Natural Gas Generator Fuel Consumption Chart Generator Rated Size (kW) 30 40 60 75 100 125 150 175 200 230 250 300 350 400 500 600 750 1000 1250 1500 1750 2000 2250 1/4 Load (cu.ft./hr) 181 181 250 334 361 431 500 570 653 737 792 945 1098 1237 1529 1835 2266 3002 3739 4476 5213 5949 6686 1/2 Load (cu.ft./hr) 250 320 403 473 570 695 820 945 1070 1223 1321 1571 1821 2071 2572 3058 3809 5060 6297 7548 8785 10036 11273 3/4 Load (cu.ft./hr) 334 445 528 639 806 987 1168 1348 1529 1738 1890 2238 2599 2961 3670 4379 5463 7242 9035 10814 12607 14387 16180 Full Load (cu.ft./hr) 403 556 667 848 1029 1265 1515 1765 2002 2307 2502 2989 3489 3975 4962 5949 7423 9883 12343 14804 17264 19724 22184 Note: All values in this chart are an approximation of the fuel consumption of a “generic” natural gas generator based on the size of the generator and the operating load being placed on it. Actual consumption may increase or decrease based on multiple factors such as the equipment brand/manufacturer specifications, fuel quality, equipment condition, and individual operating environment. Consumption of natural gas can be converted to other common units by taking (X) cu.ft./hr. * 1031 BTU / cu.ft. (natural gas) = BTU/hr * 0.00001 = therms/hr Bryan Power Generation - 7025 Campus Dr, Colorado Springs, CO 80920 1.855.677.5355 [email protected]