.0 40.0 30.0 30.0 15.0
10 kW (3 ton)
FLA 38.4 40.5 31.5 25.5 20.9 11.1
WSA 47.6 49.7 39.1 30.9 32.1 13.7
MOP 60.0 60.0 50.0 40.0 40.0 15.0
14 kW (4 ton)
FLA N/A N/A N/A 43.2 45.6 22.1
WSA N/A N/A N/A 51.7 54.1 25.4
MOP N/A N/A N/A 60.0 60.0 30.0
17 kW (5 ton)
FLA N/A N/A N/A 44.4 46.8 22.1
WSA N/A N/A N/A 61.6 64.7 31.2
MOP N/A N/A N/A 70.0 70.0 35.0
Steam, Hot Water or None
Electric
Steam, Hot Water or None
Electrode Canister - Steam
Steam or None
Steam or None
208 230 277 208 230 480 208 230 277 208 230 480 208 230 277 208 230 480
1
1
1
3
3
3
1
1
1
3
3
3
1
1
1
3
3
3
20.6 19.7 17.2 N/A N/A N/A 24.1 25.1 22.7 N/A N/A N/A 12.4 12.3 11.1 N/A N/A N/A
23.5 22.6 25.1 N/A N/A N/A 27.0 28.0 25.1 N/A N/A N/A 15.3 15.2 13.5 N/A N/A N/A
30.0 30.0 25.0 N/A N/A N/A 30.0 35.0 30.0 N/A N/A N/A 20.0 20.0 15.0 N/A N/A N/A
20.5 19.6 17.1 N/A N/A N/A 24.0 25.0 22.6 N/A N/A N/A 12.3 12.2 11.0 N/A N/A N/A
22.8 21.9 19.0 N/A N/A N/A 29.4 30.4 27.1 N/A N/A N/A 14.6 14.5 12.9 N/A N/A N/A
35.0 30.0 25.0 N/A N/A N/A 35.0 35.0 35.0 N/A N/A N/A 25.0 25.0 20.0 N/A N/A N/A
23.0 22.1 19.2 20.7 19.8 9.8 35.3 37.4 29.7 24.4 25.6 11.5 14.8 14.7 13.1 12.5 12.4 6.1
29.4 28.5 24.6 25.0 23.4 11.9 41.7 43.8 35.0 28.7 29.9 13.6 21.2 21.1 18.4 16.8 16.7 8.2
40.0 35.0 30.0 30.0 30.0 15.0 50.0 50.0 40.0 35.0 35.0 15.0 30.0 30.0 25.0 20.0 20.0 15.0
31.1 30.2 25.4 26.8 25.9 11.5 43.4 45.5 35.9 30.5 25.9 13.2 22.9 22.8 19.3 18.6 18.5 7.8
40.3 39.4 33.0 32.2 31.3 14.1 52.6 54.7 43.5 35.9 37.1 15.8 32.1 32.0 26.9 24.0 23.9 10.4
50.0 50.0 45.0 40.0 40.0 15.0 70.0 70.0 50.0 45.0 45.0 20.0 45.0 45.0 40.0 35.0 35.0 15.0
N/A N/A N/A 34.2 32.7 17.0 N/A N/A N/A 50.0 52.0 25.3 N/A N/A N/A 24.8 24.2 12.7
N/A N/A N/A 45.1 43.3 21.4 N/A N/A N/A 64.8 67.5 31.7 N/A N/A N/A 33.3 32.7 16.0
N/A N/A N/A 50.0 50.0 25.0 N/A N/A N/A 70.0 70.0 35.0 N/A N/A N/A 45.0 45.0 20.0
N/A N/A N/A 35.4 33.9 17.0 N/A N/A N/A 51.2 53.2 25.3 N/A N/A N/A 26.0 25.4 12.7
N/A N/A N/A 48.7 47.0 24.0 N/A N/A N/A 68.4 71.1 34.4 N/A N/A N/A 36.9 36.3 18.6
N/A N/A N/A 60.0 60.0 30.0 N/A N/A N/A 80.0 80.0 40.0 N/A N/A N/A 50.0 50.0 25.0
Steam, Hot Water or None
Electric
Steam, Hot Water or None
Electrode Canister - Steam
Steam or None
Steam or None
208 230 277 208 230 480 208 230 277 208 230 480 208 230 277 208 230 480
1
1
1
3
3
3
1
1
1
3
3
3
1
1
1
3
3
3
17.5 16.6 14.6 N/A N/A N/A 21.0 22.0 20.1 N/A N/A N/A 9.3 9.2 8.5 N/A N/A N/A
20.4 19.6 17.0 N/A N/A N/A 23.9 25.0 22.2 N/A N/A N/A 12.2 12.2 10.9 N/A N/A N/A
25.0 25.0 20.0 N/A N/A N/A 30.0 30.0 25.0 N/A N/A N/A 15.0 15.0 15.0 N/A N/A N/A
17.4 16.5 14.5 N/A N/A N/A 20.9 21.9 14.5 N/A N/A N/A 9.2 9.1 8.4 N/A N/A N/A
22.8 21.9 19.0 N/A N/A N/A 26.3 27.3 19.0 N/A N/A N/A 14.6 14.5 12.9 N/A N/A N/A
30.0 30.0 25.0 N/A N/A N/A 35.0 35.0 25.0 N/A N/A N/A 20.0 20.0 20.0 N/A N/A N/A
18.7 17.8 15.6 16.4 15.5 7.7 31.0 33.1 26.1 20.1 21.3 9.4 10.5 10.4 9.5 8.2 8.1 4.0
25.1 24.2 20.9 20.7 19.8 9.8 37.4 39.5 31.4 24.4 25.6 11.5 16.9 16.8 14.8 12.5 12.4 6.1
35.0 35.0 30.0 25.0 25.0 15.0 45.0 50.0 40.0 30.0 30.0 15.0 25.0 25.0 20.0 20.0 20.0 15.0
26.1 25.2 21.0 21.8 20.9 9.4 38.4 40.5 31.5 25.5 20.9 11.1 17.9 17.8 14.9 13.6 13.5 5.7
35.3 34.4 28.6 27.2 26.3 12.0 47.6 49.7 39.1 30.9 32.1 13.7 27.1 27.0 22.5 19.0 18.9 8.3
50.0 50.0 45.0 40.0 40.0 15.0 60.0 60.0 50.0 40.0 40.0 15.0 45.0 45.0 40.0 35.0 35.0 15.0
N/A N/A N/A 17.4 26.3 13.8 N/A N/A N/A 43.2 45.6 22.1 N/A N/A N/A 18.0 17.8 9.5
N/A N/A N/A 35.9 34.8 17.1 N/A N/A N/A 51.7 54.1 25.4 N/A N/A N/A 26.5 26.3 13.8
N/A N/A N/A 50.0 45.0 20.0 N/A N/A N/A 60.0 60.0 30.0 N/A N/A N/A 40.0 40.0 20.0
N/A N/A N/A 28.6 27.5 13.8 N/A N/A N/A 44.4 46.8 22.1 N/A N/A N/A 19.2 19.0 9.5
N/A N/A N/A 41.9 40.6 20.8 N/A N/A N/A 61.6 64.7 31.2 N/A N/A N/A 30.1 29.9 15.4
N/A N/A N/A 50.0 50.0 25.0 N/A N/A N/A 70.0 70.0 35.0 N/A N/A N/A 45.0 45.0 20.0
APC NetworkAIR™ CM
15
Electrical Data
AIR COOLED - REMOTE CONDENSING
REHEAT
Electric
HUMID
Electrode Canister - Steam
VOLTAGE 208 230 277 208 230 480
PHASE
1
1
1
3
3
3
3 kW (1 ton)
FLA 22.5 22.7 20.6 N/A N/A N/A
WSA 28.1 28.4 25.8 N/A N/A N/A
MOP 30.0 30.0 30.0 N/A N/A N/A
5 kW (1.5 ton)
FLA 22.5 22.7 20.6 N/A N/A N/A
WSA 28.1 28.4 25.8 N/A N/A N/A
MOP 30.0 30.0 30.0 N/A N/A N/A
7 kW (2 ton)
FLA 31.3 32.6 25.6 22.7 23.1 10.4
WSA 39.1 40.8 32.0 28.4 28.9 13.0
MOP 40.0 45.0 35.0 30.0 30.0 15.0
10 kW (3 ton)
FLA 33.4 34.7 26.6 24.8 25.2 10.4
WSA 41.8 43.4 33.3 31.0 31.5 13.0
MOP 45.0 45.0 35.0 35.0 35.0 15.0
14 kW (4 ton)
FLA N/A N/A N/A 40.6 42.1 19.8
WSA N/A N/A N/A 50.5 52.3 24.6
MOP N/A N/A N/A 60.0 60.0 25.0
17 kW (5 ton)
FLA N/A N/A N/A 40.6 42.1 19.8
WSA N/A N/A N/A 50.5 52.3 24.6
MOP N/A N/A N/A 60.0 60.0 25.0
Steam, Hot Water or None
Electric
Steam, Hot Water or None
Electrode Canister - Steam
Steam or None
Steam or None
208 230 277 208 230 480 208 230 277 208 230 480 208 230 277 208 230 480
1
1
1
3
3
3
1
1
1
3
3
3
1
1
1
3
3
3
10.8 9.9 9.0 N/A N/A N/A 14.3 15.3 14.5 N/A N/A N/A 2.6 2.5 2.9 N/A N/A N/A
13.5 12.4 11.3 N/A N/A N/A 17.9 19.1 18.1 N/A N/A N/A 3.3 3.1 3.6 N/A N/A N/A
15.0 15.0 15.0 N/A N/A N/A 20.0 20.0 20.0 N/A N/A N/A 15.0 15.0 15.0 N/A N/A N/A
10.8 9.9 9.0 N/A N/A N/A 14.3 15.3 14.5 N/A N/A N/A 2.6 2.5 2.9 N/A N/A N/A
13.5 12.4 11.3 N/A N/A N/A 17.9 19.1 18.1 N/A N/A N/A 3.3 3.1 3.6 N/A N/A N/A
15.0 15.0 15.0 N/A N/A N/A 20.0 20.0 20.0 N/A N/A N/A 15.0 15.0 15.0 N/A N/A N/A
10.8 9.9 9.0 10.8 9.9 5.0 23.1 25.2 19.5 14.5 15.7 6.7 2.6 2.5 2.9 2.6 2.5 1.3
13.5 12.4 11.3 13.5 12.4 6.3 28.9 31.5 24.4 18.1 19.6 8.4 3.3 3.1 3.6 3.2 3.1 1.6
15.0 15.0 15.0 15.0 15.0 15.0 30.0 35.0 25.0 20.0 20.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
12.9 12.0 10.0 12.9 12.0 5.0 25.2 27.3 20.5 16.6 17.8 6.7 4.7 4.6 3.9 4.7 4.6 1.3
16.1 15.0 12.5 16.1 15.0 6.3 31.5 34.1 25.6 20.8 22.3 8.4 5.9 5.8 4.9 5.9 5.8 1.6
20.0 15.0 15.0 20.0 15.0 15.0 35.0 35.0 30.0 25.0 25.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
N/A N/A N/A 15.4 14.3 7.2 N/A N/A N/A 31.2 33.6 15.5 N/A N/A N/A 6.0 5.8 2.9
N/A N/A N/A 19.0 17.7 8.9 N/A N/A N/A 38.7 41.8 19.3 N/A N/A N/A 7.2 7.1 3.5
N/A N/A N/A 20.0 20.0 15.0 N/A N/A N/A 40.0 45.0 20.0 N/A N/A N/A 15.0 15.0 15.0
N/A N/A N/A 15.4 14.3 7.2 N/A N/A N/A 31.2 33.6 15.5 N/A N/A N/A 6.0 5.8 2.9
N/A N/A N/A 19.0 17.7 8.9 N/A N/A N/A 38.7 41.8 19.3 N/A N/A N/A 7.2 7.1 3.5
N/A N/A N/A 20.0 20.0 15.0 N/A N/A N/A 40.0 45.0 20.0 N/A N/A N/A 15.0 15.0 15.0
WATER COOLED - SELF CONTAINED
REHEAT
Electric
HUMID
Electrode Canister - Steam
VOLTAGE 208 230 277 208 230 480
PHASE
1
1
1
3
3
3
3 kW (1 ton)
FLA 20.5 21.5 13.8 N/A N/A N/A
WSA 23.9 25.0 22.2 N/A N/A N/A
MOP 30.0 30.0 25.0 N/A N/A N/A
5 kW (1.5 ton)
FLA 20.3 21.3 19.5 N/A N/A N/A
WSA 26.3 27.3 24.5 N/A N/A N/A
MOP 35.0 35.0 30.0 N/A N/A N/A
7 kW (2 ton)
FLA 29.8 31.9 25.1 19.5 20.7 9.1
WSA 37.4 39.5 31.4 24.4 25.6 11.5
MOP 45.0 50.0 40.0 30.0 30.0 15.0
10 kW (3 ton)
FLA 36.3 23.1 29.7 25.5 29.9 10.6
WSA 47.6 49.7 39.1 30.9 32.1 13.7
MOP 60.0 60.0 50.0 40.0 40.0 15.0
14 kW (4 ton)
FLA N/A N/A N/A 41.7 44.1 21.3
WSA N/A N/A N/A 51.7 54.1 25.4
MOP N/A N/A N/A 60.0 60.0 30.0
17 kW (5 ton)
FLA N/A N/A N/A 42.7 45.1 21.3
WSA N/A N/A N/A 61.6 64.7 31.2
MOP N/A N/A N/A 70.0 70.0 35.0
16
Steam, Hot Water or None
Electric
Steam, Hot Water or None
Electrode Canister - Steam
Steam or None
Steam or None
208 230 277 208 230 480 208 230 277 208 230 480 208 230 277 208 230 480
1
1
1
3
3
3
1
1
1
3
3
3
1
1
1
3
3
3
17.0 16.1 14.6 N/A N/A N/A 20.5 21.5 13.8 N/A N/A N/A 8.8 8.7 8.0 N/A N/A N/A
20.4 19.6 17.0 N/A N/A N/A 23.9 25.0 22.2 N/A N/A N/A 12.2 12.2 10.9 N/A N/A N/A
25.0 25.0 20.0 N/A N/A N/A 30.0 30.0 25.0 N/A N/A N/A 15.0 15.0 15.0 N/A N/A N/A
16.8 15.9 14.0 N/A N/A N/A 20.3 21.3 19.5 N/A N/A N/A 8.6 8.5 7.9 N/A N/A N/A
22.8 21.9 19.0 N/A N/A N/A 26.3 27.3 24.5 N/A N/A N/A 14.6 14.5 12.9 N/A N/A N/A
30.0 30.0 25.0 N/A N/A N/A 35.0 35.0 30.0 N/A N/A N/A 20.0 20.0 20.0 N/A N/A N/A
21.0 16.6 14.6 15.8 14.9 7.4 29.8 31.9 25.1 19.5 20.7 9.1 9.3 9.2 8.5 7.6 7.5 3.7
25.1 24.2 20.9 20.7 19.8 9.8 37.4 39.5 31.4 24.4 25.6 11.5 16.9 16.8 14.8 12.5 12.4 6.1
35.0 35.0 30.0 25.0 25.0 15.0 45.0 50.0 40.0 30.0 30.0 15.0 25.0 25.0 20.0 20.0 20.0 15.0
24.0 23.1 19.2 20.8 19.9 8.9 36.3 23.1 29.7 25.5 29.9 10.6 15.8 15.7 13.1 12.6 12.5 5.2
35.3 34.4 28.6 27.2 26.3 12.0 47.6 49.7 39.1 30.9 32.1 13.7 27.1 27.0 22.5 19.0 18.9 8.3
50.0 50.0 45.0 40.0 40.0 15.0 60.0 60.0 50.0 40.0 40.0 15.0 45.0 45.0 40.0 35.0 35.0 15.0
N/A N/A N/A 25.9 24.8 13.0 N/A N/A N/A 41.7 44.1 21.3 N/A N/A N/A 16.5 16.3 8.7
N/A N/A N/A 35.9 34.8 17.1 N/A N/A N/A 51.7 54.1 25.4 N/A N/A N/A 26.5 26.3 13.8
N/A N/A N/A 50.0 45.0 20.0 N/A N/A N/A 60.0 60.0 30.0 N/A N/A N/A 40.0 40.0 20.0
N/A N/A N/A 26.9 25.8 13.0 N/A N/A N/A 42.7 45.1 21.3 N/A N/A N/A 17.9 17.3 8.7
N/A N/A N/A 41.9 40.6 20.8 N/A N/A N/A 61.6 64.7 31.2 N/A N/A N/A 30.1 29.9 15.4
N/A N/A N/A 50.0 50.0 25.0 N/A N/A N/A 70.0 70.0 35.0 N/A N/A N/A 45.0 45.0 20.0
APC NetworkAIR™ CM
Electrical Data
GLYCOL COOLED - SELF CONTAINED
REHEAT
Electric
HUMID
Electrode Canister - Steam
VOLTAGE 208 230 277 208 230 480
PHASE
1
1
1
3
3
3
3 kW (1 ton)
FLA 21.2 22.2 20.2 N/A N/A N/A
WSA 23.9 25.0 22.2 N/A N/A N/A
MOP 30.0 30.0 25.0 N/A N/A N/A
5 kW (1.5 ton)
FLA 21.1 22.1 19.5 N/A N/A N/A
WSA 26.3 27.3 24.5 N/A N/A N/A
MOP 35.0 35.0 30.0 N/A N/A N/A
7 kW (2 ton)
FLA 31.5 33.6 26.5 20.4 21.6 9.6
WSA 37.4 39.5 31.4 24.4 25.6 11.5
MOP 45.0 50.0 40.0 30.0 30.0 15.0
10 kW (3 ton)
FLA 40.5 42.6 32.1 25.9 21.3 11.3
WSA 47.6 49.7 39.1 30.9 32.1 13.7
MOP 60.0 60.0 50.0 40.0 40.0 15.0
14 kW (4 ton)
FLA N/A N/A N/A 45.2 47.6 22.1
WSA N/A N/A N/A 51.7 54.1 25.4
MOP N/A N/A N/A 60.0 60.0 30.0
17 kW (5 ton)
FLA N/A N/A N/A 45.0 47.4 22.4
WSA N/A N/A N/A 61.6 64.7 31.2
MOP N/A N/A N/A 70.0 70.0 35.0
CHILLED WATER
REHEAT
Electric
HUMID
Electrode Canister - Steam
VOLTAGE 208 230 277 208 230 480
PHASE
1
1
1
3
3
3
3 kW (1 ton)
FLA 22.5 22.7 20.6 N/A N/A N/A
WSA 28.1 28.4 25.8 N/A N/A N/A
MOP 30.0 30.0 30.0 N/A N/A N/A
5 kW (1.5 ton)
FLA 22.5 22.7 20.6 N/A N/A N/A
WSA 28.1 28.4 25.8 N/A N/A N/A
MOP 30.0 30.0 30.0 N/A N/A N/A
7 kW (2 ton)
FLA 31.3 32.6 25.6 22.7 23.1 10.4
WSA 39.1 40.8 32.0 28.4 28.9 13.0
MOP 40.0 45.0 35.0 30.0 30.0 15.0
10 kW (3 ton)
FLA 33.4 34.7 26.6 24.8 25.2 10.4
WSA 41.8 43.4 33.3 31.0 31.5 13.0
MOP 45.0 45.0 35.0 35.0 35.0 15.0
14 kW (4 ton)
FLA N/A N/A N/A 40.6 42.1 19.8
WSA N/A N/A N/A 50.5 52.3 24.6
MOP N/A N/A N/A 60.0 60.0 25.0
17 kW (5 ton)
FLA N/A N/A N/A 40.6 42.1 19.8
WSA N/A N/A N/A 50.5 52.3 24.6
MOP N/A N/A N/A 60.0 60.0 25.0
Steam, Hot Water or None
Electric
Steam, Hot Water or None
Electrode Canister - Steam
Steam or None
Steam or None
208 230 277 208 230 480 208 230 277 208 230 480 208 230 277 208 230 480
1
1
1
3
3
3
1
1
1
3
3
3
1
1
1
3
3
3
17.7 16.8 14.7 N/A N/A N/A 21.2 22.2 20.2 N/A N/A N/A 9.5 9.4 8.6 N/A N/A N/A
20.4 19.6 17.0 N/A N/A N/A 23.9 25.0 22.2 N/A N/A N/A 12.2 12.2 10.9 N/A N/A N/A
25.0 25.0 20.0 N/A N/A N/A 30.0 30.0 25.0 N/A N/A N/A 15.0 15.0 15.0 N/A N/A N/A
17.6 16.7 14.6 N/A N/A N/A 21.1 22.1 19.5 N/A N/A N/A 9.4 9.3 7.9 N/A N/A N/A
22.8 21.9 19.0 N/A N/A N/A 26.3 27.3 24.5 N/A N/A N/A 14.6 14.5 12.9 N/A N/A N/A
30.0 30.0 25.0 N/A N/A N/A 35.0 35.0 30.0 N/A N/A N/A 20.0 20.0 20.0 N/A N/A N/A
19.2 18.3 16.0 16.7 15.8 7.9 31.5 33.6 26.5 20.4 21.6 9.6 11.0 10.9 9.9 8.5 8.4 3.8
25.1 24.2 20.9 20.7 19.8 9.8 37.4 39.5 31.4 24.4 25.6 11.5 16.9 16.8 14.8 12.5 12.4 6.1
35.0 35.0 30.0 25.0 25.0 15.0 45.0 50.0 40.0 30.0 30.0 15.0 25.0 25.0 20.0 20.0 20.0 15.0
26.9 26.0 21.6 22.4 21.3 9.6 40.5 42.6 32.1 25.9 21.3 11.3 18.7 18.6 15.5 14.0 13.9 5.9
35.3 34.4 28.6 27.2 26.3 12.0 47.6 49.7 39.1 30.9 32.1 13.7 27.1 27.0 22.5 19.0 18.9 8.3
50.0 50.0 45.0 40.0 40.0 15.0 60.0 60.0 50.0 40.0 40.0 15.0 45.0 45.0 40.0 35.0 35.0 15.0
N/A N/A N/A 27.9 26.8 13.8 N/A N/A N/A 45.2 47.6 22.1 N/A N/A N/A 18.5 18.3 9.8
N/A N/A N/A 35.9 34.8 17.1 N/A N/A N/A 51.7 54.1 25.4 N/A N/A N/A 26.5 26.3 13.8
N/A N/A N/A 50.0 45.0 20.0 N/A N/A N/A 60.0 60.0 30.0 N/A N/A N/A 40.0 40.0 20.0
N/A N/A N/A 29.2 28.1 14.1 N/A N/A N/A 45.0 47.4 22.4 N/A N/A N/A 19.8 19.6 9.8
N/A N/A N/A 41.9 40.6 20.8 N/A N/A N/A 61.6 64.7 31.2 N/A N/A N/A 30.1 29.9 15.4
N/A N/A N/A 50.0 50.0 25.0 N/A N/A N/A 70.0 70.0 35.0 N/A N/A N/A 45.0 45.0 20.0
Steam, Hot Water or None
Electric
Steam, Hot Water or None
Electrode Canister - Steam
Steam or None
Steam or None
208 230 277 208 230 480 208 230 277 208 230 480 208 230 277 208 230 480
1
1
1
3
3
3
1
1
1
3
3
3
1
1
1
3
3
3
10.8 9.9 9.0 N/A N/A N/A 14.3 15.3 14.5 N/A N/A N/A 2.6 2.5 2.9 N/A N/A N/A
13.5 12.4 11.3 N/A N/A N/A 17.9 19.1 18.1 N/A N/A N/A 3.3 3.1 3.6 N/A N/A N/A
15.0 15.0 15.0 N/A N/A N/A 20.0 20.0 20.0 N/A N/A N/A 15.0 15.0 15.0 N/A N/A N/A
10.8 9.9 9.0 N/A N/A N/A 14.3 15.3 14.5 N/A N/A N/A 2.6 2.5 2.9 N/A N/A N/A
13.5 12.4 11.3 N/A N/A N/A 17.9 19.1 18.1 N/A N/A N/A 3.3 3.1 3.6 N/A N/A N/A
15.0 15.0 15.0 N/A N/A N/A 20.0 20.0 20.0 N/A N/A N/A 15.0 15.0 15.0 N/A N/A N/A
10.8 9.9 9.0 10.8 9.9 5.0 23.1 25.2 19.5 14.5 15.7 6.7 2.6 2.5 2.9 2.6 2.5 1.3
13.5 12.4 11.3 13.5 12.4 6.3 28.9 31.5 24.4 18.1 19.6 8.4 3.3 3.1 3.6 3.2 3.1 1.6
15.0 15.0 15.0 15.0 15.0 15.0 30.0 35.0 25.0 20.0 20.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
12.9 12.0 10.0 12.9 12.0 5.0 25.2 27.3 20.5 16.6 17.8 6.7 4.7 4.6 3.9 4.7 4.6 1.3
16.1 15.0 12.5 16.1 15.0 6.3 31.5 34.1 25.6 20.8 22.3 8.4 5.9 5.8 4.9 5.9 5.8 1.6
20.0 15.0 15.0 20.0 15.0 15.0 35.0 35.0 30.0 25.0 25.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
N/A N/A N/A 15.4 14.3 7.2 N/A N/A N/A 31.2 33.6 15.5 N/A N/A N/A 6.0 5.8 2.9
N/A N/A N/A 19.0 17.7 8.9 N/A N/A N/A 38.7 41.8 19.3 N/A N/A N/A 7.2 7.1 3.5
N/A N/A N/A 20.0 20.0 15.0 N/A N/A N/A 40.0 45.0 20.0 N/A N/A N/A 15.0 15.0 15.0
N/A N/A N/A 15.4 14.3 7.2 N/A N/A N/A 31.2 33.6 15.5 N/A N/A N/A 6.0 5.8 2.9
N/A N/A N/A 19.0 17.7 8.9 N/A N/A N/A 38.7 41.8 19.3 N/A N/A N/A 7.2 7.1 3.5
N/A N/A N/A 20.0 20.0 15.0 N/A N/A N/A 40.0 45.0 20.0 N/A N/A N/A 15.0 15.0 15.0
APC NetworkAIR™ CM
17
Dimensional Data
Spot-cooled -- 3-5kW (1-1.5 ton)
* All dimensions are in inches (mm).
18
APC NetworkAIR™ CM
Dimensional Data
Spot-cooled -- 7-10kW (2-3 ton)
* All dimensions are in inches (mm).
APC NetworkAIR™ CM
19
Dimensional Data
Spot-cooled self contained -- 3-5kW (1-1.5 ton)
* All dimensions are in inches (mm).
20
APC NetworkAIR™ CM
Dimensional Data
Spot-cooled self contained -- 7-10kW (2-3 ton)
* All dimensions are in inches (mm).
APC NetworkAIR™ CM
21
Dimensional Data
Ducted -- 3-5kW (1-1.5 ton)
* All dimensions are in inches (mm).
22
APC NetworkAIR™ CM
Dimensional Data
Ducted -- 7-10kW (2-3 ton)
* All dimensions are in inches (mm).
APC NetworkAIR™ CM
23
Dimensional Data
Ducted -- 14-17kW (4-5 ton)
* All dimensions are in inches (mm).
24
APC NetworkAIR™ CM
Dimensional Data
Ducted self contained -- 3-5kW (1-1.5 ton)
* All dimensions are in inches (mm).
APC NetworkAIR™ CM
25
Dimensional Data
Ducted self contained -- 7-10kW (2-3 ton)
* All dimensions are in inches (mm).
26
APC NetworkAIR™ CM
Dimensional Data
Ducted self contained -- 14-17kW (4-5 ton)
* All dimensions are in inches (mm).
APC NetworkAIR™ CM
27
Air-Cooled Condensers
Air-cooled condenser—performance/electrical data
OHE SKU
Voltage
Control
Ambient
Temperature
Air Quantity
95F
105F 115F CFM
L/s
Fan/Motor
Connection
Qty.
HP
RP
M
Hot
Gas
Weight
Liquid Lbs
Kg
Electrical Data
FLA MCA MOP
ACCD75000 208-230/1/60
FSC
3kW
N/A
N/A
2,400 1,132
1
1/4
1075
3/8”
3/8”
96
44
2.0
2.5
15.0
ACCD75001
FSC
3kW
N/A
N/A
2,400 1,132
1
1/4
1075
3/8”
3/8”
96
44
1.0
1.3
15.0
ACCD75002 208-230/1/60
FL
3kW
N/A
N/A
2,400 1,132
1
1/4
1075
3/8”
3/8”
96
44
2.0
2.5
15.0
ACCD75003
FL
3kW
N/A
N/A
2,400 1,132
1
1/4
1075
3/8”
3/8”
96
44
1.0
1.3
15.0
ACCD75008 208-230/1/60
FSC
N/A
3kW
N/A
2,400 1,132
1
1/4
1075
5/8”
5/8”
96
44
2.0
2.5
15.0
ACCD75009
FSC
N/A
3kW
N/A
2,400 1,132
1
1/4
1075
5/8”
5/8”
96
44
1.0
1.3
15.0
ACCD75004 208-230/1/60
FSC
5kW
N/A
N/A
2,400 1,132
1
1/4
1075
5/8”
5/8”
96
44
2.0
2.5
15.0
ACCD75005
480/1/60
480/1/60
480/1/60
FSC
5kW
N/A
N/A
2,400 1,132
1
1/4
1075
5/8”
5/8”
96
44
1.0
1.3
15.0
ACCD75006 208-230/1/60
FL
5kW
N/A
N/A
2,400 1,132
1
1/4
1075
5/8”
5/8”
96
44
2.0
2.5
15.0
ACCD75007
FL
5kW
N/A
N/A
2,400 1,132
1
1/4
1075
5/8”
5/8”
96
44
1.0
1.3
15.0
3kW
5kW
2,100
991
1
1/4
1075
7/8”
5/8”
114
52
2.0
2.5
15.0
480/1/60
480/1/60
ACCD75010 208-230/1/60
FSC
7kW
10kW 5kW
ACCD75011
FSC
7kW
5kW
10kW
3kW
5kW
2,100
991
1
1/4
1075
7/8”
5/8”
114
52
1.0
1.3
15.0
ACCD75012 208-230/1/60
FL
7kW
10kW N/A
N/A
2,100
991
1
1/4
1075
7/8”
5/8”
114
52
2.0
2.5
15.0
ACCD75013
FL
7kW
N/A
10kW
N/A
2,100
991
1
1/4
1075
7/8”
5/8”
114
52
1.0
1.3
15.0
480/1/60
480/1/60
ACCD75014 208-230/1/60
FSC
14kW 7kW 7kW
17kW 10kW
5,050 2,383
1
1/3
1075 1-1/8”
7/8”
180
82
3.4
4.3
15.0
ACCD75015
FSC
14kW 7kW
17kW 10kW 7kW
5,050 2,383
1
1/3
1075 1-1/8”
7/8”
180
82
1.7
2.1
15.0
480/1/60
ACCD75016 208-230/1/60
FL
14kW
N/A
17kW
N/A
5,050 2,383
1
1/3
1075 1-1/8”
7/8”
180
82
3.4
4.3
15.0
ACCD75017
FL
14kW N/A
17kW
N/A
5,050 2,383
1
1/3
1075 1-1/8”
7/8”
180
82
1.7
2.1
15.0
480/1/60
ACCD75018 208-230/1/60
FSC
14kW
N/A 17kW 10kW 6,450 3,044
1
1/2
1075 1-1/8”
7/8”
260
118
3.9
4.9
15.0
ACCD75019
FSC
N/A
14kW
10kW 6,450 3,044
17kW
1
1/2
1075 1-1/8”
7/8”
260
118
2.0
2.4
15.0
ACCD75022 208-230/3/60
FSC
N/A
N/A 14kW 10,100 4,767
17kW
2
1/3
1140 1-1/8”
7/8”
450
204
6.8
7.7
15.0
ACCD75023
FSC
N/A
14kW
N/A 17kW 10,100 4,767
2
1/3
1140 1-1/8”
7/8”
450
204
3.4
3.8
15.0
480/1/60
480/3/60
FLA = Full Load Amps
MCA = Minimum Circuit Amperes
MOP = Maximum Overcurrent Protection
*Single Fan Condenser with Fan Speed Control must be single phase.
28
APC NetworkAIR™ CM
Air-Cooled Condensers
1-fan air-cooled condenser
APC PART
CIRCUIT
CONTROL
VOLTAGE
ACCD75000
single
Fan Speed
208-230/1/60
ACCD75001
single
Fan Speed
480/1/60
ACCD75002
single
Flooded
208-230/1/60
ACCD75003
single
Flooded
480/1/60
ACCD75008
single
Fan Speed
208-230/1/60
ACCD75009
single
Fan Speed
480/1/60
ACCD75010
single
Fan Speed
208-230/1/60
ACCD75011
single
Fan Speed
480/1/60
ACCD75004
single
Fan Speed
208-230/1/60
ACCD75005
single
Fan Speed
480/1/60
ACCD75006
single
Flooded
208-230/1/60
ACCD75007
single
Flooded
480/1/60
ACCD75012
single
Flooded
208-230/1/60
ACCD75013
single
Flooded
480/1/60
1-fan air-cooled condenser
APC PART
CIRCUIT
CONTROL
VOLTAGE
ACCD75014
single
Fan Speed
208-230/1/60
ACCD75015
single
Fan Speed
480/1/60
ACCD75016
single
Fan Speed
208-230/1/60
ACCD75017
single
Fan Speed
480/1/60
APC NetworkAIR™ CM
29
Air-Cooled Condensers
1-fan air-cooled condenser
APC PART
CIRCUIT
CONTROL
VOLTAGE
ACCD75018
single
Fan Speed
208-230/1/60
ACCD75019
single
Fan Speed
480/1/60
2-fan air-cooled condenser
30
APC PART
CIRCUIT
CONTROL
VOLTAGE
ACCD75022
single
Fan Speed
208-230/3/60
ACCD75023
single
Fan Speed
480/3/60
APC NetworkAIR™ CM
Fluid Coolers
Glycol-cooled fluid cooler—performance/electrical data
OHE SKU
Voltage
Ambient
Temperature
40%
Ethylene
Glycol @
130F
Air Quantity
Fan/Motor
95F
105F
PD(ft)
@GPM
CFM
L/s
Qty
HP
RPM
ACFC75106 208-230/1/60
3kW
N/A
5.9@3
2,400
1,132
1
1/4
1075
ACFC75107
3kW
N/A
5.9@3
2,400
1,132
1
1/4
1075
ACFC75108 208-230/1/60
5kW
N/A
5.9@4
2,400
1,132
1
1/4
ACFC75109
5kW
N/A
5.9@4
2,400
1,132
1
ACFC75110 208-230/1/60
7kW
3kW
5kW
3.5@6
2,100
991
ACFC75111
7kW
3kW
5kW
3.5@6
2,100
ACFC75112 208-230/3/60 10kW
480/1/60
480/1/60
480/1/60
Conne
ct-ions
Weight
Glycol
Volume
Electrical Data
Lbs
Kg
Gal
L
FLA MCA MOP
7/8”
96
44
1.1
4.2
2.0
2.5
15.0
7/8”
96
44
1.1
4.2
1.0
1.3
15.0
1075
7/8”
96
44
1.1
4.2
2.0
2.5
15.0
1/4
1075
7/8”
96
44
1.1
4.2
1.0
1.3
15.0
1
1/4
1075
1-1/8”
114
52
1.6
6.0
2.0
2.5
15.0
991
1
1/4
1075
1-1/8”
114
52
1.6
6.0
1.0
1.3
15.0
7kW
4.5@15
5,050
2,383
1
1/3
1140
1-3/8”
180
82
2.6
9.8
2.6
3.3
15.0
10kW 7kW
4.5@15
5,050
2,383
1
1/3
1140
1-3/8”
180
82
2.6
9.8
1.3
1.6
15.0
ACFC75114 208-230/3/60 14kW 10kW
5.6@20
6,450
3,044
1
1/3
1140
1-5/8”
260
118
3.8
14.4
2.6
3.3
15.0
14kW 10kW
5.6@20
6,450
3,044
1
1/3
1140
1-5/8”
260
118
3.8
14.4
1.3
1.6
15.0
ACFC75116 208-230/3/60 17kW 14kW
15.5@15
10,100 4,766
2
1/3
1140
1-3/8”
450
204
4.0
15.1
5.2
5.9
15.0
17kW 14kW
15.5@15
10,100 4,766
2
1/3
1140
1-3/8”
450
204
4.0
15.1
2.6
2.9
15.0
ACFC75113
ACFC75115
ACFC75117
480/3/60
480/3/60
480/3/60
ACFC75118 208-230/3/60
N/A
17kW
15.5@15
12,400 5,852
2
1/3
1140
1-3/8”
470
213
4.0
15.1
5.2
5.9
15.0
ACFC75119
N/A
17kW
15.5@15
12,400 5,852
2
1/3
1140
1-3/8”
470
213
4.0
15.1
2.6
2.9
15.0
480/3/60
FLA = Full Load Amps
MCA = Minimum Circuit Amperes
MOP = Maximum Overcurrent Protection
*Fluid coolers can be selected for multiple indoor air conditioning units from the factory. Consult factory
for help configuring many-to-one or one-to-many glycol loops.
APC NetworkAIR™ CM
31
Fluid Coolers
1-fan fluid cooler
APC PART
VOLTAGE
ACFC75106
208-230/1/60
ACFC75107
480/1/60
ACFC75110
208-230/1/60
ACFC75111
480/1/60
ACFC75108
208-230/1/60
ACFC75109
480/1/60
1-fan fluid cooler
32
APC PART
VOLTAGE
ACFC75112
208-230/3/60
ACFC75113
480/3/60
APC NetworkAIR™ CM
Fluid Coolers
1-fan fluid cooler
APC PART
VOLTAGE
ACFC75114
208-230/3/60
ACFC75115
480/3/60
2-fan fluid cooler
APC PART
VOLTAGE
ACFC75116
208-230/3/60
ACFC75117
480/3/60
ACFC75118
208-230/3/60
ACFC75119
480/3/60
APC NetworkAIR™ CM
33
Remote Condensing Units
Remote condensing unit—performance/electrical data
Model
OHE SKU
Voltage
Control
3kW (1 ton)
ACCG75200
208-230/1/60
ACCG75201
5kW (1.5 ton)
7kW (2 ton)
10kW (3 ton)
14kW (4 ton)
17kW (5 ton)
Fan/Motor
HP
-20 F
1
1/15
3/8”
208-230/3/60
-20 F
1
1/15
ACCG75202
480/3/60
-20 F
1
ACCG75226
208-230/1/60
-30 F
ACCG75227
208-230/3/60
ACCG75228
Electrical Data
Kg
FLA
5/8”
172
78
6.8
15.0
15.0
3/8”
5/8”
172
78
4.7
15.0
15.0
1/15
3/8”
5/8”
172
78
2.6
15.0
15.0
1
1/15
3/8”
5/8”
172
78
6.8
20.0
20.0
-30 F
1
1/15
3/8”
5/8”
172
78
4.7
20.0
20.0
480/3/60
-30 F
1
1/15
3/8”
5/8”
172
78
2.6
20.0
20.0
ACCG75203
208-230/1/60
-20 F
2
1/15
3/8”
5/8”
223
101
9.1
15.0
15.0
ACCG75204
208-230/3/60
-20 F
2
1/15
3/8”
5/8”
223
101
5.9
15.0
15.0
ACCG75205
480/3/60
-20 F
2
1/15
3/8”
5/8”
223
101
3.8
15.0
15.0
ACCG75224
208-230/1/60
-30 F
2
1/15
3/8”
5/8”
223
101
9.1
24.0
25.0
ACCG75230
208-230/3/60
-30 F
2
1/15
3/8”
5/8”
223
101
5.9
24.0
20.0
ACCG75231
480/3/60
-30 F
2
1/15
3/8”
5/8”
223
101
3.8
20.0
20.0
ACCG75206
208-230/1/60
-20 F
2
1/15
3/8”
7/8”
225
102
13.2
20.0
25.0
ACCG75207
208-230/3/60
-20 F
2
1/15
3/8”
7/8”
225
102
7.7
15.0
15.0
ACCG75208
480/3/60
-20 F
2
1/15
3/8”
7/8”
225
102
4.6
15.0
15.0
ACCG75232
208-230/1/60
-30 F
2
1/15
3/8”
7/8”
225
102
13.2
29.0
30.0
ACCG75233
208-230/3/60
-30 F
2
1/15
3/8”
7/8”
225
102
7.7
24.0
25.0
ACCG75234
480/3/60
-30 F
2
1/15
3/8”
7/8”
225
102
4.6
20.0
20.0
ACCG75209
208-230/1/60
-20 F
1
1/3
1/2”
7/8”
311
141
20.2
24.3
40.0
ACCG75210
208-230/3/60
-20 F
1
1/3
1/2”
7/8”
311
141
13.4
20.0
25.0
ACCG75211
480/3/60
-20 F
1
1/3
1/2”
7/8”
311
141
6.9
15.0
15.0
ACCG75235
208-230/1/60
-30 F
1
1/3
1/2”
7/8”
311
141
20.2
38.0
50.0
ACCG75236
208-230/3/60
-30 F
1
1/3
1/2”
7/8”
311
141
13.4
38.0
40.0
ACCG75237
480/3/60
-30 F
1
1/3
1/2”
7/8”
311
141
6.9
24.0
25.0
ACCG75212
208-230/1/60
-20 F
1
1/3
1/2”
1-1/8”
319
145
29.5
36.0
50.0
ACCG75213
208-230/3/60
-20 F
1
1/3
1/2”
1-1/8”
319
145
19.8
23.9
40.0
ACCG75214
480/3/60
-20 F
1
1/3
1/2”
1-1/8”
319
145
10.0
15.0
15.0
ACCG75238
208-230/1/60
-30 F
1
1/3
1/2”
1-1/8”
319
145
29.5
48.0
60.0
ACCG75239
208-230/3/60
-30 F
1
1/3
1/2”
1-1/8”
319
145
19.8
38.0
50.0
ACCG75240
480/3/60
-30 F
1
1/3
1/2”
1-1/8”
319
145
10.0
29.0
30.0
ACCG75215
208-230/1/60
-20 F
1
1/3
1/2”
1-1/8”
333
151
34.3
42.0
50.0
ACCG75216
208-230/3/60
-20 F
1
1/3
1/2”
1-1/8”
333
151
22.7
28.0
45.0
ACCG75217
480/3/60
-20 F
1
1/3
1/2”
1-1/8”
333
151
10.6
15.0
20.0
ACCG75241
208-230/1/60
-30 F
1
1/3
1/2”
1-1/8”
333
151
34.3
59.0
60.0
ACCG75242
208-230/3/60
-30 F
1
1/3
1/2”
1-1/8”
333
151
22.7
40.0
50.0
ACCG75243
480/3/60
-30 F
1
1/3
1/2”
1-1/8”
333
151
10.6
29.0
30.0
APC NetworkAIR™ CM
Liquid Suction
Weight
Lbs
FLA = Full Load Amps
MCA = Minimum Circuit Amperes
MOP = Maximum Overcurrent Protection
34
Connection
Qty
MCA MOP
Remote Condensing Units
1-fan remote outdoor condensing unit
APC PART
VOLTAGE
CONTROL
ACCG75200
208-230/1/60
-20 F Flooded
ACCG75201
208-230/3/60
-20 F Flooded
ACCG75202
480/3/60
-20 F Flooded
ACCG75226
208-230/1/60
-30 F Flooded
ACCG75227
208-230/3/60
-30 F Flooded
ACCG75228
480/3/60
-30 F Flooded
2-fan remote outdoor condensing unit
APC PART
VOLTAGE
CONTROL
ACCG75203
208-230/1/60
-20 F Flooded
ACCG75204
208-230/3/60
-20 F Flooded
ACCG75205
480/3/60
-20 F Flooded
ACCG75224
208-230/1/60
-30 F Flooded
ACCG75230
208-230/3/60
-30 F Flooded
ACCG75231
480/3/60
-30 F Flooded
ACCG75206
208-230/1/60
-20 F Flooded
ACCG75207
208-230/3/60
-20 F Flooded
ACCG75208
480/3/60
-20 F Flooded
ACCG75232
208-230/1/60
-30 F Flooded
ACCG75233
208-230/3/60
-30 F Flooded
ACCG75234
480/3/60
-30 F Flooded
APC NetworkAIR™ CM
35
Remote Condensing Units
1-fan remote outdoor condensing unit
36
APC PART
VOLTAGE
CONTROL
ACCG75209
208-230/1/60
-20 F Flooded
ACCG75210
208-230/3/60
-20 F Flooded
ACCG75211
480/3/60
-20 F Flooded
ACCG75235
208-230/1/60
-30 F Flooded
ACCG75236
208-230/3/60
-30 F Flooded
ACCG75237
480/3/60
-30 F Flooded
ACCG75212
208-230/1/60
-20 F Flooded
ACCG75213
208-230/3/60
-20 F Flooded
ACCG75214
480/3/60
-20 F Flooded
ACCG75238
208-230/1/60
-30 F Flooded
ACCG75239
208-230/3/60
-30 F Flooded
ACCG75240
480/3/60
-30 F Flooded
ACCG75215
208-230/1/60
-20 F Flooded
ACCG75216
208-230/3/60
-20 F Flooded
ACCG75217
480/3/60
-20 F Flooded
ACCG75241
208-230/1/60
-30 F Flooded
ACCG75242
208-230/3/60
-30 F Flooded
ACCG75243
480/3/60
-30 F Flooded
APC NetworkAIR™ CM
Pump Specifications
Pump performance
130
40
120
25
20
5
BHP ABSORBED
15
TOTAL DYNAMIC HEAD IN FEET
30
10
3600 R.P.M.
110
100
100
90
90
80
80
70
70 1 HP
60
60
0.75 HP
50
40
50
40
0.5 HP
30
30
20
20
10
10
PERCENT EFFICIENCY
TOTAL DYNAMIC HEAD IN METERS
35
0
10
0
20
1.0
30 40 50 60 70 80 90 100 110 120 130
CAPACITY IN U.S. GALLONS PER MINUTE
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10
CAPACITY IN LITERS PER SECOND
Pump connection sizes
HP (kW)
1/2 (.37)
3/4 (.56)
1 (.75)
LINE
Suction
Discharge
Suction
Discharge
Suction
Discharge
Size (inches)
1-1/4
1
1-1/4
1
1-1/4
1
Pump electrical data
HP (kW)
1/2 (.37)
3/4 (.56)
1 (.75)
VOLTAGE
FLA
MCA
FLA
MCA
FLA
MCA
208-230/3/60
2.4
3.0
3.5
4.4
4.6
5.8
480/3/60
1.1
1.4
1.6
2.0
2.1
2.6
*Values are calculated based on 3-phase power.
FLA = Full Load Amperes
MCA = Minimum Circuit Amperes
APC NetworkAIR™ CM
37
Pump Specifications
3-17kW (1-5 ton) Single Pump Package
* All dimensions are in inches (mm).
3-17kW (1-5 ton) Dual Pump Package
* All dimensions are in inches (mm).
38
APC NetworkAIR™ CM
Guide Specifications
PART 1 — PART 1 GENERAL
1.01
SUMMARY
A. The environmental control system shall be designed specifically for precision temperature and
humidity control applications. It will automatically monitor and control heating, cooling,
humidifying, dehumidifying, and filtering functions for the conditioned space. The evaporator
airflow pattern shall be spot-cooled or ducted.
1.02
DESIGN REQUIREMENTS
A. The system shall be as described in the following specification as manufactured by APC.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10 .
11 .
12 .
1.03
Model: ____________________________.
Total cooling capacity: _______________ MBH (kW).
Sensible cooling capacity: _____________ MBH (kW).
Return air temperature: _______________ º F (º C) DB.
Return air temperature: _______________ º F (º C) WB.
Entering Chilled Water: _______________ º F (º C)
Leaving Chilled Water: ________________º F (º C)
Humidity: __________________________% RH.
Air quantity: _______________________ CFM (L/s).
External Static Pressure _______________inches (Pa).
Humidifier capacity: _________________ lbs/hr (kg/hr).
Electrical supply: ________ V, _________ ph, 60 Hz.
SUBMITTALS
A. Submittals shall be provided with the proposal and shall include: capacity data, electrical data,
physical data, electrical connection drawing, and piping connection drawing.
1.04
QUALITY ASSURANCE
A. The system shall be completely factory-tested prior to shipment. Testing shall include, but not
be limited to: complete pressure and leak testing to ensure system integrity, “Hi-Pot” test, and
controls calibration and settings. Each system shall ship with a completed test report to verify
completion of factory testing procedure. The system shall be NTRL listed, MCA, and
electrical system shall be UL Listed to UL 1995 and CSA 22.2 No. 236.
1.05
WARRANTY
A. System parts shall be warranted for a period of 12months from date of shipment from factory.
APC NetworkAIR™ CM
39
Guide Specifications
PART 2 — PART 2 PRODUCT
2.01
STANDARD COMPONENTS
A. THERMOSTAT CONTROLLER
1 . The unit control shall provide two separate heat and cool temperature setpoints with a
minimum 2 degree spacing between them. The controller shall activate heating or cooling
functions automatically in regards to setpoint versus measure conditions. The control
setpoint rate shall be 60-85 degrees F. Units requiring humidity control shall have separate
humidity and dehumidity setpoints with a minimum 4% RH spacing between them.
B. CABINET CONSTRUCTION
1 . The cabinet and frame shall be constructed from welded structural steel. hanger mounting
brackets shall be part of the chassis and shock mounts shall be provided for vibration
isolation. The unit shall offer service access to all components via removable access
panels lined with 1/2” thick insulation for noise reduction.
C. FAN/MOTOR SECTION
1 . The air distribution system for the 3-10kW (1-3 ton) units shall be comprised of a directdrive fan motor with a double-inlet blower and permanently sealed ball-bearing type
blower bearings. The air distribution system for the 14-17kW (4-5 ton) units shall be
comprised of a belt drive fan motor with a double-inlet blower and permanently sealed
ball-bearing type blower bearings.
D. ELECTRICAL PANEL
1 . The electrical system shall conform to National Electrical Code (NEC) requirements. The
control voltage shall be 24 VAC, wired in accordance with NEC Class 1 requirements. The
wire for the control circuit shall not be smaller than 18-gauge AWG. Each wire shall end
with a service loop and be securely fastened by an approved method. Control wires more
than 6 in. (150 mm) shall be color-coded or numbered every 3 in. (80 mm) for ease of
service tracing. All electrically-actuated components shall be easily accessible from the
front of the unit. EAch high voltage unit shall be individually protected on all three phases.
Main power shall be connected to a circuit breaker mounted on the electrical panel. The
compressor and motor shall have overload and short circuit protection. The electrical box
shall include all components and controls required for system operation. AN emergency
cool override manual switch shall be provided with provision for control using a field
supplied thermostat. Incoming power is _________ V, _________ phase, 60 Hz.
E. REFRIGERATION SYSTEM AND COMPRESSOR
1 . Each refrigeration system shall consist of a single hermetic compressor, externally
equalized expansion valve, filter-dryer, high pressure switch, refrigerant sight glass, and
moisture indicator.
40
APC NetworkAIR™ CM
Guide Specifications
F. EVAPORATOR COIL & DRAIN PAN
1 . The evaporator coil shall use the latest heat-transfer technology, raised lanced-aluminum
fins and rifle-bored copper tubes. Coil end-supports shall be galvanized steel. An insulated
stainless steel drain pan for condensate shall be included.
G. CHILLED WATER COIL
1 . The cooling coil shall be constructed of copper tubes and aluminum fins and shall be
mounted over a stainless steel condensate drain pan. The coil circuiting shall ensure water
distribution over the entire coil face area. Capacity, chilled water flow rate, and system
pressure drop shall be based on an entering water temperature of 45º F (7.2º C) and
leaving water temperature of 55º F (12.8º C).
2.02
OPTIONAL COMPONENTS
A. CONDENSER
1 . The 3-10kW (1-3 ton) water and glycol cooled systems shall employ a coaxial style
condenser that uses efficient tube within a tube counterflow heat transfer to remove the
heat of compression. The 14-17kW (4-5 ton) models shall employ a brazed plate
condenser that uses the latest heat transfer technology. Type 316L stainless plates shall be
brazed together in a vacuum furnace and shall comply with ASME pressure vessel code.
B. WATER-REGULATING VALVES
1 . Water and glycol systems shall utilize two-way or three-way valves to regulate the amount
of water or glycol supplied to the condenser in response to refrigerant discharge pressure.
The standard valve pressure rating shall be 150 psi (1030 kPa).
2 . Valves with a pressure rating of 350 psi (2413 kPa) ship loose for field installation. Space
restrictions within the cabinet prevent the valves from being factory installed when reheat
and humidity are selected.
C. CHILLED WATER CONTROL VALVE
1 . Cooling capacity shall be controlled with a slow-close, 2-way, motorized valve rated for
125 psi (862 kPa).
D. AIR FILTER
1 . A 20” x 20” x 1” (508 mm x 508 mm x 25 mm), 30% efficient ASHRAE 52.1-92 return
air filter shall be integrally mounted on all 3-10kW (1-3 ton) systems. Two 16” x 25” x 1”
(406mm x 635mm x 25mm), 30% efficient ASHRAE 52.1-92 return air filters shall be
integrally mounted on all 14-17kW (4-5 ton) systems.
APC NetworkAIR™ CM
41
Guide Specifications
E. MICROPROCESSOR CONTROLLER W/REMOTE DISPLAY
1 . The microprocessor controller shall provide total environmental control. The system,
based on the main controller, shall offer up to eight analog inputs, two analog outputs,
twelve digital inputs and thirteen digital outputs. The operator interface shall provide a 4line, 80-character backlit LCD display. User-friendly menu structure along with clearly
defined prompts shall allow the operator to easily move about the program and monitor
the following functions and alarm conditions.
a. Status: Complete status monitoring shall be provided within the status menu of the
microprocessor controller, and shall include the following information: current
temperature, current humidity, temperature setpoint, humidity setpoint, cooling status,
heating status, humidification status and dehumidification status.
b. Alarms: Quick access to any alarm condition shall be facilitated through the menu
structure. Presence of a new alarm shall sound an audible alarm. A red alarm LED on
the display panel shall remain illuminated until such time that all alarms have been
cleared. Alarm annunciation shall include: loss of airflow, clogged filter, high head
pressure, low suction pressure, high temperature, low temperature, high humidity, and
low humidity. The temperature and humidity alarm setpoints are user adjustable.
c. Setpoint: The microprocessor controller shall provide independent setpoints for
heating, cooling, humidification, and dehumidification. Automatic setpoint cross-over
protection shall prevent the setting of the heat setpoint above the cool setpoint and the
humidify setpoint above the dehumidify setpoint. Setpoint adjustment shall be capable
of being protected via security code.
d. Configuration: Flexibility shall be offered through the use of the configuration menu.
Site configuration shall be stored in the EEPROM and be protected from unauthorized
tampering by the user selectable 4-digit security password in the security menu.
Configuration options shall include: Fahrenheit or Celsius display, compressor
minimum off-time, power-loss restart time-delay, primary-secondary transfer
functions, alarm input polarity, alarm enable, temperature deadbands, humidity
deadbands, and small room delay.
e. Run time: The major components within the unit shall have independent run-timers
that monitor and store accumulated run-hours on the components. Run timers shall be
provided with operator-adjustable run-time alarms for component maintenance.
f. Security: The microprocessor shall have multiple security levels to prevent
unauthorized adjustment of the important system parameters. A user-selectable 4-digit
password shall allow setpoint and configuration changes.
F. MICROPROCESSOR CONTROLLER W/REDUNDANT GROUP CONTROL
1 . Up to six units shall have the ability to communicate with each other to automatically
switch upon alarm condition, or time rotation.
42
APC NetworkAIR™ CM
Guide Specifications
G. MICROPROCESSOR CONTROLLER W/REMOTE SENSOR(S)
1 . Environmental sensor(s) shall be strategically placed, up to 50ft from the unit to better
meet the site’s cooling needs. The sensor shall be positioned to permit air movement
across the sensor.
H. PROGRAMMABLE THERMOSTAT/HUMIDITY CONTROLS
1 . The system shall be supplied with a wall-mount programmable thermostat for temperature
control. The thermostat shall have full seven-day programming flexibility with battery
backup and an LCD display. The display shall continuously indicate time-of-day, day-ofweek, current program period and current room temperature. When equipped with a
humidifier and/or reheat, a hair-element humidistat and/or dehumidistat shall be supplied
to control humidification and/or dehumidification.
I.
REMOTE RELAY SHUTDOWN
1 . Remote shutdown of the system can be done by a factory installed relay with a 24V, 120V,
or 240V coil. The relay must be powered by others to disable the cooling system.
J.
REHEAT/HUMIDITY LOCKOUT
1 . When facilities have limited backup power capacity, this lockout shall prevent the
operation of electrical loads that are not essential for continued site operation.
K. HUMIDIFIER
1 . Humidifier shall be self-contained steam-generating type, factory piped and wired, with
disposable cylinder and automatic solid-state control circuit. Capacity: ______ lb/h (g/s).
L. OPTIONAL BLOWER/MOTOR HP
1 . An optional 5HP motor shall be used for increased CFM or to accommodate special air
filters, high external static pressure, etc. while maintaining the standard CFM rating.
M. ELECTRIC REHEAT
1 . Reheat elements shall be low watt density, loaded equally on all phases and shall be
electrically and thermally protected by both automatic and manual reset thermal cutouts.
Reheat capacity shall be ___________ MBH, ___________ kW, controlled in ________
(#) steps.
N. HOT GAS REHEAT
1 . The water- or glycol-cooled unit shall be supplied with a factory-installed copper tube and
aluminum fin hot gas reheat coil. The coil shall be controlled by the main controller
through a factory piped and wired three-way heat reclaim regulator and check valve.
APC NetworkAIR™ CM
43
Guide Specifications
O. HOT WATER REHEAT (MODULATING)
1 . The unit shall be supplied with factory-installed copper tube, aluminum fin, and hot water
reheat coil in place of electrical heater elements. Capacity shall be ________ MBH (kW),
with ________ GPM (L/s) of ________ º F (º C) entering hot water temperature. Hot
water shall be controlled with a modulating control valve.
P. HOT WATER REHEAT (2-WAY ON/OFF)
1 . The unit shall be supplied with a factory-installed copper tube, aluminum fin, reheat
steam-coil in place of electrical heat elements. Capacity shall be _______MBH (kW) with
5 psi (35 kPa) of saturated steam. Steam shall be controlled with an on/off solenoid valve.
Q. FUSED DISCONNECT
1 . A NEMA 1 fused disconnect, complete with fuses, shall ship loose for field installation.
R. HOT GAS BYPASS
1 . Activation of the hot gas bypass circuit shall maintain the evaporator coil temperature
during low load conditions.
S. SHIP LOOSE SPOT WATER DETECTOR
1 . A water detector shall ship loose for field installation into ductwork. Upon sensing liquid,
unit shall send a signal to the master control giving the operator possible alarm indication
options for shutdown. The water detector shall be provided with 15 ft (5 m) of wire.
T. SHIP LOOSE FIRESTAT
1 . A firestat shall ship loose for field installation into ductwork with a sensing element within
the ductwork. Upon sensing of a high temperature, the unit shall send a signal to the main
controller shutting down the unit and activating a visual and audible alarm.
U. SHIP LOOSE SMOKE DETECTOR
1 . A smoke detector shall ship loose for field installation into ductwork. Upon sensing smoke
the main controller shall shut down the unit and activate a visual and audible alarm.
V. SHIP LOOSE CONDENSATE PUMP
1 . The Condensate Pump shall ship loose for field attachment to the side of the unit. The
condensate pump shall be complete with a 1.7qt. (1.6L) reservoir, float switch, and pump/
motor assembly and shall pump 36 gal/h (0.06 L/s) at 15 ft. (4.6m) head.
44
APC NetworkAIR™ CM
Guide Specifications
W. ENVIRONMENTAL MONITORING AND MANAGMENT
1 . Environmental Monitoring Unit: A stand-alone unit shall perform continuous temperature
and humidity sensing through two available proves and contact monitoring. Unit shall be
controlled by available web, control console, or SNMP interface with network connection.
In the event of an environmental anomaly, notification shall be sent to the customer via email or SNMP. The unit shall be 18.25”x9”x2.75”(464mm x 229mm x 70mm).
2 . Environmental Management System: A browser-accessible, 1U, rackmountable appliance
shall allow monitoring of environmental conditions. Monitoring of one temperature, one
humidity, and one vibration sensor shall ship standard. When conditions change,
notifications shall be sent via email to the appropriate personnel. The EMS shall provide
eight input contacts, 2 output relays, and controllable power outlets for defining actions
remotely should conditions warrant it.
X. MODBUS/JBUS GATEWAY
1 . The Gateway shall translate transmission protocol from the system’s network into
ModBus/JBus communication protocol. One gateway shall support up to 16 units.
Y. OHE DISCONNECT
1 . A non-fused disconnect switch shall be wired to an outdoor heat exchanger to disconnect
high voltage power if necessary.
APC NetworkAIR™ CM
45
Guide Specifications
PART 3 — PART 3 INDIVIDUAL SYSTEMS
3.01
AIR-COOLED
A. The indoor unit shall consist of an evaporator section including evaporator coil, blower
package, controls, electrical section, and compressor.
B. CONDENSER
1 . Outdoor Propeller Fan Condenser: The outdoor condenser casing shall be made of
aluminum, and all structural supports, coil frame, motor drive supports, and mounting legs
shall be made of galvanized steel. The condenser shall have copper tubes expanded into
aluminum fins. Headers and connections shall be copper. The coil shall be pressure tested
and sealed for shipment. The condenser motors shall have permanently lubricated, sealed,
ball bearings, and internal overload protection and operate on ________ V, ________ ph,
60 Hz power. Motors shall be 1140 RPM and mounted inside the condenser casing for
weather protection, and shall be wired to a terminal strip in a weatherproof panel on the
unit. The direct drive, aluminum fan blade and painted steel hub assembly, shall be
protected by a heavy-gauge, vinyl-coated, steel-wire fan guard. On multiple units, each
fan section shall be separated by full-width baffles to prevent bypass air. The condenser
shall be sized for ________ º F (ºC) ambient, and condensing temperature controls shall be
fan speed for -20º F (-29º C) winter ambient.
2 . Flooded Controls: Flooded controls shall maintain head pressure to -30º F (-34.4ºC) by
regulating the effective condensing area within the condenser coil. Controls shall ship
loose. Receiver shall be insulated in the field and equipped with a field supplied heater.
C. CONDENSING UNIT
1 . Outdoor Propeller Fan Condensing Unit: The remote outdoor propeller type air-cooled
condensing unit shall consist of a copper tube/aluminum fin condenser coil and a directdrive propeller fan(s). The fan blades are aluminum and riveted to painted steel spider and
hub. Head pressure control down to -20º F (-29º C) shall be achieved by installation of
flooded controls. A head pressure control valve shall bypass the condenser coil to
maintain a desirable condensing temperature.
3.02
WATER-COOLED
A. The water-cooled system shall consist of an evaporator section including evaporator coil,
blower package, controls, electrical section, compressor, and water-cooled condenser. The
condenser shall be stainless steel brazed plate design and shall be controlled by 2-way (3-way
optional) head pressure-regulated valve. Maximum water pressure shall be 400 psi (2758 kPa).
46
APC NetworkAIR™ CM
Guide Specifications
3.03
GLYCOL-COOLED
A. The glycol-cooled system shall consist of an evaporator section including evaporator coil,
blower package, controls, electrical section, compressor, and glycol-cooled condenser. The
condenser shall be stainless steel brazed plate design and shall be controlled by 2-way (3-way
optional) head pressure-regulated valve. Maximum water pressure shall be 400 psi (2758 kPa).
B. FLUID COOLER
1 . Outdoor Fluid Cooler: The fluid cooler casing shall be of aluminum, and all structural
supports, coil frame, motor-drive supports, and mounting legs shall be made of galvanized
steel. The fluid cooler coil shall have copper tubes expanded into aluminum fins. Headers
and connections shall be copper. The coil shall be pressure-tested and sealed for shipment.
The fluid cooler motors shall have permanently lubricated, sealed, ball bearings, and
internal overload protection. Motors shall be mounted inside the fluid cooler casing for
weather protection and wired to a terminal strip in a weatherproof panel on the unit. The
direct-drive, aluminum fin blade and painted steel hub assembly shall be protected by a
heavy-gauge, vinyl-coated, steel-wire fan guard. On multiple fan units, each fan section
shall be separated by full-width baffles to prevent bypass air. The Fluid Cooler shall be
sized for 95º F (35º C) ambient, and operate on ________ V, ________ ph, 60 Hz power.
C. PUMP PACKAGE
1 . Single Pump Package: The pump package shall be comprised of a centrifugal pump in a
vented enclosure with pump starter, separate Fluid Cooler fan and pump circuit breakers,
Aquastat, and fan cycling contractors to control the fluid temperature. The controls shall
be mounted in a weather-tight box. A _______ gal (L) expansion tank and Airtrol fitting
shall be supplied for field installation. The pump size shall be sized for ________ GPM
(L/s) at ________ ft (m) external head, and operate on ________ V, ________ ph, 60 Hz
power.
2 . Dual Pump Package: The dual pump package shall consist of two centrifugal pumps in an
enclosure. Pump starters, automatic pump switch-over controls, lead-lag pump selector
switch, separate Fluid Cooler fan and pump circuit breakers, Aquastat, and fan cycling
contractor to control the fluid temperature shall be mounted in a separate weather-tight
box. A _______ gal (L) expansion tank and Airtrol fitting shall be supplied for field
installation. Each pump shall be sized for ________ GPM (L/s) at _________ ft (m)
external head, and operate on ________ V, ________ ph, 60 Hz power.
APC NetworkAIR™ CM
47
Guide Specifications
3.04
ECONOMIZER
A. Glycol systems shall have the option of an economizer coil that is designed to reduce
operating costs during mid to low ambient temperatures. Economizer cooling coil shall be
copper tube, aluminum fin coil located in the return air before the V-Frame evaporator coil.
The economizer coil shall be rated at ____BTU/HR (kW) sensible cooling capacity with a 45
F (7.2 C) entering glycol solution temperature. The economizer coil shall require ____ GPM
(l/s) and the total unit pressure drop shall not exceed ____feet of water (kPa), when in the
economizer mode of operation.
3.05
MULTICOOL
A. Air, Water and Glycol systems shall have the option of a chilled water coil that is designed to
be the primary cooling source to the backup direct expansion coil. The MultiCool (chilled
water) coil shall be constructed with copper tubes and aluminum fins. It shall be located in the
return air, before the V-Frame evaporator coil. The MultiCool coil shall be rated at ____BTU/
HR (kW) sensible cooling capacity with 45 F (7.2 C) entering water temperature. The
MultiCool coil shall require ____GPM(l/s) of chilled water and the pressure drop shall not
exceed ____psig (kPa).
3.06
CHILLED WATER
A. The unit shall be piped in accordance with the highest commercial quality procedures. All pipe
shall be type “L” copper. All pipe forming shall be tool bent with proper bend radii to prevent
tube flattening in the curve. The chilled water piping shall be insulated with closed cell
neoprene thermal insulation. the chilled water flow shall be controlled by a 3-way valve (2way valve optional) with a 24 VAC modulating motor.
48
APC NetworkAIR™ CM
Guidelines for Installation
The CM provides reliable, accurate temperature and humidity control of
computer rooms, laboratories, and other environments that require close
tolerance control. The unit incorporates the latest system design innovations
to provide you with optimum efficiency, reliability, and accuracy of control.
The CM system will provide years of trouble-free service, when
installed and maintained by technically qualified personnel.
Room preparation
During the design of the room, consideration should be given to the
following factors: ease of entry for the system and accessibility of piping
and wiring.
The room must be sealed with a vapor barrier to minimize migration of
moisture. Polyethylene film (plastic sheeting) is a good vapor barrier for
ceiling and wall applications. Rubber- or plastic-based paints should be
applied to concrete floors and walls. The room should be thoroughly
insulated to minimize thermal loads and make-up air (if required) should
be preconditioned to reduce additional temperature, filtration, and
moisture loads.
APC should be notified before installation if the unit is incorrect for the
application.
Unit location
The location of the unit is important for efficient and balanced
environmental control in your room. The air conditioner should be
located as close as possible to the largest heat load. If improperly
installed, erratic control or mechanical failure can and will result.
Service access
At least 24" (610 mm) of clear space must be left in front of the unit for
routine service (filters, humidifier). We strongly recommend
approximately 32" (813 mm) clearance in front of the unit.
APC NetworkAIR™ CM
49
Guidelines for Installation
Receiving the unit
Your CM unit has been completely tested and inspected prior to
shipment. To ensure that you have received the unit in excellent
condition, perform a careful inspection of the crating and the unit
immediately upon receipt. Verify that all parts ordered were received as
specified and that the unit is the correct size and voltage necessary to
fulfill your environmental control needs. Report any damage discovered
to the freight carrier. If necessary, contact the APC field service
department for help in repairing or replacing damaged parts. While APC
is not responsible for damage incurred in transit, we want to make sure
that you have no undue delays in your system start-up.
Rigging
The unit is manufactured with a formed steel frame for maximum
strength and unit integrity. However, as with all electrical and
mechanical equipment, you must take care with proper rigging of your
unit.
When using a forklift to move the unit, use the shipping skid to protect
the bottom of the unit. When using chains, cables or rope to lift the unit,
use spreader bars to prevent damage to the finished panel.
Utility connections
All connections are made through the bottom left of the unit for ease of
service connections. Refer to the installation manual for pipe sizes and
specific locations for your unit.
Power unit
The CM unit uses either 1-phase or 3-phase power for operation
depending on the unit. Bring the service cable through the bottom left of
the unit and through the bulkhead hole into the electrical box to the
circuit breaker provided on the left side of the electrical box. The ground
lug is located near the 3-phase high-voltage connector. THE UNIT
MUST BE UTILITY GROUNDED OR THE WARRANTY IS
VOID.
Humidifier connections
The humidifier inlet connection point is provided with the equipment. A
1/4" (6.4mm) compression connection is supplied with the unit.
Condensate drain
Condensate from the evaporator pan is collected and discharged by the
condensate pump to a 7/8" (22.2mm) fitting for field connection.
50
APC NetworkAIR™ CM
Guidelines for Installation
Water supply to humidifier
1. The humidifier fill valve orifice is sized for supply water pressure
from 15 PSIG (103.4 kPa) to 150 PSIG (1034 kPa).
2. For cases above 150 PSIG (1034 kPa), install a pressure-reducing
valve in the water feed line to the unit.
3. With extremely dirty or muddy water sources, proper filtration is
required on the unit’s incoming water line.
4. DO NOT use softened water with the humidifier. Softened water is
too conductive.
5. DO NOT use completely demineralized water with the humidifier.
The minerals allow the electrode principle to work.
6. DO NOT use a hot water source. Doing so will cause deposits that
will eventually block the fill valve orifices.
7. Water supplies with high conductivity (above 800 mW) must be
preconditioned for proper operation and longevity of the humidifier.
Water supply
A 16- to 20-mesh strainer must be installed in the water supply to the
water units to prevent clogging of brazed plate condenser. This is a field
item.Also recommended on glycol units.
Note: Because of an ongoing program dedicated to product
improvement, specifications are subject to revisions without notice.
APC assumes no responsibility, and disclaims all liability for damages
resulting from use of this information or for any errors or omissions.
APC NetworkAIR™ CM
51
52
APC NetworkAIR™ CM
®
APC Worldwide Customer Support
Customer support for this or any other APC product is available at no charge in any of the following ways:
• Visit the APC Web site to find answers to frequently asked questions (FAQs), to access documents
in the APC Knowledge Base, and to submit customer support requests.
– www.apc.com (Corporate Headquarters)
Connect to localized APC Web sites for specific countries, each of which provides customer
support information.
– www.apc.com/support/
Global support with FAQs, knowledge base, and e-support.
• Contact an APC Customer Support center by telephone or e-mail.
– Regional centers:
APC headquarters U.S.,
Canada
(1)(800)800-4272 (toll free)
Latin America
(1)(401)789-5735 (USA)
Europe, Middle East, Africa
(353)(91)702020 (Ireland)
Asia Pacific
(61) 2 9955 9366 (Australia)
– Local, country-specific centers: go to www.apc.com/support/contact for contact information.
Contact the APC representative or other distributor from whom you purchased your APC product for
information on how to obtain local customer support.
Entire contents copyright © 2004 American Power Conversion. All rights reserved.
Reproduction in whole or in part without permission is prohibited. APC, the APC logo, and
NetworkAIR are trademarks of American Power Conversion Corporation and may be
registered in some jurisdictions. All other trademarks, product names, and corporate names
are the property of their respective owners and are used for informational purposes only.
990-7205E-EN
10/2004